Natural Ventilation Controller with 24vDC drive NVC-1204

Similar documents
Natural Ventilation Controller with 24vDC drive NVC-1204

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

1.0 Digital Controller

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

Connections, displays and operating elements C D E G H. Installing the control unit

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors

Digital Precise Air Control - DPAC

Carbon Monoxide Transmitter

Networkable Fan Coil Controller Specification and Installation Instructions

Typical Operating & Maintenance Manual for SOLA-BOOST X-Air Project Name

SYX660 Commissioning Guide V Page 1 of 55

02/11/2015

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Fan Coil Unit (FCU) Application Guide

OVEN INDUSTRIES, INC.

02/11/2015

TER Active Room Temperature Sensor (Controller),

VT4810 SINGLE / DUAL ZONE CONTROLLER INSTALLATION MANUAL


I/O ZONE 560/583 USERS GUIDE

B-40/B-41 Modulating Temperature Controller

SEQUENCE OF OPERATIONS

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings

1.0 Digital Controller

- Data Brochure Boiler Control 274

SYX66x Commissioning Guide V Page 1 of 61

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

VCM-X / RNE Operator Interfaces Technical Guide

50AZ/UZ. for rooftop units. 50 Hz. Installation, operation and maintenance instructions

USER MANUAL FOR OPERATING SYSTEM

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

CONTENTS. Installation Guide. VT7200 Series

Table of Contents. W2W Open

K-Controller Brochure.qxp_ Controller Brochure 2/27/17 3:03 PM Page 4 Versa IC Platform

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller

- Data Brochure Universal Reset Module 422

Tebis application software

DHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

Temperature Controllers

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

TC-9102 Applications

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers

4 in 1 Digital Thermostat Control

Ethernet General Purpose

VCM-X / RNE Controller Operator Interface SD Technical Guide

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

F4 Process Controller Installation and Operation Guide

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

REMOTE CONTROL FOR CHILLER MYCHILLER

BAC-4000 Series AppStat

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Hydronic & HVAC Control Systems

Digital Thermostat. Models: VS35W and VS35B INSTALLER / USER MANUAL

Installer Manual KNX Touchscreen Thermostat

Digital Thermostat Models: VS30W and VS30B

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

General Purpose IO Technical Manual

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings

- Data Brochure tekmarnet 4 Thermostat 542e

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

MC200. Users Instructions. HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: Fax:

APPLICATION DATA SHEET

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

CLEVER CONTROL Version: V3

NU2 Smart Power Supply (SPS) Manual

Installation and Advanced Programming Instructions. HP8211-1RJ and HP8321-1RJ Heat Pump Thermostats

Contents. Box contents: JGSTAT2B (Black) Fixing screws (White) Icons used in this manual:

Wallace & Tiernan Controllers & Analysers ChemTrim Disinfection Controller

WALLACE & TIERNAN CONTROLLERS & ANALYSERS CHEMTRIM DISINFECTION CONTROLLER PRODUCT SHEET

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

Installation and Maintenance Manual IM

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

Better Design, Better Control, Better Systems.

Installation & Operation Manual

4 Wiring Brochure Wiring and

New Versa IC Platform

The new Xcell EC High Efficiency Range Fresh air pure and simple

Instruction, Operation, and Maintenance: Controls Software Versions: R37+

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

IGD.CO.UK

Safety / Kit Components 1

Siemens Thermostats. RDY2000BN Thermostat

Application, Installation, Operation & Maintenance Manual

Ammonia Leak Detector Manual

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

CLEANROOM MONITOR CR3A Network - Installation Instructions

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

NATURAL VENTILATION CONTROL SYSTEMS

AirTrak. Digital Control System. User Manual. Touchscreen Systems

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

OJ Waterline control system

Transcription:

Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-036 08/11

FEATURES > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) > 3 x 0-10V outputs > 3 x 24V DC relay outputs > 9 x 0-10V Analogue inputs or use as Digital Inputs > 4 x 10K3 temperature sensor inputs > Remote setpoint display option > In built calendar time clock > Din Rail Mounting Description SPECIFICATION Supply 24VDC (+/- 15%) must be rated for the total output load. Power consumption 3 VA (no RDU) plus outputs (controller only) 8 VA with RDU display 0-10V outputs 5mA max Temperature Sensors 10K3A1 Analogue Inputs 0-10V Digital Inputs Voltfree Relay outputs 24VDCrated at10 amp max. Communications Native BACnet Network MS/TP -RS485 Indication Tx/Rx comm. s Relay operation Enclosure Din Mounting (IP20) L94-VO Size 160 mm wide 92 mm high 62 mm deep The Natural Ventilation Controller NV1204 provides 3 zones of control and can operate as a stand-alone controller or integrated into a BMS with the inbuilt BACnet communications over MSTP. The controlled outputs are 24V DC reverse action relays provide proportional positioning control and incorporate an option for a remote manual selection of the ventilation positions. Each output is individually fused with PCB mounted resettable fuses and the three outputs are fed from the high current 24V DC controller supply. The output drive status is indicated by a tri-state LED showing:- Off No drive Green Window opening Red Window closing Each of the three zones can operate independently for individual control settings based on the corresponding temperature and CO2 levels Signals for Zone Occupancy, External Temperature, Wind, Rain, Heat and Fire can come from a central BMS over the BACnet communications or from a Master NV1204 controller and these signals will determine the operational status of the controller. In addition to the DC relay outputs there are 3 x 0-10V outputs that can be used for signals to the respective zone ACO/4S room user interface units. These signals with enable and disable the manual ACO operation as well as provide a signal level indicating the auto position of the controlled outputs. The controller settings are done using a RDU unit or an FPT601 connected to the controller via the RJ11 socket. The control action is Time Proportional Control (TPC) outputs from the measurement of the respective C02 and temperature values taking the greater of the 2 measured values against a Setpoint and proportional band setting for both temperature and CO2. The Proportional Positioning is based on the total run time of the ventilation actuator which will control in defined percentage steps the position of the window/vents On power up the controller will synchronise the outputs to a closed condition for the duration of the set actuator drive time plus a percentage of overrun time. The overrun time is to ensure a datum point can be established on power up since the position of the vents is not known at this time. The overrun time setting is added to the close signal each time a call is made for the vent actuators to be fully closed. A signal to open the vents during the synchronisation period will be ignored until the synchronised process is complete. Whilst the controller can be set to operate 3 independent zones the controller can be configured to alternative zone combinations for example to control outputs 1 with 2 and or 3 from one set of control parameters. 2

Manual selection of the vent position can be achieved with the ACO/4S user interface (see ACO4S operation) Temperature sensors. The temperature sensors can be either 0-10V input (ranged 0-50 C) or 10K3A1 Thermister and each zone is set to operate the controller outputs on a rise in temperature for comfort ventilation control. The 4 th temperature sensor input is allocated to the measurement of the external temperature. The external temperature and respective internal temperature values are also used for determining summer/winter seasonal conditions as well as the night Free Cooling (Purge) cycle. Control Settings The settings listed describe a range of standard options and operational features that are available from the applications library that is resident in the Natural Ventilation Controller software. The RDU user interface provides the ability to adjust zone temperature Setpoints and to select timed occupancy extension as and when required. All other setting are access code restricted and can be modified using the RDU or FPT601 unit or via the BMS using the inbuilt BACnet communications. Controller Settings & Options Description Network Native BACnet (RS485 MS/TP) or Stand-alone Unit address Sets the controller unit MAC address on MS/TP bus. Range 1 to 127 Baud Rate Communication baud rate Range Options: - 9,600 19,200 38,400 or 76,800 Dev Object ID Allows the setting of the device object ID. Range 0 to 4194302 Group Control Allows individual controllers to be set-up as a Group Master or Group Slave. This sets groups of controllers to take control information and instructions such as temperatures, Global Setpoint, occupancy, Heat, Rain and Fire inputs from a common Master (125 Slaves max). Any number of Groups can be set within the limit of 126 controllers on the MS/TP network Temperature Setpoint The controller Temperature Setpoint (GSP) is common to all zones and can be derived from :- 1) A temperature Compensated Setpoint varying with the prevailing external temperature conditions. 2) A Fixed Setpoint which is a permanent fixed value that is applied to the controller at setup. The Global Setpoint (GSP) is allocated to the three controlled zones and the individual Zone temperature setpoints can be adjusted via the RDU user display within a predefined limited range or from the BMS. Any +/- Reset Setpoint (RSP) setting from the GSP value will become the zone default value when the controller is switched On/Off. Inputs External 10K3A1 Thermister The external temperature sensor/value is used for a number of control options. a) Used for a low limit to reset the temperature control to minimum fresh air should the external temp fall below a preset level (See External Low Limit). CO2 control of the ventilation can be set to take priority in low limit temperature conditions. b) Used to monitor the external temperature in un-occupied modes to activate or inhibit free cooling (see Free Cooling). c) Used to adjust the Global Temperature Setpoint in compensated control mode. 3

