Copperad. Copperad Fan Convectors (November 2005 onwards) Installation, Operation and Maintenance Instructions To be retained by the user

Similar documents
Panther Fan Coil Units

Installation, Operation and Maintenance Instructions Document Ref:

Installation, Operation and Maintenance Instructions Document Ref:

Installation, Operation & Maintenance Instructions Document Ref:

Installation, Operation & Maintenance Instructions Document Ref:

BELGRAVIA Classic (Vertical Units) - Technical Data Sheet

Ocelot Fan Coil Units

Lo-Carbon T-series Window & Roof Models

WIRING DIAGRAMS AND OTHER RELAVENT LITERATURE WITH THE END USER. access panel Fan speed and on/off switches. Discharge spigot. Fan/motor.

OWNERS INSTRUCTION MANUAL

Installation, operation and Maintenance Manual

T-SERIES. Window & Roof Models. Installation, Set-up and Operating Instructions. 230V/1/50Hz

DOMINATORPLUS ELECTRIC RANGE APPLIANCES INSTALLATION and SERVICING INSTRUCTIONS

This appliance has been CE-marked on the basis of compliance with the Low Voltage and EMC Directives for the voltages stated on the data plate.

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FAW, FAW-C & FAW-C-T TYPE AIR WARMERS FCR & FCR-A TYPE CONVECTORS

Manual / Handbuch Spare parts list / Ersatzteilliste

Installation & Maintenance Data IM Contents

Installation and Operating Manual Drying Cabinet


G-7s. Instruction Manual. G-Series Cooler COUNTERTOP COOLER. Part No.11IPA

READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AN

Xcell 270 Longlife DC wholehouse heat recovery unit

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions

RECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL

FAN COIL UNITS IMPORTANT NOTE ABOUT EC FAN SPEED CONTROL

FLUEBOOST. flueboost 350 gas fire model

Chapter 3 Cooling, heating and ventilation systems

VERTICAL HIGH OUTPUT VHC-IOM INSTALLATION AND MAINTENANCE INSTRUCTIONS VHC INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE TECHNICIAN

ROTARY CONTROL AIR CONDITIONER

FLAT2000L/R. Low Energy Positive Input Ventilation Unit. Installation and Maintenance. Alternative inlet position. 2.1 Spigot Inserts.

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS

Vertical Stack Fan Coil Units Models: TVA, TVE, TVS

Optimax Refrigerated Retail Merchandisers

Model: Kair Whole House Ventilator Model Number: KHRVWH2000

GCG-10. Instruction Manual. G-Series Cooler. Manual is for the following models: GCG-10-N33EB G-10-N33EB UPRIGHT COOLER

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

User and Installation Instructions. Opus 700 Electric Wet Well Bain Marie OE7601 IS195 ECN2396

Warranty Policy Shortlist Warranty does not cover :- Correcting faults caused by incorrect installation of a product. Where an engineer cannot gain ac

Optimax Refrigerated Retail Merchandisers

Powers Controls Low Temperature Detection Thermostat

AGA 13 AMP RETRO-FIT WITH AIMS

INTEGRA PLUS ABC. 230V~ 50Hz. Stock Ref. N. Installation and Wiring Instructions IPX2

FW422 Integrated In Column Larder Fridge Manual for Installation, Use and Maintenance

AIR CONDITIONER ELECTRONIC CONTROL

DR-180 Through the Wall Exhaust Fan PRODUCT MANUAL & INSTALLATION GUIDE

EXTRACTOR HOOD. Please read all the instructions carefully before starting the installation. 230 / 240V 50Hz

Ceiling Sweep Fan Assembly Instructions

SLIDER CASEMENT AIR CONDITIONER

Imperial Electric Fires

FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

CANOPY RANGEHOOD. instruction manual V3FC60SS & V3FC90SS 12 MONTH WARRANTY

HI-LINE SUPER RC FAN CONVECTOR MODELS: 25-18,

ECo 2 Wall INSTALLATION GUIDE FOR ENGINEER / INSTALLER

airooncentre.co.uk irconcentre.co.uk Xpelair Low Energy Wall/Window Fan Range GX6 EC2 GXC6 EC2 Quick Order Hotline or

This appliance must be installed and serviced by a competent person as stipulated by the Gas Safety (Installation & Use) Regulations.

G-10s. Instruction Manual. G-Series Cooler UPRIGHT COOLER. Part No.11IPA

Installation, Operating and Servicing Instructions

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd

e Bath Fan with Light User s Guide

Model 1174 Electric Heater User instructions for LED effect 2kw Inset Heater

MEV-DC. Continuous Mechanical Extract Ventilation Units Installation and Maintenance. Figure 3. Fixing screw hole.

