MiLAB Oxygen Control MANUAL & INSTALLATION. MOC-100 Ver 3.0

Similar documents
Carbon Monoxide Transmitter

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Constant voltage 3-phase rectifier.

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

M1000 Alarm Annunciator

PTE0705 Electric Fence Monitor

User Manual. Dryer Controller M720

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

Sierra Model 951 Digital Flo-Box. Instruction Manual Part Number IM-951 Revision A 09-05

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

GB-DAS. Installation and user manual DEVIreg 850 controller

3. Thermal switch (70 o C thermostat) with a 3 m connection cable

02/11/2015

Instructions. Easy-wire terminal strip Microprocessor-operated. Easy remote sense. Self-checking program. Diagnostic/status LED s

MS-H-Pro-T Magnetic Hotplate-Stirrer with Timer

S304 and S305 Dust Emission Monitors. User Manual. Distributor

Janfire Pellet Burner Boiler. for single / double burner management (Version 1.1)

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

Temperature Controllers

EXPERT TRI-STAR. Temperature controller. User s Manual

Dryer Controller M720

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

CTT8 TEMPERATURE MONITOR DEVICE

User Manual. MS7-H550-Pro MS7-H550-S MS7-Pro MS7-S

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

BX444-Mc Gas Detector

Modbus RTU RS485 Manual

Electronic Pellet Burner Controller NPBC-V3M

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

Multi-Gas-Controller MGC2

MO n : 12JMC rév A

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

Metasys Integrator Airflow Application

OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19

Electronic Pellet Burner Controller NPBC-V3-1

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

OVEN INDUSTRIES, INC.

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

02/11/2015

Metasys Integrator Cleaver-Brooks Application

MAKING MODERN LIVING POSSIBLE INT INT EFIT 550. User Guide and Installation Manual. Danfoss Heating

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Nov 08 PRODUCT SPECIFICATION SHEET

CLEANROOM MONITOR CR3A Network - Installation Instructions

DIGITAL TEMPERATURE RELAY TR-100

Duct and Rough Service Carbon Monoxide Sensor

Danfoss gas detection units

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

HGM1750 Automatic Generator Module OPERATING MANUAL Smartgen Electronics

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

SEC 2000 Millenium Infrared Gas Detector

OVERVIEW ANNUCIATOR POINTS

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

Sintrol Snifter A2 EX. Manual. Version 1.2.3

Installation and Operating Manual

Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C

Advance Optima Module Magnos 17

PROGRAMMABLE 7-DAY RF THERMOSTAT

Snifter ATEX22 VERSION. User Manual. Distributor

Danfoss gas detection units

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

REC-8R Environmental Control. Operation and Installation Manual

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

FIB_FGBS-001 Universal Binary Sensor

ACCURATE ELECTRONICS INC

Pioneer-R16 Gas Monitor Operator s Manual

Digital 7 Square Plate Magnetic Stirrer

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

EC2-5x2 Series Condensing Unit Controllers

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Model A1700 Series Annunciator

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

SD2. Differential Controller. Operating and Installation Instructions F2 72.3

ELITE-600 DENTAL PORCELAN FURNACE

Dusty / Dusty Ex Low-Cost Broken Bag Detection

Thank you for buying a DEVI product. With this purchase you have obtained a product of the highest quality, designed to give long lasting comfort at

Model 9010 and 9020 Monitoring Systems

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

FUSION ALARMS TROUBLESHOOTING GUIDE CURRENT LIMIT VOLTAGE LIMIT

ETN-24-SUPER-SF Series

Operating instructions DVC-P / Bedienungsanleitung Druckregler DVC-P

D3000. Installation & Setup Guide

READ AND SAVE THESE INSTRUCTIONS

KSM-Multistoker XXL With PCT400 O2 Controller

Table of Contents SECTION PAGE

Series Temperature Controller Instruction Sheet

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

PROGRAMMABLE 7-DAY THERMOSTAT

TTSIM-1 Sensor Interface Module

Air Check O 2 Deficiency Monitor 0-25%

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL

Transcription:

