Development and Handling of Hydrocarbon Air-conditioners The Godrej Experience

Similar documents
Perspective on transition to Air-conditioners with Natural Refrigerants The Godrej Experience

Energy Efficiency & Climate Change Benefits from Room Air Conditioners Godrej Perspective

Alternatives in the AC & Chiller Sectors. Sukumar Devotta and Lambert Kuijpers OORG Refrigeration

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

FACT SHEET 9 Large Air-Conditioning (air-to-air)

Low GWP Refrigerants for Air Conditioning Applications

FACT SHEET 9 Large Air-Conditioning (air-to-air)

Possibilities of the RAC sector transformation a technical perspective

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

CHAPTER 1 INTRODUCTION

ENERSAVE Hydrocarbon Scroll Water Cooled Chiller

Study of R161 Refrigerant for Residential Airconditioning

Bringing Hydrocarbon to the Market Training & Certification

Evaluation and Development of Air-conditioners using Low GWP Refrigerant

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

Reducing Refrigerant Leakage

International Journal of Advance Engineering and Research Development

Refrigerant Dryers DRY with PDP Indicator

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Global Solutions for Ammonia Industrial Refrigeration

Natural refrigerants - naturally efficient

HFO-1234yf Performance in a Beverage Cooler

Current use of HFCs and HCFCs. Trends, alternatives and climate impact. YEREVAN, Armenia, May 18-19, International Institute of Refrigeration

HYDROCARBONS, HEAT PUMP, HOME LAUNDRY DRYER: ENVIRONMENT FRIENDLY APPLIANCE

Q. Which hydrocarbons can be used as a refrigerant? The following hydrocarbons can be used as a refrigerant in cooling & heating applications:

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control.

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

CHAPTER 1 INTRODUCTION

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

38RBS Air-Cooled Condensing Units. product selection data. commercial and industrial applications. compact design.

38RBS Air-Cooled Condensing Units. Nominal cooling capacity: kw. Features. Easy and fast installation

High Wall Split Systems Cool Only 9K - 12K - 18K - 24K. Auto. Auto. Fan Speed. Smart LCD Wireless Control. Auto Mode.

FACT SHEET 6 Transport Refrigeration

Santanu Prasad Datta (Student) P. K. Das & S. Mukhopadhyay

Introduction of Panasonic New CO2 refrigeration system (Technical Part)

TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-12CHS/K TAC-18CHS/K TAC-24CHS/K

High Efficiency Technologies for Small and Medium-Sized Air Conditioning Equipment Using R410A. Hitachi Appliances, Inc.

Ductable Range of Air Conditioners

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

Actions to Control Emission of HFCs in Japan

Chapter 10. Refrigeration and Heat Pump Systems

Evaluation of HCFC Alternative Refrigerants

VRF Outdoor Units. YMGI Group 601 Arrow Ln, O Fallon, MO ymgigroup.com Solar Series Mini & Modular

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

Energy Saving & Eco-Friendly Refrigerant

TECHNICAL SPECIFICATIONS

DTI Kenneth Bank Madsen Global Application Expert Food Retail

Condensing Units CUS 15-60

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Brazed Plate Heat Exchanger for CO Applications

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

air systems Roomtop RTC-RTH 15 to 30 - L

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

NFZP Variable Refrigerant Flow Guide Specification

30RBY/RQY Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG +

Daikin s Policy. and Comprehensive Actions on the Environmental Impact of

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

Welkom. Optimalisatie CO2 systemen m.b.v. ejecteur

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

REQUEST FOR PROPOSAL FOR SUPPLY & INSTALLATION OF Air Conditioners

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

American Brand with Global Reach. Model: SMLW-SAGL

Emad Chen. Head of Qatar Office Midea Commercial Air Conditioner

Transitioning to Alternatives and Challenges in Japan

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

CATALOGUES SUMMARY - WCHBZ Pages WCHZ Pages 19-42

Low GWP alternative refrigerants to R404A

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Miraco MISR REFRIGERATION & AIR CONDITIONING MFG. CO.

