CONDENSATE PUMP INSTALLATION MANUAL OFFICE PRO 10 READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS.
2003 DENSO SALES CALIFORNIA, INC. All rights reserved. This book may not be reproduced or copied, in whole or in part, without the written permission of the publisher. DENSO SALES CALIFORNIA, INC. reserves the right to make changes without prior notice. MovinCool is a registerd trademark of DENSO Sales California, Inc.
CONDENSATE PUMP INSTALLATION MANUAL OFFICE PRO 10
TABLE OF CONTENTS FOREWORD... 1 DEFINITION OF TERMS... 1 GENERAL WARNINGS & CAUTIONS... 2 INVENTORY... 3 PREPARATION... 4 PUMP INSTALLATION... 5 WIRING... 6 WIRING DIAGRAM... 7 HOSE INSTALLATION... 8 MAINTENANCE & TROUBLESHOOTING... 10 DRAIN TANK OVERFLOW SWITCH... 10 NOTES... 10
FOREWORD Congratulations on purchasing the CPK7 Condensate Pump. This manual explains how to install the condensate pump onto the MovinCool Office Pro 10. Please read this installation manual thoroughly to familiarize yourself with the features of the unit and to ensure years of reliable operation. You may also find it useful to keep this installation manual on hand for reference. Components and/or procedures are subject to change without prior notice. DEFINITION OF TERMS WARNING: Describes precautions that should be observed to prevent injury to the user during installation or unit operation. CAUTION: Describes precautions that should be observed to prevent damage to the unit or its components, which may occur during installation or unit operation if sufficient care is not taken. Note: Provides additional information that facilitates installation or unit operation. 1
GENERAL WARNINGS & CAUTIONS All electrical work, if necessary, should only be performed by qualified electrical personnel. Repair to electrical components by non-certified technicians may result in personal injury and/or damage to the unit. All electrical components replaced must be genuine, MovinCool or DENSO brand purchased from an authorized reseller. The condensate pump must also be a MovinCool or DENSO brand CPK7. Do not handle the pump with wet hands or when standing in water as fatal shock could occur. Disconnect all power from the MovinCool before servicing the unit for any reason. Protect the power cable from coming in contact with sharp objects. Do not kink or allow power cord to come in contact with oil, grease, chemicals, or hot surfaces. To reduce risk of electrical shock, connect MovinCool unit to a properly grounded terminal. 2
INVENTORY After unpacking your Condensate Pump Kit, please check to make sure you have the following items: Condensate Pump (1) Hose, 3/8 inch diameter, 20 feet (6.1 meters) (1) Installation Manual (1) Screws (2) Note: If any of these items are not included in the box or appear damaged, please contact your MovinCool reseller for replacement. Note: To use the Office Pro 10 condensate pump you will need two pump attachment plates which are not included with the condensate pump. Contact your nearest MovinCool reseller or distributor to order the pump attachment plates. (Kit part no. LAY45711-002A) 3
PREPARATION Remove the condensate pump from the package. Locate the protective tab on the condensate pump. REMOVE Remove the tab from the pump. CAUTION: If the protective tab is not removed the pump motor will run continuously. REMOVE 4
PUMP INSTALLATION WARNING: Make sure the MovinCool unit is unplugged from the electrical outlet or if permanently wired, make sure circuit breaker is in the off position. Remove the following items from the MovinCool unit: 1. Side Panel 2. Knock Out Tab 3. Drain Tank Remove the two (2) screws and the protective plate. The 6-pin connector is behind the protective plate. Note: Do not discard the two (2) screws. These screws will be needed if the condensate pump is no longer used. Mount the condensate pump to the pump plate (sold separately) using the two (2) screws from the pump package to fasten into place. 5
Place the condensate pump with plate attached into the drain tank area of the unit. Secure the plate to the bottom of the unit with the screw provided in the pump attachment plate kit. WIRING Connect the 6-pin wire harness of the pump to the 6-pin terminal located within the upper portion of the drain tank area. Below is the wire color to terminal configuration. Black T White: R Green: Ground Note: For complete details on how to install the pump attachment plates, see instructions in Kit No. LAY45711-002A. 6
Wiring Diagram for Office Pro 10 with Condensate Pump 7
HOSE INSTALLATION Note: The Condensate Pump Kit is equipped with a 20 feet (6.1 m) hose. This hose will be used as both a drain and an inlet hose for the condensate pump. 9" Cut a 9 inch (23 cm) section from the 20 feet (6.1 m) hose received in the Condensate Pump Kit. Connect one end of the 9 inch (23 cm) hose to the MovinCool drain stem. Insert the other end of the 9 inch (23 cm) hose into the condensate pump drain hole. If the drain hole is capped, remove the cap. Route the drain hose through the knock out tab of the side panel. Leave the side panel to the side for later. Connect the remainder of the 20 feet (6.1 m) hose to the drain outlet spout. Route the 20 feet (6.1m) drain hose as shown in the illustration. 8
Secure the vertical pump attachment plate with the remaining two screws provided with the pump attachment plate kit. Reinstall the side panel. Note: Do not use more than 18 feet (5.5 m) of drain hose vertically. This is the maximum head (lift) of the condensate pump. When securing the drain hose to the highest vertical position (no more than 18 feet (5.5m)) and running the hose to the drain, run the drain hose on a downward slope at a rate minimum of.25 inch per foot (6.5mm per 30.4 centimeters) for proper drainage. 9
MAINTENANCE & TROUBLESHOOTING WARNING: Before performing any maintenance and/or troubleshooting, unplug the unit from the electrical outlet or if permanently wired, make sure the circuit breaker is in the off position. 1) Remove any dirt or debris which may collect in the bottom of the reservoir tank. 2) On a monthly basis, check the condensate drain hose for kinks, blockage or any other damage that may obstruct condensate pump from draining properly. 3) The fan motor cover should remain on the unit to keep electrical parts free from dust, dirt and any other foreign material. DRAIN TANK OVERFLOW SWITCH The drain tank overflow switch is the unit s safety feature. It will stop the compressor operation if the pump malfunctions. To test the drain tank overflow switch, kink the drain outlet hose and pour water into the reservoir inlet drain hole. Continue to fill the reservoir until the rising water lifts the overflow switch and stops the operation. NOTE: If the Fan Mode Control DIP Switch is set to the STOP position, the entire unit (including fan operation) will turn off. If the compressor continues to operate when the reservoir is full, check your installation procedure. After testing is complete, unkink the drain outlet hose and the condensate pump will empty the reservoir. Make sure the 9 inch (23 cm) section of hose is installed into the inlet drain hole of the pump reservoir correctly. Condensate Pump 10
NOTES 11
12
DENSO SALES CALIFORNIA, INC. TECHNICAL SERVICE DEPARTMENT First Issue: June 2003 DSCA P/N: LA990009-1190 Printed in U.S.A.
(800) 264-9573 www.movincool.com DSCA P/N: LA990009-1190