Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Similar documents
IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Enhancement of COP in Vapour Compression Refrigeration System

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

II. OBJECTIVE OF RESEARCH

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Week 9. Refrigeration Cycles I. GENESYS Laboratory

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

(Refer Slide Time: 00:00:40 min)

Performance investigation of Air-conditioning system using ejector as expansion device

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

A Comparison Between Refrigerants Used In Air Conditioning

η second law = Second law efficiency

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

ISSN Vol.08,Issue.21, November-2016, Pages:

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

Performance of an Improved Household Refrigerator/Freezer

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

pdfmachine trial version

*Corresponding author;

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Pressure Enthalpy Charts

Performance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration system

Performance Enhancement of Mini Refrigerator with Phase Change Materials

R07. Answer any FIVE Questions All Questions carry equal marks *****

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

ADVANCES in NATURAL and APPLIED SCIENCES

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

INSTITUTE OF AERONAUTICAL ENGINEERING

[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor

LECTURE-17. Multi-Stage Vapour Compression Refrigeration. 1. Introduction

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

Performance Analysis of Solar Assisted Cascade Refrigeration System of Cold Storage System

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (

Performance Study of Geotropic Blends of Isobutane R600a and Propane R290 in Domestic Refrigerator as Alternative Refrigerants to R134a

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

Enhancement of COP using Nanoadditives in Domestic Refrigerator

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Performance Assessment of Water Cooled Condenser Refrigeration System

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Design of LPG Refrigeration System

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Performance Optimization of the Evaporative Condenser Design

Sarthak Thakar, 2 R.P.Prajapati 1

Experimental Performance Evaluation Of Vapour Compression Refrigeration System using R134a and R152a Refrigerants, A review

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

ADVANCES in NATURAL and APPLIED SCIENCES

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

Analysis of Vapour Compression Refrigeration System with Refrigerants R134a, R143a, R152a, R290 and R32

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

Reheating Refrigeration System

Transcription:

International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 Volume 4 Issue 6 ǁ June. 2016 ǁ PP. 52-57 Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a Rejith G Krishnan 1, Saloop T S 2, Vishnu M Mohan 3, Issac Thomas 4, Sandeep Kumar M 5 1,2,3,4,5 Department of Mechanical Engineering, College of Engineering, Munnar, Munnar P.O., 685612, Kerala State, India. Rejith G Krishnan, is a holder of Bachelor degree in Technology in Mechanical Engineering from Mahatma Gandhi University and Master degree in Technology in Mechanical Engineering with specialization in Thermal Science from Kerala University. He is currently working as an assistant professor in Mechanical Engineering Department of College of Engineering Munnar. He has 1 year of teaching experience. Saloop T S, is a holder of Bachelor degree in Technology in Mechanical Engineering from Kerala University and Master degree in Technology in Mechanical Engineering with specialization in Energy management from Cochin University of Science and Technology. He is currently working as an assistant professor in Mechanical Engineering Department of College of Engineering Munnar. He has 3 years of teaching experience. Vishnu M Mohan, is a holder of Bachelor degree in Technology in Mechanical Engineering from Kerala University and Master degreein Technology in Mechanical Engineering with specialization in Thermal and Fluid from Amritha University. He is currently working as an assistant professor in Mechanical Engineering Department of College of Engineering Munnar. He has 1 year of teaching experience. He has a conference paper in Thermodynamic Analysis of Alternatives for Enhancing Efficiency of Gas Turbine Power Plants (Int. Conf. Advances in Chemical Engineering and Technology, ICACE TKMCE'14(86-91, Elsevier publications - 2014). IssacThomas, is a holder of Bachelor degree in Technology in Mechanical Engineering from Mahatma Gandhi University and Master degree in Engineering in Mechanical Engineering with specialization in Energy Engineering from Kerala University. He is currently working as an assistant professor in Mechanical Engineering Department of College of Engineering Munnar. He has 1 year of teaching experience and 1 year industrial experience. Sandeep Kumar M, is a holder of Bachelor degree in Technology in Mechanical Engineering from Mahatma Gandhi University and Master degree in Engineering in Mechanical Engineering with specialization in from Anna University. He is currently working as an assistant professor in Mechanical Engineering Department of College of Engineering Munnar. He has 3 year of teaching experience and 1 year industrial experience. ABSTRACT: A refrigeration system was developed which combines a simplevapour compression refrigeration with a diffuser. Main purpose of this combination is to reduce compressor work and to improve the coefficient of performance. It was found through the literature, that vapor leaving the compressor with high velocity will cause damage to the condenser by erosion and also the liquid sub cooling will be inefficient. So, the vapour refrigerant leaving the compressor is allowed to pass through a diffuser to convert the kinetic energy of refrigerant to pressure energy. Thus the compressor work can be reduced and the condenser can function more effectively. In this paper we are analyzing the cycle by taking three different refrigerants, R-134a (Tetrafluoroethane), R-600a (Isobutane) and R-152a(Difluoroethane) separately. Further, energy performance characteristic is found out for above refrigerants. I. Introduction Refrigeration is widely used in domestic applications such as preservation of food, ice making etc. It is a process of removing excess heat from a space by providing mechanical work. Many research works are going on this specific area for finding better system which consumes less power and produce better performance. The improved systems reduce the effect of global warmingas well as energy consumption. It is found that the performance of a vapor compression system can be improved by increasing the evaporator temperature and by decreasing the condenser temperature. But these values are dependent on atmospheric conditions [1].Several 52 Page