If the External temperature value is supplied from the BMS then the controller physical input must be taken out of service (OOS). Whilst the NV1204 can be used for stand alone and or Group Master/Slave operation when it is connected to a BMS objects are available for centrally transmitted signals such as: - Adverse Weather (close all vent) Fire (close all vents) Occupancy. Auto Controlled Unoccupied Close all vents Night Purge (open selected vent) Zone Inputs Zone Temperature CO2 0-10V Input Manual Control (ACO/4S) The control sensor can be from a 0-10V temperature signal in the combined C02 sensor (range 0-50 C) or option configured to use one of the 10K3 Thermister inputs. A CO2 sensor is provided per zone for priority control of the ventilation. The CO2 sensor provides a linear 0-10V signal across a range of 0-2000ppm. Each zone operates with a TITAN ACO/4S unit 0-10V signal which will allow Manual selection of the vent positions Output from Nat Vent Controller to the ACO input (all values are +/- 0.5V) ACO disabled = <1V (Override is indicated static LED) Auto/Active = 2V closed (all LED s off) 1 st stage % = 4V (1 st left LED On static in Auto) X% = 6V (2 nd left LED On static in Auto X% = 8V (3 rd left LED on static in Auto) Max % = 10V (4 th left LED on static in Auto) The 0-10v input signal on the ACO/4S unit is used for enabling and disabling the ACO manual functions as well as providing indication of the auto control position of the vents. Output from ACO/4S to Controller when enabled with the input level at 2V or above and when the Manual selection is made using the ACO buttons Auto/Active = 2V closed (LED s dictated by Auto) 1 st stage % = 4V (1 st left LED On slow pulse) 2 nd stage = 6V (2 nd from left LED on slow pulse) 3 rd stage = 8V (3 rd from left LED on slow pulse) 4 th stage = 10V (4 th from left LED on slow pulse) When the controller signal is 2V or above the ACO/4S is enabled and manual operation can take place. Manual selection can only move up from the auto position and when this is done then the manual selected position is indicated with a pulsed LED. The operator can not move below the auto control position If after a manual selection has been set the Auto control input matches or exceeds the manual value then the Auto control takes priority and cancels any previous manual selection. Control Overrides In addition to the BMS override functions there are a number of control override signals within the Natural Ventilation control configuration and these are: External Low Limit If the external temperature falls below a set threshold, the normal temperature control is inhibited and the vents are reset to minimum position (option selectable). The CO2 level is still allowed to control the ventilation under low external temperature conditions. 4

