Innovative Technologies [and Design Concepts] in Commercial Foodservice

Similar documents
Designing and Operating an Energy Efficient Foodservice Facility March 12, 2014 Winnipeg, MB

Hot Water. The Efficiency Challenge!

Energy & Water Savings in Commercial Food Service

BETTER BUILDINGS BY DESIGN CONFERENCE 2008 Designing a Sustainable Commercial Kitchen FEBRUARY 13 BURLINGTON, VERMONT

Sustainable Hot Water: Better Design, Delivery, and Use

Demand-Controlled Ventilation for Commercial Kitchen Ventilation

RFMA 2016 March 13 15

Demand Control Ventilation What, When and Where?

New Era in Energy Efficiency!

25 Energy Saving Tips

FOOD SERVICE EQUIPMENT REBATES

for Energy & Water Savings in Commercial Food Service

Sanitation: Ware Washers, Water Heaters and the Plumbing of the Future

Performance of Solar Water Heating Systems in the United States

The (Hot) Water Efficient Commercial Kitchen. Charles M. Bohlig East Bay Municipal Utility District

Case Studies: Restaurant Energy Efficiency. hosted by:

for commercial kitchen ventilation

Fishnick.com. RFMA 2015 Feb 1-3, Fisher-Nickel, Inc. Field Notes: An Energy Auditor s 10 Year Odyssey in the. in Commercial Food Service

Energy Efficiency & Commercial Building Natural Gas Technologies. Presented by: Eric Burgis Energy Solutions Center

Kitchenology: Tales of Transformation and Efficient and Effective Operations

Food Service Technology Center Promoting Energy Efficiency in Food Service

Laboratory Evaluation of Hybrid and Advanced Water Heaters: Performance Overview in Hot Humid Climate

The Ed Roberts Campus Berkeley, CA

General Session Lab Meets the Real World: Case Studies of Energy Efficient Upgrades that Saved Money

Commercial Water Heater Performance: Laboratory Testing and Modeling

FCSI Conference April 20 th and 21 st Presentation by: Richard Young Senior Engineer and Director of Education

Cool Savings Program Report

LACLEDE ENERGY EFFICIENCY PROGRAMS

Data driven insights from the nation s deepest ever customer energy research

WHAT YOU NEED TO KNOW BEFORE THE NRA SHOW

High Performance Building Guide 1

Demand-Controlled Ventilation For Commercial Kitchens

* Peak kw is determined by the average kw load reduction occurring between 1PM and 4PM on weekdays during June, July and August.

Food Service Technology Center

David Reynolds, Business Development Manager. Halton Group Foodservice Division

90.1 and Designing High Performance Commercial Kitchen Ventilation Systems BY DON FISHER, P.ENG., RICH SWIERCZYNA,

Food Service Technology Center

Why ENERGY STAR? ENERGY STAR is a voluntary partnership between EPA and industry organizations.

Focus on Energy Business Programs Summary of Services and Incentives July 2009

CASE STUDY: HIGH EFFICIENCY HOT WATER SYSTEMS IN A COMMERCIAL KITCHEN. For the 2019 ACEEE Hot Water Forum, Nashville, TN

SUMMARY OF SERVICES & INCENTIVES

Hot Water System Performance Testing at PG&E s Applied Technology Services: Mimicking a Full-Service Restaurant in the Laboratory

Heat Pump Water Heaters: A Key Energy Technology for California

Specifying High-Efficiency Water Heaters for Food Service

Dehumidification: Energy Efficiency Comparisons

Food Service Technology Center

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003

Hot Water Distribution System Losses in a Net-Zero Home

Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT

Food Service Technology Center

On Balance: Heat Rejection Control a Packaged Solution

Effective ventilation is necessary for the comfort

Update Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South

Design Guide Improving Commercial Kitchen Ventilation System Performance

Enhance Facility Energy Management at Naval Expeditionary Base Camp Lemonnier, Djibouti. 12 May 2011

TECHNOLOGY AND MARKET ASSESSMENT FORUM: NATIONAL ACCOUNT PRESENTATION Presented by Melisa Marks October 26, 2011

Presentation Outline. Commercial 1 Track. Unit #4: Commercial Water Heating

InterNACHI Home Energy Inspection for th Street

NAECA Water Heaters. Tankless (Instantaneous) < 2 gallons Natural Gas 75,000 Btu 200,000 Btu Oil 105,000 Btu 210,000 Btu Electric

Strategies for Summer Utility Savings. Residential Environmental Program Series May 15, 2013

Heat Pump Water Heater Technology Development. EEBA High Performance Home Summit Ed Vineyard Oak Ridge National Laboratory

Copyright 2003 IBACOS, Inc. All rights reserved.

