AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Similar documents
NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

CHAPTER 1 INTRODUCTION

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

*Corresponding author;

Environment Protection Engineering

DEEPAK PALIWAL, S.P.S.RAJPUT

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

HFCs or the Old Refrigerants - what is the best Choice?

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

η second law = Second law efficiency

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

A Comparison Between Refrigerants Used In Air Conditioning

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

CHAPTER 1 INTRODUCTION

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Chapter 2. Alternatives to HCFCs and their Characteristics

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Study of R161 Refrigerant for Residential Airconditioning

HEAT PUMPS WITH HYDROCARBONS AS REFRIGERANTS FOR SMALL RESIDENTIAL BUILDINGS

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

A Review on selecting an Eco-friendly Refrigerant alternate to R134a in Domestic Refrigerators

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Chapter 10. Refrigeration and Heat Pump Systems

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

Design of LPG Refrigeration System

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Refrigerants and lubricants

ISSN: [Sachuthananthan * et al., 5(10): October, 2016] Impact Factor: 4.116

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

Oyelami S., Bolaji B. O.

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

JJMIE Jordan Journal of Mechanical and Industrial Engineering

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

THE USE OF HYDROCARBONS PROPANE AND ISOBUTANE IN REFRIGERATION SYSTEMS

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

International Journal of Advance Engineering and Research Development

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Energy Performance Assessment of R32/R125/R600a Mixtures as Possible Alternatives to R22 in Compression Refrigeration Systems

HCFC-22 replacement with drop-in and retrofit HFC refrigerants in a two-stage refrigeration plant for low temperature

Mechanical Heat Pump R515

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

Department of MCE, Islamic University of Technology 2. Abstract

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (

Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry

Design and Fabrication of Liquefied Petroleum Gas Refrigeration System and Comparison with Domestic Refrigerator

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Low GWP alternative refrigerants to R404A

A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane.

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

A study on retrofit methodologies for legacy air-conditioning systems to reduce their impact on global warming and ozone depletion

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA

Refrigeration Cycle Demonstration Unit R633

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

HYDROCARBONS, HEAT PUMP, HOME LAUNDRY DRYER: ENVIRONMENT FRIENDLY APPLIANCE

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Chillers and Refrigerants. Purpose of Today s Presentation. Agenda. GLHN Architects & Engineers, Inc. APPA Institute Session 322 EU

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Transcription:

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore University of Enna Abstract This paper presents the results of an experimental analysis comparing the performance of a vapour compression refrigerating unit operating with R22, and its performance in comparison to some HFCs fluids, substituting the former according to reg. n. 2037/2000. In particular, the plant working efficiency was first tested with R22 and then with three HFC fluids: R417A, R407C and R404A. The investigation verified that the performance with HFCs refrigerants did not result as efficient as when using R22. An environmental analysis also was performed. Keywords: R22; R417A; R407C, R404A. 1. INTRODUCTION Chlorofluorocarbons (CFCs) are being phased out, even if recovery is still a major problem. Hydrochlorofluorocarbons (HCFCs) will be phased out according to the time frame defined by the Montreal Protocol and next international obligations [1]. Among all the fluids that can replace the HCFCs there are the Hydrofluorocarbons (HFCs) synthetic fluid refrigerants. The HCFCs replacement with HFCs does not have damaging actions on the ozone layer, because they do not contain chlorine, yet they introduce other problems, this is because HFCs are greenhouse gases. The HCFC most widely used in refrigeration and air conditioning plants was R22. Its ban imposes the need to resort to alternative solutions which go from the redesigning of systems that run on natural fluids to that of continuing to use the same plants with substitute fluids that do not harm the ozone layer (ODP = 0), with low or zero GWP and able to operate efficiently in the existing plants running on R22 without having to revert to laborious refitting operations requiring a change in lubricating oil and components in the refrigeration plant. There are already numerous publications, both theoretical and experimental, relating to the substitution of R22 in existing plants and on the subsequent results of its substitution [2-8]. The aim of this work is to experimentally verify the validity of R22 being substituted by three HFC fluids: R417A, R407C and R404A. Test comparing these new fluids performance with R22 s were carried through an experimental facility at the Cold Energy Technology Laboratory, Department of Energy, University of Palermo. 2. EXPERIMENTAL APPARATUS Figure 1 shows the experimental vapour-compression refrigeration plant. Essentially, it consists of a vapour-compression plant having a four cylinder semi-hermetic reciprocating compressor with a volumetric flow of 32.54 m 3 /h. The fluid condensation is accomplished by transferring heat to the outside through a condenser consisting of a finned heat exchanger. The refrigerant load consists of a water-ethylene glycol mixture (10% in mass) being continuously heated by a gas boiler and then sent to an evaporator. The pressure and temperature of the working fluid are measured and recorded at the inlet and exit of each device of the plant. The mass flow rate is measured at the outlet of the liquid receiver placed downstream from the condenser.

