Bert A. McJimsey, Ph.D. Research Engineer The Trane Company Tyler, Texas. Dick Cawley, P.E. UPG Technology Team Leader The Trane Company Tyler, Texas

Similar documents
Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

R-407A R-448A R-449A

10/4/2013. The Changing State of Refrigerants

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Energy Use in Refrigeration Systems

Evaluation of HCFC Alternative Refrigerants

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

Otherwise, you can continue reading the file on the following pages.

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Air Conditioning Operation and Troubleshooting Matt Dunham

14. The center port of the manifold is used for evacuation, charging and refrigerant recovery.

Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Aspects of the. Following these key guidelines during a compressor changeout can ensure a successful, more efficient replacement.

Refrigerant changeover guidelines

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

The complete approach to the care and management of A/C & refrigeration systems

Scroll Chillers Transition from HCFC-22 to HFCs

The Essentials Of Working With R-410A

Residential Piping and Long Line Guideline

A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane.

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

Refrigeration Systems and Accessories

A/C Refrigerant. Air Conditioning systems use refrigerant to move heat from air inside the car to air outside the car

Development of HFC-134a Compressor for Domestic Refrigerator

OPERATING INSTRUCTIONS

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

MASS. MARITIME ACADEMY

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

Low GWP Refrigerants for Air Conditioning Applications

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

NZQA Expiring unit standard 3397 version 4 Page 1 of 5. Convert an automotive air conditioning system from R-12 to R-134a

Transcritical CO2 Bottle Cooler Development

Harold Ag & Mobile Products

REFRIGERANT CHANGEOVER

The Changing State of Refrigerants. Gary Parker Refrigerants Product Manager

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

Gary Parker Refrigerants Product Manager

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

APPLICATION & SERVICE GUIDE

CHAPTER 1 INTRODUCTION

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

DuPont Refrigerants. John McCormack Business Manager DuPont Chemicals and Fluoroproducts. R22 market and the ISCEON retrofit options

Chapter 2. Alternatives to HCFCs and their Characteristics

4/19/2013. The Changing State of Refrigerants

Motor Vehicle Air Conditioning (MVAC) System operation and the refrigerant cycle

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Often fellow technicians, co-workers and field personnel CHARGE REFRIGERANT DETERMINING PROPER SYSTEM

Refrigerant Recovery Unit, Model RRU134

B. A. T. Basic Appliance Training

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

OPERATING INSTRUCTIONS

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

Refrigeration Supplies

NUMBER: ISSUED: JULY 13, /336 73/23 STACKABLE CRESCENT CUBER KM-1300SWH-E SERVICE MANUAL FOR QUALIFIED SERVICE PERSON HOSHIZAKI

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

SERVICE MANUAL FOR QUALIFIED SERVICE PERSON HOSHIZAKI 89/336 73/23 SELF-CONTAINED CRESCENT CUBER KM-150BAF-E KM-150BWF-E

OPERATING INSTRUCTIONS

OPERATION & MAINTENANCE MANUAL AC860

1. Can SUPER SEAL ACR, SUPER SEAL HVACR & SUPER SEAL COMMERCIAL be used interchangeably? No, use as per application guidelines below:

National Maritime Center

Desiccants & Driers. By Norm Christopherson

KM-630MAF KM-630MWF KM-630MRF

Refrigerant Installation Quick Reference Guide

Filter Driers with Replaceable Core

SEVEN STEPS TO EFFECTIVE PRE- SEASON COOLING CHECKUPS

KM-900MAF KM-900MWF KM-900MRF KM-900MRF3

Refrigeration and. Modern. Air Conditioning. Bracciano, BS, M.Ed., Ed. Sp. Alfred F. Andrew D. Althouse, BS, (ME), MA. Carl H. Tumquist, BS, (ME), MA

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

Superheat charging curves for technicians

System Considerations for Refrigerant Blends with Temperature Glide

HFCs or the Old Refrigerants - what is the best Choice?

HOSHIZAKI MODULAR CRESCENT CUBER MODEL KM-280MAH KM-280MWH SERVICE MANUAL

OPERATION & MAINTENANCE MANUAL TX600

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Introduction and Overview of HVAC Systems Course 106

Application Guide. Refrigerant Piping Manual for Small Split Cooling and Heat Pump Systems SS-APG006-EN

HVACR Refrigeration

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

ASSIGNMENT OBJECTIVES

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

OPERATION & MAINTENANCE MANUAL RHS680

A Series Inertia Compressor Applications. Application Bulletin 115

NORDYNE has received reports of malfunctioning TXV valves in ton split systems and package units.

