Fusion HRV2 Mechanical Ventilation with Heat Recovery User / Homeowner Guide

Similar documents
Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System User / Homeowner Guide

Unity CV2GIP / CV2SVGIP Decentralised Mechanical Extract Ventilation (dmev) User / Homeowner Guide

Vireo HR155WM / HR155CM / HR185WM Mechanical Ventilation with Heat Recovery User / Homeowner Guide

Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions

Unity CV2GIP Decentralised Mechanical Extract Ventilation (dmev) Installation Instructions

MODEL: DV72 R & L. Mechanical Ventilation with Heat Recovery Installation Instructions and User Manual

Installation and Maintenance Instructions for the Installer. Please refer to the User Manual for instructions on how to operate the system

Model: Kair Whole House Ventilator Model Number: KHRVWH2000

HOTLINE:

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

airooncentre.co.uk irconcentre.co.uk Xpelair Low Energy Wall/Window Fan Range GX6 EC2 GXC6 EC2 Quick Order Hotline or

Lo-Carbon Quadra SELV

Lo-Carbon Quadra Centrifugal Fan

Centrif Duo & Centrif Duo Plus

MEV SPIDER INSTALLATION GUIDE FOR ENGINEER / INSTALLER

Lo-Carbon MULTIVENT MVDC-MS & MVDC-MS H VENTILATION SYSTEMS V~50Hz. Installation and Wiring Instructions IP22. Stock Ref.

Thank you for choosing EnviroVent

WHHR Midi & Midi Lite

Installation and Maintenance

Lo-Carbon SELV Tempra

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS.

Installation and Maintenance

Installation and Maintenance

Intake air from outside. Supply air to house. Extract air. from house. Extract air from house. Exhaust air from house to outside

Installation and Maintenance

EKF. EC kitchen extract fan range. Installation and Wiring Instructions. Stock Ref. N EKF355E1 EKF400E1 EKF450E1 EKF450E3 EKF500E3 EKF560E3

Installation and Maintenance

Installation and Maintenance

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

energisava 200 WALL & FLOOR MOUNTED VERSION INSTALLATION GUIDE FOR ENGINEER / INSTALLER

Vent-Axia Svara Multifunctional app controlled fan. Important Information 2 Installation and Wiring Instructions 3-11 Accessories 12 Pin Code 12

CMX-S. Company name: Contact: Tel: Central Mechanical Extract Ventilation (cmev) appliance. Installation and Operating Instructions

Installation and Maintenance

MODEL: BV400 Part No:

Zehnder Comfosystems. ComfoAir 180 Datasheet

energisava 200 CEILING MOUNTED VERSION INSTALLATION GUIDE FOR ENGINEER / INSTALLER

Thank you for choosing EnviroVent

Whole Room Dryer WRD, WRD/110

Thank you for choosing EnviroVent

MRXBOX95-WM2H. Mechanical Ventilation Unit with Heat Recovery and Integral Humidistat for Wall Mounting Installation and Maintenance

Lo-Carbon Quadra Centrifugal Fan

MariGlo LED. Inspiring Excellence in Fish Keeping! 45 / 60 / 90 / 120.

Parts Identification and Accessories Safety Information Installation Control Panel Layout Fully Automatic Washing...

MRXBOX95-WH1. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Intake air from outside

EZT90BL Extractor. Installation, Use and Maintenance.

Installation instructions. and User guide. Designer wall glass canopy NZ AU. HC90CGX1 & HC60CGX1 models

Green Line CMX. Central Mechanical Extract Ventilation (cmev) appliance. Installation and Operating Instructions. Model: CMX

VENTILATION. Mechanical Ventilation with Heat Recovery appliance. Installation and Operating Instructions. Models: HRX2-S, HRX2-B, HRX2-FP, HRX2-BFP

isense & isense-ht 230V Flush Mounted Domestic Continuous Extract Fans

CAUTION - READ THESE INSTRUCTIONS BEFORE USING THE MACHINE

EXTRACTOR HOOD. Please read all the instructions carefully before starting the installation. 230 / 240V 50Hz

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N

Intake air from outside. Supply air to house. Extract air. from house. Extract air from house. Exhaust air from house to outside

ELIX 1003 IPX4. Energy Efficient Centrifugal Fan with EC Motor Installation and Operating Instructions

Internal/External Wall/Window Fan Range GX6. Installation and maintenance instructions Retain for future use

Lo-Carbon SOLO Plus SELV Centrifugal Bathroom/Toilet Fan

Code of Practice - Ventilation- Mechanical Extract Ventilation (MEV) + Mechanical Ventilation with Heat Recovery (MHVR)

