Remote Booster Power Supplies XLS-BPS6, XLS-BPS60, XLS-BPS6C, XLS-BPS0, XLS-BPS00, XLS-BPS0C FEATURES SPECIFICATION DATA Extends power available to Notification Appliance Circuits (NACs). Available in 0A and 6.5A versions. Includes four independent A NACs two configurable as auxiliary outputs. Configurable signal rates. Field selectable input-to-output correlation. Two inputs allow activation by Signature Series modules or existing NACs. NACs can be configured for four Class B or two Class A circuits. 0 Vac and 0 Vac versions. On-board status LEDs for easy recognition of wiring faults. APPLICATION The Remote Booster Power Supply is a self-contained 4 Vdc power supply designed to augment fire alarm audible and visual power requirements. The booster contains all of the necessary circuits to monitor and charge batteries, control and supervise four Class B or two Class A Notification Appliance Circuits (NAC) and monitor two controlling inputs from external sources. Simple switch selection provides a wide variety of operational configurations. Each remote booster power supply is supplied with its own enclosure providing ample space for additional interface modules and a battery compartment. The Remote Booster Power Supply is available in 6.5A or 0A versions at 4 Vdc. The Remote Booster Power Supply provides additional power for audible and visual devices when constrained by system capacity or site application. Fault conditions detected by the XLS-BPS open the NAC of the main panel. This initiates a trouble condition and eliminates the need to wire a separate trouble contact back to the control panel. During alarm conditions, detected faults are overridden. The XLS-BPS default output configuration is continuous 4 Vdc on all NACs. This output is typically used to drive visual devices. XLS-BPS notification appliance circuits easily configure to any one of the three signaling rates: 0 strokes per minute (spm), -- temporal, or continuous. This makes the XLS-BPS ideal for applications requiring signaling rates not available from the main panel. It also allows independent setup of a NAC without interfering with the main panel and its initiating circuits. In addition to the three generated signal rates, the XLS-BPS can also be configured to follow the signal rate of the main panel NAC. This allows seamless expansion of existing NACs. The XLS-BPS includes seven on-board LED indications: one for each resident NAC, one for battery supervision, one for ground fault and one for ac power. The trouble contact has a 6-second delay when an ac power failure or brownout condition is detected. This reduces trouble reports during short ac brownouts. Configuration options include: ac power fail delay (6-seconds or 6 hours), sensing input to NAC output correlations and auxiliary outputs. NAC and 4 are configurable as auxiliary outputs. Auxiliary outputs can be continuously on, or turn off after 0-seconds without ac power. Jumpers configure the XLS-BPS for Class A or B wiring. U.S. Registered Trademark Copyright 00 Honeywell All Rights Reserved 74-00-
