Reliability and availability analysis of a 10 K helium refrigerator

Similar documents
Development of a measurement and control system for a 10 K refrigerator based on Siemens PLC S7-300

Measured Performance of Four New 18 K Helium Refrigerators for the LHC Cryogenic System

Performance test of a helium refrigerator for the cryogenic hydrogen system in J-PARC

Cryogenics for Neutral Beam Injector System

AVAILABILITY AND RELIABILITY OF CERN CRYOPLANTS

3.2 Cryoplant and Cryodistribution

Air Liquide Advanced Technologies Division Sassenage, 38360, France

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

A CRYOGENIC TEST STATION FOR SUBCOOLING HELIUM HEAT EXCHANGERS FOR LHC

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

ScienceDirect. Development progress of critical equipment in the CSNS cryogenic hydrogen system

Available online at ScienceDirect. Physics Procedia 67 (2015 )

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

ILNAS-EN 61649:2008. Weibull analysis. Analyse de Weibull. Weibull-Analyse

Cryogenics. Overview of the Jefferson Lab 12GeV Upgrade. J. Creel, K. Dixon, P. Knudsen, J. Wilson Jr.

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

False Alarm Analysis of the CATM-CFAR in Presence of Clutter Edge

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Design of Humidity Monitoring System Based on Virtual Instrument

Concept of a Powerful Cryogen-Free Dilution Refrigerator with Separate 1K Stage

HELIAL refrigerators. Range of automatic helium refrigerators

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Performance of the Variable Refrigerant Volume Air-Conditioning System. with Heat Recovery

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Study on an environmental simulation system of low/high temperature. for great space

The Development of Automatic Fire Alarm Standards and Related Products in China

Geothermal ORC Systems Using Large Screw Expanders

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

New fire control system design for fire fighting and rescue equipment Jianguo LUO1, a, Zehao BU2, b

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

A Small Refrigerator System for Cooling Thermal Shield of a Large Superconducting Magnet

Remote Helium Cooling Loops for Laboratory Applications

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

New Design for Energy Saving Water Dispensers

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Cryogenic refrigeration for the LHC

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

State Grid Zhejiang Electric Power Corporation Electric Power Research Institute, Hangzhou, , China

System Modeling of Gas Engine Driven Heat Pump

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Chapter 10. Refrigeration and Heat Pump Systems

The superconducting TF magnetic system of Tore Supra

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Shortcut Model for Predicting Refrigeration Cycle Performance

The reliability evaluation of LHC-5 hollow cathode heater

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Investigation, Analysis and Solution of Higher Noise of Heat Pump Water Heater

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

Advances in Liquid Nitrogen (LN 2 ) Based Lyophilization Technologies

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Experimental Investigation of the Padding Tower 1. for Air Dehumidifier

Cryogenic cooling with CUMULUS LF.

The Energy Consumption Investigation of the Hotel Central. Air-conditioning System and the Research of Energy Saving Measures

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Maintenance and Reliability Design Aspects SNS 2K Refrigeration System

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

5/12/2018 Climate Control System General Information and Diagnostics - Air Conditioning (A/C) System Recovery, Evacuation and Charging - G

OPERATIONAL EXPERIENCE ON CRYOGENIC SYSTEMS FOR LARGE-SCALE ACCELERATORS AT CERN

Indoor Thermal Environment of Residential Buildings in Three Cities of China

Functional Safety: the Next Edition of IEC 61511

Study on the North China Rural Water Supply Project O&M Cost Standard Rating

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

Experimental Research of Air Source Heat Pump Frosting and Defrosting in a. Double Stage-Coupling Heat Pump

Optimization of Hybrid Noncondensable Gas Removal System for a Flash Steam Geothermal Power Plant

Heat Transfer in Evacuated Tubular Solar Collectors

A Novel Heat Recovery System for High Temperature and High Humidity Gas Qing Hao1, a, Meng Si2, b

INFLUENCE OF DIFFERENT TEMPERING PERIOD AND VACUUM CONDITIONS ON THE RICE GRAIN BREAKAGE IN A THIN LAYER DRYER

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Research on Decision Tree Application in Data of Fire Alarm Receipt and Disposal