Fig.1: Layout of the test setup. The values of the different parameters were recorded and processed by a data acquisition system that includes a thirty channel data logger and a personal computer. The heat transfer rate discharged in the evaporator is simulated through the water-ethylene glycol mixture loop. Therefore the mass flow rate and the relative temperature are measured at the evaporator inlet section and at the evaporator outlet section. Table 1 shows the characteristics of the main components of the refrigerator, while Table 2 lists the most significant parameters of the tested fluids: R22, R417A, R407C and R404A. Table 1: Main characteristics of some of the components. Dorin compressor, model: K750CC Dorin air condenser model 1004 Danfoss thermostatic expansion valve model TES5 ALFA LAVAL evaporator model EC 38 Reciprocating semi-hermetic four cylinders Volume risen up to 50 Hz 32.54 m 3 /h Bore gauge 61 mm Stroke 32 mm Oil load 2.5 kg Oil type Mineral 32 cst Electric feeding 220-240V(Δ)-380-420V(Y)/3/50Hz In copper pipes with aluminium finning Surface 67.4 m 2 Volume 12.8 dm 3 Number of fans 4 Absorbed power 375 W a 50 Hz With outside pressure equalization Work range -40 C to 10 C Allowed work pressure 22 bar Coaxial pipes Surface 3.78 m 2 Thermal power 25 kw

Table 2: The main characteristics of the tested refrigerants. Refrigerant R22 R417A R404A R407C Molar mass 86.48 106.75 97.60 86.20 Boiling temperature [ C] - 40.80-39.12-46.60-43.80 Critical temperature [ C] 96.15 87.04 72.14 86.05 Critical pressure [kpa] 4980 4036 3740 4630 Certainty class A1 A1 A1 A1 3. TEST PROCEDURES The objective of the tests was to determine how the vapour-compression refrigeration plant actually behaved when the different types of refrigerant fluids were used. This way it was possible to obtain adequate information on the plant with replacement fluids other than R22 while working under different conditions. The tests are intended to provide indications on the performance of the refrigeration system designed and built to operate with R22 when the original fluid has been replaced with other HFCs fluids. The same thermostatic expansion valve with an exchangeable orifice was used for all the tests. The orifice component was changed with the different fluids in order to avoid swinging during trials. The thermostatic expansion valve was regulated in order to set certain overheating parameters of the fluids (Δt s = 5 C). The condensation temperature was set at 38 C. The experimental tests simulated a real running consistent with the technical specifications of the evaporator. The inlet for the water-glycol mixture was maintained at the constant temperature of 12 C. The mass flow rate was chosen within a specific range in order to have the outlet glycol-water mixture temperature between 4 and 10 C. The mass flow rate was kept constant at a chosen value, and the inlet and outlet temperatures were recorded in order to determine the exchanged thermal power. The tests were performed after reaching steady operating conditions. The control parameters indicating the attainment of the above conditions were: pressure and temperature in the inlet and outlet evaporator sections. The working conditions were considered steady when the temperature changes were smaller than 0.3 C and the pressure variations were 5 kpa and 20 kpa in the low and high pressure circuit respectively. The pressure and temperature values at the fundamental points in the cycle were experimentally taken and read for each tested fluid. After, in the table of the thermodynamic properties of each of the tested fluids we have read the corresponding enthalpy values, necessary to be able to calculate the COP. The setup of the thermostatic expansion valve was changed by replacing the orifice depending on the different fluids being tested (R22, R417A, R407C and R404A). 4. EXPERIMENTAL RESULTS The plant was run on R22 under various working conditions in order to verify its efficiency. The evaporator energy balance was found by evaluating the thermal power transferred in it by determining the enthalpy difference between the terminal sections of the exchanger of both the water-glycol solution and the R22. Seven different test conditions were run to compare the exchanged thermal power of water-ethylene glycol mixture and the change in the working fluid enthalpy.

