BOILER SYSTEM CHEMICAL TREATMENT 101

Similar documents
Volume 10 Summer Understanding Terminology Key to Treatment Program Success

WARE Boiler book on-line

Protective Chemistry for Steam Boiler Wet Layup posted to DPS client area on:

WELCOME TO THE AWT REGIONAL TRAINING PROGRAM

3.1 Deaerator Systems

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

THE CONDENSATE STORY. Patrick Rogers Nalco Company Spokane, Washington

Strategies in Optimizing Condensate Return

Reactor-Boiler and Auxiliaries - Course 433 BOILER STEAM AND WATER SYSTEMS

Steam Ancillary Equipment. Primary Steam System, Water Treatment and Auxiliary Steam System Equipment

Kube Engineering. Industry Guide. Power Industry

Boiler Basics. Design and operation

10 HUGE Mistakes Facilities Make in Boiler Operation and How to Avoid Them

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016

CHAPTER 18 EVAPORATION AND FREEZING

Water Treatment Improves Your Bottom Line DAVE PICOU WATER CARE SERVICES DIVISION JOHN SCHULTZ TEXTILE CARE DIVISON

Diocese of Cleveland Facilities Services Corporation

S. P. THERMAL SYSTEMS INC.

Descaler & Prevention

Feedwater Treatment Manual

Adca Training. Part 2

Tray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com

THE INVESTIGATION BEGINS!

Carry Out Maintenance Procedures

Crop Management Practices. By Simon Bedasie

SuperStor Glass Lined Storage Tank

SuperStor Ultra Stainless Steel Storage Tank

TEMPLATE ASSISTED CRYSTALLIZATION. Presented By Ryan Lessing 11/13/2014

CHAPTER 6. HEATING PRODUCTION EQUIPMENT AND SYSTEMS

Polymer Dilution Blend and Feed Specifications For General Use

Math & Physics. Complete combustion requires an Air-FuelRatio of 14.7 to 1 for combustion.

GENERAL BULLETIN 08. A Division of Neptune Chemical Pump Company MIXER COMPANY

Pretreatment Processes for the Aluminum Extrusion Industry. Harry Adams - BCI Surface Technologies Bruce Chambeau Republic Chemical Co., Inc.

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

Akiki Engineering Est.

Case Study and 700 HP Steam Boilers - Scale

Typical damages to Boilers & Economizers

Condensate Management Solutions

Steam Contamination - Causes & Cures

Other Things I Should Know?

Akiki Engineering Est.

Which RO/DI Water Heater is Right For Your Application? By: Caitlin Carrier

Dissolving Pulp From Cotton Linters BASIC INFORMATION. IPS Engineering

Basic information about quick steam generators/boilers System GEKA Heat Technology Gottfried Kneifel

Boiler Feed Manual. L-BF-SL (US)

Pesticide Applicator Equipment Cleaning to Prevent Carryover. Chuck Schuster University of Maryland Extension

Steam and air don't mix. Chemical dosing of feedwater

Water Quality in Hydronic Systems April 16, 2015 with Guest Speaker Jim Poehling, P.E., LEED AP Q&A Documentation

Soil. Acidic soils... 1/19/2014

Aqua Balance. User s Information Manual. WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water

THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY

HAVABLACK S2G BLACK OXIDE SALTS FOR IRON & STEEL

ANIMAL, PLANT & SOIL SCIENCE D3-2 SOIL CHEMISTRY

If your soil has a high salinity content, the plants

Understanding the Balance

Ashirwad Carbonics (India) Private Limited

CHAPTER 3 BASIC STEAM CYCLE

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION WATER TREATMENT

Spray Flow II cc/liter Atmospheric Deaerator. industrialsteam.com

Spray Flow II cc/liter Atmospheric Deaerator. industrialsteam.com

MEGA 2010 Advances in Hot Side SO3 Mitigation Technology

Boiler. Fire tube Boiler:

.2 Section Waste Management and Disposal..5 Section Cleaning and Startup of Mechanical Piping Systems.

