GOLDFIELDS PRIMARY SCHOOL. TENDER SPECIFICATION For ELECTRICAL SERVICES MECHANICAL ENGINEER:

Similar documents
.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

Telecity. Table of Contents. Page. Section 3.2

Attachment F. Campus Capital Needs Sales Surtax Funded Detail Report

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

NZQA registered unit standard 5897 version 3 Page 1 of 5. Design electronic security intruder alarm systems

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

GARCIA GALUSKA DESOUSA Consulting Engineers

TAITA TAVETA UNIVERSITY P.O.BOX , VOI, KENYA Tel: TENDER NO: TTU/T/01A/

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD.

MAZAGON DOCK SHIPBUILDERS LIMITED

Brighton Area Fire Authority

1.3 REFERENCE STANDARDS

Electrical Design Guidelines Table of Contents

Electrical Inspection Special Electrical

PLATTEVILLE MIDDLE SCHOOL

Special Provision No. 682S27 June This Special Provision refers to the following standards, specifications or publications:

NYC Department of Education

LIGHTING CONTROLS

MAZAGON DOCK SHIPBUILDERS LIMITED

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

PROFILE. industrial services rental trading

09 ELECTRICAL 0902 Electrical

SECTION INTRUSION DETECTION

Brochure. Security Designed, Installed by Experts

NYC Department of Education

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

ACP10 & ACP50 Security Systems

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Installation, Operating and Maintenance Manual

NYC Department of Education

Oakdale Primary School Expansion Project Appendix C Elec Equipment Schedule

Magna-Sygg Model K Operations and Maintenance Manual

NZQA registered unit standard version 1 Page 1 of 5

NYC Department of Education

NZECP 19: 1994 ISSN COVER PAGE

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section CHLORINE GAS LEAK DETECTOR

4 August Islington Fire Protection Transpower NZ Limited

NYC Department of Education

RFP Addendum 2 March 31, 2016

SECTION FIRE DETECTION AND ALARM

Telecommunications Survey

Electrical Inspection Special Electrical

C-Bus Four Channel Analogue Output Unit Installation Instructions

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

Emergency Voice Communication System (EVCS) Consu ltant s Specific atio n CONTENTS

Australian Standard. Emergency escape lighting and exit signs for buildings. Part 1: System design, installation and operation AS 2293.

Networked Access Control Panel. Installation Guide

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

NYC Department of Education

DONALD H. BERG, ARCHITECT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

WASHINGTON METROPOLITAN AREA TRANSIT AUTHORITY SAMPLE TASK WORK STATEMENT Fire Life Safety Upgrade Alexandria Facilities

For your commercial needs, we offer the following services:

RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan

Campus Sign Plan. Adopted by the Campus Planning Committee Adopted: June 26, 2006 Revised: April 14, 2016

NZQA registered unit standard version 1 Page 1 of 5

Guide Specifications. HyperPod System PART 1 - GENERAL 1.01 SUMMARY

Garfield Elementary School Feasibility Study for New Library Building Project Number A C

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District

Card Access Control Specifications

AS/NZS 3190:2011 AS/NZS

FIRE ALARM: BY OTHERS, IF REQUIRED.

Electronic Safety and Security

Currently, all electrical upgrades would be voluntary, but there are situations in which upgrades would be required.

FIRE ALARM: BY OTHERS, IF REQUIRED.

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control/Communicator

DIVISION 14 - CONVEYING SYSTEMS. 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts.

Unified Fire Authority - Fire Prevention Bureau

NZQA registered unit standard version 4 Page 1 of 5

NYC Department of Education

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion

SETION EMERGENCY LIGHTING NATIONAL FIRE PROTECTION ASSOCIATION (NEPA) (2006) Life Safety Code, 2006 Edition

East Central College

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

lighting management standalone sensors

Working in Partnership with our Customers.

NYC Department of Education

USD 380 Centralia, Frankfort & Vermillion

1 P a g e w w w. s m o k e c o n t r o l. c o. nz

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17

FIRE & LIFE SAFTEY STANDARD

AS/NZS 3133:2008 AS/NZS

NZQA unit standard version 2 Page 1 of 6. Perform installation and maintenance of telecommunications radio systems and services

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

NZQA registered unit standard 5881 version 6 Page 1 of 5. Demonstrate knowledge of electronic security devices

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

CONDITIONS OF SERVICE - NBN SERVICES 1. ABOUT

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

NYC Department of Education

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Australian/New Zealand Standard

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

Transcription:

GOLDFIELDS PRIMARY SCHOOL TENDER SPECIFICATION For ELECTRICAL SERVICES PROJECT MANAGER: School Support Dunedin ARCHITECTURAL DESIGNER: Katipo Design ELECTRICAL ENGINEER: Pedersen Read Dunedin MECHANICAL ENGINEER: Wintech