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

THE TORE SUPRA CRYOGENIC SYSTEM. Design and operation

VAPOR COMPRESSION HEAT PUMP USING LOW TEMPERATURE GEOTHERMAL WATER: A CASE STUDY OF NORTHERN THAILAND

HYDROCARBON REFRIGERANT SYSTEM COMMISSIONING REPORT. Duvel International Trading (China) Limited

A TRNSYS Simulation Case Study on Utilization of Heat Pump For both Heating and Cooling

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Pocket Dilution Cooler

Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units

SPECIFICATION OF FOUR NEW LARGE 4.5 K HELIUM REFRIGERATORS FOR THE LHC

R32 Compressor for Air conditioning and Refrigeration applications in China

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Experimental Study and Analysis of Condenser Performance under Dual Backpressure Operation Mode

Transcription:

Reliability and availability analysis of a 0 kw@0 K helium refrigerator J Li,, L Y Xiong, L Q Liu, H R Wang, and B M Wang Key Laboratory of Cryogenics, Technical Institute of Physics and Chemistry, Chinese Academy of Sciences, Beijing, 0090, China University of Chinese Academy of Sciences, Beijing 00049, China jingli@mail.ipc.ac.cn Abstract. A 0 kw@0 K helium refrigerator has been established in the Technical Institute of Physics and Chemistry, Chinese Academy of Sciences. To evaluate and improve this refrigerator s reliability and availability, a reliability and availability analysis is performed. According to the mission profile of this refrigerator, a functional analysis is performed. The failure data of the refrigerator components are collected and failure rate distributions are fitted by software Weibull++ V0.0. A Failure Modes, Effects & Criticality Analysis (FMECA) is performed and the critical components with higher risks are proposed. Software BlockSim V9.0 is used to calculate the reliability and the availability of this refrigerator. The result indicates that compressors, turbine and cryopump are the critical components and the key units to this refrigerator. The mitigation actions with respect to design, testing, maintenance and operation are proposed to decrease those major and medium risks.. Introduction A 0 kw@0 K helium refrigerator has been established in the Technical Institute of Physics and Chemistry, Chinese Academy of Sciences. This refrigerator allows the production of an equivalent cooling capacity of 0 kw at 0 K. This refrigerator has been accepted technically in May 05. It has been operating more than 7 hours (three days) successfully several times to pass the technical acceptance. According to the project requirement document, the Mean Time to Failure (MTTF) of this 0 kw@0 K refrigerator should be at least 8000 hours. In order to evaluate and increase this refrigerator s reliability and availability, a reliability and availability analysis is performed. An ITER Reliability, Availability, Maintainability and Inspectability (RAMI) program is adopted []. The failure data of the similar refrigerators components were collected. Software Weibull++ V0.0 is used to fit these failure data s distributions. Software BlockSim V9.0 is used to calculate this refrigerator s reliability and availability. The result indicates that compressors, turbine and cryopump are the critical components and the key units. The mitigation actions mainly about the preventive maintenance are given.. Overview of the 0 kw@0 K refrigerator Figure shows the Process Flow Diagram (PFD) of the 0 kw@0 K refrigerator. As shown in figure, this 0 kw@0 K refrigerator consists of two main parts, i.e. the compressor station and the cold box. The compressor station is composed of two screw compressors, an oil removal system (ORS), a helium buffer tank and a gas management valve panel composed of three room temperature valves, CV-, CV-

and CV-3. The cold box is a vacuum insulated cold box which contains two heat exchangers, the first stage heat exchanger HEX and the second stage heat exchanger HEX and two control cryovalves including a Liquid Nitrogen (LN) supply valve CV-4, a turbine inlet valve CV-5, and a turbine. E-3 is a dummy load which provides a heat capacity of 0 kw. These two screw compressors are in parallel. Each compressor provides half capacity of 400 g/s. LN CV-4 ORS GN CV- CV-5 Turbine C- C- CV- CV-3 Buffer tank E-3 HEX HEX Figure. The Process Flow Diagram (PFD) of the 0 kw@0 K refrigerator 3. Functional analysis of the 0 kw@0 K refrigerator Based on the process flow diagram of this 0 kw@0 K refrigerator, a functional analysis is performed. The principal functionality of this 0 kw@0 K refrigerator is to provide 0 kw@0 K cooling power with the support of the auxiliary system. The simplified functional analysis of this refrigerator is summarized in figure. The main function To provide 0 kw@0 K cooling power has been split into two parts, the first part is sub-function of the refrigerator To provide cryogenic environment and 0 kw@0 K cooling power and the second part is To provide services and features to support main function of 0 kw@0 K refrigerator. 3.. To provide cryogenic environment and 0 kw@0 K cooling power This functionality has been split into two main functions. To provide cryogenic environment; The turbine.

