technical data air conditioning systems FTXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air

Similar documents
Air Conditioners. Technical Data FTXS-G

EEDEN technical data. air conditioning systems FTXS-G2V1B. Indoor units. Split - Sky Air

technical data air conditioning systems FVXS-FV1B R-410A Split Sky Air

technical data air conditioning systems FDKS-CVMB Concealed ceiling, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FT(Y)S-B Wall Mounted Unit Split Sky Air

technical data air conditioning systems FTKS/FTXS-C FTKS/FTXS-B Wall Mounted, Inverter Controlled Unit Split Sky Air

Air Conditioning. Technical Data. Wall mounted unit EEDEN FTX-J3

Air Conditioning. Technical Data. Flexi type unit EEDEN FLXS-B(9)

Air Conditioners Technical Data

Air Conditioning. Technical Data. Wall mounted unit EEDEN FTXG-JW

Daikin air conditioners for your home

Air Conditioners Technical Data

1 Features. Outdoor Units R-410A RYN-E3V1B. Split Sky Air Outdoor Units

technical data air conditioning systems FHYP-B Ceiling Suspended Unit Split Sky Air

technical data air conditioning systems FHYKP-B Ceiling Mounted Corner Cassette Split Sky Air

w w w. d a i k i n. e u ATXS-E

FTXS20G FTXS25G FTXS35G FTXS42G FTXS50G FTXS60G FTXS71G

Daikin air conditioners for your home

Air Conditioning. Technical Data EEDEN RXS-F8

technical data air conditioning systems RZQ-B Pair/Twin/Triple/Double Twin Application, Inverter Controlled Unit Split Sky Air

Full range. A class energy label. for your home WALL MOUNTED UNIT. air to air heat pumps. FTXS-G

Daikin air conditioners for your home

EEDEN technical data EKRTR. Altherma. Altherma

technical data air conditioning systems FHYCP-B7 4-way Blow Ceiling Mounted Cassette (950x950) Split Sky Air

technical data air conditioning systems RMXS-E7V3B1 Super multi plus Split Sky Air

Designed. colder climates. for AIR TO AIR HEAT PUMPS FTXS K FTXS-20-25K

Air Conditioning. Technical Data EEDEN AZQS-BV1

Pure comfort & design

for your home FTXS-G WALL MOUNTED UNIT

technical data air conditioning systems Indoor Units FCQ-C8VEB

Air Conditioning. Technical Data. Multi model application EEDEN MXS-E

Air Conditioners Technical Data

Air Conditioning. Technical Data. Pair, Twin, triple, double twin EEDEN RZQ-C

Air Conditioning. Technical Data. Concealed ceiling unit EEDEN FDXM-F

for your home FLXS-B Flexi type unit air to air heat pumps

Air conditioners Heating & Cooling

Pure comfort & design

EDUS Heat Pump - D-Series

BENEFIT FROM LOWER FUEL COSTS.

Air Conditioning. Technical Data. Ceiling suspended unit EEDEN AHQ-C

DAIKIN EMURA. FORM. FUNCTION. REDEFINED. THE NEW INDOOR AIR CONDITIONING UNIT FROM DAIKIN.

Air Conditioning. Technical Data EEDEN RZQSG-L(3/8)V1

TABLE OF CONTENTS RMXS-E8V1B

technical data air conditioning systems Indoor Units FBQ-C7VEB

EEDEN technical data ERHQ AA. Altherma. Altherma

Pure comfort & design

Air Conditioning Technical Data FFA-A > FFA25A2VEB > FFA35A2VEB > FFA50A2VEB > FFA60A2VEB

Air conditioners Heating & Cooling

Daikin air conditioners for your home, shops, restaurants and offices

Air Conditioners Technical Data

Air Conditioners. Technical Data FTY-H

Pure comfort & design

Ceiling Suspended Unit

Air Conditioners. Technical Data FBQ-C

Air conditioners, heating & cooling for the retailmarket and offices

Air Conditioning. Technical Data EEDEN RZQSG-L(8)Y1

Air Conditioning. Technical Data. 4-way blow ceiling mounted cassette EEDEN ACQ-C

Air conditioners, heating & cooling for shops,restaurants and offices

Remote control infrared ARC433B76 ARC433A8 ARC433B69

Air Conditioners. Technical Data RZQG-L

Air Conditioning Technical Data FAA-A > FAA71AUVEB > FAA100AUVEB

Air Purifiers. Technical Data MC70L

Air Conditioning. Technical Data EEDEN RZQG-L8/7V1

TABLE OF CONTENTS ERSQ-AAY1

AIR CONDITIONERS, HEATING & COOLING for your home

Air Conditioners Heating & Cooling

Air Conditioning. Technical Data. Small concealed ceiling unit EEDEN FDBQ-B

technical data air conditioning systems RZQ B8W1B Split Sky Air

emura Form. function. redefined.