! E1. GOLDFIELDS SCHOOL NEW CLASSROOM BLOCK... 3 E2. DRAWINGS... 3 E3. DESIGN BUILD SUBMISSION... 3 E4. INCOMING SERVICES TO BLOCK... 3 E5. SWITCHBOARD FOR NEW CLASSROOM BLOCK... 4 E6. LIGHTING... 4 E7. PLUG SOCKET OUTLETS AND DATA OUTLETS... 4 E8. STRUCTURED CABLING... 4 E9. SECURITY SYSTEM... 4 E10. FIRE ALARM SYSTEM... 4 E11. CLASS CHANGE SYSTEMS... 5 E12. GENERAL... 5 E13. WARRANTIES AND DEFECTS LIABILITY PERIOD REQUIREMENTS... 5 E14. Ministry of Education Warranties... 6 E15. DOCUMENTS TO BE COMPLIED WITH... 6 E16. PROVISION OF DOCUMENTATION... 6 2240 Goldfields Primary School Cromwell Page: 2 of 6

GOLDFIELDS SCHOOL NEW BLOCK E1. GOLDFIELDS SCHOOL NEW CLASSROOM BLOCK Pedersen Read provide a Scope of Works which outlines the items that will form part of the electrical services of the contract for the establishment of the new classroom block at Goldfields School. This document is to be used as a scope of works for design build electrical contractors to base their tender submission on. We provide the scope of works for electrical services on a heading by heading basis as follows. E2. DRAWINGS Documents that relate to this contract shall include the following: E1.1 - Electrical Site Plan E2.1 - Electrical Services Plan E3. DESIGN BUILD SUBMISSION Tenderers shall allow to provide a tender submission to design, supply, install and commission an electrical installation that complies with the criteria set out within this document as follows. E4. INCOMING SERVICES TO BLOCK Incoming services are to be provided to the new block as set out below. Tenderers are to allow to provide a site plan with intended cable routes outlined within the tender submission. Incoming power supply to be derived from the main switchboard within the Administration block from MSB where indicated on the attached drawing. The submain cable shall be rated for 50Amps three phase. The cable size has been specified on the drawings. Allow to connect to the MSB via new 50A MCB. Cabling to be concealed within conduit along exterior of building under walkway. Installation to match the existing conduit installed for the data cabling. Structured cabling backbone cabling shall originate from the existing Patch Panel located within the Administration building indicated on the attached drawing as Patch Panel AG1, this backbone cabling shall be in compliance with the Ministry of Education Information Technology Infrastructure Cabling Switching Policy and Guidelines for Schools this backbone cabling shall be installed from the main site data patch panel within the Administration Block to the new patch panel CG1 within the new classroom block. Backbone cabling shall incorporate fibre cabling and 2No Cat 6 tie cables for telephone cabling interfaced to the telephone systems at the site to allow patching of phone outlets to any data outlet. New Fire alarm cabling shall be to be extended from the new fire alarm panel within the MSB room to the new classroom block. The new classroom block building fire alarm system shall form a new zone on the new fire alarm panel which shall cover the new classroom block. Note an interface is to be provided to allow full site evacuation when activation of any fire alarms system occurs. Class change activations on the existing type 1 alarm system should not initiate a fire alarm call. Class change cabling to be extended from the adjacent existing clapper bell on the existing block B, this shall be extended to a new white clapper bell installed on the exterior of the new classroom block. MOE approved security services shall be provided in the new classroom block. Security LAN cabling to be installed from the Administration building MSB room to the new classroom block to allow for future site wide connection of the security system. 2240 Goldfields Primary School Cromwell Page: 3 of 6

E5. SWITCHBOARD FOR NEW CLASSROOM BLOCK The new classroom block will be provided with a new switchboard which shall be of metal clad construction and in full compliance with all applicable standards. This switchboard shall incorporate all circuit breakers for services within the block and spare capacity to allow supply to additional subcircuits in the future. 36 ways shall be provided. Switchboard shall have evacuation lighting controls and exterior lighting controls etc. E6. LIGHTING Evacuation lighting to be provided in compliance with F6 of the building code, this will incorporate illuminated exit signs to all exit doors and emergency lighting testing facilities at the distribution board. Exterior lighting will be controlled by an auto/off manual switch on the switchboard and be installed as indicated on the architectural drawings. In auto mode day light switch and time clock control will apply. 4 core cabling to be installed to all exterior lights. E7. PLUG SOCKET OUTLETS AND DATA OUTLETS At each data outlet position allow to provide 2 double plug socket outlets (one with 10mA RCD protection). Allow to provide power supply to 1No. hot water cylinder. Allow to provide surge protected power supply to data patch panel. All socket outlets and light switches shall be from the PDL600 series E8. STRUCTURED CABLING Allow to provide data outlets as indicated on the drawings including high level outlets for future wireless modules. Allow to provide a data cabinet in the form of a suitably sized wall mount enclosure (Min. 12RU) in compliance with MOE guidelines. All structured cabling systems shall be in accordance with MOE guidelines. All installers of data services shall be registered on the MOE website. Allow for Cat 6 patch panel, Cat 3 voice panel, fibre tray and terminations. Allow for 6 core OM3 fibre cabling from the AG1 data cabinet to the new CG1 data cabinet. Allow to terminate in the existing fibre tray at AG1, allow for matching connectors and labelling. Allow to install new fibre and tie cables in the existing conduit from AG1 to BG1. (There is currently a draw wire installed) and extend in new conduit to the new classroom block from block B. E9. SECURITY SYSTEM Provide MOE approved (concept 4000) security system within the new classroom block, provide new PIR detectors, external sounder and 1No code pad and commission. Install a security system LAN cable from the new classroom block to the main switchboard room for a future security system to cover the remainder of the school. E10. FIRE ALARM SYSTEM Provide a new addressable fire alarm panel within the main switchboard room. This new fire alarm panel shall provide fire alarm services to the new classroom block and also provide a smoke detector within the MSB room of the administration block. This panel will become the main fire alarm panel for the school as the fire alarm in the remaining blocks are upgraded. The new addressable fire alarm panel shall interface with the existing Type 1 clapper bell and the existing conventional F1 panel installed in the Hall. 2240 Goldfields Primary School Cromwell Page: 4 of 6