Installation and Operating Service Manual

PIPING APPLICATION GUIDE

9.0 Systems For Domestic Water Installations

Boiler Additives And Filtration

Technical manual 2G-TA 04 - Gas

Series 300 VTB. Installation Instructions

1. Cleaning Technology. o 1.1 Power o 1.2 Grit o 1.3 Temperature o 1.4 Chemical o 1.5 Time. 2. Chemical-Concentration Management

Deaerators for Industrial Applications

O Pro electric storage water heater

CLEAVER-BROOKS MODEL CBL PACKAGED BOILER

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV

Condensate Recovery and Return System SDR A

Peters. Peters Professional and Peters Excel provide a wide selection of the highest quality water-soluble fertilisers available

Three elements of fire. Heat Oxygen Fuel. Remove one of the three and the fire is extinguished.

Hydrazine Analyzer Series 2171 Specifications

SECTION Boiler Controls & Waste Heat Recovery

Industrial Descale Solutions & Descale Services

BOILER HOUSE PRODUCTS GMS

WHITE PAPER The Importance of Rinsing in Metal Finishing Operations

Refrigeration air dryer

Wallace & Tiernan Gas Feed Systems V2000 Chlorinator

A Newsletter published by. for Industrial Steam and Power Users

Deaerator. Specifications

VARIATION IN BEARING CAPACITY OF CONTAMINATED LATERITE SOIL. Dr R N Khare

Digital Salt / TDS Meter. 390a. The Value Leader TM

ACC is suitable for all types of diesel engines. The ACC / fresh water mixture has no flash point and cylinder lubrication is not impaired.

.03 ATMOSPHERIC DEAERATOR

Instruction and Maintenance Manual. Spiral Heat Exchanger

CHX Heat Recovery THE Solution. Steam Plant Systems, Inc.

Operation Refilling and Maintenance Manual SFS-10. Hatsuta Seisakusho Co. Ltd. SFS-10-E1404-(A-012)

With the advancement of perennial production,

Technical Specifications & Pricing

The Solution to Your Marine-Based Water-Scale Problems! RYDLYME Marine

Inherent Factors Affecting Soil ph. Soil ph Management

Chapter 8: Soil ph and Lime Management

Transcription:

BOILER SYSTEM CHEMICAL TREATMENT 101 The primary function of a boiler is to transfer heat from hot gases generated by the combustion of fuel into water until it becomes hot or turns to steam. The steam or hot water can then be used in building or facility processes. Boiler feedwater often contains impurities, which impairs boiler operation and efficiency. Chemical additives can be used to correct the problems caused by these impurities. To improve feedwater quality, and steam purity, these chemicals can be injected directly into the feedwater or steam. Benefits of Chemical Treatments Increase boiler efficiency; Reduce fuel, operating and maintenance costs; Minimize maintenance and downtime; and Protect equipment from corrosion and extend equipment lifetime. CHEMICAL TREATMENTS FOR WATERSIDE OF BOILER TUBES The feedwater is composed of makeup water (usually city water from outside boiler room/ process) and condensate (condensed steam returning to the boiler). The feedwater normally contains impurities, which can cause deposits and other related problems inside the boiler. Common impurities in water include alkalinity, silica, iron, dissolved oxygen and calcium and magnesium (hardness). Blowdown, a periodic or continuous water removal process, is used to limit the concentration of impurities in boiler water and to control the buildup of dissolved solid levels in the boiler. Blowdown is essential in addition to chemical treatments. List of Problems Caused By Impurities in Water Boiler Waterside Fouling Scale is one of the most common deposit related problems. Scale is a buildup of solid material from the reactions between the impurities in water and tube metal, on the water-side tube surface. Scale acts as an insulator that reduces heat transfer, causing a decrease in boiler efficiency and excessive fuel consumption. More serious effects are overheating of tubes and potential tube failure (equipment damage).