modifications are suggested by several investigators to the simple vapor compression cycle to enhance the coefficient of performance. Yari et al. [2] developed a new configuration of the ejector-vapour compression refrigeration cycle, whichuses an internal heat exchanger and intercooler to enhance the performance of the cycle. Obtained results showed that there was an increase of 8.6% and 8.15% in coefficient of performance and second law efficiency values respectively of the new ejector-vapour compression refrigeration cycle as compared to the conventional ejectorvapour compression refrigeration cycle with R125. It was also found that there was increase of 21% in the coefficient of performance of the new ejector-vapour compression cycle compare to the conventional vapour compression system. Yinhai Zhu et al [1],developed a hybrid vapor compression system with an integrated ejector cooling cycle. The ejector cooling cycle is driven by the waste heat from the condenser in the vapor compression refrigeration cycle. The additional cooling capacity from the ejector cycle is directly input into the evaporator of the vapor compression refrigeration cycle. The results show that the COP is improved by 9.1% for R22 system. Moo-Yeon lee et. al. [3] have studied the performance of a small capacity directly cooled refrigerator by using the alternative to R-134a.The compressor displacement volume of the alternative system with R600a/R290 (45/55) has modified from that of the original system with R-134a to the optimized R600a/R290 system was approximately 50% of that of the optimized R-134a system. The capillary tube lengths for each evaporator in the optimized R600a/R290 system were 500mm longer than those in the optimized R-134a system. The power consumption of the optimized R-134a system was 12.3% higher than that of the optimized R600a/R290 system. The cooling speed of the optimized R600a/R290 (45/55) system at evaporator 0 o C was improved temperature by 28.8% over that of the optimized R-134a system. NeerajaUpadhyayet. al. [4] developed a new configuration of the diffuser and sub-cooling in vapour compression refrigeration cycle, for sub-cooling, a fan is used. By using diffuser, power consumption is less for same refrigeration effect, so performance is improved. The size of the condenser can be reduced, as the heat transfer is considerably increased due todiffuser application. So cost of the condenser will be reduced. The parameters like pressure and temperature were measured. After result analysis, it is found that the COP was enhanced from2.65 to 3.38 in the case when conventional vapour compression refrigeration system was used with diffuser. In the present work, an isentropic diffuser is taken for the analysis which is able to produce 0.5bar pressure rise if the refrigerant leaving the compressor with sonic flow. Here the compressor, which increases the pressure of a low pressure vapour refrigerant, will consume less work than in the base cycle. So for getting same refrigeration effect as in the base cycle, less compressor work is needed. Diffuser is a device which converts kinetic energy of the fluid in to pressure energy. After leaving the diffuser the refrigerant enters the condenser with moderate velocity. This will prevent the splashing of liquid and therefore condenser size will be optimum, for producing sub-cooling[5]. Here we assume 5degree of sub-cooling and 5 degree of super heating at condenser outlet andcompressor inlet respectively. A heat exchanger is provided in between the condenser and evaporator for producing the same. Here, we are considering three different refrigerants (R-134a, R-600a & R152a) which does not contain chlorine atom, and an analysis is done for finding the rate of increase of coefficient of performance with respect to the base cycle. The evaporator temperature varies from 16 0 C to 6 0 C and the condenser temperature is kept as 30 0 C, constantin both cases (with and without diffuser). For each value of temperature, COP is calculated separately and a theoretical comparison is done for finding best refrigerant for the particular design. II. System Description In this, basic system is a simple vapour compression refrigeration system with a heat exchanger, coupled between condenser and evaporator to improve the refrigeration effect. The new system has a diffuser attached before the condenser as shown below 53 Page

