Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Similar documents
PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Energy Use in Refrigeration Systems

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

B. A. T. Basic Appliance Training

Refrigeration Systems and Accessories

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs

MASS. MARITIME ACADEMY

Pressure Enthalpy Charts

14. The center port of the manifold is used for evacuation, charging and refrigerant recovery.

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

HVAC Fundamentals & Refrigeration Cycle

System Considerations for Refrigerant Blends with Temperature Glide

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

The Refrigeration Cycle

USING THE P-T CARD AS A SERVICE TOOL

The Refrigeration Cycle

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

Refrigeration and Air Conditioning

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

RTP Technical Bulletin

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Cooling Fundamentals

Refrigeration Manual. Part 1 - Fundamentals of Refrigeration

Refrigerant changeover guidelines

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

10/4/2013. The Changing State of Refrigerants

Use this Construction/HVAC Glossary to answer the questions below.

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

HVAC/R Refrigerant Cycle Basics

Basic Principals of Air conditioning By Dr. Esam Mejbil Abed

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Vehicle Level Heating and Air Conditioning Description and Operation A/C System - Manual. A/C System - Manual

THERMOSTATIC EXPANSION VALVES Part 1

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

CHAPTER 3 BASIC STEAM CYCLE

REFRIGERANT CHANGEOVER

Short Questions with Answers APPLIED THERMODYNAMICS(5 TH MECHANICAL) Chapter No-1

HEAT PUMPS. Carrier Corporation GT72-01A Cat. No

Technical Development Program

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

YOUR BASIC REFRIGERAION SYSTEM SVASD MAY 26, 2011

TWO- AND THREE-STAGE CASCADE REFRIGERATION SYSTEM By: Paul B. Reed

March 10, 2016 San Joaquin Valley RETA Meeting

Vacuum Gauge. Measures lower-than-atmospheric pressure Digital scales. microns psi in. Hg millibars pascals torr millitorr

A Treatise on Liquid Subcooling

Sustainable Techniques in Refrigerated Space

Refrigeration Basics from a Brewery Perspective

The Essentials Of Working With R-410A

AIM: TO STUDY THE PERFORMANCE OF THE DOMESTIC REFRIGERATION RIG.

Technical Bulletin (TB-0037)

Refrigerant Installation Quick Reference Guide

Residential Piping and Long Line Guideline

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

A/C Cooling Load calculation and measurement

Chapter 9. Refrigeration and Liquefaction

APPLICATION & SERVICE GUIDE

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Refrigeration Systems

THERMODYNAMICS PREPARED BY DW & JD

The Changing State of Refrigerants. Gary Parker Refrigerants Product Manager

R-407A R-448A R-449A

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

EXHIBIT G REFRIGERANT MANAGEMENT POLICY

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Warm Case Troubleshooting Guide 9/18/2014

SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION

Otherwise, you can continue reading the file on the following pages.

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

HEATING, AIR CONDITIONING & REFRIGERATION TECHNOLOGY DEPARTMENT COURSE SYLLABUS

The Saturation process

How to Trap: Conversion Factors

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

How to Trap: Process Air Heaters

Steam Trap Selection

How to Trap: Trap Selection and Safety Factors

Carwin COMPRESSOR SELECTION PROGRAM

Transcription:

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration. Describe the term ton of refrigeration. Describe the basic refrigeration cycle. Explain the relationship between pressure and the boiling point of water or other liquids. Describe the function of the evaporator or cooling coil. Explain the purpose of the compressor. List the compressors normally used in residential and light commercial buildings. Discuss the function of the condensing coil.

Unit Objectives After studying this chapter, you should be able to: State the purpose of the metering device. List four characteristics to consider when choosing a refrigerant for a system. List the designated colors for refrigerant cylinders for various types of refrigerants. Describe how refrigerants can be stored or processed while refrigeration systems are being serviced. Plot a refrigeration cycle for refrigerants (r-22, r-12, r-134a, and r-502) on a pressure/enthalpy diagram.