To provide services and features to support main function of 0 kw@0 K refrigerator To provide atmospheric temperature GHe A. To control and monitor 0 kw@0 K refrigerator A.3 To provide auxiliary cold power A. To provide vacuum environment A.4 To provide cryogenic environment and 0 kw@0 K cooling power To provide cryogenic environment A. The turbine A. Figure. Simplified functional analysis of the 0 kw@0 K refrigerator 3.. To provide services and features to support main function of 0 kw@0 K refrigerator There are four sub-functions. To provide atmospheric temperature gas Helium; To provide auxiliary cold power; To control and monitor 0 kw@0 K refrigerator; To provide vacuum environment. 4. Reliability and availability calculation of this 0 kw@0 K refrigerator 4.. General assumptions The mission profile of this refrigerator, i.e. the purpose of this refrigerator is to provide 0 kw@0 K cooling capacity which is the maximum cooling capacity of this refrigerator. To study the reliability and availability of this refrigerator, the following assumptions should be taken into account. The failure of each of two compressors leads to lack of cooling power which is provided by this 0 kw@0 K refrigerator; The failure of Liquid Nitrogen pre-cooling system leads to lack of cooling power which is provided by this 0 kw@0 K refrigerator; In a pessimistic approach, it is considered that failure of any valves ( room temperature valves, CV-, CV-, CV-3 and all the nine cryogenic valves including CV-4, CV-5) leads to loss of refrigerator s cooling capacity; Only significant leakages of each of two heat exchangers lead to the stoppage of the refrigerator operation. 4.. Refrigerator components failure rate distribution The failure data of refrigerator components are important not only for reliability and availability calculation but also for failure modes, effects and criticality analysis (FMECA). Historical failure data in various sources should be searched and statistical assessments on components failures have been done []. Failure data are also collected from the manufacturer and the operating experience of the cryogenic

system [3, 4]. The experimental results and field data can also be analysed by graphical analysis using a Weibull plot [5]. In this paper, some refrigerator components, such as compressors, cryopump, Liquid Nitrogen precooling system, PLC and turbine, the failure data of them are collected from several refrigerator users in China. These users include the Free Electron Laser Facility of Peking University (PKU-FEL), Shanghai Synchrotron Radiation Facility (SSRF) and Beijing Electron-Positron Collider (BEPCII). The other refrigerator components failure data, for example, the heat exchangers and the valves (room temperature valves and cryovalves), are cited from operating experience of the cryogenic system [3, 4]. The failure data composed of complete data and right censored data. Figure 3 shows the sketch of complete data and right censored data. 0 0 Figure 3. The sketch of complete data and right censored data As figure 3 shows, when the Time to Failure (TTF) is equal to X, the failure data is a complete data. If the TTF is greater than X, TTF is unpredicted, the failure data is a right censored data. Only the complete data and right censored data are adopted to calculate the failure rate distribution in this research. The software Weibull++ V0.0 is used to fit the failure rate distribution. The following example illustrates how to fit the compressors failure rate distribution. The compressors used in 0 kw@0 K refrigerator is designed and produced by MAYEKAWA. The collected failure data of similar screw compressors are used to calculate the compressor s failure rate distribution. Table shows the complete failure time of compressor (marked as F) and right censored data of compressor (marked as S). Table. Collected compressor s failure data. No. F/S Time to F or S (hrs) No. F/S Time to F or S (hrs) S 340 5 S 6888 F 344 6 S 44 3 F 6504 4 F 78 Software Weibull++ V0.0 is used to fit the compressor s failure rate distribution. Maximum Likelihood Estimation (MLE) is adopted because there is right censored data. After calculation, the distribution of the compressor s failure rate is P-weibull distribution, β=.94, η=76.5 hrs. Failure rate (t= year) = 0.8

