GAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications

Similar documents
8+* Bulletin No November 1997

MERIT SERIES Downflow

ELITE SERIES Downflow - High Efficiency Blower Motor

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

GSR21Q GAS FURNACES EXISTING NEG EXISTING NEG ENGINEERING DATA HORIZONTAL POSITION. Typical Applications DOWN-FLO POSITION

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E

ELITE SERIES Lo-Boy. AFUE - 83% Heating Input - 101,000 to 151,000 Btuh Nominal Add-on Cooling to 5 Ton. OIL FURNACES El0183b

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES

G34M Bulletin #69/ August 2003

SL280DFV. DAVE LENNOX SIGNATURE COLLECTION Downflow - Two-Stage Heat - Variable Speed Blower

GSR21Q PULSE21 SERIES

RGE 13 A T - 1 A

DuralokPlus Aluminized Steel Heat Exchanger G 32 V

13 GEP A L P - 1 A

T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ. Thermal Efficiency - up to 82% Input - 40,000 to 300,000 Btuh

G61MP. ELITE SERIES Multi Position Two Stage Heat G A S F U R N A C E S. AFUE 94.1% Input 44,000 to 132,000 Btuh Nominal Add on Cooling 2.

OHR23. ELITE SERIES Horizontal/Downflow. AFUE - Up to 83.5% Input - 105,000 to 154,000 Btuh Nominal Add-on Cooling - 2 to 5 Tons O HR 23 Q 3/4-105/120

G61MP. ELITE Series Multi-Position - Two-Stage Heat. AFUE - Up to 95% Input - 44,000 to 132,000 Btuh Nominal Add-on Cooling - 2.

COMPACT UNIT HEATERS Low Profile - Horizontal - 60 HZ. Steady-State Efficiency - up to 81% Input - 30,000 to 75,000 Btuh

DAVE LENNOX SIGNATURE COLLECTION Lo-Boy - Variable Speed Blower

MERIT SERIES Downflow

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

MERIT SERIES Up Flow / Horizontal

Product Data. 58EFA Horizontal Gas Furnace. 50, ,000 Btuh Input

CB18/CBS18 Bulletin # September 1994 Supersedes August 1986

B24/C22/24 COILS BLOWER COIL UNITS ENGINEERING DATA. Bulletin # June 1994 Supersedes August B24 Blower Unit (With Optional Electric Heat)

FEATURES. Gas Furnace provides the efficiency customers want with 78% Annual Fuel Utilization Efficiency (AFUE).

G60UHV(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

ML180UH. MERIT SERIES Upflow / Horizontal. AFUE - 80% Input - 44,000 to 132,000 Btuh Nominal Add-on Cooling - 2 to 5 Tons ML 1 80 UH 070 X P 36 B

Gas Valve. Combustion Air Intake. Supply Air Blower AM30. Typical Applications

Upflow/Downflow Horizontal Right or Left Gas-Fired Furnace

Upflow/ Horizontal Downflow/Horizontal Condensing, Direct Vent Gas-Fired Furnace

Model GB1AAV UPFLOW GAS FURNACE. Series G SS-GB1A-04 FEATURES

DAVE LENNOX SIGNATURE COLLECTION Downflow - Two-Stage Heat - Variable Speed Blower

AFUE 95% Heating Input 50,000 to 200,000 Btuh

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

MERIT SERIES Upflow / Horizontal

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

ELITE SERIES Upflow / Horizontal - High Efficiency Blower Motor

ML 1 80 UH 070 X E 36 B

MERIT SERIES Upflow / Horizontal

Downflow/Horizontal Right Induced Draft Gas Furnace

ELITE SERIES Upflow / Horizontal - High Efficiency Blower Motor

80% Variable Speed, Two Stage Heating Furnace. Cooling Capacity CFM in. w.c. (125 Pa)

G60DFV(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

Upflow/ Downflow Horizontal Right or Left Gas-Fired Furnace

Upflow/Horizontal Condensing, Gas-Fired Furnace

DAVE LENNOX SIGNATURE COLLECTION Upflow / Horizontal - Two-Stage Heat - Variable Speed Blower

Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80

MERIT SERIES Downflow

Corp L12 Revised G24M SERIES UNITS

Upflow/Horizontal Right or Upflow/Horizontal Left Induced Draft Gas Furnace XR 80

TECHNICAL SPECIFICATIONS

Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace

Upflow/Horizontal Condensing, Gas-Fired Furnace XB 90 PUB. NO

VNE GAS FURNACE 2- STAGE VARIABLE SPEED UPFLOW/HORIZONTAL

TECHNICAL GUIDE MODELS: P*DH GAS-FIRED CONDENSING / HIGH EFFICIENCY DOWNFLOW / HORIZONTAL FURNACES 91 AFUE DESCRIPTION WARRANTY FEATURES

Upflow/Horizontal Left, Downflow/Horizontal Right Two Stage Condensing Gas-Fired Furnace

LRP14GE. SEER AFUE - 81% 2 to 5 Tons Cooling Capacity - 22,600 to 57,000 Btuh Input Gas Heating Capacity - 54,000 to 126,000 Btuh

SKYPAK II, 3 Ton Series, gives you a

ELITE SERIES Upflow / Horizontal - Two-Stage Heat

395CAV Sizes 045 thru 155 Series H and J

Upflow/Horizontal Left Downflow/Horizontal Right Condensing, Direct Vent Gas-Fired Furnace FREEDOM 90 SINGLE STAGE

G6RC Series TECHNICAL SPECIFICATIONS

LRP14DF. Dual-Fuel Residential - R-410A L RP 14 DF X P A MODEL NUMBER IDENTIFICATION

XC80 TUD2B060ACV32A TUD2B080ACV32A TUD2C080ACV42A TUD2B100ACV32A TUD2C100ACV52A TUD2D120ACV52A TUD2D140ACV52A

48SS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

Product Data. 95% AFUE Single Stage Furnace Upflow / Downflow / Horizontal. ama ! WARNING

MERIT SERIES Up Flow / Horizontal

AFUE - 80% Input - 44,000 to 132,000 Btuh Nominal Add-on Cooling to 5 Tons GAS FURNACES ML180UHE

TECHNICAL SPECIFICATIONS

FSA, FOA, SEP & HED Series Unit Heaters and Duct Furnaces

Product Data. 58PAV Energy-Efficient Induced-Combustion Upflow Furnace. Input Capacities: 45,000 thru 155,000 Btuh. 80% AFUE At Budget Price

PGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

FG7T (C and L Series)

KG6RC Series TECHNICAL SPECIFICATIONS FEATURES AND BENEFITS

XV80i. Upflow/Horizontal 80% 2-Stage, Variable Speed Gas-Fired Furnace with Whole House Air Cleaner PUB. NO

Upflow/ Horizontal Downflow/Horizontal Condensing, Direct Vent Gas-Fired Furnace

Upflow/ Horizontal Left, Downflow/ Horizontal Right Two Stage Condensing Gas-Fired Furnace XL 90

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

Product Data. 58TUA WeatherMaker 8000TS with Comfort Heat Technology Upflow Furnace. Series 120 Input Capacities: 40,000 thru 135,000 Btuh

SKYPAK II Heating & Cooling Self Contained Packages

Downflow/Horizontal Condensing, Gas-Fired Furnace XB 90 PUB. NO

UNIT HEATER CATALOG. Form RZ-NA-C-UH (Version F)

G51MP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

Direct Fired Heater Model AD Specification

RG7D 1-Stage Heat Series

TECHNICAL GUIDE MODELS: P*UR GAS-FIRED CONDENSING / HIGH EFFICIENCY UPFLOW FURNACES 92 AFUE DESCRIPTION WARRANTY FEATURES Rev.