MiLAB Oxygen Control MANUAL & INSTALLATION MOC-100 Ver 3.0

Contents 1 INTRODUCTION...3 2 FUNCTIONS...4 2.1 O 2 REGULATION...4 2.2 DISPLAY BOARD...4 2.3 COMMUNICATION THROUGH PANEL...5 2.3.1 Set parameters...5 3 PARAMETERS...6 3.1 O 2 REGULATION WITH ANALOG OUTPUT...6 3.2 O 2 REGULATION TROUGH VALVE...7 3.3 O 2 MEASURING DEVICE....8 3.4 O 2 ALARM...9 3.5 TEMPERATURE MEASUREMENT...9 3.6 EFFICIENCY... 10 3.7 ALARM FOR TEMPERATURE OF EXHAUST GAS... 10 3.8 ALARM INDICATION AND MEASURE.... 11 3.8.1 Alarm 1: To high O 2 -level.... 11 3.8.2 Alarm 2: To low O 2 -level... 11 3.8.3 Alarm 3: Temperature alarm for exhaust gas.... 11 3.8.4 Alarm 4: Sensor heating alarm... 12 3.8.5 Alarm 5: Electronic alarm... 12 3.8.6 Alarm 6: Sensor signal alarm... 12 3.9 COMMUNICATION THROUGH TERMINAL/PC... 12 3.9.1 Connection diagram... 12 3.9.2 Connection... 13 3.9.3 Process data... 13 3.9.4 Commands.... 13 3.10 LIST OF PARAMETERS... 14 4 TECHNICAL DATA.... 15 4.1 VOLTAGE SUPPLY... 15 4.2 TECHNICAL SPECIFICATION... 15 5 INSTALLATION... 16 5.1 MECHANICAL INSTALLATION... 16 5.1.1 MOC-100... 16 5.1.2 Sensor... 16 5.2 ELECTRICAL INSTALLATION... 16 5.2.1 Electrical installation drawing.... 16 5.2.2 If MOC-100 does not work... 16 5.2.3 Repair report.... 17 2

1 Introduction MOC-100 is a regulation and control unit for a lambda-sensor. It is specially design for controlling the oxygen level in exhaust gases. It includes four alternative functions: Regulate the amount of air to achieve the wanted O 2 level. Regulate fuel feeding to achieve the wanted O 2 level. Regulate a open/close airvalve to achieve the wanted O 2 level. Work as O 2 measuring device to other systems. The choice of function depends on parameter setting. To maintain safe and reliable combustion MOC-100 contains also the following options: One alarm output to indicate the following: To high O 2 -level To low O 2 -level Sensor alarm Electronic unit alarm Measure temperature of exhaust gas and temperature of supply air Calculate and show efficiency Generate a break signal by getting alarm from temperature of exhaust gas To start the MOC-100 just activate the start signal. The heat of the sensor turns on when this signal is active. During preheat of the sensor and when unit is not active the O 2 -level will show --, and the output of the analog signal depends on the value of parameter 7. Preheating takes about 90 seconds. MOC-100 starts regulating when the sensor is hot. 3

2 Functions 2.1 O 2 regulation O 2 regulation is one of MOC-100 s main functions. This function regulates all the time the amount of air alternative fuel based on O 2 -level at the O 2 -sensor. O 2 regulation and other available functions are illustrated by following picture: air BOILER fuel PRIMARY AIR SECONDARY AIR Chimney Pt 100 Pt 100 O 2 sensor Valve M F M F Valve 0-10 V Valve Other systems O 2 -value 0.1-21.0% -Efficiency -Valve position -Alarm indication 1-6 Room temperature or Exhaust temperature + - Panel Control Parameter setting Analog output 0-10V -Terminal communikation Digital output 24 VAC MOC-100 MiLAB Oxygen Control RS 232 Alarm output 24 VAC Power supply 230 VAC Start signal 24 VAC Desired O 2 value is set by parameter 1. To achieve the wanted O 2 level MOC-100 regulates the amount of air or fuel automatically. 2.2 Display board The front panel includes three displays. Top : O 2 level in %, Range 0.1-21. Middle: Valve position in % alternative efficiency. Bottom: Temperature of exhaust gas alternative room temperature. Parameter settings decide what shows in middle and bottom display. Alarm indicates by blinking display and showing an alarm code. 4

