UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

Similar documents
1.1 This section applies to air handling units for HVAC Systems.

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

SECTION AIR HANDLING UNIT

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

A. This Section includes air-handling units with coils for indoor installations.

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

A. Codes and Standards that are Standard at the University:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

Selecting the Correct Fan

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

University of Delaware

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

Construction Standards Page

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION AIR DUCT ACCESSORIES

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

CAT-SIUH-2000(3) SUPERSEDES CAT-SIUH-98(2) SARAVEL INDUSTRIAL UNIT HEATERS

Introduction to Fans. The Basics of Fan Principles and Terminology

Large Capacity Fan Coil Units Catalog Belt-Drive and Direct-Drive Cabinet and Hideaway Models

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION FAN COIL UNITS

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

AIR HANDLER SPECIFICATION

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

TYPICAL CPA SPECIFICATIONS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL

SECTION (15833) - HVAC POWER VENTILATORS

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS

SECTION ROOFTOP REPLACEMENT AIR UNITS

SECTION CENTRAL HVAC EQUIPMENT

Submittal Data Performance Data Electrical Data

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

SECTION CONVECTION HEATING AND COOLING UNITS

SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL

KAP Horizontal Product Coolers

FCC Fan-Coil Units High-Performance, Vertical

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

SECTION WATER-SOURCE UNITARY HEAT PUMPS

Modular Supply Make-Up Air Unit

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS

Advance Release September 2009

City of Duluth Festival Center 04/25

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

SECTION CUSTOM FAN WALL AIR HANDLING UNITS

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS

ENVIRO UNIT ENGINEERING MANUAL KES SERIES

C13-Series Engineering Guide

SECTION AIR COILS

Product Specifications. Vertical Floor Consoles By First Co.

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

AIR HANDLING. B. Section Building Automation and Control System Guidelines. C. Section Air Cleaning Devices and Filters

CxA to Answer this Section

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT

Chilled Water DOAS Fan Powered Terminal Units

48GS(N) STANDARD EFFICIENCY 48GX(N) HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING ELECTRIC COOLING UNITS

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

Catalog Destiny Indoor Air Handler. Models Horizontal Configuration. Vertical Configuration

SECTION AXIAL FANS

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

DIVISION 15 MECHANICAL

48GS HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

Large Capacity Fan Coil Units Belt and Direct Drive Cabinet and Hideaway

SSL & SBS Engineering Guide

B. Unit shall be shipped as a single package unless the unit is too large to fit on a standard tractor-trailer.

3.0 Factory packaged or modular constructed AHUs, when approved for use, shall conform to the following criteria:

Direct Fired Heater Model AD Specification

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise T-Series AHU Full Spec. Prepared by: Phone Number: Prepared for: Acceptable Manufacturers

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

Ducted Propeller. Airflow Volume

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

SeasonMaker ThinLine Fan-coil Units

PRODUCT CATALOG BLOWER COILS.

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

62DA,DB,DC,DD,DE,DF07-38

Contents INDEX. TDM Series Indirect Fired Heaters

Transcription:

GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible, locate all air handling units inside the building or in a penthouse. Rooftop locations and above ceiling locations are not permitted without PM approval. 1.2. Exterior units will be designed specifically for outdoor installation. All piping will be within the unit enclosure. 1.3. Where exterior equipment is to be located above a roofing system, adequate space shall be provided below equipment to allow for roof maintenance as specified by NRCA Roofing Manual. Avoid multiple rooftop penetrations. Permanent stairs are required for access to unit for any units 18 or more above the roof. 1.4. Vibration and sound transmission from mechanical equipment will not exceed ASHRAE sound criteria. 2. Coils 2.1. All coils shall be piped counterflow and be drainable. 2.2. Coils shall be a maximum of 8 rows and a maximum of 10 fins/in. 2.3. When the coil selection requires more than an 8 row coil, designer shall provide 2 independent coils with an access section with doors in between the coils. 2.4. Cooling coils shall be selected for a 46 F entering water temperature and a 14 F ΔT. MS&T can be designed with a 10 F T and 45 F entering water temperature. 2.5. Hot Water Coils 2.5.1. Hot Water Coils should be designed for 180 F entering water temperature and a 20 F ΔT. 2.5.1.1. S&T Only: Hot water coils shall be designed for a 120 F entering water temperature and a 20 F ΔT. 2.5.1.2. If steam is unavailable, design for 140 F entering water temperature and a 20 F T. 2.5.2. Hot Water Coils used for pre-heat are required to be pumped. See Detail. 2.6. Steam Coils shall only be used for replacement of an existing steam coil. 2.6.1. Steam coils shall be designed for 5 psig steam, and gravity return. This may necessitate elevating the unit above the housekeeping pad to provide sufficient height for a gravity return. 2.6.2. Steam heating coils should be designed with a smaller face area than the AHU cabinet. Coil heating capacity is based mostly on the coil size. Coils face area shall be only as large as required by the required heat load. Higher velocity through the steam coil is acceptable. Steam coils which are the same Page 1 of 7 23 7000

size as the AHU cabinet are greatly oversized and will have very uneven temperatures across the coil face. It is not unusual to see freezing temperatures at the bottom or side opposite the steam supply to the coil. This may cause the steam coil and the adjacent chilled water coil to freeze. 2.6.3. Integral Face and bypass damper pre-heat coils are preferred. Standard internal/external face and bypass coil arrangements are not permitted. 3. Arrangement 3.1. Draw through arrangements are acceptable for units with winter mixed air temperature greater than 40F. Hot water pre-heating coils are required on units with mixed air between 40 F and 55 F. Systems with a mixed air above 55 F do not require heating coils. 3.2. Blow through arrangements are required when winter mixed air temperatures are below 40F. Cooling coils will be located downstream of the supply fan. 3.3. All air handling units will consist of factory fabricated components. Modifying or field fabricating mixing boxes or filter sections are not permitted. 4. Fans 4.1. Fans will be selected to provide highest efficiency and lowest noise characteristics practical while meeting specific system requirements. Sound level shall not exceed 85db, three (3) feet from the unit. This means that if a AHU cabinet size has 3 possible fan sizes, consultant shall select the largest diameter, slowest RPM speed fan available. Fans operating at RPMS > 1800 are allowed only with permission of the Project Manager. 4.2. The following fan types are acceptable: 4.2.1. DWDI, Forward curved, Airfoil or backward inclined 4.2.2. Plenum type 4.3. Inline centrifugal, tubeaxial or vaneaxial fans are PROHIBITED. 4.4. Return fans shall be provided only when return/exhaust/relief duct system pressure drop exceeds 0.30 wg. 4.5. Relief fans are required whenever the economizer air relief path ΔP exceeds 0.05 Wg. (0.05 wg exerts 5 lbs of force on a 36 x 72 exterior door and will prevent the door from closing and locking) 4.6. Variable speed drives shall be provided by Division 26, not the AHU manufacturer. 4.7. Central-station air-handling units and their components shall be factory tested in accordance with the applicable portions of ARI 430 - Standard for Central-Station Air-Handling Units and shall be listed and bear the label of the Air-Conditioning and Refrigeration Institute. 4.8. The fan-system operating point shall fall within range recommended for proper operation as indicated in Figure 5-4, AMCA Standard 201-90 "Fans and Systems". Fan type and characteristics will be selected to assure stable non-pulsing performance in required operating ranges. Fan s Class shall be high enough for 10% over speed without exceeding RPM for the class. Fan shall be selected low enough on the fan curve to allow 5-10% increase in static pressure without causing the fan to go into the unstable range. Page 2 of 7 23 7000