Honeywell Refrigerants. Retrofit Guidelines. R-404A/R-507A to: R-448A Solstice N40

APPLICATION DATA SHEET

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

Purdue e-pubs. Purdue University. T. Hamada Mitsubishi Heavy Industries Ltd. N. Nishiura Mitsubishi Heavy Industries Ltd.

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

Transcription:

The Eleventh Symposium On Improving Building Systems in Hot and Humid Climates MAY, 1998, FORT WORTH TEXAS RELIABILITY OF HEAT PUMPS CONTAINING R-410A REFRIGERANT Bert A. McJimsey, Ph.D. Research Engineer The Trane Company Tyler, Texas Dick Cawley, P.E. UPG Technology Team Leader The Trane Company Tyler, Texas ABSTRACT As a result of the Montreal Protocol in 1987 and subsequent approval of the U.S. Clean Air Acts, air conditioning manufacturers in the United States may not produce new products containing Hydrochlorofluorocarbons or HCFC after 2010 because of their potential destruction of stratospheric ozone. Residential and commercial rooftop units usually contain hydrochlorofluorocarbon -22, (also referred to as HCFC-22 or R-22). R-22 has been used successfully as a refrigerant in HVAC equipment for over 40 years. High volume production through these years has helped manufacturers to produce reliable products. R- 410A, a hydrofluorocarbon (HFC) mixture, is a leading candidate to replace R-22 in residential and light commercial air-conditioners and heat pumps. Most manufacturers do not have enough experience using R-410A to confidently design and build reliable R-410A units. The HVAC industry joined together in 1992 by forming AREP, Alternate Refrigerant Evaluation Program, to share pre-competitive data on alternate refrigerants. One major manufacturer announced a formation of black smudge on internal surfaces of field trial units using HFCs. Several causes were suggested but none were published. Reports of capillary tube plugging were rampant. Moisture in the Polyol Ester (POE) oils used with HFC refrigerants will break down to acid and alcohol when exposed to heat. Manufacturers have many tools to establish reliability with a product prior to mass production. Units and compressors can be run on life tests. Prototype test units can be built in the factory and then installed in the field by service technicians. Examples and results from each of these techniques are described within the paper. INTRODUCTION Air-conditioner and heat pump manufacturers must mass-produce reliable products to achieve a profit. The level of reliability with R-22 has come with over 40 years of continuous improvement. Switching to another refrigerant such as R-410A negates much of the learned information that makes the current product so reliable. Some manufacturers offer up to 10-year warranties on the products they produce. Customers have grown to expect air-conditioners to last for 15 years or longer. Unreliable mass produced products will alienate customers and cost the manufacturer high warranty repair expense. R-410A is a leading candidate to replace R-22 in unitary air-conditioning equipment. R-410A does not contain chlorine, which destroys ozone in the stratosphere. Because R-22 will not be phased out of new equipment until 2010 there will a period of time where both R-22 and R10A products will be available. R-410A products will have to compete head to head against R-22 products. Once manufacturers decide which refrigerant they wish to use, the challenge of designing and building a reliable cost equivalent system begins. Reliability testing can be extensive and expensive. Long lead times are required to understand system weaknesses before production. By explaining the reliability testing that goes into new product development and the known problems with HFC refrigerants and POE oils the customer will be able to make an informed decision about the refrigerant to choose in an air-conditioner. RELIABILITY ISSUES The reliability of many air-conditioner system components will not be affected by the refrigerant such as the fan systems, sheet metal