In this 0 kw@0 K helium refrigerator, there are two compressors. Each compressor provides half capacity of 400 g/s. To provide full capacity, each compressor should be available. Hence, in functional analysis, these two compressors are in series. Figure 4 shows the reliability block diagram of these two compressors. Figure 4. Reliability Block Diagram of two series compressors Failure rate of these two series compressors (t= year) = 0.35 This failure rate 0.35 will be used in the Failure Modes, Effects & Criticality Analysis (FMECA). The other refrigerator components failure rate distributions are also fitted with the same method. Table shows refrigerator components failure rate distribution and recover time for each component. That recover time is used to calculate the availability of this 0 kw@0 K helium refrigerator. That recover time is a mean time which is cited from Technical Institute of Physics and Chemistry (TIPC) repair experience. Table. Refrigerator components failure rate distribution and recover time No. Components Failure rate distribution Source Time to recover (TIPC experience) Compressor Weibull-P One week, 68 hrs, with spare parts b β=.94, η=76.5 hrs on sites Room temperature P-Exponential One week, 68 hrs, with spare parts a valves Mean Time = 76335877 hrs on sites 3 Log-normal-P LN precooling One day, 4 hrs, with spare parts on Log-Mean=9.76 hrs b system* sites Log-Std=0.508 4 Heat exchanger P-Exponential With significant leak, half a year, a Mean Time = 635789 hrs 4380 hrs 5 Cryovalve P-Exponential a One week, 68 hrs, with spare parts 6 Turbine 7 PLC control system Mean Time = 76335877 hrs Weibull-P β=.8, η=406. hrs Log-normal-P Log-Mean=9.93 hrs Log-Std=0.93 b b on sites One week, 68 hrs, with spare parts on sites One day, 4hrs, with spare parts on sites Weibull-P One day, 4 hrs, with spare parts on 8 Cryopump a β=.34, η=90.3 hrs sites a Cited from operating experience of the cryogenic system [3, 4]. b Fitted with collected failure data, using software Weibull++ V0.0. * LN precooling system doesn t include valve CV-4, CV-4 is considered in cryovalves. 4.3. Reliability and availability calculation of the 0 kw@0 K refrigerator According to the functional analysis and the general assumptions, a Reliability Block Diagram (RBD) of this 0 kw@0 K refrigerator can be established. Figure 5 shows the Reliability Block Diagram (RBD) of this refrigerator. In figure 5, all the components which include two compressors, three room

temperature valves, one LN precooling system (not including valve CV-4), two heat exchangers, six cryovalves, one turbine, one PLC control system and one cryopump are all in series. Figure 5. Reliability Block Diagram of this 0 kw@0 K refrigerator According to the figure 5, Reliability Block Diagram and the table 3, refrigerator components failure rate distribution, the reliability of this refrigerator is calculated using software BlockSim V9.0. According to the recovery time of Table, the availability of this refrigerator is also calculated using software BlockSim V9.0 by Monte Carlo simulation (0,000 simulations). Table 3 shows the reliability and the availability of this refrigerator. 0 kw@0 K refrigerator Table 3. The reliability and the availability of the 0 kw@0 K refrigerator Reliability for 3 months Reliability for year MTTF (hrs) Availability (for year) Time for 99.9% availability (hrs) 95.8% 5.0% 9 99.5% 960 Table 3 shows the Mean Time to Failure (MTTF) of this 0 kw@0 K helium refrigerator is 9 hours, it is about one year. This refrigerator s availability for one year is 99.5%. Time for 99.9% availability is 960 hours, it is 40 work days. 4.4. Reliability importance The Reliability Importance (RI) is a parameter to show which component has the greatest effect on the whole refrigerator s reliability. After the calculation using software BlockSim V9.0, the results show that in the short period of time within years, compressor, LN precooling system, PLC control system, cryopump and turbine have more effect on the whole refrigerator s reliability. In the longer period of time within 5 years, compressor has the most effect on the whole refrigerator s reliability. 5. Failure modes, effects and criticality analysis (FMECA) According to the functional analysis of this 0 kw@0 K refrigerator, a FMECA analysis was performed using a bottom-up approach to list the function failure modes and evaluate their risk level. The severity and occurrence rating scale is defined in Table 4 [6]. Table 4. Severity and Occurrence rating scale. Severity (S) Rating scale Occurrence (O) {Failure rate per year} Less than hour < 5 0 4 (less than once in 000 years) Between hour and day 5 0 4 << 5 0 3 (less than once in 00 years) Between day and week 3 5 0 3 << 5 0 (less than once in 0 years) Between week and months 4 5 0 << 5 0 (less than once in years) Between months and year 5 5 0 << 5 (less than five times per year) More than year 6 5 (more than five times per year)

