TECHNICAL DATA MODEL V-HIP SPECIFIC APPLICATION ATTIC SPRINKLER VK660

Similar documents
MODEL V-BB SPECIFIC APPLICATION TECHNICAL DATA

culus Listed: Category VNIV Refer to the Approval Chart on page 3. VK697 Attic Upright Sprinkler Specifications:

ATTIC UPRIGHT SPECIFIC APPLICATION SPRINKLER VK696 TECHNICAL DATA

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

micromatic standard response Upright sprinkler VK100 (K5.6)

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

microfast quick response Pendent sprinkler VK302 (K5.6)

standard response elo upright sprinkler

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

standard response Fusible Link Upright sprinkler VK204 (K8.0)

TECHNICAL DATA. Page 1 of 6

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK120 (K8.0) TECHNICAL DATA

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK470 (K3.0) TECHNICAL DATA

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

micromatic Standard response Horizontal Sidewall sprinkler

MICROMATIC STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

TECHNICAL DATA vk470 (K3.0)

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

quick response horizontal sidewall sprinkler vk360 (K8.0)

QUICK RESPONSE EXTENDED COVERAGE CONCEALED HSW SPRINKLER VK630 (K8.0) TECHNICAL DATA

TECHNICAL DATA. Page 1 of 5

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

freedom residential Upright sprinkler vk467 (k4.9)

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

freedom residential pendent sprinkler vk466 (K5.2)

standard response/ quick response extended coverage

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

standard response large orifice dry

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

Form No. F_ Rev 14.1 Page 1 of 6 TECHNICAL DATA

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK494 (K4.9) TECHNICAL DATA

Microfast quick response Fusible element hsw sprinkler

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

standard response fusible link sidewall sprinkler VK112 (K5.6)

TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK498 (K5.8) TECHNICAL DATA

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK3311 (K4.2) TECHNICAL DATA

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

microfast sr/qr extended coverage pendent sprinkler

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

MICROFAST SR/QR EXTENDED COVERAGE HSW SPRINKLER VK605 (K5.6) TECHNICAL DATA

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK460 (K5.8) TECHNICAL DATA

micromatic Standard response Horizontal Sidewall sprinkler

microfast quick response extended coverage hsw sprinkler vk606

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

micromatic standard response stainless steel sprinklers

MICROMATIC STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK104 (K5.6) TECHNICAL DATA

TECHNICAL DATA OBSOLETE

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

mirage standard response concealed pendent sprinkler vk492 (K5.6)

microfast and microfasthp quick conventional sprinklers

Page 1 of 7. Form No. F_ Rev Replaces Form No. F_ Rev 17.1 (added 205deg version)

quick response Sprinkler 105a October 25, 2010

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

freedom residential horizontal sidewall sprinkler Vk450 (k4.2)

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

Standard Spray concealed horizontal sidewall sprinkler VK481

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

TECHNICAL DATA. The Viking Corporation s Web site at Overall Length (Sprinkler Body): 2-5/16 (59 mm)

December 14, 2015 Page 1 of 7 TECHNICAL DATA

QUICK RESPONSE FUSIBLE ELEMENT HSW SPRINKLERS VK308 AND HP VK320 (PART NOS AND 13955) TECHNICAL DATA

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

freedom residential horizontal sidewall lead free sprinkler VK4840 (k4.2)

standard/quick response extended coverage light and ordinary hazard elo sprinklers

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

Transcription:

Page 1 of 9 1. DESCRIPTION The is a Specific Application Attic Sprinkler designed to provide superior fire protection in combustible and non-combustible sloped attic spaces when compared to standard spray attic protection. With specific application criteria for use with Model V-BB (Back to Back), Model V-SD (Single Directional), and Attic Upright Specific Application Sprinklers, the Viking attic sprinklers provide an extended coverage spacing alternative to standard spray sprinklers. They make it possible to use a single line of piping at the attic peak, eliminating the need for branch lines and greatly reducing the number of required sprinklers and associated material and installation costs. Viking Attic Sprinklers can be installed with either steel or CPVC piping (CPVC allowed on wet pipe systems only), and are available in brass or with corrosionresistant Electroless Nickel PTFE (ENT) coatings where salt water and other corrosive elements are a consideration. They are culus Listed with specific application guidelines for use as special sprinklers as defined by the National Fire Protection Association (NFPA), and are culus Listed for extended coverage in combustible and non-combustible construction. The culus Listing was achieved using full-scale fire tests within wood truss construction. The sprinkler offers coverage for the hip area of the attic. Like the models V-BB and V-SD the throws a water pattern down the slope of the attic; however, the is located along the hip rather than the ridge and throws water toward the outer edge of the attic space in a 90 pattern allowing the water to trap the fire in the corner. The sprinkler provides reduced response time due to its narrow spacing of 6 ft. (1,8 m) and maximum throw capability of 28 ft (measured horizontally). The sprinkler is installed with the flow shaper parallel with the slope to allow maximum coverage of the eaves and hip area. V-HIP Attic Sprinkler SIN K-factor Pitch 5.6 (80.6 metric) 4:12 < 12:12 2. LISTINGS AND APPROVALS culus Listed: Category VNIV Refer to the Approval Charts and Design Criteria on for culus Listing requirements that must be followed. 3. Specifications: Minimum Operating Pressure: See Design Criteria - UL on page 4. Rated to 175 psi (12 bar) water working pressure Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: 1/2 (15 mm) NPT Nominal K-Factor: 5.6 U.S. (80.6 metric*) * Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to -65 F (-55 C) Overall Length: 2-11/16 (68 mm) Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass Flow shaper: Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: 18-8 Stainless Steel Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Yoke: Phosphor Bronze - UNS-C51000 Flow shaper Screw: Stainless Steel UNS-S31600 Replaces Form No. F_092116 Rev 17.2 (Added P65 Warning.)

Page 2 of 9 Ordering Information: (Also refer to the current Viking price list.) Sprinkler base part number: 20952 To order the Attic Sprinkler, add the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, ENT = JN Temperature Suffix: E = 200 F (93.3 C) For example, sprinkler with a Brass finish and 200 F (93.3 C) temperature rating = Part No. 20952AE Available Finishes And Temperature Ratings: Refer to the approval chart on page 3. Accessories: (Also refer to the Viking website.) Sprinkler Wrench: Standard Wrench: Part No. 10896W/B Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A B. Twelve-head capacity: Part No. 01725A 4. INSTALLATION The Model V-HIP Sprinkler must be installed in the upright position with the top of the flow shaper parallel to the slope of the hip ridgeline and the flow direction (indicated by arrows on the top of the flow shaper) pointing down the 2 opposing slopes. Refer to appropriate NFPA Installation Standards. NOTICE TOP OF FLOW SHAPER PARALLEL TO HIP RIDGELINE DO NOT hold the sprinkler using the flow shaper. Use the wrench flats and the standard sprinkler wrench to install. Figure 1: Installation 5. OPERATION During a fire condition, the heat sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the flow shaper, forming a uniform spray pattern to extinguish or control the fire, and protect the piping in the attic space. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Sprinkler is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking s current list price schedule or contact Viking directly.

Page 3 of 9 Sprinkler Temperature Classification TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Nominal Temperature Rating 1 Maximum Ambient Ceiling Temperature 2 Bulb Color Intermediate 200 F (93.3 C) 150 F (65 C) Green Sprinkler Finishes: Brass, ENT 3 Footnotes 1 The sprinkler temperature rating is stamped on the flow shaper. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 culus Listed as corrosion resistant. 1-3/4" (45 mm) 1-3/8" (35 mm) 2-11/16" (68 mm) 1/2" (15 mm) NPT 7/16" (11 mm) Nominal Pipe Engagement Figure 2: Sprinkler Dimensions Part Number 1 SIN Maximum Pressure APPROVAL CHART Viking V-HIP Specific Application Sprinkler For Combustible and Non-Combustible Sloped Attic Spaces Thread Size Nominal K-Factor Overall Length Listings and Approvals 3 NPT BSP U.S. metric 2 Inches mm culus 4 FM LPCB 20952 175 psi 1/2 15 mm 5.6 80.6 2-11/16 68 A1, A2 -- -- -- -- Approved Temperature Rating Approved Finish A - 200 F (93.3 C) 1 Also refer to Viking s current price schedule. Footnotes 1 - Brass, 2 - ENT 5 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process. 4 Listed by Underwriters Laboratories Inc. for use in the United States and Canada. 5 culus Listed as corrosion resistant.

