Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Similar documents
Thermostatic Expansion valves, type TUA/TUAE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

MAKING MODERN LIVING POSSIBLE. Thermostatic expansion valves, type TR 6 REFRIGERATION & AIR CONDITIONING DIVISION.

Thermostatic Expansion Valves Type TR 6

Flexible. Upgrade and service with ease Extend lifetime with modular design. Thermostatic expansion valves Type TE5-55

MAKING MODERN LIVING POSSIBLE. One valve for all purposes. TGE - thermostatic expansion valves REFRIGERATION & AIR CONDITIONING DIVISION

Capacity regulators, type CPCE and LG REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Thermostatic expansion valves for ammonia Type TEA

Check valve Types NRV and NRVH

Revolutionary ETS Colibri valves Engineered to give you maximum flexibility and dependability

LINE COMPONENTS VALVES

Product Catalog VALVES

T2 thermostatic expansion valves regulate the injection of refrigerant liquid into evaporators. The refrigerant superheat determines the amount.

RD refrigerant distributors, for thermostatic expansion valves REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Hot gas bypass regulator, type CPCE Liquid gas mixer, type LG (accessory)

General information on refrigerant controllers

Liquid Distributor Type RD

Tube-in-tube heat exchanger Type HE

HANDBOOK REGULATOR VALVES. Ed REGULATOR VALVES RP-ED 01/ ENG 1

These valves can also be ordered as a bidirectional valve, allowing control of flow in both directions for use on heat pump applications.

FSW SECTION. Product guide. Expansion Valves, Solenoid Valves Water Valves & Oil Pressure Switches F SECTION. 71

Refrigerant valves. Valves for precise control and optimum energy efficiency in refrigeration systems. Answers for infrastructure.

Bulletin , March Electric Hot Gas Bypass Valves

Refrigeration and Air Conditioning Controls. Applications. PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING

Filter Driers with Replaceable Core

JCseries EVAPORATIVE CONDENSER. engineering data

OACS Outdoor Air-Cooled Central Chillers

THERMOSTATIC EXPANSION VALVES

REFRIGERATION PRODUCTS

Accumulators - Suction Line

Sporlan Valve Division Parker Hannifan/CIC Group

Chapter-8 Capacity Control of Refrigeration Systems

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e.

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

V48 Series 3-Way Water Regulating Valves For Cooling Tower Systems

Danfoss scroll compressors SH- In parallel installation

Danfoss scroll compressors SH - In parallel installation

SANHUA S OFFER FOR REFRIGERATION APPLICATIONS

Zero ODP and negligible GWP when using hydrocarbons. Zero. portfolio for hydrocarbons.

Typical Piping Diagram

DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: , Fax#: ,

Low Pressure Sight Glass Up to 35 bar MWP Type SG

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

BALANCED PORT Q-VALVE

Part IV: Flow Side Components Flow Diagram

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

COMMECH SERIES AIR CONDITIONING CSH SEMI-HERMETIC SCREW PACKAGES. ORIGINAL MANUFACTURED EQUIPMENT Commech Series New Models BA AUS

Optyma Slim Pack Condensing Units

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

50% Refrigeration solutions to lower energy costs and reduce environmental impact. Foodservice Solutions. Up to

Commercial High-Efficiency Condensing Units

Refrigeration Systems

Tube-in-tube heat exchanger Type HE

ef cooling - FURRER Industriekühlung GmbH Technical Data Water Cooling Units EPI-A 2 - EPI-A 6 norden cooling

EXPANSION VALVES. See Red Dot Catalog Also. * 2 ton valves - all other valves are 1 1/2 ton (1) Includes M1 Adapter 71R8050 EX02280

Emerson Superheat Control. The smart solution for your application

PULSE WIDTH MODULATING VALVES

DESIGN STANDARDS SECTION 15600

CATALOGUES SUMMARY - WCHBZ Pages WCHZ Pages 19-42

500 EX Fusion Compressor Series

THE PRODUCTS YOU NEED. THE QUALITY YOU WANT. THE INNOVATION YOU DESERVE.