Oxygen Attack Oxygen attack is the most common causes of corrosion inside boilers. Dissolved oxygen in feedwater can become very aggressive when heated and reacts with the boiler s internal surface to form corrosive components on the metal surface. Oxygen attack can cause further damage to steam drums, mud dams, boiler headers and condensate piping. Acid Attack Acid attack is another common cause of corrosion. Acid attack happens when the ph of feedwater drops below 8.5. The carbonate alkalinity in the water is converted to carbon dioxide gas (CO2) by the heat and pressure of the boilers. CO2 is carried over in the steam. When the steam condenses, CO2 dissolves in water to form carbonic acid (H2CO3) and reduces the ph of the condensate returning to the boilers. Acid attack may also impact condensate return piping throughout the facility. BOILER SYSTEM CHEMICAL TREATMENTS AND FEED EQUIPMENT REQUIREMENTS Product Feed Considerations An often-overlooked fact is that the water treatment program usually represents a small percentage of the overall costs of a boiler operation. However, poor treatment or equipment performance can create domino effects increasing operating and maintenance costs. For best results, all chemicals for internal treatment of a steam generating facility must be fed continuously and at proper injection points. Chemicals may be fed directly from the storage tank (neat) or may be diluted in a day tank with high-purity water. Certain chemicals may be mixed together and fed from the same day tank. Chemical feed points are usually selected as far upstream in the boiler water circuit as possible. For chemical feed beyond the feedwater pump or into the steam drum, the pump must be matched to the boiler pressure. For high-pressure boilers, proper pump selection is critical. Basic Boiler System Schematic

As shown in the figure, a steam generating system includes three major components for which treatment is required: the deaerator, the boiler, and the condensate system. Oxygen scavengers are usually fed to the storage section of the deaerator. The boiler internal treatment is fed to the feedwater pump suction or discharge, or to the steam drum. Condensate system feed points also vary, according to the chemical and the objective of treatment. Typical feed points include the steam header or other remote steam lines. Chemical Treatments Lime Softening and Soda Ash Lime is added to hard water to precipitate the calcium, magnesium and, to some extent, the silica in the water. Soda ash is added to precipitate non-bicarbonate hardness. The process typically takes place in a clarifier followed by a hydrogen cycle cation exchange and a hydroxide cycle anion exchange demineralization. Both hydrated lime and soda ash can be purchased as a liquid, a slurry or in a dry granular form. Specialized handling and preparation systems are required for dry storage and makedown. Oxygen Scavengers A deaerator removes most of the oxygen in feedwater; however, trace amounts are still present and can cause corrosion-related problems. Oxygen scavengers are added to the feedwater, preferably in the storage tank of the feedwater, to remove the trace mount of oxygen escaped from the deaerator. The most commonly used oxygen scavenger is sodium sulfite. Sodium sulfite is cheap, effective and can be easily measured in water. Sulfite (Oxygen Scavenger) Uncatalyzed sodium sulfite may be mixed with other chemicals. The preferred location for sulfite injection is a point in the storage section of the deaerating heater where the sulfite will mix with the discharge from the deaerating section. If sulfite is fed alone, the following basic equipment is needed: skid mounted dual metering pumps (duty/stand-by) with stainless steel wet end/trim pulsation dampener stainless steel relief valve stainless steel check valve stainless steel Y-strainer stainless steel tubing, valves, and fittings flowmeter calibration cylinder pressure gauge with diaphragm seals electrical junction boxes dilution water line c/w static mixer (optional) drip pan (optional) In all cases, an injection quill should be used.