Page 4 of 9 DESIGN CRITERIA - UL Chart 1 (Also refer to Approval Chart) Allowable, flow, pressure and slope for attic protection using Viking Sprinklers ADDITIONAL DESIGN CRITERIA - UL Chart 2 (Also refer to Approval Chart 1 and Design Criteria - UL Chart 1) Allowable, flow, pressure and slope for attic protection using Viking Sprinklers Design criteria: Flow and pressures refer to Design Criteria - UL Chart 1. System type: Wet systems and dry systems. Piping types: Steel (wet and dry) CPVC (wet systems only). Occupancy classification: Light hazard only. Viking V-HIP Sprinkler Spacing Maximum coverage area: The maximum coverage area for the V-HIP sprinkler is the distance down the greater of the 2 slopes, multiplied by 2, then multiplied by the distance between the V-HIP sprinklers on the branchlines, measured along the slope. Minimum distance of V-HIP sprinkler between other sprinklers along branchline: 4'-0" (1,22 m) - From V-BB and V-SD Sprinklers. 3'-0" (0,91 m) - From V-HIP Sprinklers. 7'-0" (2,13 m) - From Attic Upright Sprinklers. 6'-0" (1,83 m) - From Standard Spray Sprinklers. Maximum distance of V-HIP sprinkler between other sprinklers along branchline: 6"-0" (1,83 m) - Center to center from V-BB, V-SD, and V-HIP Sprinklers. 10'-0" (3,05 m) - Center to center from Attic Upright Sprinklers. Flow shaper position below peak, ridge, or deck: For all roof pitches as per the listing from 4:12 12:12 the maximum flow shaper distance down is 22 (560 mm), and the minimum flow shaper distance down is 16 (405 mm). Minimum distance from truss: 6 (152 mm) from nearest edge of the truss. Maximum distance from center line of the ridge: 6 (152 mm) on either side of the center line. Draft curtains: Where used to allow Attic Upright Sprinkler installation shall be constructed to contain heat, may be constructed of minimum ½ (13 mm) plywood or equivalent. Continues on next page.

Page 5 of 9 Continued from previous page. Use of UL Listed CPVC BlazeMaster piping (wet systems only): Can be used to supply the sprinklers protecting the floor below the combustible concealed space when covered with 6 (152 mm) of non-combustible insulation over the horizontal or vertical piping, and extending 12 (304 mm) on both sides of the center line of the piping. If the piping is located in the joist, the width of the joist channel must be entirely covered to 6 (152 mm) above the top of the piping. The area above the piping must be protected with the Model V-HIP's, V-BB s, V-SD s, or the Attic Upright Sprinklers. Listed CPVC BlazeMaster piping may also be used exposed to feed wet systems using Viking V-HIP sprinklers in accordance with the following requirements, and in accordance with Figure 6: Risers are vertical and protected by V-BB, V-SD, or V-HIP sprinklers located a maximum of 12" (304 mm) away from the riser centerline. Model V-HIP, V-BB, or V-SD sprinklers are mounted directly to the branchline. Model V-HIP, V-BB, or V-SD sprinklers are installed on arm-overs a maximum of 6 (152 mm) laterally from the center line of the branch line. Model V-HIP, V-BB, or V-SD sprinklers are installed on vertical sprigs attached to the branchline. Model V-HIP, V-BB, or V-SD sprinklers are installed on angled sprigs a maximum of 6 (152 mm) laterally from the centerline of the branchline. Installed with a minimum lateral distance of 18 (456 mm) from any device that produces and releases heat, i.e. attic furnace, kitchen or bathroom exhaust fan, flue vents, heat lamps, and other such devices. Insulation requirements are provided solely for fire protection purposes and not for freeze protection. Non-combustible insulation needs to be verified for chemical compatibility with the CPVC piping at www.lubrizol.com Refer to Sections 8.8.5.2.1.3 and 8.8.5.2.1.7 of NFPA 13, 2016 for requirements if installed on greater than 2-1/2 (64 mm) diameter piping. Hydraulic requirements: Viking V-HIP sprinklers must be calculated in accordance with the following figures and guidelines. The design area shall include the most hydraulically demanding sprinklers, and in certain cases may require more than one set of calculations to verify the system s design. The following figures cover hydraulic requirements for Viking V-HIP, V-BB, and V-SD sprinklers, when installed with Attic Upright (or Standard Spray) Sprinklers. Refer to figures-unless otherwise noted, all figures portray a 60 (18,3 m) roof span: Figure 7 V-BB and V- Sprinklers Figure 8 V-SD and V- Sprinklers Figure 9 V- Sprinklers Figure 10 V-BB, V-, and Attic Upright Sprinklers at the Eaves V-BB (Back to Back) V-SD (Single Directional) Attic Upright V-HIP Top Side Top Side Top Side Top Side Figure 3: Sprinkler Type Legend