Challenges from flammability concerns and related safety standards, possibilities for compact systems limiting charge sizes

The Current Path of Refrigerants

European Experience in Certification of competence in ODS substitutes: F-gas and Alternative Refrigerants. Pune, 5 th March 2015

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator

Air Conditioning Repairs: Maintenance Required

American Brand with Global Reach. Heat Pump Decorative Wall Mount Split Unit

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers. NEW GXG-S Series GSG-S Series Debut

ISSN: [Sachuthananthan * et al., 5(10): October, 2016] Impact Factor: 4.116

Technical Development Program

V4 Plus Heat Recovery VRF. Linda Lin Pre-sales Engineer

Technical Manual. Multi Split Trio Quattro DCI REFRIGERANT R410A HEAT PUMP

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Call us today! (800)

SPLIT SYSTEM AIR CONDITIONERS, HEAT PUMPS AND PACKAGED SYSTEM PRODUCTS Built Exclusively for Manufactured Housing


Transcription:

Development and Handling of Hydrocarbon Air-conditioners The Godrej Experience UNFCCC Side Event, Bonn, 10 th June 2013

Introduction Who we are Godrej & Boyce Mfg. Co. Ltd - The Flagship Company of the Godrej Group Into Business since 1897 One of the largest privately held Industrial Corporations Annual Turnover of Rs. 62 Billion (approx.) for FY 2012-13 All India presence with 20 Branches & 51 Showrooms Family of 11000 + employees

Introduction The Appliance Division The largest business unit of Godrej & Boyce Mfg. Co. Ltd Established in 1958 Annual Turnover Rs. 17 Billion (approx) for FY 2012-13 Products Refrigerators Washing Machines Air-conditioners Chotukool (Thermo-electric refrigerator) Introduced 100% CFC free refrigerators in 2000, using hydrocarbon technology the first and only Indian company to do so

Introduction Commitment to the Environment Land area in Vikhroli - 3200 acres of which 1750 acres is reserved for conservation of Mangrove Forests the lungs of Mumbai

Agenda Background Product Development Manufacturing Set-up Service Training & Network Further Research

Background The trigger Decision of the 19 th MOP to the Montreal Protocol - Accelerated phase out of HCFCs German Ministry of Environment under it s International Climate Initiative through GIZ invited Indian air-conditioner manufacturers to participate in a project on HC-290 to reduce greenhouse gas emissions Godrej responded to the call.

Product Development

Lab Modifications Lab modifications to suit testing of HC-290 Safety Protection Multi-point sensing gas detectors to cover all parts of test chamber Low (1%), mid (1.5%) and high (2%) alarm levels with appropriate actions initiated at each level Auto Exhaust System Ventilation dimensioned to bring gas concentration below low alarm level within 10 min Ventilation and exhaust air system at bottom (Propane heavier than air) Electrical Equipment Ex-proof lighting and blowers All buttons and switches with ex. Protection

Lab Modifications Static Electricity Prevention Proper earthing for equipment Doors to have rubber seals Test stands with anti-static epoxy paint Fire Emergency Devices Auto water spray (mist head device) CO2 fire extinguishers Security Identification Warning markings Safety procedures on lab doors

Product Research Test methodology Published data on performance of HC-290 vis-à-vis HCFC-22 Drop-in performance* 3~15% drop in cooling capacity 2~8% improvement in COP Charge quantity 45~50% by weight The strategy Drop-in testing Use standard HCFC-22 compressor with 5~10% higher rated capacity Depending on results, work on other elements of refrigeration system *Devotta S, Padalkar AS, Sane NK. 2005, Performance assessment of HC-290 as a drop-in substitute to HCFC-22 in a window air conditioner, Int. J. of Refrig. 28: 594-604.

Product Research Drop-in Test Results (vis-à-vis HCFC-22) Cooling capacity lower by 6% COP higher by 14% Power consumption lower by 17.8% Charge quantity 50% (by weight) average 575 g. Compressor of 10% higher capacity Cooling capacity higher by 4.3% COP higher by 7% Power consumption lower by 3.5% Charge quantity 51% (by weight) average 585 g. Charge quantity - a matter of concern

Product Research Charge limit as per EN 378 m max = 2.5 x LFL 5/4 x h 0 x A 1/2, where m max is the allowable maximum charge in a room in kg; A is the room area in m 2 ; LFL is the lower flammable limit in kg/m 3 ; h 0 is the installation height of the appliance in m. For a typical 5kW split AC unit, m max = 2.5 x 0.038 5/4 x 2.3 x 14 1/2 = 361 g.