REMOTE SUPPLIES SPECIFICATIONS (0) Models: The Honeywell XLS-BPS Series Booster Power Supplies extend NACs as a stand-alone booster power supply. See the Ordering Information section for available models. The power supply requires standby batteries (not provided) for 4 or 60 hours of standby followed by 5 or 0 minutes of alarm and can support up to 0A hour batteries. The booster supply also requires four independent supervised NACs. NACs can be configured to follow the NAC input from the main panel or activate from Intelligent Signature Series modules. The booster NACs may be configured for independent operation at a continuous rate, at 0 SPM, or at -- temporal. Booster fault conditions will not impede alarm activation of NAC host circuits. -/ (89) -/8 (86) 7 (4) TOP VIEW (0) 7 (78) FRONT VIEW ALL KNOCKS FOR /4 (9) CONDUIT -/ (89) Electrical Ratings: AC Line Voltage: 6.5A Booster: 0 Vac or 0 to 40 Vac, 50/60 Hz, 50W. 0A Booster: 0 Vac or 0 to 40 Vac, 50/60 Hz, 75W. Notification Appliance Power: 6.5A Booster: A maximum per circuit at 4 Vdc nominal, 6.5A maximum total for all NACs and auxiliary circuits. 0A Booster: A maximum per circuit at 4 Vdc nominal, 0A maximum total for all NACs and auxiliary circuits. Auxiliary Outputs: Two configurable outputs replace NACs and/or 4, NAC and/or 4 are configurable as auxiliary outputs. Input Current (from an existing NAC): ma at Vdc, 6 ma at 4 Vdc. Temperature Ratings: F to 0 F (0 C to 49 C). Humidity Ratings: 0 to 9% RH, non-condensing. Wiring: Gauge: 8 to AWG (0.8 to. sq mm). NAC Style: Class A or B. WIRG Fig.. XLS-BPS dimensions in in. (mm). M45 Single boosters can be placed anywhere on a notification appliance circuit. Because existing NAC end-of-line resistors are not required to be installed at booster terminals, multiple boosters can be driven from a single NAC circuit without the need for special configurations. See Fig. through 6 for typical wiring applications. IMPORTANT Do not attempt to wire the booster from these diagrams. For installation instructions, refer to form no. P/N 70946, Booster Power Supply Installation Manaual and form no. 85000-085 for a list of compatible devices. Output Signal Rates: Continuous, 0 SPM, -- temporal, or follow NAC from installed panel. Mounting: Signature module accommodates three two-gang modules. TO NEXT SIGNALG DEVICE, BOOSTER, OR RESISTOR Battery Size, Maximum: 0Ah ( of V, 0A). Approvals: UL, ULC, FM, CSFM. Dimensions: See Fig.. FIRE ALARM CONTROL PANEL SENSOR PUT SENSOR PUT NAC PUT NO. M46 Fig.. Multiple Signature modules branching single NAC. 74-00
REMOTE SUPPLIES TO NEXT SIGNALG DEVICE, BOOSTER, OR RESISTOR FIRE ALARM CONTROL PANEL SENSOR PUT NAC PUT NO. TO NEXT SIGNALG DEVICE, BOOSTER, OR RESISTOR SENSOR PUT NAC PUT NO. TO NEXT SIGNALG DEVICE, BOOSTER, OR RESISTOR SENSOR PUT NAC PUT NO. M47 Fig.. Multiple boosters cascaded from a single NAC. TO NEXT SIGNALG DEVICE, BOOSTER, OR RESISTOR SENSOR PUT NAC PUT NO. TO NEXT SIGNALG DEVICE, BOOSTER, OR RESISTOR ALL FIVE PUTS ACTIVATE WHEN PUT NAC NO. ACTIVATES (BASED ON PROGRAMMG) FIRE ALARM CONTROL PANEL SENSOR PUT SENSOR PUT NAC PUT NO. SENSOR PUT TO NEXT SIGNALG DEVICE, BOOSTER, OR RESISTOR NAC PUT NO. ALL FIVE PUTS ACTIVATE WHEN PUT NAC NO. ACTIVATES (BASED ON PROGRAMMG) M48 Fig. 4. Multiple notification appliance circuits branched from single control panel. 74-00
