STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY SPECIFICATIONS FOR FUSION SPLICE AND SPLICE ENCLOSURE FIBER OPTIC CABLE

Similar documents
Fiber Optics for Todays Industry Applications

Fiber Optic and CAT 5, 6, 7 and 8 Installer Premise Cabling

Special Provision No. 683S28 December 2017

FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS - Item No. FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS (TEMPORARY) - Item No.

SECTION TESTING OF FIBER OPTIC CABLES

STANDARD TEST PROCEDURE PRE-TEST QUALITY OF OPTIC FIBRE CABLE ON DRUMS TYPE OF CABLE :

Hands-On CAT 5/6 & Fiber Optic Installer

A. General: Horizontal and backbone cabling shall be verified in accordance with ANSI/TIA/EIA-568-C and the addendum for fiber optic testing.

ECP OPTICAL FIBRE SPLICING, TESTING AND COMMISSIONING REQUIREMENTS

SECTION TESTING OF FIBER OPTIC CABLES

Hands-On Fiber Optics ISP/OSP - Advanced Combo- Tech

Hands-On Fiber Optic ISP / OSP Combo-Tech Splicing, Termination & Testing

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK

OTDR - FHO5000-xxx. Optical Time Domain Reflectometer

Dome Fiber Optic Closure SC-221

FLX380-30x FlexTester OTDR

Basic Professional Fiber Optic Installation

Fibre (TIA) Field Test Specification

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

A. The requirements of this Section and the other Division 26, 27 & 28 Sections apply to all the video surveillance system work.

High cost performance choice

High cost performance choice

CITY OF AUSTIN ARTERIAL MANAGEMENT DIVISION SPECIFICATIONS FOR THE INSTALLATION AND MAINTENANCE OF SINGLE MODE FIBER OPTIC CABLE

Fibre Specification Standards

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

Benefits of Enhanced Event Analysis in. Mark Miller

OPTICAL TIME-DOMAIN REFLECTOMETER

Ensuring Cabling Performance in the Customer-Owned Outside Plant. Keith Foord Product Manager Greenlee Communications

Ensuring Cabling Performance in the Customer-Owned Outside Plant

Installation Instructions

Sumitomo Fiber Specification SE-6** Non-Zero Dispersion Shifted Single-Mode Fiber. PureGuide SM Optical Fiber, TIA Type IVd. Issued: November 2003

The Optical Time Domain Reflectometry and the Fusion Splicer Laboratory exercise

Sumitomo Fiber Specification SE-9** Non-Zero Dispersion Shifted (NZDF) Zero Water Peak Large Effective Area Single Mode Fiber

STANDARD FOR INDOOR-OUTDOOR OPTICAL FIBER CABLE

Ensuring the Health of Tomorrow s Fiber LANs Part II OTDR Trace Analysis Become an Expert Troubleshooter with Advanced OTDR Trace Analysis

iotdr Series Portable OTDR Test Set iotdr Series OTDR Tester is entirely new portable product released by OPWILL.

OTDR II. Tier-2 Optical Time Domain Reflectometer for Multimode and Single-mode Fiber Cabling

Noyes OFL 250B Specs Provided by

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

4120 Fire Alarm Network Reference

Yokogawa Meters & Instruments Releases AQ1200E, AQ1205A, AQ1205E, and AQ1205F OTDR Multi Field Testers

136"ElectricCooktop. nstructlons _,00, JP961, JP968, JP969, ZEU769. I Iinstallation. -&WARNING - This appliance must be properly grounded.

AV6416 OTDR. Product Overview: Main Features:

RLH Industries, Inc. Cleaning and Testing Fiber Optic Cable. Reference Guide MD A 0507

INSTALLATION OF VENTING SYSTEM COMPONENTS WARNING

VACUUM VALVES AND HOSES

M700-Series Multifunction OTDR

Section PERIMETER SECURITY SYSTEMS

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

Installation Instructions

SECTION AUTOMATIC TRANSFER SWITCHES

130"ElectricCooktop. nstructlons _,0, JP355, JP910, JP930, JP940, JP950. I Iinstallation. -&WARNING - This appliance must be properly grounded.

New Mass Fusion Splicer FSM-50R Series

FHO5000 Series Triple-Proof OTDR

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S

OWL. Laser OWL Series. Operations Guide. Singlemode Light Sources. Optical Wavelength Laboratories. Date: October 1, 2015

Side Entry Insulation Damage Repair Sleeve (SEIDRS) Raychem Devices Products

Fire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for Panel and Remote Mounting. Features. Operation.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

CEILING FAN OWNER'S MANUAL

palmotdr Series Handheld OTDR

Ribbon All In One Fusion Splicer

STANDARD FOR INDOOR-OUTDOOR OPTICAL FIBER CABLE

CEILING FAN OWNER'S MANUAL

CEILING FAN OWNER'S MANUAL

136"ElectricCooktop. nstructlons. I Iinstallation. -&WARNING - This appliance must be properly grounded.

OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D

FLCH4R Garage and Utility Electric Heater

Functional Performance Test

Fibre Optic Basics FIA Summer Seminar 2014

HELKAMA. Optical Fibre Cables

OPTICOM Fiber Optic Splice Module

The Rise of Tier 2 Testing

palmotdr Series Handheld OTDR

SECTION ELECTRICAL IDENTIFICATION

MEGOHMETER. PCS ITALIANA srl TECHNICAL DATA DESCRIPTION:

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

OCH-SSE series Direct Wired Units Indoor * and Outdoor Comfort Heaters

OBL-301A. Optical Break Locator. Operation Guide

13-SDMS-02 REV. 00 SPECIFICATIONS FOR NON-METALLIC, TIGHT BUFFERED & RETRACTABLE, MICRO FIBER OPTIC CABLE FOR INTERNAL INSTALLATION

The Definitive Handheld OTDR for FTTx Testing OTDR AXS Compact, lightweight handheld OTDR optimized for access/fttx network testing

Chapter 1 General... 5

ETSI TS V1.2.1 ( )

Summer Breeze Heater Service Manual

BlueHeat AirTop 2000 Heater

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

ASSMANN ELECTRONIC GmbH ASSMANN SYSTEM GUARANTEE. DIGITUS Professional Fiber Optic Cabling System. Appendix B - Provisions for acceptance

Check It Panel. 1 Phase Simplex Demand Dose Operation, Maintenance & Installation Manual. Introduction. Safety Guidelines

Field Test Procedure for Optical Fibre Link Measurements

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER

Data Sheet. Self regulating process heating tapes RS stock numbers ,

Electrical Safety Requirements

OPX-BOX. Platform Highlights. Software Support. Key Features

DWDM OTDR with Tunable Laser MTP-200-D100. Hand-held High Performance OTDR. Series

Certified Fibre Optic Specialist - Testing

M210 Multifunction Micro OTDR

OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters

Transcription:

STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 SPECIFICATIONS FOR FUSION SPLICE AND SPLICE ENCLOSURE FIBER OPTIC CABLE N.J. Specification No. Effective Date: July 1, 2001 New Jersey Department of Transportation Specifications for Fiber Optic Fusion Splice and Splice Enclosure. The purpose of these specifications is to describe minimum acceptable design requirements for this item. GENERAL - I 1-1 Select fibers in a fiber optic trunk cable shall be spliced to another trunk cable or to a termination cable as required for the connection of system components at locations as shown in the contract documents, and shall conform to these special provisions. 1-2 The splices shall only be fusion type, mechanical splices are not permitted. 1-3 The splices shall be encased in a splice enclosure at all locations identified in the contract documents. 1-4 If the installer requires additional splice enclosures to support the pulling plan, these enclosures shall be provided and installed at no additional cost to the State. 1-5 The construction and testing of the fiber optic splices and splice enclosures shall comply with all applicable Electronic Industry Standards (EIA/TIA), International Telegraph and Telephone Consultative Committee (CCITT), ANSI, ASTM standards and FDDI specifications. SPLICE CHARACTERISTICS - II 2-1 The field splices shall connect the fibers of two or more fiber optic trunk cables together or shall connect termination cable fibers to trunk cable fibers as indicated on the plans and conductor schedules. All remaining fibers shall be passed through the splice enclosure without damage. 2-2 All fusion splices shall be made with a fusion splicer. The unit shall be portable, capable of AC or internal battery-powered operation. The unit must be able to splice fibers with 250 micrometer coating and 900 micrometer coating with little or no modification in the field. The fusion splicer shall be capable of full battery recharge in an eight-hour charging period. The fusion splicer shall have the following capabilities: A. splice-protection-sleeve heater Page 1 of 5

B. battery with charging unit and associated power cables, C. spare electrodes, fuses and lamps D. power meter/light source with carrying cases. 2-3 The power meter/light source shall be a calibrated pair that is portable, battery operated. The units will meet or exceed the following parameters for operation on single mode fiber: A. operating wavelength: 1300 / 1550 nanometers B. range: +3 to -45 dbm C. measurement scale: dbm D. accuracy: 0.5 db or better 2-4 Splice construction is detailed in the Supplemental Specifications. SPLICE ENCLOSURE CHARACTERISTICS - III 3-1 The splice enclosure shall be air tight, water tight, corrosion resistant, rodent proof, and re-enterable. 3-2 The splice enclosure shall be manufacturer certified for below ground, junction box (pull box) installation. 3-3 The splice enclosure shall be no larger than 7 inches diameter by 30 inches long (nominal). Small junction boxes or enclosures may require a smaller splice case, for which the splice case shall be approximately 22.5 inches long, 5.5 inches wide, and 5 inches high (inner splice case shell dimensions). 3-4 The splice case shall be designed and equipped with the necessary mounting hardware to be attached to the side of the junction box, and to be suspended vertically with sufficient clearance at each end for acceptable cable bends. 3-5 The splice enclosure shall be a complete kit including the following: A. Connection brackets B. Stand-off studs with locking nuts C. Grounding clamps D. Outer shell (usually in 2 halves) E. Inner shell assembly in two parts Page 2 of 5