Unit Objectives After studying this chapter, you should be able to: Plot a refrigeration cycle on a pressure/enthalpy diagram for refrigerant blends r-404a and r-410a. Plot a refrigeration cycle on a pressure/enthalpy diagram for a refrigerant blend (r-407c) that has a noticeable temperature glide.

INTRODUCTION TO REFRIGERATION Cooling to preserve products and provide comfort 1900s were the beginnings of mechanical refrigeration systems Refrigeration process temperature ranges High temperature Air conditioning (comfort) Medium temperature Fresh food preservation Low temperature Frozen food preservation

REFRIGERATION Process of transferring heat from a place where it is objectionable to a place where it makes little or no difference Heat naturally flows from a warmer substance to a cooler substance Heat will flow naturally from a 100 F house if the outside temperature is 80 F Mechanical refrigeration is needed if the house is 80 F and the outside temperature is 100 F

Heat flows naturally from a warmer substance to a cooler substance Outside temperature 80 F Inside Temp 100 F

Heat flows naturally from a warmer substance to a cooler substance Outside temperature 100 F Inside Temp 80 F Mechanical refrigeration would be needed to cool this house

RATING REFRIGERATION EQUIPMENT It takes 144 btu to melt one pound of ice at 32 F 2,000 pounds of ice (1 ton) will require 288,000 btu to melt (144 btu x 2,000 pounds) If the melting of 1 ton of ice takes place in one day (24 hours), 12,000 btu must be absorbed by the ice every hour (288,000 btu / 24 hours) 12,000 btu/hr = 200 btu/min = 1 ton of refrigeration

THE REFRIGERATION PROCESS Heat is pumped from a cool box to a warm room Pumping of heat is similar to pumping water uphill Air conditioners pump heat from inside to the outside Inside temperature 75 F, Outside temperature 95 F Cooling (indoor) coil temperature 40 F Condenser (outdoor) coil temperature 125 F Indoor heat travels to the indoor coil System heat flows from the outdoor coil to the outside air

Outdoor coil at 125 F Outside temperature 95 F Inside Temp 75 F Heat flows naturally from the air inside the house to the cooling coil (evaporator) Cooling coil at 40 F Heat also flows naturally from the condenser coil to the ambient air surrounding the coil

TEMPATURE AND PRESSURE RELATIONSHIP Water boils at 212 F at atmospheric pressure (29.92 in. Hg) Water boils at 250 F if pressure is increased to 15 psig Water boils at 40 F if pressure is reduced to 0.248 in. Hg Refrigerants are substances that boil at low pressures and temperatures and condense at high pressures/temperatures Saturation temperature Point at which the addition or removal of heat will result in a change of state During a change of state, the temperature remains constant

REFRIGERATION COMPONENTS Evaporator - Absorbs heat from area to be cooled Compressor Creates pressure difference needed to facilitate refrigerant flow through the system Condenser - Rejects system heat Metering device Regulates refrigerant flow to the evaporator

THE EVAPORATOR Heat exchange surface used to absorb heat Located on the low-pressure side of the system between the metering device and the compressor Operates at temperatures lower than the medium being cooled or conditioned Absorbs heat by boiling a low temperature liquid into a low temperature vapor

THE EVAPORATOR (cont d) Refrigerant typically enters the evaporator as a liquid/vapor mix (75% liquid, 25% vapor) Superheat The heating of a vapor above its saturation temperature Ensures that no liquid refrigerant enters the compressor Equal to the evaporator outlet temperature minus the evaporator saturation temperature Design superheat is typically between 8 F and 12 F Superheated vapor does not follow a pressure/temperature relationship

AIR CONDITIONING APPLICATION: R-22 EVAPORATOR 41 F 43 F 45 F 50 F Last drop of liquid 68.5 psig In green region, the P/T relationship does not hold 40 F Superheated vapor to the compressor 68.5 psig (40 F from P/T chart) Liquid/vapor mixture from the metering device

THE COMPRESSOR Pumps heat-laden vapor from the evaporator to the condenser by increasing the refrigerant pressure Reduces pressure on the low-side of the system Increases pressure on the high-side of the system Common compressor types include the scroll, reciprocating and the rotary Positive displacement compressors require that the compressed gas be moved to the condenser

Low pressure, low temperature superheated vapor enters the compressor High pressure, high temperature superheated vapor leaves the compressor Refrigerant from the evaporator Suction line Discharge line Refrigerant to the condenser Refrigerant in the compressor is superheated, so it does not follow a pressure/temperature relationship!