SURFACE WARM CEILING HEATERS

900 Quadrant Steam Shower Cabin with 6 Body Jets

Zip Tudor. Affix Model Number Label Here Installation Section & Operating Heading Instructions. Single point open outlet (vented) water heaters

Installation, Operating and Servicing Instructions

Lo-Carbon MULTIVENT MVDC-MS & MVDC-MS H VENTILATION SYSTEMS V~50Hz. Installation and Wiring Instructions IP22. Stock Ref.

MRXBOX95-LH1/LH2. Mechanical Ventilation Unit with Heat Recovery for Loft Mounting Installation and Maintenance. Spigot 4.

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80

harborbreezeoutlet.com

GCG-9. Instruction Manual. G-Series Cooler. Manual is for the following models: GCG-9-N13EB G-9-N13EB GCG-9-B13EB UPRIGHT COOLER

COOKER HOOD USER HANDBOOK FOR INSTALLATION AND OPERATION MODELS CRC95

SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12

Installation and Operation Manual For Hunter Ceiling Fans

T-SERIES. Wall & Panel Models. Installation, Set-up and Operating Instructions. 230V/1/50Hz

HEA USER MANUAL. 1 Version: 22. June 2010

Original instructions AR

Easy installation in both new construction and retrofit RN80L RN110L READ AND SAVE THESE INSTRUCTIONS INSTALLATION GUIDE

Duct Heaters volts/1 phase volts/3 phase volts/3 phases volts/3 phases. Flange Type Duct Heater.

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER

Zip Econoboil. On wall boiling water. Installation instructions & user manual. Model number: ,

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

"Microbox" DC Models MBOX 125/2DC MBOX 125/2DC204

Installation and Maintenance Manual IM 1102

e Heater/Exhaust Fan/Light User s Guide

Cooker Hood CHIM60 CHIM70 CHIM90 CHIM101 CHIM110. Installation & User s instructions

HEX390 Heat Exchanger

installation and operation manual for Hunter Ceiling Fans

9 inch and 12 inch Axial Fans Models MV230P, MV230AR and MV300AR Instructions for installation, maintenance and safe use.

IMPORTANT INSTRUCTIONS - OPERATING MANUAL

PHV-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Owner s Guide and Installation Manual

Installation and Operating Instructions. Budget priced instant boiling water heater for beverages.

GUH52SD 52 cm GUH75 75 cm Canopy Hood

INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS

Natural Ventilation. e-stack A-Series Ventilation System for Buildings with Atria. Installation and Maintenance. Palletised

MEV SPIDER INSTALLATION GUIDE FOR ENGINEER / INSTALLER

BSF60WH / BSF60SS BUILT IN ELECTRIC FAN OVEN. Instruction Manual. Please read these instructions carefully before use and retain for future reference

MEDIUM DUTY ELECTRIC FRYER OWNER S MANUAL. Click here for. Parts List. Manual Part No: MD Electric Fryer - 1 Manual Rev No: 1

How to get the most from your Integrated Tumble Dryer HJA 8800

Transcription:

Copperad Fan Convectors (November 2005 onwards) Installation, Operation and Maintenance Instructions To be retained by the user Copperad QA/IOM/58 Issue 2

1 GENERAL 1.1 GENERAL DESCRIPTION This manual covers the Copperad Fan Convector range. These are cabinet type units intended for either vertical or horizontal mounting. Controls can be contained within the casing to give a clean outline or installed remote (on-site by the contractor) for easy customer control. 1.2 RECEIPT AND PREPARATION The units are wrapped and display the serial number, model reference, site reference (where appropriate). Installation, operation and maintenance instructions, together with wiring and any special instructions are all supplied with the unit. On receipt, check that all details are correct to the Customer Schedules prior to opening packaging. Damage should be reported to the the supplying B S S branch immediately. It is recommended that packaging is kept in place and the units stored in a safe area until the necessary services are completed, in order to avoid the possibility of damage on site. 2 INSTALLATION 2.1 REMOVAL OF ACCESS PANEL The panel should be affixed to the casing by means of the hook at the bottom of the front panel. Screw fixing through the top of the grille then ensures positive retention of the front panel to the case. Key locks may alternatively be provided where key locks are fitted, the screw fixing at the top of the grille may also be carried out for additional safety. Screw fixing through grille Key Operated Locks 2.2 FIXING A PLINTH To fix a plinth, which will be in a separate package, line it up to the casing with the long side flange to the front. Mark the hole positions on the bottom casing panels and drill no 30 holes for the self tapping screws. 2.3 REMOVING MOTOR PLATE IMPORTANT: Isolate unit electrically at mains controls. Remove front access panel. Disconnect the section of the terminal block marked LTC. Disconnect casing earthwire. Remove the front seal plate by loosening the two M5 bolts Slide out the motor-plate