F. Splice trays with all required retainers and supports G. Cable restraints H. End plates (caps) as required I. Inner shell supports J. Outer shell clamp assemblies K. Insulation/sealing tape L. Resin filling cups and funnels M. Resin encapsulant sealant 3-6 The splice enclosure shall be designed so that the encapsulant sealant will fill the area between inner and outer shells and provide a moisture barrier. The sealant input method shall be by pouring in through sealable ports. The sealant shall be such that it is easily removed to provide for a re-enterable enclosure. 3-7 The splice enclosure shall be designed so that the fiber optic cable shall enter the splice enclosure through the end plates. The end plates (or caps) of the splice enclosure shall be air and water tight, and shall form an air and water tight seal with the splice case body. Each end plate shall have factory installed cable entry inserts for two cables for securing the entering cables in an air and water tight seal. Fiber optic cables shall be restrained within the splice enclosure such that there is no discernible tensile force on the optical fiber. 3-8 The splice enclosures shall have sufficient capacity to splice up to 144 optical fibers; although, the nominal maximum number of optical fiber splices is 48 per enclosure. In some cases one trunk cable fiber shall result in two fiber splices. This situation occurs whenever trunk cable fibers are spliced to termination cable fibers. The fibers in the trunk cable are cut and spliced to two termination cable fibers to provide a continuous path from the trunk cable, into the serviced item through the termination cable, and back out to the trunk cable fiber (and on to the next serviced item). 3-9 Splice trays shall be provided in each enclosure for holding, protecting and organizing the optical fibers. Splice trays shall be all dielectric, provide sufficient space for coiling of optical fibers to prevent micro bending, and have capability to pass uncut/unaffected fibers through the enclosure. The placement of the bare optical fibers in the splice tray shall be such that there is no discernible tensile force on the optical fiber. 3-10 A single splice tray shall be used for no more than the maximum number of optical fiber splices, depending on the manufacturer's specification. Sufficient splice trays shall be provided with each splice enclosure to accommodate the required splices. TESTING - IV Page 3 of 5

4-1 Attenuation tests shall be performed on all spliced optical fibers with an OTDR (Optical Time Domain Reflectometer) capable of recording and displaying anomalies of 0.2 decibels as a minimum. Single mode fibers shall be tested at 1300 nanometers and 1550 nanometers. The OTDR with transit case shall be designed for use on single mode fiber at 1300 and 1550 nanometer wavelength, and shall be a field unit exhibiting the following characteristics: A. dead zone: 49.2 feet or better B. attenuation range: 15 decibels or better C. distance range: 32,808.4 feet or longer D. accuracy: ± 6.6 feet E. printer: must be capable of printer output internal storage. 4-2 The OTDR shall have a printer capable of producing a verifying test trace with fiber identification, numerical loss values, the date and the operator's name. It shall also have a DOS based 3.5 inch disk recording capability that has associated software to do comparisons and reproductions on A4 paper (8.5" x 11"), via a personal computer. TRAINING - V 5-1 Prior to constructing the first splice unit, training shall be provided for the Department's engineering, maintenance and operations staff, at a facility provided by the Department. The training shall include all material and manuals required for each participant. 5-2 Maintenance training of fusion splicer and OTDR operation shall be provided for a minimum of 32 hours for at least 5 personnel with an electronics background. The training shall include operation instructions, theory of operation, circuit description, field adjustments, preventive maintenance procedures, troubleshooting, interpretation of results, and repair of all components. INSTRUCTIONS AND GUARANTEES - VI 6-1 One set of complete assembly plans and instructions, and installation and use manuals shall be supplied with each five splice enclosures furnished. 6-2 No changes or substitutions in these requirements will be acceptable unless authorized in writing. Inquiries regarding this specification shall be addressed to the Manager, Office of ITS Engineering, New Jersey Department of Transportation, P.O. Box 613, 1035 Parkway Avenue, Trenton, New Jersey 08625. 6-3 The Supplier agrees upon the request of the Manager, Office of ITS Engineering to deliver to the Office, a sample of a completed spliced cable in a splice enclosure, to be supplied in compliance with these specifications for inspection and test before acceptance. The sample shall be returned. Page 4 of 5

6-4 The supplied splice enclosures shall carry a two-year warranty, from the date of project acceptance by the State, to be free of defects. The installer shall fully inspect the units prior to installation and within the warranty period. The installer shall be fully responsible for the installation of defect free units and for the replacement of any unit found to be defective due to improper construction or improper installation for two years after the State's acceptance of the project. Page 5 of 5