The vapour refrigerant leaving the evaporator (1 I ) is assumed to be dry saturated, which absorbs sensible heat from the heat exchanger and the vapour becomes super-heated. Here the heat exchanger is designed so as to give a 5 degree of super heat i.e.,t 1 T 1 I= 5. This super-heatedvapour enters the compressor, which increase the pressure from stage 1 to 2(if diffuser is not used) and from 1 to 2 I (if diffuser is used). The compression process is isentropic and the work done by the compressor to raise the pressure equals to the enthalpy difference between both stages. W compressor = h 2 h 1 (without diffuser) W compressor = h 2 I h 1 (With diffuser) Using the diffuser, the compressor work is reduced and the high pressure vapour refrigerant enters the condenser. Here therefrigerant rejects its latent heat of vaporization and attains liquid state(2-3 I ). The excess heat in the refrigerant is again rejected in the heat exchanger and the liquid get sub cooled. Here also T 3 -T 3 I = 5 This sub cooled liquid is expanded through an expansion device to a lower pressure state 4 is an isenthalpic process (3-4). After the expansion, refrigerantabsorbs excess heat from the evaporator to becomevapour at the end. This is assumed to be a constant pressure process. Refrigeration effect produced = h 1 -h 4. Corresponding Pressure- Enthalpy diagram has been shown in Figure 2. P-h diagram gives enthalpy at various points and the difference in enthalpy gives the amount of energy absorbed or rejected. In the P-h diagram, path 1-2-3-4 is the base cycle without diffuser. h 1 Iis the enthalpy of saturated vapor refrigerant corresponding value of P 1 h 1 = h 1 I + C pv (T 1 T 1 I) (1) Process 1-2 is an isentropic process so that S 1 =S 2 (2) S 1 = S 1 I + C pv ln (T 1 T 1 I) (3) S 2 = S 2 I+ C pv ln (T 2 T 2 I) (4) Here the only unknown value is T 2 which can be calculated from 2 S 2 IandT 2 I are corresponding saturated values which will find out from the table. By calculatingt 2, corresponding value of enthalpy can be calculated h 2 =h 2 I +C pv (T 2 T 2 I) (5) h 3 = h 3 I - C pl (T 3 I-T 3 ) (6) h 3 Ican be calculated from table and T 2 I = T 3 I From process 3-4 enthalpy at the exit of the expansion device will be equal as the enthalpy at the exit of the heat exchanger (h 3 =h 4 ) So the refrigeration effect produced = h 1 - h 4 (7) Work done on the compressor = h 2 h 1 (8) Coefficient of performance of base cycle = (h 1 - h 4 )/(h 2 h 1 ) (9) 54 Page

For same refrigerant, if diffuser is attached at the exit of compressor, the compressor work is changed from (h 2 h 1 ) to (h 2 II -h 1 ). Even though the vapour refrigerant exit from the compressor at the state 2 II and the remaining pressure rise is occur inside the diffuser. From the assumption the pressure rise in the diffuser is 0.5bar and it reject the refrigerant at the state 2 that of a base cycle. The evaporator temperature and condenser temperature are kept same and for same refrigerant the coefficient of performance is find out. Coefficient of performance of modified cycle COP =(h 1 - h 4 )/(h 2 II -h 1 ) (10) Percentage increase in Coefficient of performance {(h 1 - h 4 )/(h 2 II -h 1 )- (h 1 - h 4 )/(h 2 h 1 )}/(h 1 - h 4 )/(h 2 h 1 )}* 100 (11) Using this relation, percentage of increase of coefficient of performance of each refrigerant at different evaporator temperature is plotted. III. Results and Discussions The present study used R-134a, R-600a and R-152a as the working fluids. The thermodynamic properties of the refrigerants were calculated from [6]. Figure 3 shows variation of coefficient of performance of each refrigerants with respect to the evaporator temperature. The condenser temperature is fixed as 30. Figure 3 Coefficient of performance Vs Evaporator temperature of R-134a From the graph we can observe the variation of COP at each evaporator temperature. It is clear that the COP at each evaporator temperature is more in the cycle which is having a diffuser. With increase in evaporator temperature, the COP of the cycle increases in both cases. It shows a linear relationship between the COP with and without diffuser up to the temperature -8 and then there is a slight increase in difference in COP with both the systems. Maximum COP occurs at -6 of evaporator temperature which is 6.84 (with diffuser). Figure 4 shows the same graph for R-152a as refrigerant. The operating conditions are same as that of previous one. Figure 4 Coefficient of performance Vs Evaporator temperature of R-152a 55 Page