The tests show that although the plant did not have any inconveniences while running after the drop-in operations, from the energy point of view this substitution involves substantial drawbacks. Figure 2 shows the trend of COP in function of the water ethylene glycol mixture load for the tested fluids. As far as the comparison among the different refrigeration fluids is concerned, it can be noted that the R22 results are better than those reported with R417A, R404A and R407C, which resulted more modest. 5.0 4.5 4.0 COP 3.5 3.0 2.5 2.0 0.5 0.6 0.8 0.9 1.0 1.2 1.3 R22 3.7 3.8 4.1 4.2 4.3 4.4 4.5 R417A 2.4 2.7 2.8 3.2 3.3 3.7 3.9 R404A 2.2 2.4 2.6 2.8 3.1 3.1 3.3 R407C 3.2 3.4 3.6 3.7 3.8 4.1 4.2 Fig. 2: COP trend in function of the load of the water ethylene glycol mixture. This implies a higher consumption of energy that would be reflected in greater environmental impact; therefore we compared the impact on the greenhouse effect caused by the use of different refrigerants, by calculating the TEWI, that is a parameter that takes into account the greenhouse effect caused by the direct release when using a plant with a specific refrigerant and the indirect greenhouse effect caused by CO 2 release in the plant where the electricity for the refrigerating plant is produced. The direct greenhouse effect in our working system was evaluated on the amount of working fluid loaded in the system and by estimating the annual refrigerant loss equal to 7% of the load. Table 4 shows the values of the direct greenhouse effect of the working fluids, reported as amount of CO 2 released in the environment. Table 4 Direct greenhouse effect for each fluid Refrigerant Load [kg] GWP Direct Contribution [kg CO 2 ] R22 16.15 1500 25,436 R417 18.25 1950 37,367 R404A 18.70 3260 64,010 R407C 19.10 1526 30,603 The indirect greenhouse effect is: CO 2, i.e.e = α Pot / COP N SL (1) where α = kg CO 2 emitted per generated kwh, Pot = plant refrigerating power, COP = coefficient of performance, N = hours of equipment operation per year, SL = service life (years

of equipment operation). To evaluate CO 2, i.e.e the following values were adopted for the terms specified above α = 0.45 [kg CO 2 / kwh], N = 1000 [h/year], SL = 15 [year]. Furthermore this contribution depends on the COP system. Finally by adding the two types - direct and indirect contributions - we calculated the TEWI for the fluids and obtained the values in Figure 3 where they are plotted in function of the secondary fluid flows. 150,000 130,000 TEWI 110,000 90,000 70,000 50,000 0.5 0.6 0.8 0.9 1.0 1.2 1.3 R22 70,556 69,611 66,796 65,904 64,589 63,615 62,606 R417A 109,176 100,333 96,996 90,600 87,891 83,099 80,747 R404A 139,345 134,617 128,418 124,711 118,622 117,752 115,427 R407C 83,173 79,945 77,609 75,723 74,548 71,963 70,686 Fig. 3: Trend of the TEWI in function of the glycol water load. 5. CONCLUSIONS Several series of tests were performed on R22 (the reference fluid) and the alternative fluids (R417A, R407C and R404A). Unfortunately, the COP experimental measurements show that substituting a pure HCFC fluid such as R22 is disadvantageous since the different replacement fluids give a less satisfactory rendering due to their particular thermo-physical properties in a system sized for the given original fluid. This should lead to a reflection on the use of alternative fluids in existing systems. Also from an environmental point of view the TEWI increment may be far more damaging than the low ODP of the original fluid. The European Regulation EC 842/2006 established that the GWP impact when calculating the TEWI is to be taken into account among the various directives issued to improve our planet environment. The main priority in this context becomes the use of the proper refrigerants in order to facilitate the achievement of the set objectives that is: incrementing energy efficiency and lowering the overall environmental impact. References [1] Regolamento CE. No. 2037/2000, 29 June, 2000. [2] Cavallini A. Working fluids for mechanical refrigeration. Int. J. Refrigeration 1996;19: 485 96. [3] Zheo Y., Yitai M., Ye L. New alternatives for R22. Energy 1997; 22 (7): 669 76. [4] Gabrielli C., Vamling L. Replacement of R22 in tube-and-shell condensers: experiments and simulations. Int. J. Refrigeration 1997; 20: 165 78. [5] Aprea C., Greco A. An exergetic analysis of R22 substitution. Appl. Therm. Eng. 2002; 22:1455 69. [6] Aprea C., Mastrullo R., Renno C., Vanoli G.P. An evaluation of R22 substitutes performances regulating continuously the compressor refrigeration capacity. Appl. Therm. Eng. 2004; 24: 127 39. [7] Calm J.M., Domanki P.A. R22 replacement status. ASHRAE J. 2004; 45(8): 29 39.