Sulfite shipped as liquid concentrate is usually acidic and, when fed neat, corrodes stainless steel tanks at the liquid level. Sulfite storage tanks must be fiberglass, or polyethylene. Lines may be PVC or 316 stainless steel. Catalyzed Sulfite (Oxygen Scavenger) Catalyzed sulfite must be fed alone and continuously. Mixing of catalyzed sulfite with any other chemical impairs the catalyst. For the same reason, catalyzed sulfite must be diluted with only condensate or demineralized water. To protect the entire preboiler system, including any economizers, catalyzed sulfite should be fed to the storage section of the deaerating heater. Caustic soda may be used to adjust the ph of the day tank solution; therefore, a mild steel tank cannot be used. Materials of construction for feed equipment are the same as those required for regular sulfite. Hydrazine (Oxygen Scavenger) Hydrazine is compatible with all boiler water treatment chemicals except organics, amines, and nitrates. However, it is good engineering practice to feed hydrazine alone. It is usually fed continuously into the storage section of the deaerating heater. Because of handling and exposure concerns associated with hydrazine, closed storage and feed systems have become standard. Materials of construction are the same as those specified for sulfite. Organic Oxygen Scavengers Many organic compounds are available, including hydroquinone and ascorbic acid. Some are catalyzed. Most should be fed alone. Like sulfite, organic oxygen scavengers are usually fed continuously into the storage section of the deaerating heater. Materials of construction are the same as those specified for sulfite. Neutralizing Amines Neutralizing amines are high ph chemicals that neutralize the carbonic acid formed in the condensate (acid attack). The three most commonly used neutralizing amines are morpholine, diethyleminoethanal (DEAE) and cyclohexylamine. Neutralizing amines cannot protect against oxygen attack; however, it helps keep oxygen less reactive by maintaining an alkaline ph. Neutralizing amines may be fed to the storage section of the deaerating heater, directly to the boiler with the internal treatment chemicals, or into the main steam header. Some steam distribution systems may require more than one feed point to allow proper distribution. An injection quill is required for feeding into a steam distribution line. Neutralizing amines are usually fed based on condensate system ph and measured corrosion rates. These amines may be fed neat, diluted with condensate or demineralized water, or mixed in low concentrations with the internal treatment chemicals. A standard packaged pump skid and tank can be used for feeding. Filming Amines Filming amines are various chemicals that form a protective layer on the condensate piping to protect it from both oxygen and acid attack. The two most common filming amines are octadecylamine (ODA) and ethoxylated soya amine (ESA). Combining neutralizing and filming amine is a successful alternative to protect against both acid and oxygen attack. The filming amines should be continuously fed into steam headers at points that permit proper distribution. A single feed point is satisfactory for some systems. In every case, the steam distribution should be investigated and feed points established to ensure that all parts of the system receive proper

treatment. Filming amines must be mixed with condensate or demineralized water. Water containing dissolved solids cannot be used, because the solids would contaminate the steam and could produce unstable amine emulsions. The use of stainless steel tanks is recommended. Equipment specifications are the same as those for regular sulfite, except that a vapor-type injection nozzle or quill is required. Internal Treatment Chemicals There are three major classifications of chemicals used in internal treatment: phosphates, chelants, and polymers. These chemicals may be fed either separately or in combination; in most balanced treatment programs, two or three chemicals are fed together. The preferred feed point varies with the chemical specified. For example, when caustic soda is used to maintain boiler water alkalinity, it is fed directly to the boiler drum. When caustic is used to adjust the feedwater ph, it is normally injected into the storage section of the deaerating heater. Phosphate Mono-, di- or trisodium phosphate and sodium polyphosphate can be added to treat boiler feedwater. Phosphate buffers the water to minimize ph fluctuation. It also precipitates calcium or magnesium into a soft deposit rather than a hard scale. Additionally, it helps to promote the protective layer on boiler metal surfaces. However, phosphate forms sludge as it reacts with hardness; blowdown or other procedures should be established to remove the sludge during a routine boiler shutdown. Phosphates are usually fed directly into the steam drum of the boiler, although they may be fed to the feedwater line under certain conditions. Treatments containing orthophosphate may produce calcium phosphate feed line deposits; therefore, they should not be fed through the boiler feed line. Orthophosphate should be fed directly to the boiler steam drum through a chemical feed line. Polyphosphates must not be fed to the boiler feedwater line when economizers, heat exchangers, or stage heaters are part of the preboiler system. If the preboiler system does not include such equipment, polyphosphates may be fed to the feedwater piping provided that total hardness does not exceed 2 ppm. In all cases, feed rates are based on feedwater hardness levels. Phosphates should be fed neat or diluted with condensate or high-purity water. Mild steel tanks, fittings, and feed lines are appropriate. If acidic phosphate solutions are fed, stainless steel is recommended. Chelants Nitrilotriacetic acid (NTA) and ethylenediamine tetraacetic acid (EDTA) are the most commonly used chelants. Chelants combine with hardness in water to form soluble compounds. The compounds can then be eliminated by blowdown. Chelants treatment is not recommended for feedwater with high hardness concentration Chelants should not be fed if the feedwater contains a significant level of oxygen. Chelants should never be fed directly into a boiler The preferred feed location for chelants is downstream of the feedwater pump. All chelant treatments must be fed to the boiler feedwater line by means of a stainless steel injection nozzle at a point beyond the discharge of the boiler feed pumps. If heat exchangers or stage heaters are present in the boiler feed line, the injection point should be at their discharge. Care should be exercised in the selection of metals for high-temperature injection quills. At feed solution strength and elevated temperatures, chelating agents can corrode mild steel and copper alloys; therefore, 304 or 316 stainless steel is recommended for all feed equipment. Equipment specifications are the same as those for regular sulfite. Chelant products may be fed neat or diluted