Product Research Smaller diameter condenser tubes Trials with 5mm diameter internally grooved Cu tubes (instead of 7mm) Cooling capacity lower by 0.5% COP higher by 21% Power consumption lower by 18% Charge quantity 50% (by weight) average 355 g. Availability, an issue Only one manufacturer of 5mm diameter condensers Development shelved

R&D Methodology Micro-channel heat exchangers (brazed aluminium) the game changer Use of 50 channel condensers in conjunction with higher efficiency compressors Cooling capacity lower by 3% COP higher by 16.5% Power consumption lower by 20% Charge quantity 46% (by weight) average 360 g. Charge quantity on the threshold of EN 378 requirements

R&D Methodology The way forward Use of micro-channel condensers with smaller channel sizes Explore availability of condensers with 5mm (or lower) diameter Cu tubes

The Manufacturing Project

The Manufacturing Project Tripartite agreement, Ozone Cell/GIZ/Godrej Dec 2010 to set up manufacturing facility for annual output of 180,000 Split and Window type Airconditioners Equipment Specifications, Tendering June 2011 Equipment Delivery Dec 2011 Installation & Commissioning Jan ~ March 2012 TuV Audit of Manufacturing Line March 2012 BEE Certification March 2012 Pilot Production - April 2012

The Manufacturing Project Safety Measures on Manufacturing Line Gas Sensors and Alarm Systems Refrigerant Storage Area Refrigerant Charging system Product Performance Test Chamber Product Repair Area Ex-proof electrical hardware in areas handling refrigerant Product Performance Test Chamber Ventilation System in areas handling refrigerant Refrigerant Charging system Product Performance Test Chamber Product Repair Area

The Manufacturing Project Gas charging station with ventilation ducting & gas alarms

The Manufacturing Project Repair area gas recovery system with ducting & gas alarm interlock Fire proof junction boxes in Refrigerant charging areas

The Manufacturing Project Ventilation system in HC 290 gas charging station and performance test chamber with two speed option & gas alarm mechanism and complete power cutoff interlock

The Manufacturing Project The Product AC Cooling Capacity : 3375W Compressor details : Rotary Power Supply : 230/1/50 (V/Phase/Hz) Power Input : 912W EER : 3.7 Star Rating : 5 Star AC Cooling Capacity : 5000W Compressor details : Rotary Power Supply : 230/1/50 (V/Phase/Hz) Power Input : 1325W EER : 3.7 Star Rating : 5 Star For a complete list of products, visit our website http://www.godrejappliances.com

The Manufacturing Project Risk Analysis & Mitigation Leak simulation testing* Under a catastrophic, instantaneous leak situation, between 65% - 75% of the refrigerant exits the system In off-mode, when using a gas detector inside the IDU (set at 20% of LFL) to indicate a leak and initiate IDU airflow, the floor concentration did not exceed 70% of LFL (charge equivalent to 40% of LFL; 450 g in a 30 m 3 room) Use of solenoid shut-off valves in the liquid line (and where necessary, in the suction line) can further reduce the leakage to around 20% of the charge quantity

The Manufacturing Project Leak Detection & Mitigation Refrigerant Leak Detection System Issues a visible and audible alarm under the simultaneous existence of the following condition: Machine current and sensed temperature are less than a determined value. The device must remain active after the initial activation till the device is reset. Upon issuing an alarm, the device must: Override the signal from the machine controller and switch OFF the compressor and Override the signal from the machine controller and operate the blower on the IDU and fan on the ODU at maximum speed.

The Manufacturing Project Leak Detection & Mitigation Refrigerant Leak Mitigation System Solenoid shut-off valves in the event of the start of a release, a shut off valve in the liquid or delivery line and where necessary in the suction line can close in order to prevent flow of refrigerant from the high side of the system to the leak hole; During off-mode the valve(s) could be normally-closed so that the refrigerant is automatically prevented from flowing towards the leak.