Page 6 of 9 TABLE 1: DESIGN CRITERIA REF DESCRIPTION MINIMUM MAXIMUM A Flow Shaper to ridge, peak or deck 16" (405 mm) 22" (560 mm) B Distance from face of truss 6" (152 mm) -- C Distance between sprinklers (as measured along the slope) 3'-0" (0,9 m) 6'-0" (1,8 m) Distance to peak (as measured along the slope) -- D D GE 3'-0" (0,9 m) C N AI M GE ID PR HI D RI A B Figure 4: Design Criteria 1 Outside wall 7-6" (2,3 m) Maximum Horizontal Slope x Ma Roof Slope Maximum span 28'-0" (8,5 m) Horizontal Ma x6 3'-0" (0,9 m) Maximum On the Slope 6'-0" (1,8 m) Maximum 3'-0" (0,9 m) Minimum On the Slope Form No. F_092116 18.10.25 Rev 17.2.P65 Figure 5: Design Criteria 2-0" 28' ) 5m (8, HIP RIDGE ' (1,8 m)

Page 7 of 9 X X: 6" (150 mm) Maximum Y: 12" (300 mm) Maximum X Direct mount X Armover sprig Angle Sprig Armover Y Y Y Y Figure 6: Exposed CPVC with V-HIP Sprinklers Wet Sytems: Calculate the most demanding 5 sprinklers Dry Sytems: Calculate the most demanding 7 sprinklers and then calculate the most demanding contiguous 9 sprinklers with a maximum of 7 to be V-BB Sprinklers. Use the most demanding calculation. Ridge Ridge Valley Figure 7: V-BB and V- Sprinklers

Page 8 of 9 Wet Sytems: Calculate the most demanding 5 sprinklers Dry Sytems: Calculate the most demanding 9 sprinklers with a maximum of 7 to be V-SD sprinklers. Ridge Wall or draft curtain at ridge Figure 8: V-SD and V- Sprinklers Wet Sytems: Calculate the most demanding 5 sprinklers. Dry Sytems: Calculate the most demanding 9 sprinklers. NOTE: Wet system shown Figure 9: V- Sprinklers

Page 9 of 9 Where the total number of Attic Upright Sprinklers at the hip is 4 or less: Wet Systems - Calculate the most demanding 5 V-BB, V-SD, or V- sprinklers plus up to 2 most demanding Attic Upright sprinklers Wall or draft curtain at ridge Ridge Dry Systems - Calculate the most demanding 9 V-BB, V-SD, or V- sprinklers plus up to 2 most demanding Attic Upright sprinklers (Out of the 9, calculate a maximum of 7 V-BB sprinklers). Where the total number of Attic Upright sprinklers at the hip is greater than 4: Wet Systems - Calculate up to the most demanding 5 V-BB, or V- sprinklers plus up to 2 most demanding Attic Upright sprinklers, then calculate the most demanding region up to 1500 ft 2 (137 m 2 ) containing Attic Upright sprinklers (Region 2 below). Use the most demanding calculation. Dry Systems - Calculate up to the most demanding 9 V-BB, or V- sprinklers then add the 2 most demanding Attic Upright sprinklers, then calculate the most demanding region up to 1950 ft 2 (181 m 2 ) containing Attic Upright sprinklers. Use the most demanding calculation. 10' (3m) Region 1 with V-BB, V-HIP, or Attic Upright Sprinklers 10' (3m) Region 2 with Attic Upright or V-HIP Sprinklers 6' (1,8 m) 6' (1,8 m) 60' (18,3 m) 80' (18,4 m) 10' (3m) Figure 10: V-BB, V-, and Attic Upright Sprinklers at the Eaves Replaces Form No. F_092116 Rev 17.2 (Added P65 Warning.)