Provide new addressable type 4 fire alarm system (Smokes within the new classroom block and thermals in the exterior veranda, the fire alarm system shall be fully compliant with NZS4512:2010. An interface is to be provided to allow full site evacuation when activation of any fire alarms system occurs. Class change activations on the existing type 1 alarm system should not initiate a fire alarm call. Provide site indicator mimic panel. The sounders within the new classroom block shall match the existing clapper bell sound until the whole site is converted to verbal messaging. E11. CLASS CHANGE SYSTEMS The existing class change system at the school is via clapper bells. Allow to provide an additional clapper bell on the new classroom block and extend cabling from the existing clapper bell on the adjacent block B. The new clapper bell shall be painted white. E12. GENERAL All works to comply with AS/NZS:3000:2007. All works to comply with MOE guidelines. As built documentation to be provided for all electrical services. Staff training to be given on all equipment. A maintenance period of 12 months will apply from final completion. MOE Warranties for electrical services shall apply to this contract Allow to carry out a full site evaluation prior to submission of a tender. E13. WARRANTIES AND DEFECTS LIABILITY PERIOD REQUIREMENTS All items of equipment shall be subject to a Defects Liability period of twelve months from the date of Practical Completion. The Warranty period for various items which shall commence at the completion of the Defects Liability period shall be as follows Workmanship 12 months after completion of Defects Liability Period Structured Cabling Systems 15 years after completion of Defects Liability Period (Vendors Warranty) Security Systems 12 months after completion of Defects Liability Period Light Fittings 12 months after completion of Defects Liability Period Fluorescent tubes and lamps 12 months after practical completion or the rated life of lamp provided by the manufacturer based on normal operating hours of facility. Whichever is less. Exterior Paint finishes on any component of the electrical installation including lights. 4 years after completion of Defects Liability Period Switchboards and distribution boards 12 months after completion of Defects Liability Period Switchgear including light switches and plug socket outlets 12 months after completion of Defects Liability Period. Control Systems 12 months after completion of Defects Liability Period. Where products are provided with a longer warranty period as normal practice the longer period shall apply. 2240 Goldfields Primary School Cromwell Page: 5 of 6

E14. Ministry of Education Warranties Within schools, all new or upgraded electrical installations shall have the following warranties A minimum two (2) year installation warranty A minimum two (2) year systems and components warranty A minimum five (5) year electrical appliance warranty, where the appliance is supplied by the electrical contractor. E15. DOCUMENTS TO BE COMPLIED WITH The following documents are to be referenced and complied with in the design build submission. Ministry of Education document titled Ministry of Education Information Technology Infrastructure Cabling Switching Policy and Guidelines for Schools which is available on the MOE website at www.minedu.govt.nz. AS / NZS 3000:2007 standard NZS 4512:2010 standard New Zealand Building Code All applicable New Zealand Standards Particular reference to be given to F6 and F8 of building code Ministry of Education document titled The supply and installation of intruder systems for the Ministry of Education. Ministry of Education document titled Ministry of Education Standard Specification Security Alarm System which is available on the MOE website at www.minedu.govt.nz. Ministry of Education document titled Fire safety and Design Requirements for Schools which is available on the MOE website at www.minedu.govt.nz. Ministry of Education document titled Ministry of Education Information Technology Infrastructure Cabling Switching Policy and Guidelines for Schools which is available on the MOE website at www.minedu.govt.nz. E16. PROVISION OF DOCUMENTATION The following documents are to be provided at times outlined. At the time of tender a plan showing planned routes for cabling around the site should be submitted. At the time of tender a plan showing outlet positions should be submitted for sign off by the project manager. For building consent purposes the electrical contractor shall allow to provide a Producer statement PS1: Design outlining compliance of design with the building code. At the completion of the project. Allow to provide an electrical certificate of compliance for the completed electrical installation. At the completion of the project. Allow to provide a Vendors warranty statement for the structured cabling systems. This shall be in compliance with the MOE guidelines. At the completion of the project. Allow to provide an FPIS certificate of Compliance for the fire alarms system. At the completion of works the electrical contractor shall allow to provide a Producer statement PS3: Construction outlining compliance of design with the building code. During the course of the project the electrical contractor shall allow to fill in MOE project management forms as requested by the project manager. 2240 Goldfields Primary School Cromwell Page: 6 of 6