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental

Elevating Your Offering

Above & Beyond. Refrigerated Compressed Air Dryers

Easy Find the right products fast with our Quick Selection Guide. Products and technologies for all your application needs, today and tomorrow

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

Thermostatic Expansion Valves

Suction Accumulators. Introduction. Suction Accumulators

Head Pressure Control Valves

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

MAKING MODERN LIVING POSSIBLE. Check valve for EVRA, EVRAT and PM valves in liquid lines type NRVS. Technical brochure

Hi-Pres. Self Contained A/C Unit HI-PRES MARINE & OFFSHORE

Technical Information

PURESTREAM CHILL-CUBE TM BY FRIULAIR

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated.

ELIMINATOR Hermetic filter drier for CO₂ DMSC for Sub-critical and DMT for Trans-critical application

Danfoss Scroll for Refrigeration MLM / MLZ

Pressure switch KPU. Data sheet

Suction Line Accumulators

Brazed Plate Heat Exchanger

EPCE00-10B. Powerful. air cooled. Hydronic systems EUWA*40-200K(A)X

Air-Cooled Condensing Units with Compact Screw Compressors

Zero Superheat Control

System Considerations for Refrigerant Blends with Temperature Glide

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

Operating instructions Open two-stage compressor FZ 16

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

Energy Use in Refrigeration Systems

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN

Brazed Plate Heat Exchanger

FIRST IN RELIABILITY FIRST IN CHOICE

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

Transcription:

Capacity regulator (hot gas bypass), type TUH/TCHE/ REFRIGERATION AND AIR CONDITIONING Technical leaflet

Contents Page Introduction........................................................................................3 Features............................................................................................3 Standard range.....................................................................................3 Identification.......................................................................................4 Technical data......................................................................................4 Ordering...........................................................................................5 Capacity............................................................................................6 R134a - Replacement capacity...................................................................6 R134a - Mass flow rate..........................................................................7 R22 - Replacement capacity.....................................................................8 R22 - Mass flow rate.............................................................................9 R404A/R507 - Replacement capacity........................................................... 10 R404A/R507 - Mass flow rate.................................................................. 11 R407C - Replacement capacity................................................................ 12 R407C - Mass flow rate........................................................................ 13 R410A - Replacement capacity................................................................ 14 R410A - Mass flow rate........................................................................ 15 Design/Function.................................................................................. 16 Dimensions and weight........................................................................... 17 Application....................................................................................... 19 2 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 Danfoss A/S (RC-CMS/MWA), 05-2005

Introduction TUH/TCHE/ capacity regulators adapt compressor capacity to actual evaporator load in applications operating at an evaporating temperature of around 0 C. TUH/TCHE/ valves are typically used in applications such as: Air driers Water chillers Fitted in a bypass between the high and lowpressure sides of the air-drier system, TUH/TCHE/ maintain compressor suction pressure by injecting hot gas/cool gas from the high-pressure side. TUH has internal pressure equalisation and opens when pressure drops at the valve outlet. TCHE/ have external pressure equalisation and open directly when compressor suction pressure drops. For all types, the bulb only serves as a reservoir for the charge. However, it is recommended that the bulb be mounted in a location where temperature variation during operation is limited (see application drawings). Features Bimetal connections straightforward and fast soldering (no wet cloth or refrigeration pliers required) high connection strength Refrigerants R410A, R134a, R404A/R507, R407C, R22 and other refrigerants on request. Replacement capacities up to 70.3 kw (20.1 TR) for R410A Stable regulation Tight across the seat Compact design small dimensions and low weight Hermetically tight design Stainless steel element high corrosion resistance capillary tube joints of high strength and vibration resistance Laser-welded, stainless steel diaphragm element optimum function long diaphragm life high pressure resistance Adjustable setting accurate setting fine tuning possible Low p-band Low hysteresis have an advanced filter/strainer design Standard range (Variants available on request) Standard models: One standard range per refrigerant Refrigerants R134a, R404A/R507, R407C, R22, R410A Capillary tube length TUH 0.8 m / 2.6 ft. TCHE 0.9 m / 2.9 ft. 10 1.5 m / 5.0 ft. 20 1.5 m / 5.0 ft. 40 3.0 m / 10 ft. 80 3.0 m / 10 ft. Connections Inlet: 10 mm / 3 / 8 in. Outlet: 12 mm / 1 / 2 in. 10 & 20 Inlet: 16 mm / 5 / 8 in. Outlet: 16 mm / 5 / 8 in. 40 Inlet: Outlet: 22 mm / 7 / 8 in. 22 mm / 7 / 8 in. Orifice sizes TUH Orifice 9 TCHE Orifice 3 Orifice 4 10 Orifice 10 20 Orifice 20 40 Orifice 40 80 Orifice 70 80 Inlet: Outlet: 28 mm / 1 1 / 8 in. 28 mm / 1 1 / 8 in. Danfoss A/S (RC-CMS/MWA), 05-2005 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 3