MERIT Series R-410A - Upflow / Horizontal

U n i t H e at e r s

G I E TECHNICAL GUIDE 95.5% AFUE SINGLE STAGE RESIDENTIAL GAS FURNACES MULTI-POSITION MODELS: TG9S DESCRIPTION FEATURES WARRANTY SUMMARY

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

Cooling Capacity CFM in. w.c. (125 Pa)

ML180UHT (ce) MERIT SERIES Upflow / Horizontal 50HZ. Net Input to 34.8 kw Nominal Add-on Cooling to 17.

F8AUH Gas Furnaces Up-Flow/Horizontal

Transcription:

ENGINEERING DATA Typical Applications G20RE and G20RXE WhisperHeat DOWN-FLO GAS FURNACES *78.0% A.F.U.E. 50,000 to 150,000 Btuh Input Add-On Cooling 2 thru 5 Nominal Tons *Isolated Combustion System rating for Non-Weatherized Furnaces GAS FURNACES G20RE/ G20RXE Bulletin #480112 March 1993 Supersedes May 1991 EXISTING NEG Closet Installation With cooling coil Utility Room Installation With cooling coil and humidifier Applications G20RE and G20RXE series gas fired furnaces include eight models with input capacities of 50,000, 75,000, 100,000, 125,000 and 150,000 Btuh and energy efficiencies (AFUE) of 78.0%. G20RE models are available with either natural gas or LPG. G20RXE models are available with natural gas only. Down-flo furnaces are designed for installations with the distribution duct work installed under the floor or tunneled into a concrete slab floor. Units can be installed in a family or recreation room, utility room or closet. Approvals Units are certified by A.G.A. Laboratories and ratings are certified by GAMA. Units have been rated and tested in the Lennox Research Laboratory according to DOE test procedures and FTC labeling regulations. G20RXE models meet California Nitrogen Oxides (NO x ) Standards and California Seasonal Efficiency requirements. Blower data is from unit tests conducted in the Lennox Laboratory air test chamber. Equipment Warranty DURACURVE Aluminized Steel Heat Exchangers have a limited warranty for a full twenty years. Solid-state ignition modules have a limited warranty for a full three years. All other components have a limited warranty for one year. Refer to the Lennox Equipment Limited Warranty certificate included with the equipment for details. Lennox DURACURVE Aluminized Steel Heat Exchanger Lennox developed heat exchanger eliminates fatigue failure, ticking, resonance and cleanability problems. In the unique design of this heat exchanger the sides of the clam sectionform a flue restriction zone comprised of two concentric cylinders. As the sidesgrow, they expand and move, but in the same direction and at the same rate. The result is perfect combustion, proper venting and absolute freedom of movement for the metal. Design also results in high input to heat surface ratio, low resistance to air travel, reducing blower motor horsepower requirements and ease of cleaning. Heavy gauge aluminized steel construction provides long service life. Compact size of heat EXISTING NEG exchanger permits low overall design of furnace cabinet and smooth lines give minimum resistance to air travel. Laboratory life cycle testing proves long life of the heat exchanger. NOTE Specifications, Ratings and Dimensions subject to change without notice. 1993 Lennox Industries Inc.