Variable Ventilation for the Kitchen:

Heating and Hot Water

Cooling Options for Geothermal and Concentrating Solar Power Plants

Energy Efficient Options for Residential Water Heating

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

The Energy+ Household:

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church

Residential Water Heating

Field Evaluation of Pre-Commercial Residential Gas Heat Pump Water Heaters

Sivu 2/8 Rate data Description Suomi Shut off times total 0.0 h/day Weekends with shut off times yes Daytime rate of heat pump Time for daytime rate 5

MEASURED PERFORMANCE DATA FOR

Heat Pumps and Public Swimming Pools, a Perfect Match

Getting the Heat. Out of the Kitchen

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

UPGRADES. [Energy Efficiency] Base Points

Natural Gas Energy Efficiency Program. The Hotel/Lodging Industry

Benefits of ENERGY STAR Commercial Water Heaters in the Food Service Industry

Updates From an In-Depth Hot Water System Replacement Project in a Full-Service Restaurant

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.

CONVECTION OVENS FOR FOOD SERVICE APPLICATIONS BLODGETT SHO-E

Daikin Blueprint: Delivering Hot Water with a Chiller

Farm Energy Audit Workshop

Special Topics on Residential HVAC

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

COMMERCIAL Washington Incentives

2009 IECC Commercial Mechanical Requirements

Energy-Efficiency Options for Residential Water Heating

WATER HEATING PAGETTE

Living the (Solar) Dream Powering your lifestyle with the sun Ron Kube. Photo: Great Canadian Solar

2012 Catalog Version AUG 2012 Noritz America Corporation. All rights reserved.

MSYS 4490 AC Systems

COMMERCIAL. Oregon Incentives

energy-efficient Hot Water Never Looked So Good

REFRIGERATION Open case to New Reach-in Low or Medium Temperature Low Temp Coffin to New High Efficiency Reach-In...

Path to Energy Savings & Solar

How to Heat Water in All-Electric Homes & Apartments?

Hot Water Generation for Commercial and Industrial Applications. Paul Marsden Specification Sales Manager

Transcription:

Innovative Technologies [and Design Concepts] in Commercial Foodservice Don Fisher, P. Eng. Fisher Consultants PG&E Food Service Technology Center 925-866-5770 dfisher@fishnick.com

Food Service Technology Center: Who? What? Why? The Food Service Technology Center (FSTC) is an unbiased energy-efficiency research program funded by California utility customers. Specializing in commercial food service. Promoting energy efficiency and performance Celebrating 27 years of hard work!

rebate info design guides cost calculators seminars energy tips contact information

Our Mission is to bring MPG and Performance information to the entire commercial food service world.

Why? Food Service is Energy Intensive! 7 times more 5 times more Source: www.energy.ca.gov/2006publications/cec-400-2006-005/cec-400-2006-005.pdf

We ve had some major success:

ENERGY STAR Categories www.energystar.gov/cfs Refrigeration Hot Holding Cabinets Fryers Steamers Griddles Dish Machines Ice Machines Convection Ovens

Appliance Testing Laboratory create ASTM Standard Test Methods & miles-per-gallon numbers for appliances The controlled environment levels the playing field.

A single appliance can consume more energy per year than your home! >

If your had to gas each appliance every morning, one s perspective would quickly change

Consider Total this Operating line s Energy Cost Bill $11,400 Manual Griddle $3,000/yr Broiler Range $3,000/yr $1,000/yr Ovens $2,000/yr Fryer $2,000/yr Refrigerated Chef Ba $400/yr

Each commercial kitchen can include dozens of energy uses. Example: A typical McDonald s kitchen has about 70 different pieces of gas and electric equipment.

What have we learned?

Appliances are not created equal!

What makes an appliance more efficient? Induction Good Heat Exchange Smart Controls Insulation Powered or IR Burners

...less efficient? Poor Heat Exchange Low-Cost Components No Insulation Manual Control

Dead giveaway for an Inefficient Fryer Cast Iron Burner

Insulation Saves Energy! 40% Reduction in Energy Use

at $0.90 per therm! Rated input: 144,000 Btu/hr Assume average consumption of 100,000 Btu/h Over a 10 hr Day 360 days per year @ $0.90/therm 100,000 Btu/h = 1 therm, so.. 1 therm x 10 hr x 360 days = 3600 therms/yr = 3600 therms x $0.90 = $3240/yr!

Why not a lid?

The Steamer Challenge: The closed-system steamer is much more energy and water efficient

8-Year Life-Cycle Cost Three-pan Steamer Example $17,500! $950 Based on 10 /kwh and $5 a unit for water

But is there a compromise in equipment performance?