Ventilation. Technical Data. Outdoor air processing unit, ventilation and air processing EEDEN FXMQ-MF

for your home FTYN-GX FT(Y)N-F

ON/OFF. Domestic Air conditioner. Wall mounted Type Arc-Series CAUTION HSU-14HR03/R2 HSU-18HR03/R2 1. READ THIS MANUAL CAREFULLY TO

EEDEN technical data ERHQ AA

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FDQ-B

EEDEN technical data. air conditioning systems RZQS71-140C7V1B. Split Sky Air

Including mounting plate. General Rating Nameplate. Terminal strip with earth terminal

Wall Mounted Unit ATX-JV / ARX-JV

for small rooms in multi application

Air conditioners, heating & cooling. for large spaces. air to air heat pumps. FDQ-B

Daikin Sensira R-32. Refreshingly new. Discreet wall mounted unit providing high efficiency and comfort

Heating. Technical Data. Daikin Altherma low temperature monobloc EEDEN EBLQ-BB6W1

Air Conditioners Technical Data

Heating. Technical Data EEDEN ERRQ-AY1

Daikin air conditioners for shops, restaurant and offices

Air Conditioning Technical Data RZASG-MV1

EEDE06-9. technical data. Altherma ERYQ A EKHBH007A / EKHBX007A EKSWW

EEDEN technical data. air conditioning systems RZQ-DV1. Split Sky Air

Information for end users. Floor standing units. 24/7 comfort in a contemporary package

EEDEN technical data. air conditioning systems RZQS-DV1. Split Sky Air

Air Conditioning Technical Data RZAG-MV1

Heating. Technical Data. Daikin Altherma low temperature monobloc EEDEN EDHQ-BB6V3

TABLE OF CONTENTS ERHQ BAV3

Fan Coil Units. Technical Data FWC-BT/BF

technical data air conditioning systems FH(Y)B-FK7 Concealed Ceiling Unit Split Sky Air

technical data Fan coil unit FWB small duct unit

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FXMQ-MB

Air Conditioners Heating & Cooling

RESIDENTIAL AIR TO AIR HEAT PUMPS Designed for colder climates. Optimised for heating

Daikin Sensira. Refreshingly new. Discreet wall mounted unit providing high efficiency and comfort

Transcription:

technical data FTXG-C Wall Mounted, Inverter Controlled Unit air conditioning systems Split Sky Air

Split - Sky Air ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment Daikin units comply with the European regulations that guarantee the safety of the product. Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory. Specifications are subject to change without prior notice. Zandvoordestraat 300 B - 8400 Ostend Belgium www.daikineurope.com EEDE05-1/3 05/005 Prepared in Belgium by Goekint Graphics

TABLE OF CONTENTS FTK/XS-DVMW 1 Features...................................................................... Specifications................................................................ 3 FTKS-D Nominal capacity and power input........................................... 3 Technical Specifications...................................................... 3 Electrical Specifications....................................................... 4 FTXS-D Nominal capacity and power input........................................... 4 Technical Specifications...................................................... 5 Electrical Specifications....................................................... 6 3 Dimensional drawing & centre of gravity................................. 7 Dimensional drawing......................................................... 7 Centre of gravity............................................................. 8 4 Piping diagram.............................................................. 9 5 Wiring diagram............................................................ 10 6 Sound data................................................................. 11 Sound pressure spectrum.................................................... 11 Split Sky Air Indoor Units 1

t i / l I Indoor Units R-410A FTK/XS-DVMW - r AS o X0 o 1 d 4K np T- 1SRF Features 1 Comfort mode reassures draught-free operation Vertical auto-swing function moves the discharge flaps up and down for efficient air distribution throughout the room You have the choice out of 5 fan speeds to select Daikin s special dry programme reduces humidity in the room without variation in room temperature Night set mode saves energy by preventing overcooling or overheating during night time Powerful mode can be selected for rapid cooling Indoor unit silent operation: "Silent" button on the remote control lowers the operation sound of the indoor unit by 3dB(A). The new titanium apatite photocatalytic air purification filter increases the active surface area for effective purification and deodorisation ECONO mode decreases power consumption so that other appliances that need large power supply can be used The movement sensor saves power consumption in unoccupied rooms Daikin remote controls give you easy control at your fingertips. optional 5 steps standard (integrated titanium apatite) Split Sky Air Indoor Units