Identification - Main valve data is given on the element (fig. 1) and on the valve body (fig. 2). Main valve data example, fig. 1 TUH = Type 068U2954 = Code number R404A = Refrigerant 5 +5 C = Adjusting range in C +23 +41 F = Adjusting range in F PS 34 bar/ MWP 500 psig = Max. working pressure 104B = Date marking (week 10, year 2004, weekday B = Tuesday) Fig. 1 Main valve data example, fig. 2 = Normal flow direction inch = Connection in inches (MM = millimetres) ORIF 9 = Orifice number 9 1.3 TR = Replacement capacity in Tons of Refrigeration 4.5 kw = Replacement capacity in kw Fig. 2 Identification - Main valve data example, fig. 3 10 = Type 3.0 TR = Rated replacement capacity Q nom in Tons of Refrigeration 10.3 kw = Rated replacement capacity Q nom in kw R410A = Refrigerant 5 +5 C = Adjusting range in C +23 +41 F = Adjusting range in F 067Lxxxx = Code number PS 42 bar/ MWP 600 psig = Max. working pressure Fig. 3 PS Technical data Max. valve body temperature: 120 C / 248 F Transient peak: 150 C / 302 F Permissible working pressure R134a, R22, R407C, R404A: PS = 34 bar / MWP = 500 psig R410A PS = 42.5 bar / MWP = 615 psig Max. test pressure R134a, R22, R407C, R404A: p = 37.5 bar / 540 psig R410A: p = 47 bar / 680 psig P-band max. 0.5 bar / 7.3 psig Setting The valve is set to start opening at an evaporating temperature of +2 C/+36 F. The setting can be changed by turning the setting spindle. The temperature at which the valve starts opening is increased by turning the spindle anti-clockwise and decreased by turning the spindle clockwise. Specifically designed for hot gas applications. All valves react only on to suction pressure variations. 4 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 Danfoss A/S (RC-CMS/MWA), 05-2005