Gas Fryer Efficiency 70 Cooking-Energy Efficiency (%). 60 50 40 30 20 10 Low Efficiency Mid Efficiency High Efficiency 0 1 3 5 7 9 11 13 15 17 19 21 23 25 Test Fryer Number

Gas Fryer Idle Rates Idle Energy Rate (x 1,000 Btu/h). 18 16 14 12 10 8 6 4 2 0 1 3 5 7 9 11 13 15 17 19 21 23 25 Test Fryer Number High Efficiency

Gas Fryer Production Capacity 80 70 High Capacity High Efficiency Production Capacity (lb/h). 60 50 40 30 20 10 0 Low Capacity 1 3 5 7 9 11 13 15 17 19 21 23 25 Test Fryer Number

High Efficiency = High Performance

And Now... Something Really Cool!

Gas Ranges Have Low Efficiency (approx 30%)

Can the Pot Make a Difference? Fins Improve Heat Transfer

Let s Compare Heat-Up Times* 25 Heat-Up Time (min)* 20 15 10 5 0 Standard (Control) Pot Prototype Pot A *Time to heat 20 lb water from 70 F to 200 F per ASTM F1521

Can Range Efficiency Be Improved? Cooking Energy Efficiency (%) 50% 45% 40% 35% 30% 25% 20% 15% 10% 5% 0% Standard (Control) Pot Prototype Pot A http://www.fishnick.com/publications/appliancereports/ranges/eneron_pot_testing.pdf

and Hot!

Induction Cooktops Induction Wok! 85% plus efficiency and no standby energy!

Ice Machines Candidates for Load Shifting?

Bridges Restaurant, Danville CA Ice Machine Calculated Energy Use Old Ice Machine New Machine Rate Capacity (lb/24 h) 751 1,180 Rated Energy Use (kwh/100 lb/ice) 6.6 4.62 Normalized Duty Cycle (%) 81 52 Annual Energy Savings (kwh) - 4,986 On-Peak Reduction (kw) - 2.2

Cost Savings: Bridges By moving the operation of the ice machine to mostly offpeak periods the energy cost savings would be $508. 55% Reduction in energy and demand charges The Demand Charge savings would be an additional $481. Using a simple time clock to delay the operation of the ice machine this restaurant would see an annual savings of $989.

Evaporator Fan Motors Install high-efficiency electronically commutated motors (ECM) Example: Low efficiency motor draws 135 watts ECM motor draws only 44 watts Save 91 watts or $120 dollars a year of fan energy Save $60 to $120 dollars a year of compressor energy Motor costs about $150 Payback is less than one year! Operating cost based on an electric utility rate of $0.13/kWh

Leveraging Energy and Water Savings in Hot Water http://www.fishnick.com/design/waterheating/water_heating_design_guide_final.pdf

High Efficiency (Condensing) Water Heater Blower Air Inlet Burner Water Outlet Exhaust Water Inlet

High Efficiency Pros condensing 95% + efficiency Standby loss: 600 1000 Btu/h potential lower cost installation Cons condensing more complex not the standard potential for repair delay higher first cost

Tankless (Instantaneous) Takagi Industrial Co. USA Inc.

Tankless Pros smaller footprint outside installation possible (some climates) no standby loss Cons 80-84% thermal efficiency low-flow limits may need multiple units special installation required (stainless venting) maintenance may be higher High efficiency condensing models (>94%) are now available in North America!

PIER Funding for Research at PG&E Applied Technology Services

ANSI TE Test at PG&E ATS Lab Standby loss of HE tank is 670 Btu/h versus SE tank at 1650 Btu/h

Retro-Commissioning Results from ATS Lab System delivery efficiency of a distribution system with 1 -thick insulation

Retro-Commissioning Results from ATS Lab System delivery efficiency of a non-insulated distribution system dropped by 9%!

Intelligent Water Heaters? Easy to read and accurate thermostats are needed Condensing water heaters with central processing units

Hand Sink Delivery Problems from a High- Foot-Traffic Facility with no Recirculation 1-month data set Recorded 10-sec data intervals Filtered only for flow periods Sorted by temperature Temp. deemed satisfactory for hand washing if >100 F Results of testing 100 F water reached the lavatory 14% of the total draw time and the staff hand sink only 3% of the total draw time

One Solution: Distributed Generation A hybrid system that is a combination of electric tankless heaters at remote hand sinks and a simple distribution system in the kitchen fed by a water heater placed centrally Benefits: works well with low flow aerators, saves energy and increases hot water delivery performance

Another Solution: Demand Circulation The task of demand circulation is to circulate hot water in the supply line and down to specified fixtures on demand and deactivate automatically when hot water has reached its target. Demand circulation saves energy and improves hot water delivery.