Specifications -1 NOMINAL CAPACITY AND POWER INPUT For indoor units only: INDOOR UNITS FTKS0DVMW FTKS5DVMW FTKS35DVMW NOMINAL INPUT Cooling kw 0.035 0.035 0.040 For combination indoor + outdoor units (air cooled): COOLING ONLY - INVERTER CONTROLLED (air cooled) FTKS0DVMW FTKS5DVMW FTKS35DVMW RKS0DVMB RKS5DVMB RKS35DVMB Cooling capacity min~nom~max kw 1.~.0~.6 1.3~.5~3.0 1.4~3.4~3.8 Nominal input min~nom~max kw 0.30~0.49~0.83 0.30~0.685~0.96 0.30~1.045~1.7 EER 4.08 3.65 3.5 Energy label A A A Annual energy consumption Cooling kwh 45 343 53 - TECHNICAL SPECIFICATIONS FTKS0DVMW FTKS5DVMW FTKS35DVMW Casing Colour White Dimensions Packing Height mm 340 340 340 Width mm 855 855 855 Depth mm 65 65 65 Unit Height mm 83 83 83 Width mm 800 800 800 Depth mm 195 195 195 Weight Machine Weight kg 9.0 9.0 9.0 Gross Weight kg 1.0 1.0 1.0 Heat Exchanger Dimensions Length mm 610 610 610 Nr of Rows Fin Pitch mm 1.40 1.40 1.40 Nr of Stages 1 1 1 Tube type Hi-XA (7) Fin Type ML fin (Multi louver) Fan Type Cross flow fan Air Flow Rate Cooling High m 3 /min 8.7 8.7 8.9 Medium m 3 /min 6.7 6.7 6.9 Low m 3 /min 4.7 4.7 4.9 Silent m 3 /min 3.9 3.9 4.0 Fan Motor Model KFD-80-40-8B Number of steps 5 steps, silent and auto Motor Speed (cooling) High rpm 190 190 1310 Medium rpm 1050 1050 1070 Low rpm 810 810 830 Silent rpm 710 710 730 Fan Motor Output W 40 40 40 (high) Cooling Sound Power High dba 56.0 56.0 57.0 Sound Pressure High dba 38.0 38.0 39.0 Low dba 5.0 5.0 6.0 Silent dba.0.0 3.0 Refrigerant Type R-410A Split Sky Air Indoor Units 3

- TECHNICAL SPECIFICATIONS FTKS0DVMW FTKS5DVMW FTKS35DVMW Piping connections Liquid (OD) Gas Drain Diameter (OD) Diameter (OD) Diameter (OD) mm 6.35 6.4 6.4 mm 9.5 9.5 9.5 mm 18 18 18 Heat Insulation Both liquid and gas pipes Air Filter Removable/washable/Mildew proof Air direction control Left, right, up and downwards Temperature control Microcomputer control Standard Titanium apatite photocatalytic air purification filter Accessories Quantity manual Installation manual Infrared remote control Batteries Quantity Remote control holder Indoor unit fixing screws Quantity Mounting plate -3 ELECTRICAL SPECIFICATIONS FTKS0DVMW FTKS5DVMW FTKS35DVMW Power Supply Name VM VM VM Phase 1 1 1 Frequency Hz 50/60 Voltage V 0-40/0-30 Current Nominal running Cooling A 0.16 0.16 0.18 current (RLA) Wiring For Power Supply Quantity 3 3 3 connections Remark 4 for interunit wiring (included earth wiring) Voltage range Minimum -10% Maximum +10% Power Supply Intake Outdoor unit only -4 NOMINAL CAPACITY AND POWER INPUT For indoor units only: INDOOR UNITS FTXS0DVMW FTXS5DVMW FTXS35DVMW NOMINAL INPUT Cooling kw 0.035 0.035 0.040 Heating kw 0.035 0.035 0.040 For combination indoor + outdoor units (air cooled): COOLING ONLY - INVERTER CONTROLLED (air cooled) FTXS0DVMW FTXS5DVMW FTXS35DVMW RXS0DVMB RXS5DVMB RXS35DVMB Cooling capacity min~nom~max kw 1.3~.0~.6 1.3~.5~3.0 1.4~3.4~3.8 Heating capacity min~nom~max kw 1.3~.7~4.1 1.3~3.4~4.5 1.4~4.0~5.0 Nominal input Cooling min~nom~max kw 0.30~0.49~0.83 0.30~0.685~0.96 0.30~1.045~1.7 Heating min~nom~max kw 0.9~0.66~1.30 0.9~0.9~1.43 0.31~1.155~1.56 EER 4.08 3.65 3.5 COP 4.09 3.70 3.46 Energy label Cooling A A A Heating A A B Annual energy consumption Cooling kwh 45 343 53 4 Split Sky Air Indoor Units

