PRODUCT BULLETIN. Rev. A Monitoring Station offering PN Rev. B as a direct replacement. OVERVIEW / DESCRIPTION

Similar documents
GLD-30 Gas Leak Detector

B-40/B-41 Modulating Temperature Controller

True Auto-Purge System

Electro-Sentry. Users Manual

EXPERT TRI-STAR. Temperature controller. User s Manual

CT224 Setup Tutorial

INSTALLATION & USER MANUAL

EasyTronic III MANUAL SERVICE

IMR Environmental Equipment, Inc Central Ave. St. Petersburg, FL Phone:

Operating Manual UV Monitor UVT 18

SCAN200E USER S MANUAL

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

Product Manual SZ1145

KRSCP Self-Contained Walk-In Unit Installation and Service Manual Addendum

RTD TEMPERATURE SENSING SYSTEM

System Accessories, LCD Annunciators

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Product Manual SZ1144

TDU Series LCD Thermostat For EFCB and EVCB Controllers. Models. Features. Functions. Onboard Sensors. Model # Temp RH CO2 Color.

Stainless Steel Condensing Boiler Connection Instructions To Additional Heating Devices

Follett Performance Plus

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

Application Manual Loop Water Controller

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

Farm Hand CCU 111 / CCU 10R. Manual for use and maintenance. Farm Hand. Climate Controller. HC/MMA/UmGB /13 rev 1.

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL

Dryer Master DM510 Commissioning Guide

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR THE HUBBELL MODEL TX / HX TANKLESS WATER HEATER

Temperature Controller CC24-7 UNIBOX USER S MANUAL Legion Dr. Mason, MI USA October 2010 Ph. (517) Fax (517)

EST User Manual. (Please read this manual carefully before using)

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Flopurge TS. Operation Manual

Duct and Rough Service Carbon Monoxide Sensor

SHQ15 A, 25 A HEATER CONTROLLERS

OPERATING MANUAL. EchoTherm PROGRAMMABLE DIGITAL CHILLING INCUBATOR MODELS IN35, IN45 and IN55-12VDC. DOCUMENT NUMBER IN35-03 Revised 15 May 2015

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

READ AND SAVE THESE INSTRUCTIONS

Compact Genset Controller, CGC 400 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

THX-DL Data Logger USER & INSTALLATION MANUAL V

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

NexSysLink. 2 CAN Display Operation Manual. CAN Instruments Product Family

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

NetworkAIR AFX. Operation and Maintenance AFX65 AFX18

Model 4880 Status Output Display Module Manual

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Instruction Manual August sitrans CU 02

THERMAX Efficiency Monitor

Dryer Controller M720

Instruction Manual December 2001 ENACOCU02

Tachometer/Hourmeter/Trip. Installation and Operation Manual

User Manual. Dryer Controller M720

Direct Steam Injection Humidifier

RES-210 (-211, -220, -221) / RES-420

Dryer Moisture Systems Inc. Dryer Master GM 2. Product Manual. Revision 1.0 January, 2007 Revision 1.01 March, Prepared by:

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

QD-ENG-68 Controller for Thermoelectric Thermal Management

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Sensor Cloud User Manual


Spa Touch Control Panel with 2000, 2100 controllers. (Spa Owner s Manual insert)

PHASE NON-COIN USER S MANUAL (S.A.F.E.)

Gas Detection System TOX ALARM DG2000-Garage

TC-9102 Applications

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

DNC-PS700-A10 Differential Pressure Control Meter. Operation and Installation Manual

Multi-Steam HDR* SKD-R Series Direct Steam Injection Humidifier with Integrated Re-Evaporator. Installation Instructions and User Manual

PRX-320 Waterproof Proximity Access Operating Instructions and Installation Manual

SmarTemp Control fx 2.0

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

Operating Manual RCM420

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide

AQUATROL Zone Synchronizing Universal Injection/Mixing Boiler Reset Controls AQ252

