Emergency Ventilation System Design - Preliminary Report Shishir Gupta

Similar documents
CFD Analysis of Fire Characteristics on Subway Junction Station

Delhi Metro System. Emergency and Fire Safety Measures in. - by Sanjeev Kumar & Kailash Chandra Joshi. Fire Protection & Safety

Smoke Management in Subway Stations Due to Train Arson Fire Scenario

incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

VENTILATION & FIRE SAFETY

Tunnel Axial Flow Fan

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Case Study 1 Underground Car Park

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Tunnel Fire Dynamics and Evacuation Simulations

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background

DMRC at a Glance. Registered : May Construction Commenced : Oct Operation Commenced : Dec Operates 213 RKM in 7 lines, 158 Stations

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

Considerations in the Design of Smoke Management Systems for Atriums

COMPLEX COMMISSIONING AND QUANTITATIVE TESTING GOTTHARD BASE TUNNEL VENTILATION SYSTEM

Preliminary Fire/Life Safety Assessment Task No (Submittal No. PH b14

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

Hot Issues in Fire Engineering July 2014

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD

APPLICATION OF CFD SIMULATIONS FOR LOCATING OUTDOOR UNITS ON HIGH RISE TOWER Basant Kumar Gupta 1, Anand Patil 2

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany

Underground fires in metro systems failures, accidents and terrorism

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG

FOGTEC Rail Systems. Rolling Stock Applications. Fire Protection Solutions from one source. Experts in Fire Protection

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

SECTION PLUMBING/HVAC FINAL TESTING, ADJUSTING AND BALANCING

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

and Sprinkler System in Resalat Tunnel of Tehran

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

GAS DETECTOR LOCATION. Ø.Strøm and J.R. Bakke, GexCon AS, Norway

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Underground carpark ventilation

Japanese Case Study: How to maintain the fire safety in subway station and tunnel

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Simulation of Full-scale Smoke Control in Atrium

MINISTERIO DE FOMENTO

AXIAL & JET FANS FOR TUNNEL VENTILATION

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015

Shalaby Institute of Fire Protection Heyrothsberge, Germany.

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

Ventilation for Smoke Control, Fire Control & Life Safety in Tunnels. Dr. Ricky Carvel BRE Centre for Fire Safety Engineering University of Edinburgh

A Novel Approach for the Thermal Management. of PC Power Supply

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018

technical specification smoke venting systems

METRO WP4. CFD-simulations of a single exit underground station. Hans Nyman Torkel Dittmer RESEARCH REPORT 2012:4 STUDIES IN SUSTAINABLE TECHNOLOGY

Displacement Ventilation

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Performance of an Improved Household Refrigerator/Freezer

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

Smoke Control Requirements for New Railway Infrastructure. Ir Peter Law

[Eswaran, 3(3): March, 2014] ISSN: Impact Factor: 1.852

Computational simulation of road tunnel fire protection by sprinklers

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Mass Notification and Intelligent Response TM The European Way

A comparison between emergency ventilation systems semi-transvers ventilation and natural ventilation in Road Tunnel A

GreenJet Transfer Fans

Interfacing Fire Alarm, Sprinkler and Elevator Systems

Technical Presentation on

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel

CHAM Case Study Numerical Simulation of a Air-to-air Cross-flow Heat Exchanger

Redesign of Bennett Hall HVAC System

Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2

Fire Engineering in High Rise 15 November 2013

Crossrail Fire Safety Designs

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Design of an Air Cooled Telephone Booth Using Solar Energy as Non-Conventional Energy Source

ASHINGTON BLYTH & TYNE RAIL RE-OPENING PROJECT. The Case For A Station at SEGHILL

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

International Journal of Advance Engineering and Research Development

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title:

Case Study 1 Underground car park

CASE HISTORY: RETROFIT OF COAL MILL EXHAUST FAN STUDY OF FAN PERFORMANCE AND EROSION

PASSENGER RAIL NETWORK LIGHTING OF STATION ENVIRONMENT TO COMPLY WITH DISABILITY STANDARDS FOR ACCESSIBLE PUBLIC TRANSPORT

STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER

Compression of Fins pipe and simple Heat pipe Using CFD

Full Service Central Station Fire Alarm Listing Evaluation

Design of Fire safety in Multi Occupancy Residential Accommodation

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

An experimental study of the impact of tunnel suppression on tunnel ventilation

Road tunnel safety rules in Italy: the tunnel country

Transcription:

Emergency Ventilation System Design - Preliminary Report Shishir Gupta (shishir@mechartes.com), Abstract The existing stations and tunnels of Metro Railway, Kolkata are not equipped with effective emergency ventilation system. The original design provides only normal ventilation for passengers comfort and physiological requirements. Hence, it was required to design modifications to enable effective emergency ventilation in case of fire / smoke scenario in station / tunnel / subway premises. In order to accomplish this objective, following studies were conducted: 1. Smoke extraction system design for a typical station of Kolkata Metro. 2. Smoke extraction system design for a typical tunnel system. 3. To demonstrate effectiveness through Computational Fluid Dynamic (CFD) analysis (3- Dimensional). 3D CFD analysis was done for emergency ventilation systems. The results of flow analysis were analyzed to compare current system and original system. It was ensured that the CFD results agree to the overall mass balance across the system. Further, it was also observed from the analysis the shortcomings of the current system and possible design changes for better ventilation on station as well as in the tunnel. Based on these simulations, flow velocities across individual inlets, exhausts and ramps were calculated to enhance the mass evenness of flow across the system. These calculations along with depending criteria like heat load, design alternatives etc. were considered in this study. Based on all these considerations and calculations as per the fire protection standards, the design of emergency ventilation system was arrived. 1

Typical Station Design The Kolkata Metro Line network incorporates the following tunnel section, station and ventilation structures for fire study: Approximately, the average length of tunnel between any two stations in this line is 800mts Typical station is an island type station with double Rail track on each side of the platform at the platform level; In the current system, each platform has air-conditioned air inlet of 130 cubic meters per second. In the current system, each platform has exhaust of 50 cubic meters per second from Under Platform Exhaust (UPE) to exhaust the heat generated due to braking of the trains at each station. In tunnel at each side, 80 cubic meters per second exhaust shaft is provided for the current system. Mid-Tunnel Exhaust Ramp Openings Air-Conditioned air Inlet (At station) ` Ramp Openings Mid-Tunnel Exhaust UPE UPE Half section of Typical Tunnel (400 m) Typical Station (Island Type) Half section of Typical Tunnel (400 m) Red Arrow ( ) : Exhaust ; Green Arrow ( ) : Inlet ; Blue Arrow ( ) : Open to atmosphere Fig 2.1: Schematic representation of Typical station and Typical Tunnel 2

Fig 2.2: Three-Dimensional CAD model for Typical station In this station design, the system is considered including station platform, both side station track way, first floor (Ticketing counter) and the ground level to platform level stairs passage.two half typical tunnels on each side of the station represent the complete system under analysis. It is very much important to consider the whole system with connecting half tunnels for the smoke extraction ventilation system. The model above also shows the converging connection between typical tunnel and typical station. 3

FIRE DATA Maximum Fire Size 15 MW NBC and NFPA standards Radiation 25% NBC and NFPA standards Maximum Fire Perimeter 44.5 m Assuming fire on one coach Other relevant information Maximum time for fire brigade & personals to reach at the fire point : 1 Hr Smoke detector & Heat Detector sensors are already installed in the system Emergency Batteries are installed in train to provide back-up power in case of emergency for operation of train The rake drivers are trained & instructed to make efforts to bring train to station in case of any emergency like accidental fire A water supply line is installed at each station to provide water from 1600 to 2100 Gallon to deal with fire calamities. 4