2.3 Communication through panel To set parameters and reset alarm MOC-100 has tree buttons. By pressing buttons you may communicate directly with MOC-100 and change parameters 1-17. 2.3.1 Set parameters The buttons are working together with the display. Communication is available by moving from normal mode to set parameter mode. To change mode do the following. Press + and - button together until the display is blank. Release the buttons and the following display will show. MOC-100 is now in set parameter mode. + - 1 Plus-button increases the value of a parameter. Number on display shows the parameter you are working with. (1-17) Minus-button decreases the value of a parameter. Display beside has no function. 1 2 5 Enter-button is used for setting of a parameter and at the same time jump to next parameter on the list (1-17). Display shows the parameter value. To finish parameter setting and move back to the normal mode do in the same way as the starting. Press + and - button together until the display is blank, release the buttons and MOC- 100 is now back in normal mode. MOC-100 has also a time-out function. MOC-100 automatically chances back to normal mode after 5 minutes, if no button have been pushed. 5

3 Parameters Parameters 1-17 are set by buttons or through terminal. This chapter shows which parameters are applicable for each main function. Further ahead shows how to set options. This chapter also gives more details of some parameters. Default value = delivery setting. OBSERVE! PARAMETERS WRITTEN WITH BOLD STYLE HAS A MAJOR INFLUENCE TO THE CHAPTER FUNCTIONS. 3.1 O 2 regulation with analog output When MOC-100 is used to control air, to maintain a wanted O 2 level, the analog output is proportional to the required air volume. This signal can regulate for example a speed controlled fan. If MOC-100 is used to control the amount of fuel this signal can control for example fuel pump, stoker or similar. Connect according to MOC 1301E. ( Look at appendix ) Parameter Scale, code Default 1: O 2 demand Step = 0.1 % O 2 50 2: O 2 alarm limit high Step = 0.1 % O 2 90 3: O 2 alarm limit low Step = 0.1 % O 2 30 4: Time before O 2 -alarm active Step 0.1 minute 50 5: Type of analog output 2 = Air regulation 2 3 = Fuel regulation 6: Analog output in stop mode, Scale 0-255 0=0Volt, 255 =10Volt 0 7: Analog out under preheating and fault according to parameter 6120 8: k-factor O2 regulation Scale 0-255 50 9: Open /Close valve regulation 0 10: Valve position in stop mode 0 11: Valve position under preheating and fault 50 12: Temperature measurement 0 13: Efficiency 0 14: Type of fuel 1 15: Temperature limit for exhaust gas alarm 100=100 0 C 100 16: Time delay exhaust gas alarm Step 0.1 minute 50 17: Use fresh-air test to sensor 0 Parameter setting above is used to regulate the amount of air with the analog output. Change parameter 5 to 3 if fuel regulation chosen. This means that the analog output decreases when the O 2 level is decreasing. To trim and make influence to function adjust parameters written with bold style. Parameter 6 defines analog output in stop mode. Parameter 7 defines analog out during preheat and fault condition. Parameter 8 defines how quickly air respective fuel should react to changes in O 2 level. Higher value gives a faster reaction. The following options may be used together with analog output control: O 2 Alarm (chapter 3.4) Temperature measurement (chapter 3.5) Efficiency (chapter 3.6) Alarm for temperature of exhaust gas (chapter 3.7) 6