THE CONDENSER Rejects sensible and latent heat from the system that was absorbed by compressor and evaporator Located on the high-pressure side of the system The refrigerant condenses from a high temperature vapor to a high temperature liquid Condensing temperature is determined by the high side pressure in the system Refrigerant is subcooled at the outlet of the condenser

Subcooling THE CONDENSER (cont d) The cooling of liquid refrigerant below its saturation temperature Standard air-cooled systems are designed to operate with a minimum of 10 F of subcooling High efficiency condensers operate with more subcooling than standard efficiency systems Determined by subtracting the condenser saturation temperature from the condenser outlet temperature

AIR CONDITIONING APPLICATION: R-22 CONDENSER Refrigerant is desuperheating 110 F First drop of liquid 130 F 185 F 226 psig 200 F In green regions, the P/T relationship does not hold 110 F Superheated vapor from compressor 110 F 106 F 101 F 98 F 95 F Refrigerant is subcooling Subcooled liquid to the metering device

THE METERING DEVICE Controls the flow of subcooled liquid from the condenser to the evaporator Creates a pressure drop between the high and low pressure sides of the system About 25% of the liquid leaving the metering device immediately vaporizes (flash gas) Three commonly used metering devices are the capillary tube, automatic expansion valve and the thermostatic expansion valve

PUTTING IT TOGETHER: A WINDOW UNIT EXAMPLE Compressor Condenser Indoors: 75 F Outdoors: 95 F Evaporator Metering device R-22

PUTTING IT TOGETHER: A WINDOW UNIT EXAMPLE 100% vapor Saturated refrigerant 69 psig 50 F 200 F 278 psig 125 F 110 F Outdoors: 95 F 278 psig 69 psig (40 F) 75% liquid 25% vapor R-22

PUTTING IT TOGETHER: A WINDOW UNIT EXAMPLE 69 psig 50 F 200 F 278 psig R-22 125 F 110 F Superheat = 50 F - 40 F = 10 F Outdoors: 95 F Subcooling = 125 F - 110 F = 15 F 69 psig (40 F)

REFRIGERANTS R-12 used primarily for high and medium temperature refrigeration applications (manufacture banned in 1996) R-22 used primarily in air conditioning applications (slated for total phase-out in 2030) R-500 and R-502 banned in 1996 R-134a replacement for R-12 with retrofit Replacements for R-22 include R-410a and R-407c

REFRIGERANTS MUST BE SAFE Designed to protect people from sickness, injury and death Proper ventilation is required Refrigerants can displace oxygen if permitted to accumulate Modern refrigerants are non-toxic When burned, toxic/corrosive gases are created

REFRIGERANTS MUST BE DETECTABLE Methods used for detecting refrigerant leaks include: Soap bubble solution pinpoints leaks Halide leak detector uses an open flame Electronic leak detectors general area leaks Ultraviolet leak detectors pinpoints leaks Ultrasonic leak detectors uses sound waves

GENERAL REFRIGERANT NOTES Refrigerants should boil at low temperatures at atmospheric pressure so that low temperatures can be obtained without going into a vacuum It is illegal to intentionally vent refrigerant to the atmosphere (Stiff fines for violations) Mandatory certification for technicians The EPA set refrigerant phase-out schedules Refrigerant cylinders and drums are color-coded

RECOVERY, RECYCLING AND RECLAIMING OF REFRIGERANTS Refrigerant recovery is mandatory during service and installation operations Intended to reduce the emissions of CFC, HCFC and HFC refrigerants Recovery equipment must be used according to manufacturer s instructions