and electrical controls, which do not contact the refrigerant. Hermetic motors, seals, elastomers, compressors, thermal expansion devices, distributors, capillary tubes, short tube orifices, line valves, service valves, switch over valves, check valves, filters / driers, accumulators, heat transfer surfaces and connecting tubing could cause a refrigerant related failure. One major OEM found black smudge on the the internal coating of heat pumps used with R407C and a POE oil. 1 Unofficial reports blamed the compressor oil additives or residual mineral oil in the system when the systems were installed. Capillary tube plugging in room airconditioners were reported to AREP 2. A minisplit air-conditioner was converted from R-22 and mineral oil to use R407C and POE for 20 units. The rotary compressors had excessive wear. The POE decomposed and the iron concentration in the lubricant clogged the capillary tubes. The primary clogging contaminant was Iron soap formed by decomposition of the POE oil. In a field trial with R-410A heat pumps described later in this paper manufacturing process chemicals contribute to the plugging/sticking of thermal expansion valves. Cost Consequence OEMs must control in-warranty charges to operate profitably. Estimated warranty repair costs are charged to the total cost of each manufactured unit. Every service technician working on a warranty repair is someone who is not out selling units. The replacement market is a large part of total airconditioner sales and each service technician is a dealers and OEMs first opportunity to sell a replacement unit. A typical 2-ton compressor failure could lead to the following costs: Trip Charge $ 25 Diagnosis $ 25 Recover R-410A $ 50 Replace Compressor $200 Compressor Cost $350 Drier $ 9 Refrigerant 6 lb. $ 90 $749 Lubrication POE oils are more hygroscopic than mineral oils meaning they absorb more free water as well as moisture from the atmosphere. The detriment of POE oils absorbing water is that once the oil and water are exposed to heat similar to the heat found in compressors the oil and water break into acid and alcohol 3. The oil hydrolize into Carbolic acid. The TAN measurement may show a high acid content but Carbolic acid will not severely react with the metals when in moderate strength. POE oils are also better solvents than mineral oils used with HCFC refrigerants. The POE will collect much of the process fluids and metal filings and contaminants in the system and precipitate them out in expansion device or drop them in compressor sump. Deposition in the expansion device could cause plugging and force the compressor to pump refrigerant at higher pressures creating a less reliable system. POE can be formulated in many combinations of branched, linear and mixed chains. Comparing HFCs and POE miscibility to HCFCs and mineral oil must be done on a case by case method. One study 4 did report acceptable miscibility with POE oils and R407c at the same flow rates as R-22 and mineral oil. Mineral oil is not miscible in HFC refrigerants and cannot be used in many applications. R-410A Properties R-410A saturation pressures are approximately 1.6 times those of R-22. The entire R-410A vapor compression cycle takes place at higher pressures as shown in Figure 1. The higher pressures require thicker walled heat transfer surfaces and thicker walled compressor shells for scrolls. The higher pressures create higher bearing loads on the compressor. Higher bearing loads contribute to bearing wear and ultimately higher failure rates. R-410A vapor densities are over 40% higher than R-22 vapor density. R-410A compressor displacement can be lower because of the higher vapor density, approximately 70% of the compressor displacement used in an R-22 compressor. The vapor higher densities translates to lower vapor velocities in suction lines. Adequate vapor velocities are needed to return oil to the compressor. The liquid density is lower and line sizes should be examined so the liquid doesn t add too much pressure drop. One OEM has

stated that current line sets between the indoor unit and the condenser are acceptable 5. Pressure, psia 950 850 750 650 550 450 350 250 150 50-50 -50 50 150 Enthalpy, btu/lb Figure 1 - Pressure Enthalpy chart for R-410A and R-22. Contamination Air Conditioning systems may be contaminated from internal and external sources. Manufacturing chemicals such as cutting oils, unclean parts and part wash cleaning fluids in sufficient quantities contaminate the system. A common contaminate to hermetic systems is air. A field practice of purging refrigerant through the line sets and indoor unit prior to opening line valves to the outdoor unit does not remove all the air from the system. Evacuating the line sets and indoor unit is a better technique which won t leak refrigerant to the atmosphere or leave air in the system. R-22 systems seem to be benign to very small quantities of air. R-410A refrigerants with POE oils may not be so tolerant. When an outdoor unit must be replaced often the existing indoor units won t be replaced. The indoor units and line sets will contain mineral oil from the compressor that is being replaced. R-22 systems with mineral oil tolerate the additional mineral oil very well. R- 410A outdoor units attached to a previously used R-22 indoor unit may not tolerate the residual mineral oil. Initially OEMs may require new indoor units to be installed with new outdoor units. Installing R-410A systems in a dirty environment may introduce dirt into the line sets before the outdoor unit is hooked up. No systems tolerate the addition of abrasives such as dirt very well. R-410A systems may be particularly sensitive. As long as there are two refrigerants used in unitary HVAC then there exists the possibility of introducing R-22 into an R-410A system. R-22 in an R-410A system will affect the system pressures, efficiency and may well affect the reliability. Chemical Compatibility HFC refrigerants are generally more stable than HCFC refrigerants. POE oils are generally less stable than mineral oils. The more stable a substance the less likely it will react with other substances. The POE oil may react with elastomers such as those found in switchover valves, line valves, schraeder valve cores, compressor windings. The reaction may create a reliability problem by destroying the elastomer or degrading the oil lubrication properties. Process fluids used in the manufacture of compressors, coils and other components may remain on the parts at the time of final assembly. The process chemical may degrade the POE oil or may precipitate on the flow control device. LAB TESTING A sophisticated lab testing program will uncover many reliability issues. The Trane Company uses a two-prong attack by testing compressors and systems independently. The purpose of reliability testing in the lab is to reduce cost by diagnosing design flaws. Systems and compressors can be tested under closely controlled specific conditions known to cause stress in the compressors or systems. When a prototype fails in the lab the cost change the design is minimal compared to the cost to address the flaw in the field and then to also have to change the design once it has been placed into production