The Criticality which is defined as the multiplication of Occurrence and Severity (C=O S) is used to evaluate magnitude of each risk. According to its level, the criticality is divided into major risk, medium risk and minor risk, representing by red, yellow and green respectively. Criticality greater than or equal to 3 is considered to be major risk, mitigation actions are mandatory to reduce the criticality. Criticality between 7 and 3 is categorized as medium risk and mitigation actions are recommended to reduce the criticality. While criticality less than 7 is considered to be minor risk, mitigation actions are required to reduce the criticality (optional). A detailed FMECA analysis is performed on this 0 kw@0 K refrigerator. Figure 6 and figure 7 show the initial and expected criticality matrix for this refrigerator. According to figure 6, there are 4 failure modes totally. There are major risks and 6 medium risks in the initial criticality matrix. The corresponding failures modes of these two major risks are: the turbine can t accomplish predetermined function and loss of function of compressor. As shown in figure 7, in the revised criticality matrix, there are 0 major risk and 6 medium risks after implementing mitigation actions. The number of major risks is reduced. 6 C=7 C=3 6 C=7 C=3 5 5 4 4 Oi 3 Or 3 5 3 0 0 3 4 5 6 Si 0 0 3 4 5 6 Sr Figure 6. Initial criticality matrix Figure 7. Revised criticality matrix Numbers and size of circles represent number of failure modes identified for each (severity, occurrence) coordinates. Criticality thresholds (7 and 3) separate the different risk zones (minor, medium and major). 6. Risk mitigation actions The mitigation actions with respect to design, testing, maintenance and operation are applied to decrease those major and medium risks. These mitigation actions are as follows: Reinforced logistic and preventative maintenance is recommended for heat exchangers; A reparation kit including shaft coupling, oil filter, gas filter for screw compressors must be available on site; A spare of vacuum pump must be available; Three turbines have been made, one is in operation and the others are as spares on sites. Quick mounting and dismounting technology is adopted.

7. Conclusion A reliability and availability analysis has been performed on a 0 kw@0 K refrigerator which has been established in the Technical Institute of Physics and Chemistry, CAS. The failure data were collected from the similar refrigerators users in China and which distribution was calculated using software Weibull++ V0.0. The compressors, turbine and cryopump are the critical components and key units to this refrigerator. After the risk mitigation actions, the major risks are eliminated. The Mean Time to Failure (MTTF) of this refrigerator is 9 hours which is greater than 8000 hours. References [] Houtte D V, Okayama K and Sagot F 00 RAMI Approach for ITER Fusion Engineering and Design vol 85 pp 0-4 [] Pinna T, Cadwallader L C, Cambi G, Ciattaglia S, Knipe S, Leuterer F, Malizia A, Petersen P, Porfiri M T, Sagot F, Scales S, Stober J, Vallet J C and Yamanishi T 00 Operating experiences from existing fusion facilities in view of ITER safety and reliability Fusion Engineering and Design vol 85 pp 40-45 [3] ITER documentation 0 RAMI analysis of cryodistribution WBS-34 summary report ITER_D_476UDV v. [4] ITER documentation 0 RAMI analysis of cryoplant WBS-34 summary report ITER_D_45VHQV v.0 [5] Woo Seong-woo, Park Jungwan and Pecht Michael 0 Reliability design and case study of refrigerator parts subjected to repetitive loads under consumer usage conditions Engineering Failure Analysis vol 8 pp 88-830 [6] Henry D, Trouve J, Chodimella C, Navion-Maillot N, Sagot F and Serio L 0 RAMI analysis of the ITER cryoplant and cryodistribution systems AIP Conference Proceeding 434 Washington USA pp 55-558 Acknowledgments This work is supported by the Key Laboratory of Cryogenics, TIPC, CAS (CRYOQN0307).