FEATURES Aluminized Steel Burners Each burner has four rows of practically continuous ports which result in quiet and clean combustion. A crossover igniter of actual burner ports, perpendicular to the main burner, carries a positive flame from burner to burner to achieve quiet and sure ignition. X models have stainless steel NO x rods. Electronic Pilot Ignition Solid-state electronic spark igniter provides positive ignition of pilot burner on each operating cycle. Pilot gas is ignited and burns during each running cycle (intermittent pilot) of the furnace. Main burners and pilot gas are extinguished during the off cycle. This system permits main gas valve to open only when the pilot burner is proven to be lit. Should a loss of flame occur, the main valve closes, shutting down the unit. Pilot is a fully automatic operation on demand for heat. Also features Watchguard circuit. Solid-state control provides automatic reset of ignition controls after one hour of continous thermostat demand after unit lockout. Automatic Gas Control Silent operating gas controls provide 100% safety shut off. 24 volt redundant combination gas control valve combines automatic safety pilot, manual shut off knob (On-Off), pilot filtration, automatic electric valve (dual) and gas pressure regulation into a compact combination control. Dual valve design provides double assurance of 100% close off of gas to the pilot and main burners on each off cycle. Rugged Cabinet Constructed of heavy gauge cold rolled steel. Cabinet is subject to five station metal wash process resulting in a perfect bonding surface for a paint finish of bakedon enamel. The paint solution and metal are given opposite electrical charges resulting in positive adhesion and even coverage of the paint to the metal surfaces. Cabinet surface temperatures are low due to interior metal liners on each side of cabinet and foil faced fiberglass insulation on vestibule panel, side panels and on back panel. Complete service access is accomplished by removing furnace and blower compartment doors and access panels. Safety interlock switch located on the blower vestibule panel automatically shuts off power to the unit when filter access door is removed. Gas piping and electrical inlet knockouts are provided in both sides of the cabinet. Return air opening is flanged for ease of duct connection. Supply air opening matches the supply air opening in add-on Lennox down-flo evaporator coils. Combustion Air Damper Damper is factory installed in the aluminized steel burner box extension of the heat exchanger. Energy saving damper closes off combustion air flow through the heat exchanger during burner off cycle to prevent loss of heated air up the flue. Heavy gauge aluminized steel damper is gasketed for tight seal and rotates smoothly in nylon bearings. Equipped with a heavy duty synchronous spring return damper motor. Removable top on burner box allows access into the burner area for servicing and field conversion to LPG. Damper proving switch confirms that damper is open before allowing main gas valve to open. Flame Rollout Switch Manual reset switch is furnished as standard and is factory installed on the burner box. Switch prevents unit operation in the event combustion products passage through the flueway is reduced or blocked. Blocked Safety Shutoff Sensor Manual reset temperature sensor prevents unit operation in case of flue blockage and meets ANSI requirements. Sensor is furnished as standard and is factory installed on the draft hood. Limit Controls Factory installed and accurately located limit controls (dual) have fixed temperature settings and are located in furnace and blower sections. Protects unit in case of abnormal operating conditions. BCC2-2 Blower Control Center Furnished and factory installed on blower vestibule panel. Solid-state board contains all necessary controls and relays to operate furnace. Fan control consists of adjustable blower timed-off delay (90 to 330 seconds) and fixed blower timed-on delay (45 seconds). For airconditioning applications, blower is automatically energized on thermostat demand for cooling. Provisions have been made for additional wiring connections required for power humidifiers and electronic air cleaners. Also included is a low voltage terminal strip for thermostat connections. Wiring Junction Box Power supply connections are made at the wiring junction box which is located on the furnace vestibule panel. Box contains control transformer. Transformer 24 volt control transformer is furnished as standard equipment and is factory installed in wiring junction box. Transformer has fuse wired in series for added protection. Powerful Blowers Units are equipped with quiet multispeed direct drive blowers. Each blower assembly is statically and dynamically balanced. Multiple-speed leadless motor is resiliently mounted. A choice of blower speeds is available on each blower. See blower performance charts. Cleanable Air Filters Washable or vacuum cleanable frame type filters are furnished as standard. Polyurethane media is coated with oil for increased efficiency. Factory installed filter rack is furnished for easy filter replacement. OPTIONAL ACCESSORIES (Must Be Ordered Extra) Continuous Low Speed Blower Kit (Optional) Field installed kit LB-63646A (67H91) is available to provide continuous low speed blower operation. Kit includes switch and all necessary wiring. Kit is not furnished and must be ordered extra. Not used if Twinning Kit is used. Furnace Twinning Kit (Optional) Field installed kits are available to operate two furnaces simultaneously. Two kits are available Twinning Kit for Continuous Low Speed Blower LB-63093C (35J93) or Twinning Kit for Non-Continous Low Speed Blower LB-63093B (64H88) Kits consists of heavy gauge steel control box and two auxiliary limit controls. Control box has electrical inlet knockouts and contains low voltage and high voltage terminal strips, blower control relay, heat relays, door interlock relay and 24 volt control transformer. All controls are factory installed and wired. Limit controls are field installed in each furnace. Holes for mounting control box are provided. Box may be field installed in any convenient location adjacent to or on one of the furnaces. Down-flo Additive Base (Optional) Additive base is required for heating only units installed on combustible floors. Base is not furnished and must be ordered extra for field installation. See specifications table. Not required in add-on cooling applications. LPG Conversion Kit (Optional) For LPG models a conversion kit is required for field changeover from natural gas. Kit is not furnished and must be ordered extra. See specifications table for order number. Not available for X models. Thermostat (Not Furnished) Heating thermostat is optional equipment and must be ordered extra. See Thermostats bulletin in Accessories Section and Lennox Price Book. For all-season applications, heating and cooling thermostat is available with the condensing unit. 1.