Technical data (Continued) Adjustment range for start opening Valve Type Refrigerant Adjustment range for start opening TUH TCHE 10 [ C] [ F] R134a 7 +11 C +20 +51 F R22 / R407C 4 +8 C +25 +46 F R404A 3 +7 C +27 +44 F R410A 2 +6 C +29 +42 F R134a 6 +9 C +22 +48 F R22 / R407C 3 +6 C +26 +43 F R404A 3 +6 C +28 +42 F R410A 5 +8 C +22 +47 F R134a 6 +9 C +22 +48 F R22 / R407C 6 +9 C +22 +48 F R404A 5 +8 C +24 +46 F R410A 4 +7 C +25 +44 F Valve Type Refrigerant Adjustment range for start opening [ C] [ F] R134a 7 +10 C +19 +51 F 20 R22 / R407C 6 +9 C +21 +48 F R404A 5 +8 C +22 +47 F R410A 6 +9 C +21 +48 F R134a 5 +8 C +24 +46 F 40 R22 / R407C 5 +8 C +24 +46 F R404A 4 +7 C +26 +44 F R410A 3 +6 C +27 +43 F R134a 4 +7 C +25 +44 F 80 R22 / R407C 5 +8 C +23 +46 F R404A 4 +7 C +25 +44 F R410A 3 +6 C +28 +42 F Ordering Supplied with bulb strap TUH TCHE Standard range Refrigerant Type Orifice no. 1) The nominal replacement capacity is the regulator capacity at evaporating temperature t e = 2 C / 28 F, condensing temperature t c = +40 C / 104 F, reduction of suction temperature / suction pressure t s = 4 K / 7 F. 2) Valves with inch connections have 1 /4 in. pressure-equalisation. 3) Valves with mm connections have 6 mm pressure-equalisation. R134a, R22, R404A/R507, R407C, R410A Nominal replacement capacity 1 ) Pressure equalisation Connection Inlet Outlet kw TR in. 2 ) Code no. mm 3 ) Code no. R134a TUH 9 1.8 0.5 int. 3 / 8 1 / 2 068U2953 10 12 068U2950 TCHE 3 2.6 0.8 ext. 3 / 8 1 / 2 068U4540 10 12 068U4530 TCHE 4 3.4 1 ext. 3 / 8 1 / 2 068U4537 10 12 068U4534 10 10 2.9 0.8 ext. 5 / 8 5 / 8 067L1500 16 16 --- 20 20 6.5 1.9 ext. 5 / 8 5 / 8 067L1600 16 16 --- 40 40 11.3 3.2 ext. 7 / 8 7 / 8 067L3500 22 22 --- 80 70 20.8 5.9 ext. 1 1 / 8 1 1 / 8 067L3600 28 28 --- R404A/R507 TUH 9 4.5 1.3 int. 3 / 8 1 / 2 068U2954 10 12 068U2951 TCHE 3 5.9 1.7 ext. 3 / 8 1 / 2 068U4541 10 12 068U4531 TCHE 4 7.6 2.2 ext. 3 / 8 1 / 2 068U4538 10 12 068U4535 10 10 5.1 1.5 ext. 5 / 8 5 / 8 067L1501 16 16 --- 20 20 11.3 3.2 ext. 5 / 8 5 / 8 067L1601 16 16 --- 40 40 20.0 5.7 ext. 7 / 8 7 / 8 067L3501 22 22 --- 80 70 41.3 11.8 ext. 1 1 / 8 1 1 / 8 067L3601 28 28 --- R407C TUH 9 2.8 0.8 int. 3 / 8 1 / 2 068U2955 10 12 068U2952 TCHE 3 4.1 1.2 ext. 3 / 8 1 / 2 068U4542 10 12 068U4532 TCHE 4 5.3 1.5 ext. 3 / 8 1 / 2 068U4539 10 12 068U4536 10 10 4.1 1.2 ext. 5 / 8 5 / 8 067L1502 16 16 --- 20 20 9.1 2.6 ext. 5 / 8 5 / 8 067L1602 16 16 --- 40 40 16.6 4.7 ext. 7 / 8 7 / 8 067L3502 22 22 --- 80 70 28.8 8.2 ext. 1 1 / 8 1 1 / 8 067L3602 28 28 --- R22 TUH 9 3.0 0.9 int. 3 / 8 1 / 2 068U2959 10 12 068U2957 TCHE 3 4.1 1.2 ext. 3 / 8 1 / 2 068U4546 10 12 068U4544 TCHE 4 5.3 1.5 ext. 3 / 8 1 / 2 068U4547 10 12 068U4545 10 10 5.4 1.6 ext. 5 / 8 5 / 8 067L1503 16 16 --- 20 20 11.9 3.4 ext. 5 / 8 5 / 8 067L1603 16 16 --- 40 40 20.8 5.9 ext. 7 / 8 7 / 8 067L3503 22 22 --- 80 70 37.5 10.7 ext. 1 1 / 8 1 1 / 8 067L3603 28 28 --- R410A TUH 9 7.3 2.1 int. 3 / 8 1 / 2 068U2960 10 12 068U2958 TCHE 3 10.0 2.9 ext. 3 / 8 1 / 2 068U4548 10 12 068U4528 TCHE 4 12.9 3.7 ext. 3 / 8 1 / 2 068U4549 10 12 068U4529 10 10 10.3 3.0 ext. 5 / 8 5 / 8 067L1504 16 16 --- 20 20 22.6 6.4 ext. 5 / 8 5 / 8 067L1604 16 16 --- 40 40 34.9 10.0 ext. 7 / 8 7 / 8 067L3504 22 22 --- 80 70 70.3 20.1 ext. 1 1 / 8 1 1 / 8 067L3604 28 28 --- Danfoss A/S (RC-CMS/MWA), 05-2005 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 5

Replacement capacity Replacement capacity [kw] 6 5 4 3 2 1 0-6 -5-4 -3-2 -1 0 1 2 3 R134a eta isentrop =0.7 p evap = 0.2 bar TCHE 3 TCHE 4 TUH 9 Replacement capacity [kw] 35 30 25 20 15 10 5 0 eta isentrop =0.7 p evap = 0.5 bar 10 20 40 80 Correction factor for condensing temperature R134a Condensing temperature +30 C +40 C +50 C 0.8 1.0 1.2 Above capacities have to be multiplied with the correction factor. 6 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 Danfoss A/S (RC-CMS/MWA), 05-2005