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

PAC-2750 ELECTRIC COOLING FAN CONTROLLER

Secondary Sensing System

TOUCHSCREEN. COMFORTSENSE Day Programmable Thermostat. 4 Heat / 2 Cool Universal Multi Stage MODEL NUMBER IDENTIFICATION L U FEATURES

ACTIVE INFRARED BARRIER

SYSTEM 5000 USER MANUAL

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

Networkable Fan Coil Controller Specification and Installation Instructions

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

Refrigerated air dryers

Ammonia Leak Detector Manual

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating Instructions. Temperature and Humidity EC Control. Model 35YV93

ENGINE MONITOR VOTT MODEL: YEAR WARRANTY

Briza Line. Digital Display Unit (Room Thermostat) Model BLC 13-RS Wall Mounting Cat Model BLC 33-RS Semi Flush Mounting Cat.

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR THE HUBBELL TANKLESS WATER HEATER

Flostop TS D7E and A8E. Operation Manual

1.1 Remote Annunciator Controller (RAC) using the one ATC-300+ connected via RS-485 network.

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic,

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free

Transcription:

PRODUCT BULLETIN ISSUE/DATE: March 28, 2008 rev A BULLETIN NUMBER: AQ032808 SUBJECT: Monitoring Station PRODUCT LINE: Aquafine UV Equipment TOPIC: REVISION TO THE 41114-1 MONITORING STATION OVERVIEW / DESCRIPTION Aquafine Corporation has qualified a new revision to the 41114-1 Monitoring Station. Attached with this Product Bulletin are the set up and operating instructions for the UV Monitoring Station PN 41114-1 Rev. B. DETAILS Aquafine has released a redesign version of the UV Monitoring Station. The latest version has eliminated the use of trim potentiometers to adjust the UV alarms and set points. Controller setting and adjustments are now completed thru software. We have also added password protection to eliminate adjustment by unauthorized personnel. Please note that this Revision B Monitoring Station is a direct replacement for the Revision A Monitoring Station. Aquafine will begin manufacturing equipment with this Revision B Monitoring Station effective March 14, 2008. Rev. A Monitoring Station offering PN 41114-1 Rev. B as a direct replacement. REVISION CHANGE Was: 41114-1 Rev. A Is: 41114-1 Rev. B WARRANTY Standard 12 Month Aquafine Warranty applies. ASSISTANCE If you require technical assistance or have any comments or suggestions on the content/format of this bulletin, please contact your Authorized Distributor or Customer Care Representative at Aquafine. 800-423-3015 Telephone 661-257-2489 FAX www.aquafineuv.com Aquafine will continue to support legacy equipment manufactured with PN 41114-1

1 Wiring Prior to working on the electrical panel, all electrical power must be removed and isolated from the system. Please note that there maybe additional electrical power connected to the system if there are customer interface wire connected to the alarm contacts from the Low UV sensor or High Temperature alarm. Monitoring Station Rev A Monitoring Station Rev B Fig 1 Existing Wiring Termination points to (Rev A) the Monitoring Station 0-1 VDC 4-20mA Detector Input Bare- Red- Black- Green- White- Brown- Low UV -NC 1 -COM 1 -NO 1 -NC 2 -COM 2 -NC 2 Power In -G -N -H NC 1 - COM 1- NO 1 - NC 2 - COM 2 NO 2 - + - + - Temperature

Fig 2 Existing Wiring to the Monitoring Station Rev A Wires to Temperature relays AC Power Wires Detector Cable connections Fig 3 Wiring termination Points to the Monitoring Station Rev B Page 3 of 9

H AC Input N AC Input N AC Input NO 1 Temp COM 1 Temp NC 1 Temp NO 2 Temp COM 2 Temp NC 2 Temp NO 1 UV COM 1 UV NC 1 UV NO 2 UV COM 2 UV NC 2 UV Detector In - Brown - White - Green - Black - Red - Bare Analog Out - + 4-20mA - -4-20mA - 0-1 VDC - +0-1 VDC Fig 4 Wiring to the Monitoring Station Rev B AC Power Wires Wires to temperature relay Detector Cable Connections Wiring the Unit The wiring consist of the following Page 4 of 9