4.8.1. Inlet and Discharge outlets shall be designed to not create a system effect. 5. Filters 5.1. Filters will comply with ASHRAE Systems and Equipment Handbook, Chapter 25, Table 2 and the following: 5.1.1. Office areas shall have a minimum MERV 10 5.1.2. Classrooms shall have a minimum MERV 10 5.1.3. Laboratories shall have a minimum MERV 13 5.1.4. Animal areas shall have a minimum efficiency of 85% (MERV 13) 6. Internal Access 6.1. All units shall be provided with access sections to enable inspection, cleaning and repair of individual components. Access shall be provided to mixing dampers, both sides of coils, and fan sections. Compact fluorescent or LED lights shall be provided in all access sections and connected to a common switch/timer. MINIMUM WIDTH OF ACCESS SECTION SHALL BE 24. 7. External Maintenance Access Requirements 7.1. Access and service space shall comply with International Mechanical Code, section 306. 7.2. All HVAC equipment will be located to facilitate accessibility, maintainability and replacement. Minimum clearance on the side for fan access, filter access or coil access is 48. All other sides must have a minimum of 24 to walk around the unit. 7.3. All coils within air handling units, will be capable of being pulled without obstruction of equipment, pipes, conduit, etc., or requiring removal of any other coil in the same unit. Two units may share the same coil pull space. Coil pull space may utilize a double-wide mechanical room door if the mechanical room is not large enough. 7.4. Mechanical contract drawings shall show the access areas as a hatched area adjacent to the unit. Access doors shall also be shown at all required locations. A plan and elevation view of each air handling unit is required. 7.5. All mechanical equipment/systems will be installed on a 4" minimum concrete housekeeping pad, and where required, steel support framing as required to allow proper housekeeping, cooling coil condensate trap installation, steam condensate drainage, and access. See Detail for standard trap sizing detail. 7.6. Future replacement of the entire unit shall be considered. SPECIFICATION REQUIREMENTS: The following statements shall be included in the contract specification: 1. Access limitations on replacement units: Replacement Air handling Units may be restricted to existing size limitations. Units which exceed these limitations cannot be considered as they will not fit in the existing locations. The size limitations are indicated on the attached data sheets. Page 3 of 7 23 7000

2. Unit Construction 2.1. Unit casing panels shall consist of formed and reinforced exterior 18 gage galvanized steel panels, 2 inch thick, 3.0 lb/cu ft density, fiberglass insulation and an interior 20 gage G90 solid galvanized steel liner. 2.2. Access doors shall be insulated double wall construction. Latch handles, Ventlock 310 or equal, shall provide positive closure to prevent leakage. Door hinges shall be securely fastened to unit casing. Tack welds are not acceptable. Door gaskets shall be a minimum of 3/8 inch around the entire door perimeter. 2.3. Unit sections with access doors shall be provided with floors capable of supporting maintenance personnel. 2.4. Provide a service light in all accessible sections and the fan cabinet. 2.5. Provide a double wall, internally insulated, sloped stainless steel drain pan under each coil including piping and header. 2.6. Provide unit with an 8 base rail. 3. Fan Section 3.1. Fans will comply with AMCA Standard 210 and ASHRAE Standard 51. 3.2. Statically and dynamically balanced fans and shafts. 3.3. Fan shaft shall be solid steel, turned, ground, and polished. Fan wheels shall be keyed to the shaft. Shafts to be designed for 80% of first critical harmonic. 3.4. Shaft Bearings shall be grease-lubricated ball bearings selected for L10 = 200,000 hours. 3.5. Extend grease fittings extended to an accessible location outside the fan section. 3.6. Motors and fan wheel shall have fixed pitch sheaves. 3.7. Fan/Motor belt drives and sheave combination shall be selected with a 1.5 service factor using a Drive Selection Program such as Gates Designflex Pro. Manufacturer shall submit the drive selection program output with the AHU submittal. 3.8. Fan section shall be run-balanced at the factory at the scheduled RPM. 3.9. An allowance of 1.5 inches or manufacturers recommended maximum, whichever is higher, Static Pressure for dirty filters shall be added to the internal static pressure calculation before fan selection. 3.10. Fan Drive shall have an OSHA compliant guard. 4. Motors 4.1. Motors will be designed to operate continuously at all speeds with variable speed drives having carrier frequency of 12 KHZ or higher without large fluctuations in amps drawn at any single speed. 4.2. Motor Construction: Open, drip-proof, NEMA Standard MG 1, general purpose, continuous duty, Design B, insulation class H. 4.3. Motor shall not operate within the service factor range. 4.4. Premium efficiency motors are required. 4.5. Indicate the full identification of manufacturer, ratings, characteristics, construction, and special features. Page 4 of 7 23 7000