If 1000 flawed thermal expansion valves were put into units and subsequently had to be repaired under warranty the cost would be Trip Charge $ 25 Problem Diagnosis $ 25 Refrigerant Recovery $ 50 Replace TXV $ 50 TXV Cost $ 50 $200 x 1000 $200,000 Without a sophisticated test program such a failure could easily be introduced - with a comprehensive test program - such instances can almost certainly be minimized. This example does not show the cost associated with selling 1000 flawed units to customers, these customers most certainly would think twice about buying from the same company. Compressor Testing Compressors are the most complicated component of air-conditioner systems. If the compressor fails the system will fail. Many tests can be run on a compressor in a life test stands or compressor calorimeter without requiring a complete system to be built around it. Compressor life test stands and calorimeters are similar in design and are depicted in Figure 1. In both cases the compressor is instrumented to measure suction and discharge temperature and pressure, power consumption, and compressor sump and dome temperatures. Flowmeter Sight Glass Liquid RecieverP Hot Gas Water Throttling Valv Valve Liquid Throttling Valve T P P T Compressor Condenser Compressor calorimeters are generally used to test the performance of a compressor and determine how much mass flow the compressor will generate while requiring a measured amount of power. Both test apparatus control the compressor suction pressure, suction temperature and discharge pressure. The suction quality can be controlled also to simulate a flooded evaporator condition. Compressor life test stands are used to stress the compressor repeatedly over extended periods of time. Examples could include testing high, low, flooded start, heat pump, low charge, overcharge, etc. System Testing Flaws can exists in the system aside from the compressor as well as system design can effect the compressor reliability. Two types of system testing are used to establish unit reliability. Extreme long term environmental testing or accelerated life testing and condition specific testing to evaluate compressor oil levels at low flow conditions low ambient heating conditions or determine the compressor temperature during cooling conditions at high ambient temperatures. Accelerated life testing of systems must be carried out in samples of significant size to find design flaws. Often 6-24 identical systems will be tested simultaneously. Such a test used by the Trane company lasts 16 weeks and consists of periods of high ambient temperature cooling conditions exceeding 130oF, low temperature heating conditions with ambient temperatures below 30oF with significant snow. R-410A heat pumps will reach discharge pressure levels above 800 psig at ambient temperatures above 130F. Other mechanical failures are introduced such as outdoor and indoor fan failure modes, to determine if a minor failure such as a fan motor failure will cause a major repair such as a compressor failure. Electrical components are stressed by using high and low voltages and voltage spikes and outages. Accelerated life testing of systems is further expanded by introducing field circumstances. Overcharging and undercharging are the two most common field errors. Both cause the system to operate in a sub-optimal level. A compressor can be forced to burnout in a system and a new compressor installed as it would be in the field and the test begins to establish replacement compressor failure rates. The POE oils may perform differently once