REMOTE SUPPLIES Signature modules are used to activate the booster. The wiring configuration in Fig. 5 eliminates the necessity of using a NAC circuit as an AUX or running a separate 4V source. Signature modules can also be used to divide the A booster output circuits into smaller current loads. MA BOARD NAC NAC 5K NAC 5K NAC4 /AUX P P L N G P4 SENSE SENSE TROUBLE BATTERY - NO NC P 47K 0 9 CCS 8 7 6 5 4 4 USED FOR ANOTHER CLASS B. 5 GOG DATA TO NEXT DEVICE. G DATA FROM PREVIOUS DEVICE OR SIGNATURE CONTROLLER. CCS DRAWS 6 ma OF CURRENT ALARM. CCS WIRG MUST BE WITH FT OF THE BOOSTER WIRG. MOUNT CONDUIT OR WITH THE BOOSTER ENCLOSURE. 4 BATTERIES. 5 UL LISTED -LE FUSE HOLDER, PART NO. 60006 WITH MAXIMUM 4A FUSE. NOTE: ANY BOOSTER TROUBLE WILL CAUSE THE CCS SUPERVISION TO REPORT A TROUBLE TO THE MA FIRE PANEL. M58A Fig. 5. Signature module used to activate booster. 74-00 4
REMOTE SUPPLIES See Fig. 6 to configure the outputs where zoning is required. MA BOARD NAC NAC 5K NAC 5K NAC4 /AUX P P L N G P4 SENSE SENSE TROUBLE BATTERY - NO NC P 47K 47K 0 9 CC 8 7 6 5 4 0 9 CC 8 7 6 5 4 RISER TO 4 VDC RISER TO NEXT DEVICE OR RISER SUPERVISORY DEVICE USED FOR ANOTHER CLASS B. S MUST BE WIRED AND PROGRAMMED ON THE SIGNATURE CONTROLLER FOR PROPER OPERATION. CC WIRG MUST BE WITH FT OF THE BOOSTER WIRG. MOUNT CONDUIT OR WITH THE BOOSTER ENCLOSURE. NOTES: - BOOSTER RECOGNIZES TROUBLE AND ALERTS CC SUPERVISION TO REPORT TROUBLE TO THE MA FIRE PANEL. - MAXIMUM OF TEN SIGA CCI/UM S FOR BOOSTER NAC. M59 Fig. 6. Multiple Signature modules as booster inputs. 5 74-00
REMOTE SUPPLIES Multiple Signature modules can be used as booster inputs. The wiring diagram in Fig. 7 can be used to configure the outputs when zoning is required. MA BOARD NAC NAC 5K NAC P NAC4 P SENSE SENSE NO TROUBLE NC BATTERY P L N G P4 - FROM EXISTG FIRE ALARM PANEL NOTIFICATION CIRCUIT OR CC. TO OR NEXT DEVICE. 0 9 CC 8 7 6 5 4.5A TOTAL 47K USED FOR ADDITIONAL CLASS B S. NOTE: MAXIMUM OF TEN SIGA CC OR SIGA UM S PER BOOSTER NAC. GOG DATA TO NEXT DEVICE. G DATA FROM PREVIOUS DEVICE OR SIGNATURE CONTROLLER. 47K.5A TOTAL 0 9 CC 8 7 6 5 4 5K GOG DATA TO NEXT DEVICE. G DATA FROM PREVIOUS DEVICE OR SIGNATURE CONTROLLER. M40 Fig. 7. Multiple Signature modules branching a single NAC. 74-00 6
REMOTE SUPPLIES ORDERG FORMATION Model Number Description Parts XLS-BPS6 6.5A Booster Power Supply (UL Listed Version). (5.9) XLS-BPS60 6.5A Booster Power Supply (0V). XLS-BPS6C 6.5A Booster Power Supply (ULC Listed Version). XLS-BPS0 0A Booster Power Supply (UL Listed Version). XLS-BPS00 0A Booster Power Supply (0V). XLS-BPS0C 0A Booster Power Supply (ULC Listed Version). Accessories V6A5 6.5 Ah Batter, two required..4 (.6) V0A 0 Ah Battery, two required. 9.5 (4.) 60006 UL Listed Fuse Holder with maximum 4A Fuse. Shipping Weight lb (kg) 7 74-00
Automation and Control Solutions Honeywell International Honeywell Europe S.A. Honeywell Latin American Honeywell Honeywell Limited-Honeywell Limitée Control Products Avenue du Bourget Region 985 Douglas Drive North 5 Dynamic Drive Honeywell Building 40 Brussels 480 Sawgrass Corporate Parkway Golden Valley, MN 554 Scarborough, Ontario 7 Changi Business Park Central Belgium Suite 00 MV 4Z9 Singapore 48607 Sunrise FL 5 74-00 J.S. Rev. 8-0 Printed in U.S.A. on recycled paper containing at least 0% www.honeywell.com post-consumer paper fibers.