Internal Low Limit Manual Control Free cooling If the internal temperature falls below a set threshold, the CO2 control and/or Manual Open signals can be inhibited (if required). Use a TITAN ACO/4S room interface unit. (see details above) During the unoccupied periods the ventilation should normally be fully closed. Free cooling is dictated by the Controller or BMS and this will allow the vents to be pre-positioned to any of the 4 vent positions for night cooling. The Free Cooling will be inhibited if the external temperature is below the low limit threshold. Time Control The occupancy times can be transmitted to the controllers by the BMS or if required the NV1204 can be programmed via its own internal calendar time scheduler. In a Group Master/Slave setup the group occupancy can be transmitted fro m the designated NV1204 Master. Setup (Engineer s settings) The NV1204 controller provides a group of global control options and a number of zone control settings. All the settings are done through the RDU or FPT601 Field Programming Tool. Or via the BMS network and the settings are as follows:- Output Control This setting determines the number of individual controlled zones and the number of outputs that can be attached to a single zone. Number of zones 1-2-3 (if 3 is selected then the following options are not allowed) DC Outputs for Zone 1 (op1 or + op2 or + op3 or all) DC Outputs for Zone 2 (op2 or op2 + op3) Global Temperature Setpoint GSP Type:- (Fixed/ Ext Temp) If Ext Temp The Global Temperature Setpoint (GSP) is determined by the external temperature compensation or Fixed. The GSP is used for the base temperature setting of the zone control point. If a Fixed setpoint is selected then this is determined at the Setup or by the BMS over the network and this value become the controller fixed default value. Compensated then a continuous temperature compensated adjustment of the GSP is exerted within the controller using the internal Winter and Summer SP with the Winter and Summer Ext SP. (see fig below). The value of the external temperature can be derived from a controller sensor or the BMS. + Winter SP Internal Setpoint GSP Summer SP Winter Ext SP External Temp Summer Ext SP + 5

The following settings need to be entered if External Temperature adjustment is used for the GSP. Winter SP:- 0 30 C Summer SP:- 0 30 C Win Ext SP:- 0 30 C Sum Ext SP:- 0 30 C The maximum internal temp erature setpoint to be used during winter conditions. The minimum temperature setpoint to be used during summer conditions. The external temperature that corresponds to the maximum winter control setpoint when using external temperature compensation to define the global setpoint. The external temperature that corresponds to the minimum summer control setpoint when using external temperature compensation to define global setpoint. If GSP is set for temperature compensation then each zone setpoint can be adjusted plus or minus providing an adjustment to the calculated setpoint that is derived from the compensated schedule. Global Settings and Control Strategies Rain Vent Position :- CO2 Setpoint :- 0-2000ppm If rain is detected by the controller then automatic control is inhibited and the ventilation dampers are driven to the minimum % setting (ZN Min % if set) until the rain detection is cleared. The CO2 sensor gives 0-10V output for a range of 0 to 2000ppm. This setting defines the point at which the CO2 value begins to open the ventilation using its own Proportional control function and this setting is common to the 3 controlled zones. Ext LL Position :- Min%/Closed/Disabled This defines whether the vents should be fully closed or set to Min% when the external temperature falls below the low limit setting. If disabled then the natural ventilation temperature control is not inhibited or reset by low external temperature conditions. Ext LL Thres :- 0 30 C This defines the external low limit threshold below which the ventilation dampers will be closed. Int LL CO2 :- Enabled/Disabled Int LL Man :- Enabled/Disabled This defines whether an internal low limit temperature will inhibit CO2 ventilation control. This defines whether an internal low limit temperature will inhibit CO2 control or manual open override from the ACO room unit Int LL Thres :- 0 30 C This is the internal low limit temperature value that will inhibit the activation of the CO2 control and manual override from the ACO. The use of the inhibit action on both conditions can be individually selected. Heat Position :- The ventilation position will automatically go to the closed or minimum % setting if Heat On is detected. CO2 :- No Ctrl/Ctrl This defines whether CO2 control is required. If Crtl is selected then the output control is based on the greater of the temperature or C02 values also if selected the CO2 values are displayed on the RDU 6