impure oil is introduced into the system. Systems can be run at extremely low charges symbolic of a leak in the system. Contaminants such as water were added to units to determine if the driers were acceptable to remove the moisture. These are test routinely used with R- 22 and were applied to R-410A. R-410A heat pumps haven t shown sensitivity to mild overcharging, undercharging or with the addition of oil from a burned out compressor. The addition of water doesn t effect the R-410A heat pump as long as there is sufficient drier capacity to absorb the water. Specific testing to measure the oil return to the compressor is done with extremely low temperature ambient and compressors with sight tubes. The line sets are also lengthened and raised to further restrict oil return to the compressor. FIELD TESTING No amount of lab testing can take the place of building units in the manufacturing environment, boxing them up, shipping them to dealers and installing them in homes and businesses. The Trane Company has installed over 45 R-410A heat pumps into residences all across the country. These 45 units were installed in the last half of 1995 and the first half of 1996. 40 of these units were built in the Tyler, Texas manufacturing facility on a temporarily converted R-22 line. More field installations are planned at the time of the writing of this paper. Installations Field Service Technicians Lab testing allows the engineer to concentrate on the hardware and field testing allows the engineer to focus on the field technician. The homeowner or final customer is concerned about cost, comfort, and reliability. The objective is to provide an R-410A product competitive with an R-22 product on those three items. The field trial brings out undiscovered issues on comfort and reliability. The customers have been well pleased with both comfort and reliability of R-410A heat pumps except for one correctable issue. 7 of the 40 field trial indoor thermal expansion devices plugged on startup. Later analysis revealed a process chemical caused stuck to the thermal expansion device and collected metal fillings and other manufacturing debris in the orifice of the thermal expansion device. The orifice is the first cold spot in the system and particles or chemicals immiscible in the oil will precipitate out. Identification and elimination of the offending process chemical fixed the problem. Four units were undercharged and operated in an inefficient manner through most of 1996. The homeowners didn t notice a lack of comfort but one homeowner complained that his unit ran all the time. One of the first units installed had an adjustable indoor unit expansion device and low charge. The homeowner complained of lack of capacity and long run times. Once these issues were fixed the homeowner was well pleased with the comfort provided by the R-410A system. Field Service Technicians have quite a surprise in store when they check line pressures on an R-410A unit. Typical summer discharge pressures run 265 psig for high efficiency R-22 units and the same R-410A unit discharge pressures are 392 psig. Temperatures, subcooling and superheat settings are similar for R-22 and R-410A systems. The overall pressure is much higher for R-410A and this requires special gauge sets with higher pressure gauges and hoses. R-410A systems must be marked significantly different from R-22 systems to keep refrigerant contamination to a minimum. Service technicians will be accustomed to working with R-22 and will automatically expect a unit to contain R-22 unless it plainly marked. Service training is imperative since POE oils are hygroscopic. Once a field failure occurs, field service technicians must keep the replacement compressor sealed until ready for use. The open compressor will absorb moisture from the atmosphere. This moisture if not absorbed by a good filter drier will react with the POE oil and form acid and alcohol. Using proper field techniques, pulling appropriate vacuum levels prior to charging have a greater potential to induce failure in the system. Keeping the system clean and dry are two of the most important steps in building and installing R-410A heat pumps.

SUMMARY R-410A is a leading candidate to replace R-22 in unitary heat pumps. Reliability can be evaluated by testing systems and compressors in the lab and in the field. ACKNOWLEDGEMENTS The authors would like to thank The Trane Company for its support in preparing this paper and permission to publish this paper. REFERENCES 1. Boyd, A..1996. Results of a Field Test Using R-407C in Split System Heat Pumps. The Tenth Symposium On Improving Building Systems in Hot and Humid Climates Proceedings. May 13-14, 1996. Pp. 302-304. Ft. Worth, Texas 2. Fujitaka, A. 1997, Field Test Experiences of a Room Air-Conditioner using R407C and R- 410A. AREP Technical Committee Meeting, January 24, 1997, Philadelphia, PA. 3. Davis, K. E., S. T. Jolley and J. R. Shanklin. 1994, Hydrolytic Stability of Polyol Ester Refrigeration Lubricants. 1994 International CFC and Halon Alternatives Conference, Washington, DC 4. Biancardi, F. R., H. H. Michels, T. H. Sienel and D. R. Pandy. Study of Lubricant Circulation in HVAC Systems. ARTI MCLR Project Number 665-53100. April 1996, East Hartford, CT. 5. Burns, L. D., L. Hoffman and D. Schuster. R-410A Experiences in Unitary Airconditioner Systems. Kobe, Japan Conference,