PLOTTING THE REFRIGERATION CYCLE Pressure-enthalpy chart Used to create a graphical representation of a system Pressure scales on the vertical axis (psia) Enthalpy scale along the bottom of the chart Horseshoe curve represents the saturation curve Refrigerant is saturated on and under the curve Enthalpy is defined as heat content

THE PRESSURE ENTHALPY CHART Subcooled liquid region Saturation curve Pressure (psia) Saturated refrigerant Superheated vapor region Enthalpy scale (btu/lb)

THE PRESSURE ENTHALPY CHART: A SAMPLE PLOT Metering device Condenser Pressure (psia) Compressor Evaporator Enthalpy scale (btu/lb)

THE PRESSURE ENTHALPY CHART: AN R-22 EXAMPLE 311.5 psia Cond. sat. temp. 130 F (296.8 psig, 311.5 psia)

THE PRESSURE ENTHALPY CHART: AN R-22 EXAMPLE 311.5 psia 83.2 psia Evap. sat. temp. 40 F (68.5 psig, 83.2 psia)

THE PRESSURE ENTHALPY CHART: AN R-22 EXAMPLE 311.5 psia 130 F 83.2 psia 0 F of subcooling, so refrigerant enters the metering device at 130 F 40 btu/lb

311.5 psia 83.2 psia THE PRESSURE ENTHALPY CHART: AN R-22 EXAMPLE 130 F Evaporator superheat is 10 F, so refrigerant leaves evaporator at 50 F 50 F 40 btu/lb 110 btu/lb

311.5 psia 83.2 psia THE PRESSURE ENTHALPY CHART: AN R-22 EXAMPLE 130 F Suction line superheat is 10 F, so refrigerant enters compressor at 60 F 60 F 40 btu/lb 110 btu/lb 112 btu/lb

THE PRESSURE ENTHALPY CHART: AN R-22 EXAMPLE 311.5 psia 130 F Refrigerant leaves compressor at 190 F 190 F 83.2 psia 127 btu/lb 40 btu/lb 110 btu/lb 112 btu/lb

THE PRESSURE ENTHALPY CHART: AN R-22 EXAMPLE 311.5 psia 83.2 psia 127 btu/lb 40 btu/lb 110 btu/lb 112 btu/lb

THE PRESSURE ENTHALPY CHART: AN R-22 EXAMPLE Metering device: A to B Evaporator: B to C Suction line: C to D Compressor: D to E B A C D E Condenser E to A 127 btu/lb 40 btu/lb 110 btu/lb 112 btu/lb

PRESSURE ENTHALPY CALCULATIONS Net Refrigeration Effect (NRE) = C B = 110 btu/lb 40 btu/lb = 70 btu/lb Heat of Compression (HOC) = E C = 127 btu/lb 110 btu/lb = 17 btu/lb Total Heat of Rejection (THOR) = E A = 127 btu/lb 40 btu/lb = 87 btu/lb Heat of Work = E D = 127 btu/lb 112 btu/lb = 15 btu/lb

UNIT SUMMARY Common refrigeration temperature ranges are high, medium and low High temperature refrigeration is also referred to as air conditioning or comfort cooling Refrigeration is the process of transferring heat from a place where it is objectionable to a place where it makes little or no difference Heat flows naturally from warm to cool substances

UNIT SUMMARY - 2 Saturated refrigerants follow a P/T relationship One ton of refrigeration is equal to 12,000 btu/hour The evaporator is the component that absorbs heat The condenser is the component that rejects heat The metering device is the component that regulates refrigerant flow to the evaporator The compressor creates the pressure difference in the system that allows the refrigerant to flow

UNIT SUMMARY - 3 Superheat is equal to evaporator outlet temperature minus evaporator saturation temperature Subcooling is equal to the condenser saturation temperature minus the condenser outlet temperature Superheated and subcooled refrigerants do not follow a pressure/temperature relationship Modern refrigerants must be safe and detectable The pressure enthalpy chart provides a graphical representation of a refrigeration system