Mass flow rate Mass flow [kg/s] 0.030 0.025 0.020 0.015 0.010 R134a p evap = 0.2 bar 0.005 0.000-6 -5-4 -3-2 -1 0 1 2 3 TCHE 3 TCHE 4 TUH 9 Mass flow [kg/s] 0.18 0.16 0.14 0.12 0.10 0.08 0.06 p evap = 0.5 bar 0.04 0.02 0.00 10 20 40 80 Correction factor for condensing temperature R134a Condensing temperature +30 C +40 C +50 C 0.8 1.0 1.2 Above capacities have to be multiplied with the correction factor. Danfoss A/S (RC-CMS/MWA), 05-2005 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 7

Replacement capacity Replacement capacity [kw] 8 7 6 5 4 3 2 R22 Start opening: t evap = 18 C p evap = 0.2 bar 1 0 TCHE 3 TCHE 4 TUH 9 Replacement capacity [kw] 70 60 50 40 30 20 10 0 p evap = 0.5 bar 10 20 40 80 Correction factor for condensing temperature R22 Condensing temperature +30 C +40 C +50 C 0.8 1.0 1.2 Above capacities have to be multiplied with the correction factor. 8 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 Danfoss A/S (RC-CMS/MWA), 05-2005

Mass flow rate Mass flow [kg/s] 0.04 0.03 0.02 0.01 0.00 R22 Start opening: t evap = 18 C p evap = 0.2 bar TCHE 3 TCHE 4 TUH 9 Mass flow [kg/s] 0.30 0.25 0.20 0.15 0.10 0.05 0.00 p evap = 0.5 bar 10 20 40 80 Correction factor for condensing temperature R22 Condensing temperature +30 C +40 C +50 C 0.8 1.0 1.2 Above capacities have to be multiplied with the correction factor. Danfoss A/S (RC-CMS/MWA), 05-2005 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 9

Replacement capacity Replacement capacity [kw] 12 10 8 6 4 R404A/R507 p evap = 0.2 bar 2 0 TCHE 3 TCHE 4 TUH 9 Replacement capacity [kw] 70 60 50 40 30 20 10 0 p evap = 0.5 bar 10 20 40 80 Correction factor for condensing temperature R404A/R507 Condensing temperature +30 C +40 C +50 C 0.8 1.0 1.2 Above capacities have to be multiplied with the correction factor. 10 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 Danfoss A/S (RC-CMS/MWA), 05-2005

Mass flow rate Mass flow [kg/s] 0.08 0.07 0.06 0.05 0.04 0.03 R404A/R507 p evap = 0.2 bar 0.02 0.01 0.00-6 -5-4 -3-2 -1 0 1 2 3 TCHE 3 TCHE 4 TUH 9 Mass flow [kg/s] 0.4 5 0.4 0 0.3 5 0.3 0 0.2 5 0.2 0 0.1 5 p evap = 0.5 bar 0.1 0 0.0 5 0.0 0 10 20 40 80 Correction factor for condensing temperature R404A/R507 Condensing temperature +30 C +40 C +50 C 0.8 1.0 1.2 Above capacities have to be multiplied with the correction factor. Danfoss A/S (RC-CMS/MWA), 05-2005 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 11

Rplacement capacity Replacement capacity [kw] 8 7 6 5 4 3 2 R407C p evap = 0.2 bar 1 0-6 -5-4 -3-2 -1 0 1 2 3 TCHE 3 TCHE 4 TUH 9 Replacement capacity [kw] 50 45 40 35 30 25 20 15 10 5 0 p evap = 0.5 bar 10 20 40 80 Correction factor for condensing temperature R407C Condensing temperature +30 C +40 C +50 C 0.7 1.0 1.4 Above capacities have to be multiplied with the correction factor. 12 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 Danfoss A/S (RC-CMS/MWA), 05-2005