3.2 O 2 regulation trough valve When MOC-100 is used to regulate air respective fuel with a valve, with position feedback potentiometer, parameters must be set according below. Make connection according to MOC 1302E. ( Look at appendix ) Parameter Scale, code Default 1: O 2 demand Step = 0.1 % O 2 50 2: O 2 alarm limit high Step = 0.1 % O 2 90 3: O 2 alarm limit Low Step = 0.1 % O 2 30 4: Time before O 2 -alarm active Step 0.1 minute 50 5: Type of analog output 2 = Air regulation 2 6: Analog output in stop mode, Scale 0-255 0=0Volt, 255 =10Volt 0 7: Analog out under preheating and fault according parameter 6 120 8: k-factor O2 regulation Scale 0-255 50 9: Open /Close valve regulation 0=off,1=air,2=fuel 1 10: Valve position in stop mode ( 0-100 ) 0 11: Valve position under preheating and fault ( 0-100 ) 50 12: Temperature measurement 0 13: Efficiency 0 14: Type of fuel 1 15: Temperature limit for exhaust gas alarm 100=100 0 C 100 16: Time delay exhaust gas alarm Step 0.1 minute 50 17: Use fresh-air test to sensor 0 Parameter setting above is used to control air by means of a valve, with a position feedback potentiometer. To trim and make influence to function adjust parameters written with bold style. Parameter 8 defines how quickly air respective fuel should react to changes in O 2 level. Higher value gives a faster reaction. Parameter 10 defines valve position in stop mode. Parameter 11 defines valve position during preheating and fault condition. 0 = fully closed valve and 100 = fully opened valve. The following options may be used together with valve regulation: O 2 Alarm (chapter 3.4) Temperature measurement (chapter 3.5) Efficiency (chapter 3.6) 7

3.3 O 2 measuring device. When MOC-100 is used to generate an analog output signal to be used in other systems set parameters according below. Connect according to MOC 1303E. ( Look at appendix ) Parameter Scale, code Default 1: O 2 demand Step = 0.1 % O 2 50 2: O 2 alarm limit high Step = 0.1 % O 2 90 3: O 2 alarm limit Low Step = 0.1 % O 2 30 4: Time before O 2 -alarm active Step 0.1 minute 50 5: Type of analog output 1 = O 2 value 1 6: Analog output in stop mode, Scale 0-255 0=0Volt, 255 =10Volt 0 7: Analog out under preheating and fault according parameter 6 120 8: k-factor O 2 regulation Scale 0-255 50 9: Open /Close valve regulation 0 10: Valve position in stop mode 0 11: Valve position under preheating and fault 50 12: Temperature measurement 0 13: Efficiency 0 14: Type of fuel 1 15: Temperature limit for exhaust gas alarm 100=100 0 C 100 16: Time delay exhaust gas alarm Step 0.1 minute 50 17: Use fresh-air test to sensor 0 Parameter setting above means that MOC-100 generates an analog output signal 0-10V that is proportional to the O 2 level. When this function is active, a status signal is available. Status signal is active if the analog output signal is proportional to the O 2 level. This means that during stop mode, preheat and fault condition this output is inactive. For connection information see MOC 1303E in appendix. The following options may be used together with this function: O 2 Alarm (chapter 3.4) Temperature measurement (chapter 3.5) Efficiency (chapter 3.6) Alarm for temperature of exhaust gas (chapter 3.7) 8

3.4 O 2 alarm To use the O 2 alarm function the following parameters have to be set: Parameter Scale, code Default 2: O 2 alarm limit high Step = 0.1 % O 2 90 3: O 2 alarm limit low Step = 0.1 % O 2 30 4: Time before O 2 -alarm active Step 0.1 minute 50 O 2 alarm function is only active when the unit is measuring an O 2 level. This means that this function is not operating in stop mode during preheat or in case of a fault condition. The O 2 value is compared to limits that are given by parameters 2 and 3. When the O 2 value is higher than parameter 2 or lower than parameter 3 a timer starts which after defined time, parameter 4, gives an alarm. Observe that this kind of alarm output is normally active, in other words the output signal is deactivate by alarm. This also means that MOC-100 generates an alarm in case of power supply failure. 3.5 Temperature measurement. Parameter that defines this function is: Parameter Scale, code Default 12: Temperature measurement 0 = Off 0 1 = Temperature of exhaust gas 2 = Temperature of air This function requires one or two temperature sensors type PT-100 be connected to each triple-pole input. Make connection according below: 24 25 26 27 28 29 30 31 32 33 34 35 36 EXHAUST GAS PT100:1 ROOM TEMP PT100 :2 If parameter 12 has a code 0 ( =Off ) there will be no temperature measurement. By setting code 1 or 2 both temperatures will be measured. Number of code decides which temperature shows on display. 9