SPECIFICATIONS Model No. G20RQ2/3E-50 G20RQ2/3XE-50 G20RQ3E-75 G20RQ3XE-75 G20RQ4E-75 G20RQ4XE-75 G20RQ3/4E-100 G20RQ3/4XE-100 Input Btuh 50,000 75,000 75,000 100,000 Output Btuh 40,000 58,000 59,000 79,000 *A.F.U.E. 78.0% 78.0% 78.0% 78.0% California Seasonal Efficiency 72.1% 74.5% 72.7% 74.4% Flue size connection (in. diameter) 4 round 4 round 4 round 5 oval Temperature rise range ( F) 20-50 50-80 30-60 50-80 High static certified by A.G.A. (in wg.) 0.50 0.50 0.50 0.50 Gas Piping Size Natural 1/2 1/2 1/2 1/2 I.P.S. (in.) **LPG 1/2 1/2 1/2 1/2 Blower wheel nominal diameter x width (in.) 10 x 8 10 x 8 11 x 9 11 x 9 Blower motor hp 1/3 1/3 1/2 1/2 Number and size of filters (in.) (2) 20 x 10 x 1 (2) 20 x 10 x 1 (2) 20 x 12 x 1 (2) 20 x 12 x 1 Tons of cooling that can be added 2, 2-1/2 or 3 2, 2-1/2 or 3 3, 3-1/2 or 4 3, 3-1/2 or 4 Shipping weight (lbs.) 175 191 223 243 Number of packages in shipment 1 1 1 1 Electrical characteristics **LPG kit (optional) Continuous Low Speed Blower Kit (optional) 120 volts 60 hertz 1 phase (less than 12 amps) All models LB-62384DD (35J90) (All non X Models) LB-63646A (67H91) (All Models) Twinning Kits Non-continuous low speed LB-63093B (64H88) (All models) (optional) Continuous low speed LB-63093C (35J93) (All models) Down-Flo Additive Part No. LB-80639BA (68386) LB-80639BB (68387) Base (optional) Shipping weight (lbs.) 6 6 Not available with LPG. *Annual Fuel Utilization Efficiency based on D.O.E. test procedures and according to F.T.C. labeling requirements. Isolated combustion system rating for non-weatherized furnaces. **LPG kit must be ordered extra for field changeover. SPECIFICATIONS Model No. G20RQ5E-100 G20RQ5XE-100 G20RQ3E-125 G20RQ3XE-125 G20RQ4/5E-125 G20RQ4/5XE-125 G20RQ4/5E-150 Input Btuh 100,000 125,000 125,000 150,000 Output Btuh 77,000 98,000 99,000 118,000 *A.F.U.E. 78.0% 78.0% 78.0% 78.0% California Seasonal Efficiency 74.6% 75.5% 74.3% 74.6% Flue size connection (in. diameter) 5 oval 6 oval 6 oval 6 oval Temperature rise range ( F) 40-70 70-100 50-80 55-85 High static certified by A.G.A. (in wg.) 0.50 0.50 0.50 0.50 Gas Piping Size Natural 1/2 1/2 1/2 1/2 I.P.S. (in.) **LPG 1/2 1/2 1/2 1/2 Blower wheel nominal diameter x width (in.) 12 x 12 10 x 8 12 x 12 12 x 12 Blower motor hp 3/4 1/3 3/4 3/4 Number and size of filters (in.) (2) 20 x 14 x 1 (2) 20 x 14 x 1 (2) 20 x 14 x 1 (2) 20 x 16 x 1 Tons of cooling that can be added 4 or 5 2, 2-1/2 or 3 4 or 5 4 or 5 Shipping weight (lbs.) 246 261 276 310 Number of packages in shipment 1 1 1 1 Electrical characteristics **LPG kit (optional) Continuous Low Speed Blower Kit (Optional) 120 volts 60 hertz 1 phase (less than 12 amps) All models LB-62384DD (35J90) (All non X Models) LB-63646A (67H91) (All Models) Twinning Kits Non-continuous low speed LB-63093B (64H88) (All models) (optional) Continuous low speed LB-63093C (35J93) (All models) Down-Flo Additive Part No. LB-80639BC (69252) LB-80639BD (69253) Base (optional) Shipping weight (lbs.) 8 9 Not available with LPG. *Annual Fuel Utilization Efficiency based on D.O.E. test procedures and according to F.T.C. labeling requirements. Isolated combustion system rating for non-weatherized furnaces. **LPG kit must be ordered extra for field changeover. 3