1. AC power wires 2. Detector input connections 3. High temperature relay alarm(s) 4. Low UV relay alarm(s) 5. Analog signal 4-20mA and 0-1VDC 1. Wiring AC power wires The existing H-N-G wires should be removed from the existing terminal to the Ac input of the new Monitoring Station. There is no voltage selector switch on rev 2. 2. Wiring the detector input connection The existing 6 wires should be removed from the existing terminal to the detector input of the new Monitoring Station. 3. Wiring the high temperature relay alarm The existing wires to the COM-NC and NO should be removed from the existing terminal to temperature input of the new Monitoring Station. Please not that there are two sets of relay contacts (1 and 2). The wiring from the existing set of contacts should be noted before removing the wires and reconnecting. 4. Wiring the low UV relay alarm The Low UV relays are generally connected to customer interface wiring. The existing wires if any should be removed and reinstalled to the Low UV input of the Monitoring station. 5. Wiring the Analog signal 4-20mA and 0-1VDC Any analog connects should be remove and re terminated. 2. SETUP AND OPERATING INSTRUCTIONS PICTURE #1 The front face plate of the UV Monitor Station Lighted LCD Display Indicates 2 lines of information Up & Down Arrows provide selection of options A) Operation The Monitoring station is a combination UV controller. The signals from the detector are displaying the UV intensity and water temperature. Each of values may have a corresponding alarm set point. The first line of the main menu display indicates the UV intensity in relative or absolute units. The second line indicates water temperature in F or C. Main display ENTER button for access to MAIN MENU and to select options Page 5 of 9

Alarm display The first line of the alarm display indicates the relative UV intensity alarm set point. The second line indicates temperature alarm set point. This display is accessed by pressing the up arrow when in the main display. B) Software set up procedure will require accessing the main menu. This process is started by depressing the ENTER button, (described in picture #1), and then entering the password. 1.) The password 1234 is entered by: a) Depressing the up arrow will cycle to each digit. b) When the digit is achieved Depress the down arrow to move to the next digit position. c) Repeat procedure until all four digits indicate the correct password. d) Then depress enter e) The Display will indicate MAIN MENU C) From the MAIN MENU the following parameters can be accessed. To modify or change these parameters follow the steps described in paragraph D 1) The UV intensity display, ( UV DISPLAY ) a) RELATIVE Display of relative intensity 0-100% b) ABSOLUTE Display absolute intensity 0-5000 µw/cm² 2) The UV intensity alarm set point ( UV ALARM ) a) ON (set point) To enable UV alarm (DEFAULT) b) EDIT Select UV alarm set point 20-90% c) OFF disable UV alarm 3) Setting the UV 100% value, ( UV 100% LEVEL ) a) DIRECT Sets 100% UV (current value of absolute intensity) b) EDIT Sets 100% to entered absolute intensity value 4) The temperature display, ( TEMP DISPLAY ) a) FAHRENHEIT - select temperature unit of measurement b) CELCIUS - select temperature unit of measurement Page 6 of 9