3.6 Efficiency To show and calculate efficiency temperature measurement must be turned on and two PT100 temperature sensors must be connected. ( See chapter 3.5 ) The applicable parameters are: Parameter Scale, code Default 12: Temperature measurement 0 = Off 1 alt 2 13: Efficiency 0 = OFF, 1 = ON 1 14: Type of fuel See table below 1 To activate this function set parameter 13 = 1. Parameter 14 decides which energy constant to be use to calculate efficiency. Beside these standard constants there is a possibility to save and use own energy constants on the assumption that a terminal or PC is available. ( See chapter 3.9 communication through terminal ) Parameter 14 chooses an energy constant from following table: 1. Heating oil 2. Natural gas 3. City gas 4. Coal gas 5. Liquid gas 6. Own constants according to parameters 35 and 36 To define own constants do contact retailer or MiLAB for further information. 3.7 Alarm for temperature of exhaust gas To use this alarm one PT100 sensor must be installed and temperature measurement has to be active according to chapter 3.5. There is one input to activate this function. See connections below. 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 24 VAC EXHAUST GAS ALARM DIGITAL IN 24VAC/DC EXHAUST GAS TEST 10

The parameters that define this function are: Parameter Scale, code Default 9: Open /Close valve regulation 0 12: Temperature measurement 0 = Off 1 alt 2 15: Temperature limit for exhaust gas alarm 100=100 0 C 100 16: Time delay exhaust gas alarm Step = 0.1 minute 50 Alarm is activate when signal called exhaust gas test is active. Temperature of exhaust gas is compared to parameter 15 and if temperature is below, the timer starts. Exhaust gas alarm will be active after a chosen time set by parameter 16. This kind of alarm output is normally active, in other words the output signal is inactive by alarm. This also means that MOC-100 generates an alarm in case of power supply failure. 3.8 Alarm indication and measure. MOC-100 include six different alarms. Alarm is indicated by a blinking display. Reason of alarm shows in middle display with a number. Following reasons may show: 1. To high O 2 -level 2. To low O 2 -level 3. Temperature alarm for exhaust gas 4. Sensor heating alarm 5. Electronic unit alarm 6. Sensor signal alarm The only alarm that must be reset manually is number 3, temperature alarm for exhaust gas. The other alarms reset automatically when the alarm situation is not valid any more. 3.8.1 Alarm 1: To high O 2 -level. Alarm high O 2 -level is generated when O 2 -level passes above parameter 2, and stays above this limit for a longer time then have been set by parameter 4. This alarm can not be reset with buttons. To do something about this alarm the process must be investigated for the cause of the problem. It can be to trim some parameters in the MOC-100. 3.8.2 Alarm 2: To low O 2 -level. Alarm low O 2 -level is generated when O 2 -level passes below parameter 2, and stays below this limit for a longer time then have been set by parameter 4. This alarm can not be reset with buttons. To do something about this alarm the process must be investigated for the cause of the problem. It can be to trim some parameters in the MOC-100. 3.8.3 Alarm 3: Temperature alarm for exhaust gas. Alarm active according to chapter 3.7. Alarm must be reset manually by pressing the button. This alarm is normally given when the burning has stopped by some reason. That is, no real burning. This can be dangerous because unburned gases can still be generated. 11