Service Training & Network

Service Training Godrej - the only Appliance company in the industry appointed by the Government of India to carry out Training for their projects like NCCOPP, HIDECOR. Godrej Vocational Training School imparts training in training institutes (ITI s) Godrej Refrigerators with HC refrigerants are produced since 2001, 13 years of manufacturing. More than 10 million units installed and serviced by Godrej trained field engineers successfully. Godrej Appliance Service has also trained field staff in Bangladesh.

Service Training All master technicians trained by a team of GIZ and Godrej experts Dissemination of this knowledge to all Godrej technicians Comprehensive training manual prepared Only certified technicians are permitted to install and service the HC 290 AC For Split ACs, flaring of connecting pipe ends not permitted in the field Only Factory flared connections used

Tested R22 and R290 split ACs Characteristic HCFC-22 air conditioner HC-290 air conditioner Nominal capacity 5.19 kw 4.83 kw Nominal COP (cooling) 3.08 3.60 Evaporator type Finned tube Finned tube Evaporator block volume 5.45 litres 5.45 litres Evap no. tubes, circuits 32, 3 32, 3 Evaporator airflow rate 850 m 3 /h 850 m 3 /h Condenser type PFC PFC Condenser block volume 6.06 litres 6.03 litres Condenser no. tubes 52 52 Compr swept volume 5.27 m 3 /h 5.39 m 3 /h Compressor rated COP 3.10 3.38 Cap tube length, OD 0.8 m, 3.0 mm 0.65 m, 3.2 mm Refrigerant charge 0.75 kg 0.36 kg

Tested R22 and R290 split ACs R22 model R290 model

Results; global performance Global results show Cooling capacity of R-290 model is 7% lower at rating conditions; gets marginally greater at higher temp by 3% Improvement in COP of R-290 over R-22 also declines Cooling capacity (kw) COP (kw/kw) Parameter Outdoor temperature 35 C 48 C 50 C 52 C 54 C HC-290 4.84 4.08 3.90 3.74 3.64 HCFC-22 5.19 4.43 4.20 4.12 Difference 7% 8% 8% 10% HC-290 3.60 2.38 2.21 2.04 1.91 HCFC-22 3.08 2.11 1.93 1.86 Difference 16% 12% 13% 10%

Relative capacity [%] Relative COP [%] Results; relative capacity and COP 100% 80% HC-290 HCFC-22 100% 80% HC-290 HCFC-22 60% 60% 40% 40% 20% 20% 0% 0% 48 50 52 Ambient temperature [ C] 48 50 52 Ambient temperature [ C]

Compression ratio [-] Discharge temp [ C] Results; pressure ratio and discharge temp 5 HC-290 HCFC-22 110 HC-290 HCFC-22 4 3 90 2 70 1 0 50 35 48 50 52 Ambient temperature [deg C] 35 48 50 52 Ambient temperature [ C]

Efficiency Temperature [ C] Results; compressor efficiency and dts 100% HC-290 HCFC-22 80 HC-290 HCFC-22 80% Volumetric 60 Condensing 40 60% 40% Global compr 30 40 50 60 Ambient temperature [ C] 20 0 30 40 50 60 Ambient temperature [ C] Evaporating

Charge (kg) Remarks on safety 1.0 0.8 0.6 high heat load low heat load 6 kw Charge size limit Despite certain obstructive safety standards, HC ACs can still be within limits 0.4 0.2 0.0 2.5 kw 0 20 40 60 80 100 120 Room size (m 2 ) [Based on Kuwait Code of Practice for design heat loads; air conditioner charge size as with the tested AC (75 g/kw) but in reality, only ¾ of charge leaks out!]

Final remarks Alternatives to HCFC-22 in ACs Concern over suitable options for high ambient regions R-410A normally considered to be unsuitable Other alternatives include HC-290 Normally efficiency in ACs is particularly good and flammability risk is know to be negligible Data on performance at high ambient is very sparse Current work presents results of testing HC-290 and HCFC-22 split ACs at high ambient Variation in COP at high temperature for HC-290 same as with HCFC-22 Variation in capacity of HC-290 same as with HCFC-22 Consistent with the theoretical calculations, but marginally better results observed Evident that HC-290 is well suited to high ambient regions

Thanks!