CIRCULATION FAILURE IN A BOILER. By K.K.PARTHIBAN, Boiler Consultant Venus Energy Audit System /

Similar documents
A CASE OF BOILER FAILURE DUE TO OVERSIZING OF BOILER FEED PUMP

LESSONS LEARNT FROM TROUBLESHOOTING

Optimizing Strategy for Boiler Drum Level Control

Problem Cause Remedial action. Gauge glass There was excess chemical dosage The normal ph recommended was 9.5 to See photo 3 & 4.

A FREAK INCIDENT OF A BED SUPERHEATER FAILURE

CONTROLLING BOILER SWELL AND SHRINK

IE059: Boiler Control and Instrumentation for Engineers & Technicians

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful

2. Sketch and describe a steam drum internal feedwater pipe. 3. Identify and describe a steam drum continuous blowdown line.

Reactor-Boiler and Auxiliaries - Course 433 BOILER STEAM AND WATER SYSTEMS

Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants. Govind Rengarajan, P.E.CEM, Dan Taylor

Steam and Gas Power Systems Prof. Ravi Kumar Department of Mechanical and Industrial Engineering Indian Institute of Technology - Roorkee

Burner Management and Combustion Control. Copyright 2014 Rockwell Automation, Inc. All Rights Reserved.

Boiler Basics. Design and operation

Green Energy Engineering, Inc.

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

MODEL ANSWER FOR ELEMENTS OF MECH.ENGG.(17413) 1) steam boiler- It is a closed vessel in which steam is produced from water by combustion of fuel.

SURGING AND BLOW OUT OF LOOP SEALS IN A CFBC BOILER. By K.K.Parthiban Venus energy audit system

STEAM & POWER ENGINEERS

Document Code: 1 (15) Issuing date: Status:

Solution of I Mid Term Steam Engineering 6ME5A

Steam Generator (Boiler) & Steam Turbine. Steam Generator (Boiler) ME 268. Model Lab

Steam and Gas Power Systems Prof Ravi Kumar Department of Mechanical and Industrial Engineering Indian Institute of Technology - Roorkee

WHAT IS A BOILER? BOILER IS AN EQUIPMENT WHICH PRODUCES STEAM AT THE REQUIRED PRESSURE AND TEMPERATURE. BOILER DESIGN, MANUFACTURE & INSTALLATION ARE

Boiler Division HPS. Triveni Boiler

AUDITING ENERGY SYSTEM EFFECTIVELY

Boiler. Fire tube Boiler:

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

A Newsletter published by. for Industrial Steam and Power Users

SAFETY AND OPERATING MANUAL

AIM OF THE EXPERIMENT:- Study of boilers (fire tube, water tube) APPARATUS REQUIRED: - SL.NO NAME OF THE APPARATUS SPECIFICATION QUANTITY 01 Fire tube

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

The equipment and materials shall be designed and constructed in accordance with the ASME code section I 2001 ED A02 and Chinese Standards.

NFPA 85 COMPLIANCES OF BMS: A CASE STUDY OF BOILER CONTROL AT SBM OFFSHORE MALAYSIA COMPANY 1. AHMED ABOUELRISH 2 Universiti Teknologi Petronas

When you complete this module you will be able to: Describe various watertube boiler designs, including large generating units.

Title: Measurement of dryness fraction by Separating Calorimeter,

Boiler Basics: Design & Application Differences. Presented by Steve Connor July 30, 2014

150 BHP, 3 Pass High-Pressure Fire Tube Boiler mounted in a 53 Trailer

Improving Boiler Stability Through Advanced Regulatory Control

PACKAGED COMMERCIAL WATERTUBE BOILERS

SULPHUR RECOVERY UNIT

Originators of the Flexible Water Tube design

Originators of the Flexible Water Tube design

Low pressure boiler* inspection and maintenance

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures.