3.8.4 Alarm 4: Sensor heating alarm Alarm is activate when MOC-100 can not measure a valid resistance in the sensor heating element. This alarm disqualifies all measurements from O 2 -sensor and O 2 value shows --. Alarm may be reset by button. Typical reason for this alarm is a damaged sensor or cabling to the sensor. Alarm deactivates automatically when failure is repaired. After checking the cabling carefully, do change sensor, if this fault remains after several reset. 3.8.5 Alarm 5: Electronic alarm This alarm is active when MOC-100 s heating output does not work. This alarm disqualifies all measurements from O 2 -sensor and O 2 value is --. Alarm may be reset by button. Check connections between MOC-100 and sensor. If this fault remains after several reset, and after checking cables and connectors, change electronic unit. Alarm deactivates automatically when failure is repaired. 3.8.6 Alarm 6: Sensor signal alarm. To use this alarm set the following parameter: Parameter Scale, code Default 17: Use fresh-air test to sensor 1 This option is not possible in all applications. The following will explain why. This alarm function tests the O 2 -sensor by checking that it reacts correctly to fresh-air that is supposed to come to sensor after combustion cycle. It is not possible to use this function without a guarantee that fresh air is blowing to the sensor, when start signal is inactive. This alarm disqualifies all measurements from O 2 -sensor and O 2 value is --. Alarm may be reset with the button. Check that gases are correctly passing the sensor, and that the sensor is not blocked. After that check connections between MOC-100 and sensor. Alarm deactivates automatically when failure is repaired. If this fault remains after several reset, change sensor. 3.9 Communication through terminal/pc 3.9.1 Connection diagram MOC-100 has an RS232 for communication. Communication cable must be connected as below: 25pol Dsub male to MOC-100 25pol Dsub female to PC 3 2 2 3 4 5 7 7 12

3.9.2 Connection To be able to communicate with MOC-100 through PC/terminal you have to use the following settings: Baud rate: 2400 Data bits: 7 Stop bits: 1 Parity: Even Flow control: None Connector: Choose a free comport 3.9.3 Process data All available process data is printed on the terminal, when the startsignal is active, as follows: Time O 2 % Valve% Gastemp. Roomtemp. Eff% Alarm 0,02 8.5 12 123 23 70% 0 0,04 8.2 12 123 23 70% 0 0,06 7.9 12 125 23 70% 0 The time is minutes and seconds from start. There will be a header printed every 40 line when the start signal is active. Otherwise a short menu shows according below: c: calibration s: set parameters 3.9.4 Commands. The commands included in the system are: c: calibration s: set parameters c: is the command to calibrate a valve with feedback potentiometer. Just type a 'c' and the valve will be calibrated and the calibration values will be stored in EEPROM. This function must be done if you install a system or if you change MOC-100 or a valve. s: is the set command that will be used to adjust one or several parameters. Here you can set all parameters. See chapter 3.10, List of parameters, for explanation of parameters. With a PC/terminal all MOC-100 parameters can be changed. 13

3.10 List of parameters Place: Date: Parameter Scale, code Default Own setting 1: O 2 demand Step = 0.1 % O 2 50 2: O 2 alarm limit high Step = 0.1 % O 2 90 3: O 2 alarm limit low Step = 0.1 % O 2 30 4: Time before O 2 -alarm generate Step 0.1 minute 50 5: Type of analog output 1 = O 2 value 1 2 = Air regulation 3 = Fuel regulation 6: Analog output in stop mode, 0-255 0=0V, 255 =10V 0 7: Analog out under preheat and fault According parameter 6 120 8: k-factor O 2 regulation Scale 0-255 50 9: Open /Close valve regulation 0 10: Valve position In stop mode 0 11: Valve position under preheating and fault 50 12: Temperature measurement 0 13: Efficiency 0 14: Type of fuel 1 15: Temp.limit for exhaust gas alarm 100=100 0 C 100 16: Time delay exhaust gas alarm Step 0.1 minute 50 17: Use fresh-air test to sensor 0 18: Blocking buttons Blocking = 0 1 29: K-value for O 2 Parameters 29-34 are written 0,068 30: M-value for O 2 behind a lock. Default values may 0 31: K-value for T1 use if right values are loose. 0,128 32: M-value for T1 80,10 33: K-value for T2 0,128 34: M-value for T2 80,10 35: Energy constant A (Suitable value) 36: Energy constant B (Suitable value) 14