EZA60BL & EZA90BL Extractors

O INSTRUCTION MANUAL P V* S N W* J F X* E R L** M** A Y* PRINTED IN P.R.C

T-SERIES. Window & Roof Models. Installation, Set-up and Operating Instructions. 230V/1/50Hz

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance

Silhouette Installation and Wiring Instructions

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

SPECIFICATION casing manufactured from aludip steel in white low energy DC external motor aluminium plate heat exchanger

MRXBOX95-WM2. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Intake air from outside

User instructions. VA20HD, VA55HD, VA55IND and VA75IND. Commercial wet/dry vacuum cleaners CAUTION - READ THESE INSTRUCTIONS BEFORE USING THE MACHINE

Double Door - Dual Zone Wine Cooler

VA 150 A, VA 150 P WINDOW EXTRACT FAN. Installation and Wiring Instructions V/1/50Hz

HS&S Alert No: 103 Date: 9 March 2017

D100, D125 & D150. Installation Instructions

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

FAITH (dmev) 230V / 24V DC SELV Flush Mounted Domestic Continuous Extract Fans

INSTALLATION INSTRUCTIONS USER GUIDE

Green Line HRX. Mechanical Ventilation with Heat Recovery appliance. Installation and Operating Instructions

CI/SfB (57.7) 1st Edition. Lo-Carbon Response/SELV dmev Unit. A new generation of Lo-Carbon continuous running fans

Optimax Refrigerated Retail Merchandisers

Watch the heatsava video

MRXBOX95-WALL. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Extract air.

MRXBOX95AB-WH1. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Wall Mounting. Installation and Maintenance

ELEGANCE IPX4 IPX7. Low Carbon Fan with EC Motor Installation and Operating Instructions. 6 models:

Lo-Carbon T-series Window & Roof Models

OWNER S MANUAL. Convair Tower Heater CTH09. (English) (CTH09)

I tho Advance. Heat recovery ventilation unit. User manual A6_ Ventilator Advance ENGELS.indd /0111/ED

Titon CME1 Q Plus Mechanical Extract Ventilation Unit

HYDROMIST LITE CARPET CLEANER OPERATOR MANUAL

aquamanta the experts in aquatic technology

XB-EFA-8L-BK & XB-EFA-8R-BK

ORIGINAL INSTRUCTIONS

Integra. Integra Plus EC MVHR. Installation & Commissioning. Stock Ref. N EC Integra Plus EC PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

Wiring the fan correctly...

User Guide. Please read carefully before use. Your Hoover Guarantee. Your Hoover Guarantee. Contents. IMPORTANT Safety Reminders

Installation instructions. and User guide. Freestanding canopy NZ AU. HF60CSW2 & HF60CSX2 models

Ceiling Mounted Ducted Exhaust Fan Kit

01 Safety. IMPORTANT Be sure to have read and understood these instructions before beginning the installation process.

HRX-aQ Range. Mechanical Ventilation with Heat Recovery appliances. Installation and Operating Instructions

MRXBOX95-WH1. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Bracket

Residential Carbon Friendly Ventilation SAP Q Eligible. ventilation

MRXBOXAB-ECO4 100% and Opposite Handed version. Typical Installation

M* U INSTRUCTION MANUAL ENGLISH N* O* P* Q** R I PRINTED IN P.R.C * Certain models only ** May vary depending on model

November This product has been reconfigured Please read these instructions

Transcription:

Fusion HRV2 Mechanical Ventilation with Heat Recovery User / Homeowner Guide Commissioning and Inspection Record: Located on page 6 of this guide, should have been completed by the Commissioning Engineer.

Contents User / Homeowner Information 1. Ventilation In Your Home Page 2 2. General Overview Page 3 3. Servicing/Maintenance Page 3 4. Commissioning & Inspection Record Page 6 5. Guarantee/Warranty Information Page 9 1.0 Ventilation In Your Home Your home has a Heat Recovery Ventilation System installed. This consists of a continuously running supply & extract system with heat recovery that is linked by a network of ducts to extract air on a continual basis from the following areas in residential dwellings Kitchen Bathroom Utility Room WC/Cloakroom Ensuite Bath/Shower Room And supply air continually to Living Room Dining Room Bedroom Study Figure 1 Page 2