c) OFF - disable temperature measurement 5) The temperature alarm set point, ( TEMP ALARM ) a) 120ºF (49ºC) set temp alarm to 120F (DEFAULT) b) 170ºF (77ºC) set temp alarm to 170F c) OFF disable temperature alarm D) The following steps will specify how to set each parameter of the monitoring station. After a parameter is set, the operator will be instructed to select RETURN once or twice to return to the operating screen. The operating screen will have the UV intensity displayed on the first line, and the temperature displayed on the second line. 1a) Setting the UV intensity display (Absolute µw/cm²or Relative %) : i. The main menu is accessed per the steps in paragraph B ii. The Display will indicate MAIN MENU iii. Use up / down arrows to scroll to UV DISPLAY in the sub-menu ENTER iv. Use up / down arrows to scroll to RELATIVE in sub menu ENTER or ABSOLUTE as indicated ENTER v. The display will indicate MAIN MENU with sub menu indicating UV DISPLAY. vi. Use up / down arrows to scroll to RETURN ENTER vii. The display should be at the main operating screen indicating UV intensity 2a) Setting the Low UV Alarm Set point: The alarm point will be a number between 20-90%. The selection is typically based upon the lamp type and operating conditions. Typical alarm set point values for equipment: with HX lamps 80% and standard lamps 60%. i. Follow the procedure in paragraph B to enter the MAIN MENU. ii. Use up / down arrows to scroll to UV ALARM ENTER. iii. Use up / down arrows to scroll to EDIT ENTER iv. Use up down arrows to scroll to preferred UV alarm threshold percentage ENTER. v. Verify main menu line indicates UV ALARM and the sub menu indicates ON( XX %) Note the XX indicates selected value vi. Use up / down arrows to scroll to RETURN ENTER. vii. Then again scroll to RETURN ENTER. viii. The display should be at the main operating screen indicating UV intensity 3a) Setting the 100% UV: Typically the UV Monitoring station intensity is set to 100% UV when new lamps and quartz sleeves have been installed and the system is operating under normal operating conditions (flow, temperature and water quality). Page 7 of 9

i. Use up / down arrows to scroll to UV 100% LEVEL is indicated in the sub menu ENTER. ii. The main menu will indicate UV LEVEL. iii. Use up / down arrows to scroll to DIRECT in the sub menu ENTER. iv. The main menu will indicate UV LEVEL, the sub menu will display an actual UV intensity value ENTER v. The MAIN MENU will be displayed, with sub menu displaying UV 100% LEVEL vi. Use up / down arrows to scroll to RETURN ENTER ix. The display should be at the main operating screen indicating UV intensity 4a) To set the temperature units (Fahrenheit or Celsius): i. Follow the procedure in paragraph B to enter the MAIN MENU. ii. Use up / down arrows to scroll to TEMP DISPLAY ENTER. iii. Use up / down arrows to scroll to desired temperature F, C or off. ENTER iv. Verify main menu line indicates MAIN MENU. v. Use up / down arrows to scroll to RETURN ENTER vi. The display should be at the main operating screen indicating UV intensity 5a) To set temperature alarm set point: The temperature alarm point is normally set to 120F. High temperature units are special equipment in which the set pint is 170F. If the temperature alarm is set to off, this will disable the temperature control feature and damage to the unit can occur. i. Follow the procedure in paragraph B to enter the MAIN MENU. ii. Use up / down arrows to scroll to TEMP ALARM ENTER. iii. Use up / down arrows to scroll to 120F (default), 170F or off ENTER iv. Verify display indicates main menu indicates MAIN MENU, and the sub menu indicates TEMP ALARM. v. Use up / down arrows to scroll to RETURN ENTER. vi. Then again scroll to RETURN ENTER. vii. The display should be at the main operating screen indicating UV intensity E) Alarm Indications 1) Low UV Alarm a) The UV alarm is activated when the detector UV measurement falls below the low UV alarm set point. Once activated, the controller will actuate the following a. There will be an audio alarm once every second for 30 seconds Page 8 of 9

b. The LCD screen flashes blue. The screen will remain flashing BLUE until the UV Intensity level adjusts above the threshold or the alarm is disabled c. The low UV output relays will change state 2) HIGH TEMP ALARM a) The high temperature alarm is activated when the detector senses a temperature above the high temperature set point. Once activated the controller will actuate the following a. There will be an audio alarm once every second for 30 seconds. b. The LCD screen flashes RED. The screen will remain flashing RED until the temperature alarm is corrected. c. The temperature output relays will change state Page 9 of 9