4 Technical data. MOC-100 include a microprocessor, PROM, RAM and EEPROM. To be able to communicate and measure it has four analog inputs, one analog output, two digital inputs and four digital outputs. Analog inputs are of different type: one for potentiometer and the rest for temperature and O 2 MOC-100 generate an analog output 0-10 V DC Digital inputs are for 24V AC/DC Digital outputs 24V AC are for preheating, valve and alarm 4.1 Voltage supply MOC-100 is supplied by normal main voltage ( 230/110 V AC 50/60Hz ) and supplies 24V AC for valve and alarm equipment. 4.2 Technical specification Inputs: 1: Analog inputs for lambda sond. Lambda sensor 2: Position feedback potentiometer 1kOhm connected between 24,25,26 3: Two PT100 bridge inputs PT100 sensor, three wires 4: Two digital inputs. 24 V AC or DC, < 25mA 5: Supply for electronics and sensor 230 V AC 50/60Hz, max. 50 VA. Voltage range: -20% - +15%. OR 110 V AC 50/60Hz, max. 50 VA. Voltage range: -20% - +15%. Outputs: 1: Heating for lambdasond. Lambda sensor 2: Analog output 0-10V DC. Max. load 10 ma. 3: Three digital outputs for valve control Max. 48 V AC, max. 500 ma, and warning output Communication: RS232 serial port. Range: Oxygen 0.1-21% Mechanical case: Plastic box, IP65. Dimensions 213 x 185 x 113 mm Operating temperature range MOC-100: -20 to +50 o C. Operating temperature range sensor housing < +500 o C Operating temperature range at cable bushing < +200 o C Operating temperature range at connecting cable < +150 o C Operating temperature range at connector < +120 o C 15

5 Installation 5.1 Mechanical Installation 5.1.1 MOC-100 1. Find a place to mount the electronic box. It should be easy to read the display and to connect a terminal/pc to communicate with the unit. 2. MOC-100 must be mounted as close to the sensor as possible. Do not to use any longer cable then the one supplied with the unit. 3. Surroundings temperature must be between -20 o C - +50 o C 5.1.2 Sensor 1. The sensor is mounted by drilling a hole, corresponding to the thread, in a steel chimney. The hole should be placed on the upper side of the chimney as close to the boiler as possible. 2. Thread with M18 x 1.5 and mount the sensor. 3. Be sure that the sensor has the same earth connection as the electronic unit ( MOC-100 ). If the O 2 level will not be stable even when you think it should be this can depend on the mounting of the sensor or that there is a leakage of air into the combustion. There are several ways to mount the sensor depending on the type of chimney and temperatures. Call supplier for help and advice. A typical problem is that the unit is always displaying 1.0 % O 2, this depends in many cases on a missing earth connection either at the sensor or at the electronic unit. 5.2 Electrical installation The electrical supply is 230/110 V AC single phase. This supply should not be taken from any type of speed controller without necessary filters. During the installation keep all 230/110 Volt wires as far as possible from the signal wires. Also use shielded cables for the analog output and temperature input signals. Connect MOC-100 to same earth as the sensor. 5.2.1 Electrical installation drawing. See appendix. 5.2.2 If MOC-100 does not work Check the following things if the unit does not measure and regulate correctly: 1. Check sensor mounting and that there is not a leakage of air. 2. Check that all cables are connected correctly. (Compare connection diagram) 3. Check that sensor has a proper earth connection to the same earth as MOC-100. 4. Check that calibration parameters 29-34 are equal with the values behind the plastic cable cover. 5. Fault code is blinking. See further explanation and advice in chapter 3.8. 16

5.2.3 Repair report. MiLAB expects that the user checks the product according to chapter 5.2.2., before a return for guarantee or service is made. Read instructions for repair report and fill the form. MiLAB Idögatan 10 TORVINGE Telephone: +46 (0)13 311604 582 73 LINKÖPING Telefax: +46 (0)13 314118 SWEDEN Test protocol ( Filled by MiLAB ) Article name Fabrication number Test made by (name and date) Instruction for repair/guarantee: MiLAB expects user to contact seller before a return is made. Make a report of problem by filling this form. Enclose form and a copy of invoice with return delivery. Form for repair/guarantee report Sender Company Ref. person Address Telephone number Date: Product information Product name Date of invoice Invoice number Fault description What happened? Place and Date? Fault Description 17