-5 TECHNICAL SPECIFICATIONS FTXS0DVMW FTXS5DVMW FTXS35DVMW Casing Colour White Dimensions Packing Height mm 340 340 340 Width mm 855 855 855 Depth mm 65 65 65 Unit Height mm 83 83 83 Width mm 800 800 800 Depth mm 195 195 195 Weight Machine Weight kg 9.0 9.0 9.0 Gross Weight kg 1.0 1.0 1.0 Heat Exchanger Dimensions Length mm 610 610 610 Nr of Rows Fin Pitch mm 1.40 1.40 1.40 Nr of Stages 1 1 1 Tube type Hi-XA (7) Fin Type ML fin (Multi louver) Fan Type Cross flow fan Air Flow Rate Cooling High m 3 /min 8.7 8.7 8.9 Medium m 3 /min 6.7 6.7 6.9 Low m 3 /min 4.7 4.7 4.8 Silent m 3 /min 3.9 3.9 4.0 Heating High m 3 /min 9.4 9.4 9.7 Medium m 3 /min 7.6 7.6 7.9 Low m 3 /min 5.8 5.8 6.0 Silent m 3 /min 5.0 5.0 5. Fan Motor Model KFD-8040-8B KFD-80-40-8B KFD-80-40-8B Number of steps 5 steps, silent and auto Motor Speed (cooling) High rpm 190 190 1310 Medium rpm 1050 1050 1070 Low rpm 810 810 830 Silent rpm 710 710 730 Speed (heating) High rpm 130 130 1360 Medium rpm 110 110 1150 Low rpm 90 90 940 Silent rpm 80 80 840 Fan Motor Output W 40 40 40 (high) Cooling Sound Power High dba 56.0 56.0 57.0 Sound Pressure High dba 38.0 38.0 39.0 Low dba 5.0 5.0 6.0 Silent dba.0.0 3.0 Heating Sound Power High dba 56.0 56.0 57.0 Sound Pressure High dba 38.0 38.0 39.0 Low dba 8.0 8.0 9.0 Silent dba 5.0 5.0 6.0 Refrigerant Type R-410A Piping connections Liquid (OD) Gas Drain Heat Insulation Air Filter Air direction control Temperature control Diameter (OD) Diameter (OD) Diameter (OD) mm 6.4 6.4 6.4 mm 9.5 9.5 9.5 mm 18 18 18 Both liquid and gas pipes Removable/washable/Mildew proof Left, right, up and downwards Microcomputer control Split Sky Air Indoor Units 5

-5 TECHNICAL SPECIFICATIONS FTXS0DVMW FTXS5DVMW FTXS35DVMW Standard Accessories Titanium apatite photocatalytic air purification filter Quantity manual Installation manual Infrared remote control Batteries Quantity Remote control holder Indoor unit fixing screws Quantity Mounting plate -6 ELECTRICAL SPECIFICATIONS FTXS0DVMW FTXS5DVMW FTXS35DVMW Power Supply Name VM VM VM Phase 1 1 1 Frequency Hz 50/60 Voltage V 0-40/0-30 Current Nominal running Cooling A 0.16 0.16 0.18 current (RLA) Heating A 0.16 0.16 0.18 Wiring For Power Supply Quantity 3 3 3 connections Remark 4 for interunit wiring (included earth wiring) Voltage range Minimum -10% Maximum +10% Power Supply Intake Outdoor unit only 1 Sound values are measured in an anechoic room. Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound level drawings of this chapter. 3 The sound power level is an absolute value indicating the power which a sound source generates. 6 Split Sky Air Indoor Units