2.0 2.1.1 2.1.2 General Overview The product incorporates a Heat Exchanger that recovers the heat energy from the extract air that would normally be lost with other ventilation systems. It does this using minimal power consumption as the product uses EC low energy motors. Depending on the way your HRV2 unit has been installed, the specific operation may vary. The unit has three speeds available, but may not have been wired to use them all. Options are 1) Trickle Speed: Operating on a continual basis. 2) Medium Speed: Activated manually using our GS1 switch or similar. 3) Boost Speed: Activated manually using our GS1 / GS2 switch or similar. te; t all three speeds may be operational. Medium speed may be disconnected. GS2 switch markings - Trickle (I) & Boost (II) Operation GS1 switch markings - Trickle (Centre), Medium (I) & Boost (II) Operation te; Other manufacturers switches may show different markings. 2.1.3 2.1.4 2.1.5 To maintain good indoor air quality within the dwelling it is important that the ventilation system remains in operation at all times unless powered down periodically for maintenance/repair. The appliance is not intended for use by young children or infirm persons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure that they do not play with the appliance. If the supply cord is damaged, it must be replaced by a special cord/assembly available from the manufacturer or its service agent. The replacement must be carried out by a qualified Electrician in accordance with IEE or local regulations. 3.0 3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 Servicing/Maintenance Your HRV2 unit contains self-cleaning backward curved impellors that require no servicing. The motors have sealed for life bearings, which do not require lubrication. Periodic cleaning of the ceiling supply & extract valves should be carried out as required, taking care not to adjust the valves set position, as this may cause an unbalanced system, resulting in either under ventilation or unnecessary over ventilation occurring. Periodic inspection and/or cleaning/replacement of filters should be carried out. Frequency greatly depends on geographic location and urban density. The filters trap dirt in the atmosphere and act as protection for both the system and the dwelling. The system s airflow can be reduced if the filters are not cleaned regularly and this can affect overall system performance. For this reason, it is important to clean the filters regularly and to replace them as often as each year. Please contact us on 01903 771021 for replacement filters. To Clean and Replace Filters To Clean Filters: Steps 1 to 8 (Approximately 6 month intervals). To Replace Filters: Leave out Steps 2 to 7 (Approximately 1 year intervals). Tip: If the unit has been installed in a new dwelling, it is advisable to clean the filters more frequently than usual because of the increase of dust in the atmosphere. Page 3

Step 1 Isolate HRV2 from the Mains Supply and proceed to remove both filters from the unit by the handles. Step 2 - Open the filter cage by unclipping all 4 catches. Two are located on each side of the filter housing Step 3 - Remove the filter screen from the frame. Step 4 The filter can be vacuumed first and then washed in warm soapy water. Rinse in cold water. Ring out any excess water and towel dry before refitting. Step 5 Position the filter material over longest edge and hook the cleaned filter screen onto the frame using the four raised plastic legs to hold in position. Step 6 Proceed to gently press the filter material into each channel before moving onto the next. Step 7 Carefully and slowly close the filter cage ensuring that the clips line up on the frame, and ensuring the filter material sits correctly. Step 8 Reinsert filters into the unit. Turn the Mains Supply back on. Page 4

3.1.6 To Clean and Replace Heat Exchanger To Clean Heat Exchanger: Steps 1 to 7 (Approximately 2 year intervals). To Replace Heat Exchanger: Leave out Step 4 (Approximately 5 year intervals). Important te: Do not attempt to wash or clean the heat exchanger with water. 1) Isolate your Heat Recovery Unit from the Mains Supply. 2) Unscrew the six front panel fixing screws and remove the panel (See Figure 9). 3) Remove the heat exchanger by gently pulling on the nylon strap, taking care not damage it. 4) Clean each face of the heat exchanger carefully with a vacuum cleaner. 5) Reinsert the heat exchanger, taking care not to cause damage. 6) Reposition the front panel and secure with the six fixing screws. 7) Turn the Mains Supply back on. Figure 9 Nylon Strap 3.1.7 Access for Maintenance Footprint of HRV2 (top view) 150mm 150mm 500mm Figure 10 Page 5

4.0 Commissioning & Inspection Record 4.1.1 This section should be used to record all installation details. The Commissioning Engineer should use the following Parts 1 to 3, to record important information relating to the installation, of which, should be incorporated into the Home Information Pack for the homeowner to keep. Part 1 System details and declarations Part 2a Installation details Part 2b Inspection of installation Part 3 Commissioning details Part 1 System details and declarations 1.1 Installation Address Details Dwelling Name/Number Street Locality Town County Post Code 1.2 Installation Details System Classification Manufacturer Model Number System 4 Balanced supply & extract ventilation with heat recovery Greenwood Air Management Limited HRV2 Serial Number (where available) Location of HRV2 Unit 1.3 Installation Engineer s Details Engineer s Name Company Address Line 1 Address Line 2 Telephone Number Post Code 1.4 Commissioning Engineer s Details (if different to 1.3) Engineer s Name Company Address Line 1 Address Line 2 Telephone Number Post Code *te. If a system has been installed that is not defined by System 1 to 4 in Approved Document F, further installation checks and commissioning procedures may be required. Seek particular guidance from the manufacturer for these systems. Page 6