IMPORTANT TE On ceiling mounted units ensure that the motor plate and seal plate are adequately supported before releasing the transit bolts. 2.4 CHANGE OF HANDING Unless otherwise specified all units will be supplied with heat exchangers having 3/4 connections at the Right Hand end. If it is necessary to reverse this handing on site this is easily achieved by following these instructions: Ensure unit has been isolated from mains power supplies. Remove the front access panel and slide out the motor plate as 2.3 above. Unscrew the two M6.0 hex head screws securing the heat exchanger, plus the M5 screw holding the connection blanking plate, and lift clear, taking care that no damage occurs to the fins of the heat exchanger fin block Undo the M5 screw holding the LTC blanking plate in place, turn the coil around and switch the blanking plate positions. Swap the LTC location around. Reverse actions above to re-fit motor-plate. Seal Plate Seal Plate Fastening Terminal Block 2.5 Change of connection orientation. LTC Blanking Plate Connection blanking plate

FIXING THE UNIT All units have pilot holes in the back plate for attaching to a wall or ceiling. Mark as required from the casing, then drill and plug to suit No 10 wood screws for vertical applications. For suspended horizontal applications, bolts or hanger rods should be used through the strengthening strips attached to the inside back of the case. 2.6 WIRING All electrical work should be carried out in accordance with current I.E.E regulations. The basic wiring diagram is as shown in Diagram no 1. Unless a switched fused spur box is to be fitted to the unit the mains lead is connected to the left hand side of the terminal block where marked mains. The casing rear or side panels should be drilled for the mains lead entry. When supplied, the switched fused spur box will be secured for transit within the unit together with it s cable gland entry bush. This box may be fixed to the outside of the casing with the entry bush, in a suitable position ( drill casing to suit). The leads coming from the spur box should be connected into the terminal block section marked mains and the incoming mains supply connected into the spur box. If remote controls are to be used, wire into the lower left hand section of the terminal block as shown in diagram no 2. The remote thermostats should be mounted on the wall in accordance with the manufacturer s instructions (supplied with each thermostat). Connect the upper left hand section of the terminal block and replace the terminal block cover plate. If the handing has been changed on site, disconnect the casing earth lead at it s casing end and reconnect at the non-pipe work end. Make sure the unit is protected by a 3 amp fuse. 2.7 ELECTRIC MOTOR PROTECTION On ceiling mounted and reverse airflow applications where the fan motor is switched off for long periods, with hot water still circulating through the heat exchanger in excess of 82 C (180 F), it is recommended that a system be employed which automatically closes the hot water supply valve to prevent damage to the electric motor due to overheating. 2.8 Thermostatic operation The T1 and T2 thermostats both have graduated scales to cover their range of operation. Since the thermostatic bulb is frequently unit mounted, it may be offset by various amounts from the measured room temperature. Set the knob at mid-range and adjust to suit comfort conditions within the room. The range corresponds to a sensed temperature range of 10 deg C to 30 deg C. T1 and T2 are adjustable and determine the comfort room temperature range. Set T2 for the low and T1 for the high point. Example T2 16 deg C and T1 20 deg C. The standard LTC is not adjustable (45 deg C) and provides a fan cut-off for the situation where the water temperature is not sufficiently high to provide warm blown air from the fan convector.. The LTC is mounted at the non-void end of the unit, and is clipped on to a return bend of the coil. To electrically test a unit to confirm operation before heat is available, short circuit terminal 2 and 3 on the terminal block. 3.0 Builders work 3.1 When using cased models for concealed applications, the builder s work surrounding the unit must have adequate provision for removing the front access panel of the unit, by providing a removable section of panelling. This is to provide access for filter cleaning etc. 3.2 A similar provision must be made for Hideaway units, although in this case the removable panelling must be large enough to pull out the complete fan tray assembly and provide access to the valves and air vent, etc. 3.3 If ducting is not fitted between the Hideaway s spigotted outlet and the air outlet grille, a suitable baffle must be provided around the spigot, to seal off the unit within the enclosure and prevent re-circulation of the discharged air.