RECORDS OF ENERGY CONSERVATION COMPARISION OF LAST TWO YEARS

2.1 Create & Agree Demobilisation Plan Maintenance Procedure

Methods for controlling one and two pipe systems for comfort, even temperature distribution and energy savings.

Originators of the Flexible Water Tube design

Steam Power Cycles Part II

CASE STUDY PAPER INDUSTRY

What to Expect from Your EtaPRO Investment


BASIC BOILERS NAME :- DATE :-

PROFILE AMBICA. Multi Fuel Three Pass, Fire Cum Water Tube Steam Boiler Mfg. Range From 0.5 TPH to 35 TPH Working Pressure up to 50Kg / cm2

BETTER HOME COMFORT AND PEACE OF MIND STARTS WITH THE BEST SERVICE PLANS.

CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES

CONTROL SYSTEM D ESIGN, E NGINEERING & C ONSTRUCTION.

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

SECTION Boiler Controls & Waste Heat Recovery

SCHNEIDER-KESSEL BERLIN

Steam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle

Guidance on Safe Operation of Boilers Ref: BG01

Chapter 10 VAPOR AND COMBINED POWER CYCLES

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

CHAPTER 2: PROPERTIES OF STEAM AND STEAM POWER

ANNEX 6. Refinery No. 1 New Area. Problems Existing in the Current Condensate Return System of the New Area of Refinery No.1

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Basic information about quick steam generators/boilers System GEKA Heat Technology Gottfried Kneifel

Solution builder. in energy management.

ASPHALT DRUM MIX PLANT - MDM 25 (20-30 TPH) I TECHNICAL SPECIFICATIONS COLD AGGREGATE FEEDER

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

SAMPLE SPECIFICATIONS

ASPHALT DRUM MIX PLANT - MDM 25 (20-30 TPH) I TECHNICAL SPECIFICATIONS COLD AGGREGATE FEEDER. Gathering cum slinger conveyor 500 mm x 7.

MASS TRANSFER EQUIPMENT DESIGN CONSIDERATIONS FOR CRYOGENIC ABSORBERS, DEMETHANIZERS AND DEETHANIZERS

USING THE P-T CARD AS A SERVICE TOOL

By, Mohammad Sarfaraz Khan DGM (Technical) Faran Sugar Mills Limited Shaikh Bhirkio, District Tando Mohammad Khan, Sindh.

hydronics WHAT S WRONG WITH THIS SCHEMATIC?

White Paper. Integrated Safety for a Single BMS Evaluation Based on Siemens Simatic PCS7 System

Steam Ancillary Equipment. Primary Steam System, Water Treatment and Auxiliary Steam System Equipment

Boiler Mountings. Engr. Omar Sadath, Maritme Lecturer & Trainer, Bangladesh

Bringing a Steam Boiler On-Line from Cold.

CONTENTS. B. System Design and Performance Requirements

Oil and gas solutions. Unicon boiler plants for steam and hot water production

Williams & Davis Boilers


A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

LACLEDE ENERGY EFFICIENCY PROGRAMS

Flash Separators. Celebrating 12 years of service to the Indian Process Industry. We sell Savings

The. Steam ONE-PIPE STEAM SYSTEMS

CONSIDERATIONS IN CONVERTING A DUAL SHELL OR A DUAL PRESSURE COAL FIRED PLANT CONDENSER INTO A COMBINED CYCLE PLANT CONDENSER

Week 13 Chapter 10 Vapor & Combined Power Cycles

MOHICAN. MOHICAN 4-Pass Water Boiler, HP, PSI Section

CONDOR RAPID CONDOR RAPID/V STEAM FORCED CIRCULATION. Design pressure 11,76 bar Steam production from 45 to Kg/h

WELCOME TO THE AWT REGIONAL TRAINING PROGRAM

FLUIDIZED BED BOILERS

DM 45 (40-60 TPH) ASPHALT DRUM MIX PLANT - DM 50 (60-90 TPH) I TECHNICAL SPECIFICATIONS DM 60 ( TPH) COLD AGGREGATE FEEDER.