Part 2a Installation details 2.1 Installation Checklist General (all Systems) Tick as appropriate Has the system been installed in accordance with manufacturer s requirements? Have relevant system installation clauses been followed as details in Tables 1, 3, 5 and 7 as applicable? If any deviation from Tables 1, 3, 5 and 7, these should be detailed here Description of installed controls (e.g. timer, central control, humidistat, PIR, etc) Location of manual/override controls 2.2 Installation Engineer s Declaration Engineer s Signature Registration Number (if applicable) Date of Inspection Part 2b Inspection of Installation This section should be completed by the commissioning engineer prior to completing Part 3. 2.3a Visual Inspections General (all Systems) Total floor area of dwelling m 2 Does the total installed equivalent ventilator area meet the requirements given in Tables 5.2a, 5.2b, or 5.2c in ADF? Have the correct number and location of terminals been installed that satisfies Table 5.2a in ADF? Is the installation complete with no obvious defects present? Do all internal doors have sufficient undercut to allow air transfer between rooms (i.e. 10 mm over and above final floor finish) Has all protection/packaging been removed such that system is fully functional? Has the ductwork installation been installed in such manner that air resistance and leakage is kept to a minimum? Has the entire system been installed such that there is sufficient access for routine maintenance and repair/replacement of components? 2.3a Visual Inspections General Have appropriate air terminal devices been installed to allow system balance? Has the heat recovery unit and all ductwork been effectively insulated where installed in unheated spaces? Condensation connection is complete and drains to an appropriate location? 2.3c Other Inspections General Upon initial start up, was any abnormal sound or vibration experiences, or unusual smells detected? Page 7

Part 3 Commissioning details 3.1 Commissioning Equipment Schedule of air flow measurement equipment used, (model and serial) 1. 2. 3. 3.2 Air Flow Measurements (Extract) System 4 Date of last UKAS calibration Room reference (location of terminals) Measured Air Flow High Rate (l/s) Design Air Flow High Rate (l/s) Refer to Table 5.1a ADF Measured Air Flow Low Rate (l/s) Design Air Flow Low Rate (l/s) Refer to Table 5.1a in ADF Kitchen Bathroom En Suite Utility Other Other Other 3.3 Air Flow Measurements (Supply) System 4 Room reference (location of terminals) Measured Air Flow High Rate (l/s) Design Air Flow High Rate (l/s) Refer to Table 5.1b ADF Measured Air Flow Low Rate (l/s) Design Air Flow Low Rate (l/s) Refer to Table 5.1b in ADF Living Room 1 Living Room 2 Dining Room Bedroom 1 Bedroom 2 Bedroom 3 Bedroom 4 Bedroom 5 Study Other 3.5 Commissioning Engineer s Declaration Engineer s Signature Registration Number (if applicable) Date of Commissioning Page 8

5.0 5.1.1 The Guarantee Period This Greenwood product (HRV2) is guaranteed for a period of 2 years from the date of purchase of the Product against fault in manufacture. In case of such fault in manufacture apparent during the Guarantee Period, Greenwood may, at its absolute discretion, repair the product, replace the product free of charge or refund the cost of the product AS LONG AS AND ONLY IF: 1. The Product is returned to Greenwood within the Guarantee Period with evidence of purchase date; 2. The Product has not been misused or handled carelessly or used on an inappropriate voltage supply; 3. Repairs have not been attempted other than by Greenwood s service staff or authorised dealers; and 4. In Greenwood s sole discretion, the Product is found to be faulty. If it were not found to be faulty, the Product would be available for collection from the relevant Greenwood s premises within one calendar month and if it was not collected, it would be subsequently delivered by Greenwood and a delivery charge will be made. (the guarantee) 5.1.2 5.1.3 5.1.4 5.1.5 5.1.6 This guarantee does not confer any rights other than those expressly set out above and does not cover any claims for consequential loss, damage or any costs incurred in the replacement of the faulty Product. This guarantee is offered as an extra benefit and does not affect your statutory right as a consumer. All information believed correct at time of going to press. All goods are sold according to Greenwood Air Management Ltd s Standard Conditions of Sale which are available on request. All dimensions in millimetres unless otherwise shown. Greenwood Air Management Ltd reserves the right to change specifications and prices without prior notice. Copyright Greenwood Air Management Ltd 2006. Page 9

Greenwood Air Management Ltd Greenwood House, Brookside Avenue, Rustington, West Sussex, BN16 3LF. Main Line Tel: (01903) 771021 Technical Services: (01903) 777135 Main Line Fax: (01903) 782398 Web: www.greenwood.co.uk Email: info@greenwood.co.uk Page 10 05.10.894 Issue 1 Dec 2009