BLOWER DATA G20RQ2/3(X)E-50 BLOWER PERFORMANCE (in. wg) High Medium Low 0 1660 1420 1155.05 1630 1400 1140.10 1600 1380 1125.15 1560 1350 1115.20 1520 1320 1100.25 1460 1295 1080.30 1400 1265 1055.40 1290 1170 1000.50 1205 1065 885.60 1045 905 800.70 860 780 675.80 710 620 550 G20RQ4(X)E-75 BLOWER PERFORMANCE (in. wg) High Med-High Med-Low Low 0 1740 1340 1085 860.05 1715 1340 1095 875.10 1695 1340 1105 885.15 1670 1345 1095 885.20 1645 1345 1085 885.25 1610 1340 1080 885.30 1575 1335 1075 885.40 1520 1310 1080 875.50 1450 1270 1065 865.60 1390 1220 1030 840.70 1310 1145 980 800.80 1210 1060 920 750 G20RQ5(X)E-100 BLOWER PERFORMANCE (in. wg) High Med-High Medium Med-Low Low 0 2510 2335 2115 1910 1690.05 2470 2300 2085 1880 1665.10 2430 2260 2055 1855 1645.15 2390 2230 2020 1820 1610.20 2350 2200 1980 1790 1580.25 2310 2165 1940 1740 1535.30 2270 2125 1905 1690 1490.40 2175 2030 1825 1625 1400.50 2080 1940 1730 1535 1330.60 1990 1835 1640 1450 1245.70 1880 1735 1545 1350 1155.80 1785 1635 1470 1280 1075 G20RQ3(X)E-75 BLOWER PERFORMANCE (in. wg) High Med-High Med-Low Low 0 1340 1250 1065 880.05 1310 1220 1050 875.10 1280 1195 1030 865.15 1250 1165 1010 855.20 1220 1135 990 840.25 1195 1105 965 825.30 1165 1075 940 805.40 1070 1000 880 755.50 990 915 815 700.60 895 835 750 645.70 815 760 665 565.80 735 660 575 470 G20RQ3/4(X)E-100 BLOWER PERFORMANCE (in. wg) High Med-High Med-Low Low 0 1805 1485 1300 1005.05 1780 1470 1290 995.10 1755 1455 1280 985.15 1720 1440 1265 965.20 1685 1425 1245 945.25 1650 1400 1215 925.30 1615 1370 1190 910.40 1515 1315 1140 870.50 1430 1250 1085 825.60 1330 1155 1025 765.70 1225 1065 920 700.80 1100 935 840 630 G20RQ3(X)E-125 BLOWER PERFORMANCE (in. wg) High Medium Low 0 1640 1345 1060.05 1610 1325 1055.10 1575 1305 1055.15 1535 1280 1040.20 1495 1255 1025.25 1455 1220 1005.30 1415 1185 985.40 1330 1095 890.50 1195 970 785.60 970 835 690.70 850 715 575.80 650 545 - - - - 4