THERMAL ENGINEERING & GAS DYNAMICS ME-6002

CASE STUDY ON EFFICIENCY & AVAILABILITY DETERIORATION IN AN AFBC BOILER

Transcription:

CIRCULATION FAILURE IN A BOILER By K.K.PARTHIBAN, Boiler Consultant Venus Energy Audit System Email ID:parthi2006@gmail.com / venus.energy@gmail.com What it is presented here might be a happening in your boiler too! It has been more than 11 years the problem was not solved by the well known Boiler Company based at Pune. The Client was hesitant in referring the mystery to me. The client explained that the water level keep vanishing from the boiler very often. The problem was solved in a single visit. The problem & the solution are presented below. THE PROBLEM There are two 8 TPH boilers in this Plant. The boiler no 1 is a three pass shell type oil cum biogas fired boiler, supplied by a Baroda based company. When the plant capacity was increased, the client installed another 8 TPH oil cum gas fired boiler from Pune based company. The new boiler is a threepass shell tube boiler with a separate steam drum. The boiler is illustrated in figure no1. There are six downcomers feeding the water from the steam drum. The steam generated enters the steam drum via three risers. The boiler Operating pressure is 14 kg/cm2g. The plant steam load is steady and the two boilers share the load. The burners were provided with modulation arrangements initially. Presently the firing rate is set manually by the operator. However, the high-pressure trips are in action. The boiler will restart automatically on low fire. At times the high pressure tripping and restarting were proper. At times, when the boiler trips on high pressure there will be low water level occurrence too. The water in the gauge glass vanishes. It has happened more than 15 times in day. The boiler would not restart immediately, as the low water level interlock does not permit the restarting. The steam pressure in the plant header would come down to 5 kg/cm2g. Once the water level is restored in boiler no2, the firing would commence and the header steam pressure comes back to normal. The plant has been suffering due to low steam pressure for many years. The water level vanishing from gauge glass was something unusual. This was not happening in boiler no1, which is a shell type boiler. The Client had experienced the problem only year later after the boiler was installed. After which the client had taken up with the supplier, who had struggled nearly for a year and the problem remained. THE SOLUTION First I suspected the NRV of boiler no 2. Client explained they had removed the NRV flap and seen. I checked the pump capacity. If it were very much oversized, the downcomers would not be getting subcooled water for circulation (due to long idle time of pump). Further, the load was more than 5 TPH per boiler. The water level vanishing problem started after a year since the boiler was installed. The change was that the load had gone up. Then I doubted the adequacy of the downcomers and risers. The circulation calculation proved that the boiler should work even at full load. During the visit the boiler was in shut down condition and hence I requested the client to open the steam drum manhole of the boiler no 2. There was no proper internal arrangement for effective circulation. There is no arrangement to separate downcomers and risers sections. The risers and downcomers were located very close. The steam mixture exiting from the riser would enter the downcomers. Thus there will not be any circulation. The water in Bottom shell and in steam drum would together swell and produce the steam. Due to restriction for cold water to enter the bottom shell, the steam ratio in the boiler water would be high. The apparent water level would be very high under normal condition. When the boiler trips on high water level, the heat input is stopped. Hence the boiler water would shrink and cause low water level.

I suggested the modifications as in figure 3. Three separate riser boxes were added so that the rising steam- water mixture would pass through the box. This helps in reducing the resistance faced earlier. The feedwater distributor is added so that the downcomers gets sub-cooled water. The client carried out the modifications and then reported the problem is solved. CONCLUSION Boilers without proper circulation can lead to tube failures on starvation. This was a case the starvation was not there, as it was a shell type boiler with a float switch tripping the boiler on low water level. Clients who have the same type of boiler installed should be experiencing the problem.

FURNACE 277

FEED WATER PIPE FEED WATER PIPE

250 FEED WATER PIPE BOX