3 Dimensional drawing & centre of gravity 3-1 Dimensional drawing 3 Split Sky Air Indoor Units 7

3 3 Dimensional drawing & centre of gravity 3 - Centre of gravity FTK/XS0,5,35DVMW/L 4D04810 8 Split Sky Air Indoor Units

4 Piping diagram FTK/XS0,5,35DVMW/L 4 Indoor unit Maffler assy 7.0 CuT Heat exchanger 6.4 CuT Thermistor on heat exch. 6.4 CuT 7.9 CuT 6.4 CuT Cross flow fan Field piping (6.4 CuT) Fan motor Field piping 9.5 CuT (1.7 CuT) Refrigerant flow Cooling Heating 4D04791 Split Sky Air Indoor Units 9

5 Wiring diagram 5 FTK/XS0,5,35DVMW/L LEGEND Rectifier Transmission circuit Field wiring outdoor Protective earth FG Frame ground F1U Fuse H1P~H3P Pilot lamp L1 Coil M1F Fan motor M1S Swing motor PCB1~PCB4 Printed circuit board R1T, RT Thermistor S1~S38 Connector S1W switch X1M Terminal strip Intelligent eye sensor Wireless remote controller Signal receiver indoor 1 Size: length 70 x width 10. Refer to purchasing specification AS30300, unless otherwise specified. 3 This drawing was drawn on CAD system. 4 Caution: Note that operation will restart automatically if the main power supply is turned off and then back on again. 3D04753 10 Split Sky Air Indoor Units

6 Sound data 6-1 Sound pressure spectrum 6 FTKS0,5DVMW/L FTKS35DVMW/L Octave band sound pressure level (0dB = 0.000μbar) Octave band sound pressure level (0dB = 0.000μbar) Approximate threshold hearing for continuous noise Approximate threshold hearing for continuous noise Octave band center frequency Octave band center frequency 1 Measurement was taken in an anechoic room. The operation noise measuring method is in accordance with JISC961. 3 Operating conditions: Power source = 30 V, 50 Hz o------o H (A = 38) and o- - - -o L (A = 5) 4 noise differs with operation and ambient conditions. Location of microphone 1 Measurement was taken in an anechoic room. The operation noise measuring method is in accordance with JISC961. 3 Operating conditions: Power source = 30/0 V, 50/60 Hz o------o H (A = 39) and o- - - -o L (A = 6) 4 noise differs with operation and ambient conditions. Location of microphone 4D04844 4D04845A Split Sky Air Indoor Units 11

6 6 Sound data 6-1 Sound pressure spectrum FTXS0,5D Cooling Heating Octave band sound pressure level (0dB = 0.000μbar) Octave band sound pressure level (0dB = 0.000μbar) Approximate threshold hearing for continuous noise Approximate threshold hearing for continuous noise Octave band center frequency Octave band center frequency 1 Measurement was taken in an anechoic room. The operation noise measuring method is in accordance with 1m JISC961. 3 Operating conditions: Power source = 30 V, 50 Hz o------o H (A = 39), o- - - -o L (A = 6) 4 noise differs with operation and ambient conditions. Location of microphone 0.8m 1 Measurement was taken in an anechoic room. The operation noise measuring method is in accordance with 1m JISC961. 3 Operating conditions: Power source = 30 V, 50 Hz o------o H (A = 39), o- - - -o L (A = 9) 4 noise differs with operation and ambient conditions. Location of microphone 0.8m 3D0481 FTXS35D Cooling Heating Octave band sound pressure level (0dB = 0.000μbar) Octave band sound pressure level (0dB = 0.000μbar) Approximate threshold hearing for continuous noise Approximate threshold hearing for continuous noise Octave band center frequency Octave band center frequency 1 Measurement was taken in an anechoic room. The operation noise measuring method is in accordance with 1m JISC961. 3 Operating conditions: Power source = 30 V, 50 Hz o------o H (A = 39), o- - - -o L (A = 6) 4 noise differs with operation and ambient conditions. Location of microphone 0.8m 1 Measurement was taken in an anechoic room. The operation noise measuring method is in accordance with 1m JISC961. 3 Operating conditions: Power source = 30 V, 50 Hz o------o H (A = 39), o- - - -o L (A = 9) 4 noise differs with operation and ambient conditions. Location of microphone 0.8m 3D048 1 Split Sky Air Indoor Units