Design of emergency ventilation system Double Speed OTE (Over Track Exhaust): An OTE system shall be installed with exhaust ducts running over the track. The capacity of this system shall be 40 m 3 /s (as per 6.4.2) at low speed and 80 m 3 /s (as per 6.4.1) at high speed. The OTE system would operate at low speed when airconditioned coaches are introduced and OTE system would operate at high speed in case of emergency. The fans and ducts for OTE shall be fire rated and AMCA (Air Movement Control Association) certified. Tunnel Ventilation Fans (TVF): Impulse fans called tunnel ventilation fans (TVF) shall be installed in the tunnel directing toward the mid tunnel exhaust. Three number of TVF shall be installed in the 400m tunnel equally spaced between the station and the mid tunnel exhaust. So each tunnel would have 6 TVF at an average installed in the direction toward the midtunnel exhaust. TVF shall be fire certified and AMCA approved. CFD Fire Simulation Results: (A) Following figures shows the smoke generated from fire inside the Platform on Railway Track at different timings Fig.5 (a) Contours of smoke from burning Coach at starting of time in 5

Fig.5 (b) Contours of smoke from burning Coach at 10 seconds time in Fig.5 (c) Contours of smoke from burning Coach at 1 minute time in EMERGENCY VENTILATION SYSTEM DESIGN, METRO RAILWAY KOLKATA 6

Fig.5 (d) Contours of smoke from burning Coach at 3 minute time in Fig.5 (e) Contours of smoke from burning Coach at 5 minute time in 7

Fig.5 (f) Contours of smoke from burning Coach at 8 minute time in Fig.5 (g) Contours of smoke from burning Coach at 10 minute time in 8

Fig.5 (h) Contours of smoke from burning Coach at 12 minute time in Fig.5 (i) Contours of smoke from burning Coach at 15 minute time in 9

Fig.5 (j) Contours of smoke from burning Coach at 18 minute time in Fig.5 (k) Contours of smoke from burning Coach at 20 minute time in 10

Fig.5 (l) Contours of smoke from burning Coach at 21 minute time in Fig.5 (m) Contours of smoke from burning Coach at 22 minute time in 11

Fig.5 (n) Contours of smoke from burning Coach at 24 minute time in Fig.5 (o) Contours of smoke from burning Coach at 25 minute time in 12

(E) Following figures shows the Visibility levels in (meters) at 1.8m height from platform level & at different timings Fig.9 (a) Visibility levels in (meters) at starting of time in Fig.9 (b) Visibility levels in (meters) at 10 second time in 13

Fig.9 (c) Visibility levels in (meters) at 1 minute time in Fig.9 (d) Visibility levels in (meters) at 3 minute time in 14

Fig.9 (e) Visibility levels in (meters) at 5 minute time in Fig.9 (f) Visibility levels in (meters) at 8 minute time in 15

Fig.9 (g) Visibility levels in (meters) at 10 minute time in Fig.9 (h) Contours of Visibility in (meters) at 12 minute time in 16

Fig.9 (i) Visibility levels in (meters) at 15 minute time in Fig.9 (j) Visibility levels in (meters) at 18 minute time in 17

Fig.9 (k) Visibility levels in (meters) at 20 minute time in Fig.9 (l) Visibility levels in (meters) at 21 minute time in 18

Fig.9 (m) Visibility levels in (meters) at 22 minute time in Fig.9 (n) Visibility levels in (meters) at 24 minute time in 19

Fig.9 (o) Visibility levels in (meters) at 25 minute time in Fig.9 (p) Visibility levels in (meters) at 26 minute time in 20

Fig.9 (q) Visibility levels in (meters) at 27.5 minute time in 21

(B) Following figures shows the Temperatures generated from burning Coach in side the Basement in different vertical planes & at different timings (Here the maximum temperatures generated are approximately 400 o C at fire location, but in order to see the lower temperature levels inside the basement we have taken 150 o C maximum range) Fig.6 (a) Contours of Temperature in ( C) at starting of time in Fig.6 (b) Contours of Temperature in ( C) at 10 second time in 22