with condensate. Chelant feed rates must be carefully controlled based on feedwater hardness, because misapplication can have serious consequences. Polymeric Dispersants. In most applications, polymeric dispersants are provided in a combined product formulation with chelants and/or phosphates. Dilution and feed recommendations for chelants should be followed for chelant-dispersant and chelant-phosphate-dispersant programs. Dilution and feed recommendations for phosphates should be followed for phosphate-dispersant programs. These combination programs typically have the best results with respect to boiler cleanliness. Neutralizing Amines Neutralizing amines are high ph chemicals that neutralize the carbonic acid formed in the condensate (acid attack). The three most commonly used neutralizing amines are morpholine, diethyleminoethanal (DEAE) and cyclohexylamine. Neutralizing amines cannot protect against oxygen attack; however, it helps keep oxygen less reactive by maintaining an alkaline ph. Neutralizing amines may be fed to the storage section of the deaerating heater, directly to the boiler with the internal treatment chemicals, or into the main steam header. Some steam distribution systems may require more than one feed point to allow proper distribution. An injection quill is required for feeding into a steam distribution line. Neutralizing amines are usually fed based on condensate system ph and measured corrosion rates. These amines may be fed neat, diluted with condensate or demineralized water, or mixed in low concentrations with the internal treatment chemicals. A standard packaged pump skid and tank can be used for feeding. Filming Amines Filming amines are various chemicals that form a protective layer on the condensate piping to protect it from both oxygen and acid attack. The two most common filming amines are octadecylamine (ODA) and ethoxylated soya amine (ESA). Combining neutralizing and filming amine is a successful alternative to protect against both acid and oxygen attack. The filming amines should be continuously fed into steam headers at points that permit proper distribution. A single feed point is satisfactory for some systems. In every case, the steam distribution should be investigated and feed points established to ensure that all parts of the system receive proper treatment. Filming amines must be mixed with condensate or demineralized water. Water containing dissolved solids cannot be used, because the solids would contaminate the steam and could produce unstable amine emulsions. The use of stainless steel tanks is recommended. Equipment specifications are the same as those for regular sulfite, except that a vapor-type injection nozzle or quill is required. Computerized Boiler Chemical Feed Systems Computerized boiler chemical feed systems are being used to improve program results and cut operating costs. These systems can be used to feed oxygen scavengers, amines, and internal treatment chemicals. A typical system incorporates a metering pump, feed verification equipment, and a microprocessor-based controller. These systems are often linked to personal computers, which are used to monitor program results, feed rates, system status, and plant operating conditions. Trend graphs and management reports can then be produced to provide documentation of program results and help in troubleshooting. In many cases, these systems can be programmed to feed boiler treatment chemicals according to complex customized algorithms. For example, chelant feed can be adjusted automatically, based on analyzer or operator hardness test results, boiler feedwater flow, and minimum/maximum allowable

product feed rates. Thus, chemical feed precisely matches system demand, virtually eliminating the possibility of underfeed or overfeed. Feed verification is another important facet of some computerized feed systems. The actual output of the pump is continuously measured and compared to a computer-calculated setpoint. If the output doesn't match the set point, the speed or stroke length is automatically adjusted. The benefits of this technology include the elimination of time-consuming drawdown measurements, the ability to feed most chemicals directly from bulk tanks, precise chemical residual control, and minimal manpower requirements. Statements and suggestions herein are based upon the best information and practices known to Hayward Gordon Ltd. However, it should not be assumed either that information is complete on the subjects covered or that all possible circumstances, safety measures, precautions, etc. have been included. These statements and suggestions are not intended to reflect provincial, municipal or insurance requirements or national safety codes; where applicable, those sources must be considered directly. Since the conditions of use are beyond our control, Hayward Gordon makes no guarantee of results and assumes no liability in connection with the information contained herein. When dealing with installation, operation or maintenance of specific pumps, the Hayward Gordon manuals and instructions pertaining to that product should be followed carefully.