4 MAINTENANCE 4.1 GENERAL WARNING! ELECTRICALLY ISOLATE THE UNIT PRIOR TO COMMENCING WORK 4.2 Filter Air filters will be fitted on either the air inlet grille or between the motor plate and coil (behind the seal plate). Filters should be gently tapped to remove most of the accumulated dust and either vacuumed clean or washed in lukewarm water with detergent. Rinse in clean water and allow to dry naturally before replacement. 4.3 Coil Remove the access panel and clean the coil with a brush or by vacuuming, taking care not to damage the coil surfaces. 4.4 Fan set The motor has sealed for life sleeve bearings, which under normal circumstances require no user maintenance. The motor deck is accessed by means of the access panel and is readily removed if required. Occasional vacuuming or cleaning of the motor plate is recommended. 4.5 Spares For spare parts, quote the model reference and code given on the product label attached within the unit. Give a complete description, voltage and/or dimensions of the part(s) required. Wiring diagrams. The basic wiring is shown above for a unit without optional control equipment fitted as such it is set to run continuously at the medium speed setting. The optional switch and thermostats which can be inbuilt are also shown together with the arrows and numbers indicating the connecting wire and terminal block positions that they would occupy if fitted. If any of these options are inbuilt, then some of the dotted links shown numbered 1 to 4 are removed, as follows If on/off thermostat T1 is required, then link 1 would not be fitted If speed control switch is required, then link 2 would not be fitted If speed change thermostat medium to low (T2) is required then link 3 would not be fitted If speed change thermostat high to medium (T3) is required then link 4 would not be fitted and link 2 must be fitted between 8 and 9.

Wiring diagrams. Notes 1. The LTC is factory fitted as shown in diagram no 1 2. T1, T2 and T3 cannot all be inbuilt and wired in together as indicated in the diagram. They must be fitted in combinations of T1 and T2, T1 and T3 or T2 and T3. If, however, a control system involving all three is required. Then it is recommended that the T1 thermostat must be remotely mounted. 3. If T3 or T2 and T3 are required to operate without a switch, then link 2 will be fitted between positions 8 and 9 on the terminal block. 4. If a unit basically wired for single speed running is required to operate at low speed, then alter link 2 to connect between positions 8 and 10 on the terminal block. Similarly, for high speed re-connect link 2 between positions 8 and 12. 5. When it is required to operate with remotely mounted controls, the units will be supplied basically wired for medium speed running as shown in diagram no 1. The remote switch and thermostats required should be fitted to the removable sections of the terminal block as shown above. 6. To fit a summer/winter switch, connect the two switch terminals to 2 and 3 in parallel with the LTC For all units, we recommend a 3 amp fuse is fitted.

5 FAULT FINDING - No fan operation Check fuse on motor plate. Check power supply to unit. Check loose wiring and breaker plugs or damage to wiring. Check switches or bypass the switches. Check impellers run freely. - No heating Check thermostat operation (change set point to maximum) where fitted. Check integrity of wiring. Check coil vented. Check hot water to unit. Check thermostat bulb in air stream. Check LTC contact on pipe-work or return bend. FAN/MOTOR FAILS TO RUN CHECK POWER SUPPLY TO UNIT ADVISE CLIENT IS A CONCEALED SWITCH OR THERMOSTAT FITTED CHECK FAN SWITCH IS ON AND ALL THERMOSTATS SET CORRECTLY SWITCH ON AND ADJUST THERMOSTATS UNIT RUNS CHECK WATER FLOW TEMPERATURE IS ABOVE 43 DEG C ISOLATE UNIT AT MAINS, THEN BYPASS LTC WITH LINK BETWEEN TERMINALS 2 & 3 THEN SWITCH POWER BACK ON RE-ATTACH LTC TO COIL CHECK LTC IS FIRMLY FITTED TO COIL UNIT RUNS UNIT RUNS ISOLATE AT MAINS AND CHECK WIRING IS TO INSTALLATION INSTRUCTIONS AND CHECK FOR LOOSE WIRES CHECK IMPELLOR FOR FREE MOVEMENT AND CONTACT LOCAL BSS SALES OFFICE FOR REPLACEMENT FAN TRAY ASSEMBLY RE-WIRE TO INSTALLATION INSTRUCTIONS UNIT RUNS

The Copperad logo is a registered trademark of S & P Coil products Ltd, Evington Valley Road, Leicester. In accordance with our policy of continual product improvement, we reserve the right to amend the data contained in this document without prior notification.