5. Coils 5.1. All coils shall have a minimum of.025 tube wall thickness and 5/8 O.D. minimum diameter. All coils shall have copper coils, aluminum fins, and nonferrous headers. 5.2. 5.2 Coils shall be a maximum of 8 rows and a maximum of 10 fins/in. 6. Access/Plenum Sections 6.1. Full-sized 24 access sections shall be provided between all coil and filter sections. Access sections shall have hinged doors with door handles. Access doors shall be provided on all sections to provide access to filters; coils, front and back of fans; dampers, etc. Bolted or screwed panels are not acceptable. 6.2. The door swing shall be the opposite of the pressure in the access section. 7. Filter Section 7.1. Provide disposable type, cotton/polyester material with additional non-woven glass fibers on the exit face. Filter performance shall be as scheduled. Air filters shall comply with Section 605 International Mechanical Code and NFPA Standard 90A "Standard for the Installation of Air Conditioning and Ventilating Systems", and be UL Class 2. 7.2. Filters shall be rated in accordance with ASHRAE Standard 52 "Method of Testing Air-Cleaning Devices Used in General Ventilation for Removing Particulate Matter. 8. Mixing Boxes/Economizer Sections 8.1. Provide parallel-blade dampers in a reinforced, galvanized steel cabinet. Damper blades shall be galvanized steel mechanically fastened to steel operating rod. Connect operating rods for each set of dampers together with a common linkage and interconnect linkages so dampers operate simultaneously and in the opposite direction (one opens when the other closes). SCHEDULE TO BE INCLUDED IN THE DRAWINGS TAG NO. MANUFACTURER/MODEL # AHU TYPE FAN TOTAL AIRFLOW TOTAL/EXTERNAL SP HP/VOLTS/PHASE COOLING COIL TYPE CFM Page 5 of 7 23 7000

MAX FACE VEL. (FPM) AIR PRESS DROP MIN. CAPACITY, TOTAL (BTUH) MIN. CAPACITY, SENSIBLE (BTUH) ENT. AIR TEMP (DB/WB) LV. AIR TEMP (DB/WB) ENT WATER TEMP (F) LV WATER TEMP (F) WATER PRESS DROP (FT) WATER FLOW (GPM) HEATING COIL TYPE CFM MAX FACE VEL. (FPM) AIR PRESS DROP MIN. CAPACITY, TOTAL (BTUH) MIN. CAPACITY, SENSIBLE (BTUH) ENT. AIR TEMP (DB/WB) LV. AIR TEMP (DB/WB) ENT WATER TEMP (F) LV WATER TEMP (F) WATER PRESS DROP (FT) WATER FLOW (GPM) FILTER SECTION PRE-FILTER TYPE / DEPTH PRE-FILTER PRESS DROP - CLEAN/DIRTY PRE-FILTER EFFICIENCY/ARRESTANCE FINAL FILTER TYPE / DEPTH FINAL FILTER PRESS DROP - CLEAN/DIRTY FINAL FILTER EFFICIENCY/ARRESTANCE Page 6 of 7 23 7000

REFERENCES Page 7 of 7 23 7000