Fig.6 (c) Contours of Temperature in ( C) at 1 minute time in Fig.6 (d) Contours of Temperature in ( C) at 3 minute time in 23

Fig.6 (e) Contours of Temperature in ( C) at 5 minute time in Fig.6 (f) Contours of Temperature in ( C) at 8 minute time in 24

Fig.6 (g) Contours of Temperature in ( C) at 10 minute time in Fig.6 (h) Contours of Temperature in ( C) at 12 minute time in 25

Fig.6 (i) Contours of Temperature in ( C) at 15 minute time in Fig.6 (j) Contours of Temperature in ( C) at 18 minute time in 26

Fig.6 (k) Contours of Temperature in ( C) at 20 minute time in Fig.6 (l) Contours of Temperature in ( C) at 21 minute time in 27

Fig.6 (m) Contours of Temperature in ( C) at 22 minute time in Fig.6 (n) Contours of Temperature in ( C) at 24 minute time in 28

Fig.6 (o) Contours of Temperature in ( C) at 25 minute time in Fig.6 (p) Contours of Temperature in ( C) at 26 minute time in 29

Fig.6 (q) Contours of Temperature in ( C) at 27.5 minute time in 30

(C) Following figures shows the Temperatures generated from fire inside Platform in horizontal plane at 1.8m height from platform level & at different timings Fig.7 (a) Contours of Temperature in ( C) at start of time in Fig.7 (b) Contours of Temperature in ( C) at 10 second time in 31

Fig.7 (c) Contours of Temperature in ( C) at 1 minute time in Fig.7 (d) Contours of Temperature in ( C) at 3 minute time in 32

Fig.7 (e) Contours of Temperature in ( C) at 5 minute time in Fig.7 (f) Contours of Temperature in ( C) at 8 minute time in 33

Fig.7 (g) Contours of Temperature in ( C) at 10 minute time in Fig.7 (h) Contours of Temperature in ( C) at 12 minute time in 34

Fig.7 (i) Contours of Temperature in ( C) at 15 minute time in Fig.7 (j) Contours of Temperature in ( C) at 18 minute time in EMERGENCY VENTILATION SYSTEM DESIGN, METRO RAILWAY KOLKATA 35

Fig.7 (k) Contours of Temperature in ( C) at 20 minute time in Fig.7 (l) Contours of Temperature in ( C) at 21 minute time in EMERGENCY VENTILATION SYSTEM DESIGN, METRO RAILWAY KOLKATA 36

Fig.7 (m) Contours of Temperature in ( C) at 22 minute time in Fig.7 (n) Contours of Temperature in ( C) at 24 minute time in EMERGENCY VENTILATION SYSTEM DESIGN, METRO RAILWAY KOLKATA 37

Fig.7 (o) Contours of Temperature in ( C) at 25 minute time in Fig.7 (p) Contours of Temperature in ( C) at 26 minute time in EMERGENCY VENTILATION SYSTEM DESIGN, METRO RAILWAY KOLKATA 38

Fig.7 (q) Contours of Temperature in ( C) at 27.5 minute time in 39

CONCLUSION Conclusion The emergency ventilation system has been designed as per the guidelines and calculations from NBC, NFPA, ASHRAE and BS Standards for emergency and fire protection. The detailed design and its operation can be seen in the chapter above. The scope of this study was the design of emergency ventilation system. This design has been arrived with the consideration that air-conditioned coaches might be introduced in future. Efforts have been made to make minimum changes in the current system and take care of retrofitting limitations. Once the design of the system is approved by MRK with regard to feasibility of execution, CFD simulations would be conducted using FDS to validate the capacities and design parameters of the final design. 40

REFERENCES 1) National Building Code (NBC) of India Bureau of Indian Standards. 2) National Fire Protection Association (NFPA) 130 2010 edition Standard for Fixed Guideway Transit and Passenger Rail Systems. 3) American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE) Handbook series 4) British Standards (BS) 7346-4:2003 5) Report on Kolkata Metro ventilation studies by IIT Kharagpur. 41