Hot Water Systems of Tomorrow Will move towards net zero-energy water heating. Heat recovery and renewable energy technologies will become the primary water heaters.

Heat Recovery Potential?

Flue Gas Heat Recovery Cooking Effluent Cool Flue Exhuast Air Fryer Flue Heat Exchanger Flue Gases Hot Water Out Cold Water In Fryer Energy Input

Conveyor: Door Type: Dishmachine with Integrated Heat Recovery Waste Air HR Drain Water HR

Advantages of Units with Heat Recovery Some models operate on the cold water line only for wash tank fill and operation! Potential to reduce the size of the water heater. Potential to reduce the length and diameter of the distribution system. Potential to eliminate the need for recirculation, no longer necessary to get 140 F water to the dishwasher (with cold-water only unit). Potential to drop heater thermostat by 20 F, saving energy.

Operating Cost Comparison

Solar Preheating More cost effective than solar water heating (where the system is designed for a high solar fraction). Lower cost collectors, less solar storage capacity

Heat Rejected from Refrigeration

Refrigerant [De-superheater] Heat Recovery? Mueller Fre-Heater Therma-Stor

Commercial Heat Pump Water Heaters High efficiency with typical COP 4 with ambient temp of 80 F in kitchen 1 unit of energy in = 4 units of heat out for water heating + 3 units of space cooling Capable of reducing cost of running an electric resistance heater by up to 75% Great way to reduce humidity in the sanitation area or capture waste heat from the cooking area in the kitchen Unit can provide spot cooling in the kitchen and heat hot water to up to 140 F

Typical Flow Rate: 0.13 gpm 51,246 gal/yr water/sewer: $340

Coffee Chain removes a water waster!

Designing Energy Efficiency into Commercial Kitchen Ventilation!

The Design Challenge! There is no piece of equipment in the commercial kitchen that generates more controversy that the exhaust hood!

Average of Operative Temperature for Kitchen Type and Kitchen Zones with 95% confidence interval (100 kitchens) 80 90 F Note: c is Cooking, p is Preparation, and d is Dishwashing zone.

Will integrated CKV-HVAC Design improve thermal comfort? And what does CKV-HVAC integration really mean? Conversely, what does NOT integrating CKV with HVAC mean?

Non-integrated design 8000 cfm 1000 cfm 7000 cfm

Integrated design 3000 cfm 6000 cfm 3000 cfm

On an air balance schedule the difference is very subtle 8000 cfm 1000 cfm 7000 cfm Non-integrated design

but the thermal comfort impact may be huge! 3000 cfm 6000 cfm 3000 cfm Integrated design

Wall Canopy with Displacement MUA (C&C = 4100 cfm, 2 charbroilers cooking)

Proximity Hood with Displacement MUA (C&C = 1250 cfm, 2 charbroilers cooking)

No 4-Way Diffusers Near Hood!

Displacement Ventilation Displacement Units

Perforated Supply Plenum (PSP)

ASHRAE Standard 90.1-2010 If a kitchen/dining facility has a total kitchen hood exhaust airflow rate greater than 5,000 cfm then it shall have one of the following: a) At least 50% of all replacement air is transfer air that would otherwise be exhausted. b) Demand ventilation system(s) on at least 75% of the exhaust air. Such systems shall be capable of at least 50% reduction in exhaust and replacement air system airflow rates, including controls necessary to modulate airflow in response to appliance operation and to maintain full capture and containment of smoke, effluent and combustion products during cooking and idle. c) Listed energy recovery devices with a sensible heat recovery effectiveness of not less than 40% on at least 50% of the total exhaust airflow.

Demand Ventilation Control Technologies Duct Temperature Sensor & Infrared Sensors Duct Temperature Sensor & Smoke Detection Duct Temperature Sensor

Large Hotel Kitchen

Front Line

Back Line

16 14 Without DVC With and Without Melink Exhaust and Makeup Fan Power With Melink DVC 5.3 kw kw W/O Melink DVC 14 kw 12 10 Avg. Reduction = 8.7 kw 8 6 4 2 0 12:00 AM 1:15 AM 2:30 AM 3:45 AM 5:00 AM 6:15 AM 7:30 AM 8:45 AM 10:00 AM 11:15 AM 12:30 PM 1:45 PM 3:00 PM 4:15 PM 5:30 PM 6:45 PM 8:00 PM 9:15 PM 10:30 PM 11:45 PM kw Time

Air-to-Air Heat Recovery Unit

West Point

Air-to-Air HX Toronto Restaurant

Gas Cost $9,000 $8,000 $7,000 $6,000 $5,000 $4,000 $3,000 $2,000 $1,000 Baseline Actual $0 Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct 36% reduction = $22,600 per year! (at $1.30/therm)