BLOWER DATA G20RQ4/5(X)E-125 BLOWER PERFORMANCE (in. wg) High Med-High Medium Med-Low Low 0 2415 2215 1980 1770 1575.05 2390 2180 1960 1750 1555.10 2360 2150 1945 1730 1535.15 2325 2115 1915 1710 1515.20 2290 2085 1890 1690 1495.25 2245 2055 1860 1665 1485.30 2195 2025 1825 1640 1475.40 2135 1970 1775 1595 1425.50 2050 1910 1720 1540 1385.60 1965 1835 1685 1485 1325.70 1905 1765 1605 1425 1260.80 1790 1695 1545 1355 1195 NOTE- All cfm data is measured external to unit with air filter in place. G20RQ4/5E-150 BLOWER PERFORMANCE (in. wg) High Med-High Medium Med-Low Low 0 2520 2190 1995 1730 1570.05 2515 2170 1965 1725 1550.10 2510 2145 1940 1720 1535.15 2475 2125 1915 1695 1510.20 2440 2100 1890 1675 1485.25 2410 2070 1855 1650 1460.30 2380 2045 1820 1630 1435.40 2320 1980 1765 1575 1385.50 2220 1920 1705 1505 1315.60 2150 1850 1635 1430 1245.70 2060 1775 1545 1335 1185.80 1945 1660 1455 1280 1130 NOTE- All cfm data is measured external to unit with air filter in place. A.G.A. INSTALLATION CLEARANCES Sides Rear Top **Front ***Floor Flue 1 inch 1 inch 1 inch **6 inches ***Combustible 1 inch *Flue *6 inches Type B vent clearances as listed by U.L. *This is clearance to all flue pipes except type B. **Measured from the draft hood relief opening. NOTE Flue sizing and air for combustion and ventilation must conform to the methods outlined in American National Standard (ANSI-Z223.1) National Fuel Gas Code. ***Clearance for installation on combustible floor if optional additive base is installed between the furnace and the combustible floor. Not required in add-on cooling coil applications if installed in accordance with local codes or National Fuel Gas Code ANSI-Z223.1. A.G.A. HIGH ALTITUDE DERATE A.G.A. certified units must be derated when installed at an elevation of more than 2000 feet above sea level. If unit is installed at an altitude higher than 2000 feet, the unit must be derated 4% for every 1000 feet above sea level. Thus, at an altitude of 4000 feet, the unit would require a derate of 16%. NOTE This is the only permissable derate for the units. 5

DIMENSIONS (inches) 1-1/16 B 17-3/4 RETURN AIR OPENING FLUE OUTLET (center side to side) D 1-1/16 26-1/8 A WHISPER HEAT CONTROL VOLTAGE (Left Side) AIR FLOW LINE VOLTAGE (Both Sides) 53 CONTROL VOLTAGE (Right Side) 2-5/8 GAS PIPING INLET (Both Sides) 8 Right Side 11 Left Side 20-1/2 Supply Air Opening 26-1/8 1-7/8 2-3/8 E C Supply Air Opening Model No. A B C D E G20RQ2/3(X)E-50 G20RQ3(X)E-75 16-1/4 14-1/8 12 3-1/8 2-1/8 G20RQ4(X)E-75 21-1/4 19-1/8 17 3-1/8 2-1/8 G20RQ3/4(X)E-100 21-1/4 19-1/8 17 3-1/4 2-1/8 G20RQ5(X)E-100 G20RQ3(X)E-125 G20RQ4/5(X)E-125 26-1/4 24-1/8 20 3-5/16 3-1/8 G20RQ4/5E-150 31-1/4 29-1/8 24-1/4 3-1/2 3-1/2 NOTE When unit is installed on a combustible floor, an additive base is required. This is optional equipment and must be ordered extra. When using additive base make opening in floor 2-5/8 inches larger (front to rear and side to side) than furnace supply air opening. 6