Mass flow rate Mass flow [kg/s] 0.05 0.04 0.03 0.02 R407C p evap = 0.2 bar 0.01 0.00-6 -5-4 -3-2 -1 0 1 2 3 TCHE 3 TCHE 4 TUH 9 Mass flow [kg/s] 0.30 0.25 0.20 0.15 0.10 p evap = 0.5 bar 0.05 0.00 10 20 40 80 Correction factor for condensing temperature R407C Condensing temperature +30 C +40 C +50 C 0.7 1.0 1.4 Above capacities have to be multiplied with the correction factor. Danfoss A/S (RC-CMS/MWA), 05-2005 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 13

Replacement capacity R410A Replacement capacity [kw] 20 18 16 14 12 10 8 6 4 2 0 Start opening: t evap = 18 C p evap = 0.2 bar TCHE 3 TCHE 4 TUH 9 Replacement capacity [kw] 120 100 80 60 40 20 0 p evap = 0.5 bar 10 20 40 80 Correction factor for condensing temperature R410A Condensing temperature +30 C +40 C +50 C 0.8 1.0 1.2 Above replacement capacity has to be multiplied with the correction factor. 14 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 Danfoss A/S (RC-CMS/MWA), 05-2005

Mass flow rate Mass flow [kg/s] 0.10 0.09 0.08 0.07 0.06 0.05 0.04 0.03 R410A Start opening: t evap = 18 C p evap = 0.2 bar 0.02 0.01 0.00 TCHE 3 TCHE 4 TUH 9 Mass flow [kg/s] 0.60 0.50 0.40 0.30 0.20 p evap = 0.5 bar 0.10 0.00 10 20 40 80 Correction factor for condensing temperature R410A Condensing temperature +30 C +40 C +50 C 0.8 1.0 1.2 Above replacement capacity has to be multiplied with the correction factor. Danfoss A/S (RC-CMS/MWA), 05-2005 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 15

Design/Function 1. Bulb with capillary tube 2. Diaphragm element 3. Setting spindle for adjustment of opening point/minimum suction pressure 4. Fixed orifice 5. Filter TUH, Angleway TCHE, Angleway 1. Bulb with capillary tube 2. Thermostatic element 3. Pressure pin seal 4. Two-way balanced port 5. Setting spindle for adjustment of static superheat SS, Straightway 16 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 Danfoss A/S (RC-CMS/MWA), 05-2005

Dimensions and weight TUH Connection dimensions, see ordering table. TUH, Angleway - all dimensions in mm Weight 0.13 kg Dimensions and weight TCHE Connection dimensions, see ordering table. TCHE, Angleway - all dimensions in mm Weight 0.15 kg Danfoss A/S (RC-CMS/MWA), 05-2005 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 17

Dimensions and weight Connection dimensions, see ordering table., Straightway Type Connection, ODF solder Capillary tube H 1 H 2 H 3 H 4 L 1 L 2 L 3 L 4 ød 1 ød 2 Weight Inlet outlet Inlet outlet length in. mm m mm mm mm mm mm mm mm mm mm mm kg 10 5 / 8 5 / 8 16 16 1.5 32 7.5 5 104 45.5 45.5 34.5 70 45 15 0.39 20 5 / 8 5 / 8 16 16 1.5 37 9 8 122 48 48 38 119 53 16.5 0.60 40 7 / 8 7 / 8 22 22 3 42 13 11 145 57.5 57.5 41 111 60 20.3 0.79 80 1 1 / 8 1 1 / 8 28 28 3 47 17 13 165 67 67 44 148 72 20.3 1.34 18 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 Danfoss A/S (RC-CMS/MWA), 05-2005

Application TUH and TCHE Note: The bulb serves only as a reservoir for the charge, however, it is recommended to mount it in a position where the temperature variation during running conditions is limited (see a and b in the application drawings). b a 1. Evaporator 2. Condenser 3. Receiver 4. Solenoid valve 5. Discharge bypass valve with adjustable setting 6. Compressor System with capillary tube expansion and internal pressure-equalised hot gas bypass valve type TUH System with capillary tube expansion and external pressure-equalised hot gas bypass valve TCHE or System with capillary tube expansion and external pressure-equalised hot gas bypass valve TCHE or Danfoss A/S (RC-CMS/MWA), 05-2005 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 19

Application 1. Evaporator 2. Condenser 3. Receiver 4. Solenoid valve 5. Discharge bypass valve with adjustable setting 6. Compressor System with thermostatic expansion valve expansion and external pressure-equalised hot gas bypass valve TCHE or 20 RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483 Danfoss A/S (RC-CMS/MWA), 05-2005