Free Cool :- Position This selects the position of the vents for Free Cooling. There are 4 positions plus closed as described in the control section. Free cooling will also be dictated by the BMS as and when required. Free Cool Int :- 0 30 C This is the internal temperature limit above which the action of Free Cooling in the un- occupied period will be allowed by the controller. Occ Override Time :- 0 8 hours This allows occupancy extension outside normal hours of operation. The controller will automatically time out and reset to the desired operation after the elapse of override time setting. Zone Settings and Control Strategies (available for each zone) Relay Drive time Relay Drive overrun timer Zn RSP Range :- 0 5 C Zn Temp Pb :- 1 5 C Zn CO2 PB :- 100 1000ppm Range 5 300 seconds This setting is the time taken by the ventilation drive mo tors to run from fully closed to fully open and is used to provide the positional adjustment of the vent to match the control voltage signal input. There will be a setting for each output and the ability to select a common time base for all 3 outputs Range 0 to 300% of drive time This setting is used to add additional drive time to the close signal to ensure the vents are fully closed each time a 0V input is seen or on start up or when the controller is switched Off or on actual power up. This is the + and - adjustment of offset of the zone GSP allowed by the BMS or RDU/FPT This defines the proportional band for the temperature control. This defines the proportional band for the CO2 control. Controller Display & Options Temp Units :- Disp CO2 :- Maintenance. Passcode Set Up Passcode (customer entry) All temperature values are shown in degrees C The CO2 value can be displayed or inhibited. The 4 digit Passcode when using a RDU/FPT as is required to enter the controller at the low level maintenance menu. The Passcode required to enter the high level Set Up menu. Physical IO 9 x Analogue Inputs Used for the C02 sensors, temp sensors and ACO manual override units.. 4 x Temperature Sensors Used for measurement of the controlled zones and the external temperature. 3 x 0-10V Analogue Outputs Outputs are configured to provide the following control options: - Zone 1 - ACO Zone 2 - ACO Zone 3 - ACO 3 x 24VDC Outputs 24V DC outputs for each of the three zones or can be used for one common zone. 7

NVC1024 Terminal layout 8

Ancillary Products The NVC-1204 Natural Ventilation Controller can be used with a number of products from Titan Products to create a fully BACnet enabled Multiple Zone Natural Ventilation System. RDU User Interface Unit The RDU User Interface Unit allows occupants to increase temperature and switch between zones. The RDU is available in a number of decorative finishes. For more details contact the sales team or visit www.titanproducts.com. ACO Window Positioning Unit The ACO Room Ventilation Positioning Unit allows occupants to select OPEN/CLOSED during the NORMAL/AUTO operational mode. The override selections will time out after a preset period and return the controller to normal operation. IO/AD3/W Window Actuator positioning module The IO/AD3/W module converts the 0-10V control signals to 24VDC relay control. The module provides time proportional control for reverse operational DC damper actuators. The module also incorporates software to ensure synchronisation of the damper position with the control signal. For more information see data sheet C-024 on www.titanproducts.com. TITAN Room CO2 Temperature Sensor Titan Products range of CO2 sensors provide 0-10V signals for CO2 and incorporates options for a temp output (0-50 C) and humidity output (0-100%). See datasheet S-052 on www.titanproducts.com. TITAN Room Temperature Sensor The compatible room temp sensor for the CCM -204 is a 10K3A1 thermistor. The TITAN product code for this is TPTRS. TITAN room temp erature sensors can be supplied in a variety of finishes and with sensing elements for other applications. For more details please see data sheet S-001 at www.titanproducts.com. TITAN Rain Detector The TPRD1 is specifically designed to detect the presence of rain. The TPRD1 incorporates a heater to evaporate any residual moisture after a rain fall which speeds up the dry detection rate. For more information please download the datasheet form www.titanproducts.com. 11

Tel: +44 (0161) 406 6480 Fax: +44 (0161) 494 8309 Email: admin@titanproducts.com Website: www.titanproducts.com Titan Products Ltd. reserves the right to alter/change the specification of their products without notification 12