When condenser temperature is constant,with the increase in evaporator temperature COP of the system also increases.for this refrigerant, the value of COP is almost same as that for R-134a. But the graph shows a more deviation as evaporation temperature increases. That means the rate of increase of COP in this case is more than that of R-134a. The maximum value of COP obtained is 6.811(with diffuser) when evaporator temperature is -6. Figure 5 Coefficient of performance Vs Evaporator temperature of R-600a For R-600a the figure shows a larger deviation compares to the previous graphs for R-134a and R- 152a. Here also with an increase inevaporator temperature, the COP of the system increases. On comparison of all the three refrigerants with refrigeration system having diffuser, R-600a gives more COP than the other two i.e., a COP of 7.5 at -6 evaporator temperature. At higher evaporator temperatures, the difference in COP is higher, so the percentage increase in COP will be higher for R-600a refrigerant compared to others, which is shown in Figure 6. Figure 6 percentage increases in COP Vs. Evaporator temperature This clearly shows a large increment in COP for R-600a refrigerant when a diffuser is mounted after the compressor. At each evaporator temperature, the increase in COP of R-600a is much higher than the other two refrigerants. It is found that if we use R-600a as refrigerant the COP can rise up to 13.25% than the base cycle. Even though other two refrigerantsr-134a and R-152a are performing well, they improve COP only upto 4.87, 5.01 respectively. IV. Conclusion COP of vapour compression refrigeration can be improved by either increasing the refrigeration effect or by decreasing the compressor work. Providing a heat exchanger, in between the evaporator and condenser will increase the refrigeration effect. The result shows that compressor work can be reduced by the application a diffuser in between compressor and condenser. A diffuser will convert the kinetic energy of the refrigerant to pressure energy without consuming any work input. This will also prevent condenser - erosion and the sub 56 Page

cooling occur effectively. Results obtained shows that, among the three different eco-friendly refrigerants, R- 600a is the better performing one. It improves the COP by 13.25% that of the base system. This may be because of the saturation temperature of the refrigerant at the state of diffuser entry is lower than that of other two refrigerants. So the compressor work, which is enthalpy change, will be lower. Thus for same design conditions R-600a is more preferred because of its properties. Nomenclature T Temperature Subscripts 1 Properties at the exit of evaporator (saturated) 1 I Properties at the exit of heat exchanger(super-heated) 2 II Properties at the exit of compressor 2 Properties at the exit of diffuser 2 I Properties corresponding to the condenser temperature (saturated) 3 I Properties at the exit of condenser (saturated) 3 properties at the exit of heat exchanger (Subcooled) 4 properties at the exit of expansion device h Enthalpy in kj/kg S entropy in kj/kgk c pv Specific heat of vapour refrigerant in kj/kgk c pl Specific heat of liquid refrigerant in kj/kgk COP Coefficient of performance REFERENCE [1]. Yinhai Zhu, Peixue Jiang, (2012) Hybrid vapor compression refrigeration system with an integrated ejector cooling cycle, International journal of refrigeration 35, 68-78 [2]. M Yari and M Sirousazar, (2007), Performance analysis of the ejector-vapour compression refrigeration cycle, PartA: Journal of Power and Energy, Vol. 221, No. 8, pp. 1089-1098 [3]. Moo-Yeon Lee, (2008) The performance of a small capacity directlycooled refrigerator by using the mixture of R600a/R290 mass fraction of 45:55 as an alternative to R134a, International Journal of Refrigeration [4]. NeerajaUpodhyay, (2014). To study the effect of Sub-cooling and Diffuser on the Coefficient of Performance of Vapour Compression Refrigeration System, International Journal of Research in Aeronautical and Mechanical Engineering ISSN: 2321-3051 [5]. R. T. Saudagar, Dr. U. S. Wankhede,(2012),Vapor compression refrigeration system with diffuser at condenser inlet,international Journal of Engineering Research and Development ISSN: 2278-067X, Volume 1, Issue 11 PP. 67-70. [6]. A.V. Domkundwar, Refrigeration and air conditioning data book, DhanpatRai&co. 2009. [7]. Yettisiva, Drsmt G. Prasanthi,(2015) Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to R-134a in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser at Condenser Inlet, International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12. [8]. C. O. Adegoke, M. A. Akintunde, and O. P. Fapetu, Comparative Exergetic Analysis of Vapor Compression Refrigeration Systems in the Superheated and Subcooled Regions, A.U. J.T., Vol. 10, No. 4, Apr.- 2007, pp. 254-263. 57 Page