Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Similar documents
First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

Public Comment No. 32-NFPA 90A-2016 [ Section No ] Statement of Problem and Substantiation for Public Comment

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

Throughout standard remove references to the following and replace with the following:

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Second Revision No. 3-NFPA [ Section No. 2.3 ]

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur.

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 1-NFPA [ Section No ]

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

NFPA 90A. Standard for the. Installation of Air Conditioning and Ventilating Systems Edition

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement

This standard shall prescribe provisions based on minimum requirements for safety to life and property.

Second Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 6/23/ :34 AM

First Revision No. 6-NFPA [ Section No. 2.2 ]

12/21/2015 National Fire Protection Association Report

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification


Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Reference to the Smoke Damage Index (SDI) is needed as it is part of the test method.

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference

First Revision No. 7-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

CHAPTER 5 REFERENCED STANDARDS. American Architectural Manufacturers Association 1827 Walden Office Square Suite 550 Schaumburg, IL

First Revision No. 1-NFPA [ Chapter 2 ]

Public Comment No. 2-NFPA [ Section No ]

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)


DUCT SYSTEMS CHAPTER 6

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

First Revision No. 1-NFPA 30A-2015 [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

First Revision No. 15-NFPA [ Chapter 2 ]

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Second Revision No. 1 NFPA [ Chapter 2 ]

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

MEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015)

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

CHAPTER 17 STANDARDS STANDARDS Broadway, New York, NY 10018,


CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003

CHAPTER 6 [CE] REFERENCED STANDARDS

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle)

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

Public Input No. 3-NFPA [ Chapter 2 ]

CHAPTER 6 REFERENCED STANDARDS. American Architectural Manufacturers Association 1827 Walden Office Square Suite 550 Schaumburg, IL

Public Input No. 107-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

IMC Significant Changes Summary Tier I

Page 1 of 65 1/29/2016 3:12 PM. Committee Input No. 39-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 20-NFPA [ Section No ]

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ]

DUCT SYSTEMS CHAPTER 6

FIF AAA (F2014) Second Draft Meeting Web/Teleconference Meeting Agenda March 18, :00 5:00 p.m. ET

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Committee Input No. 1-NFPA [ Chapter 2 ]

NFPA 211 November 2002 ROP Copyright, 2002 NFPA

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018)

Public Comment No. 13-NFPA [ Section No ]

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12.

Report on Public Input June 2014 NFPA 101

Standard for tests for flammability of plastic materials for parts in devices and appliances

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

NFPA Technical Committee on Air Conditioning. NFPA 90A and 90B Second Draft Web/Teleconference Meeting. September 24, :00 p.m. 2:00 p.m.

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

CHAPTER 5: EXHAUST SYSTEMS

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda*

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM


Remove the "Exception" text to be consistent with direction provided in the MOS.

SAF-BCF SECOND REVISIONS WITH STATEMENTS

First Revision No. 82-NFPA [ Detail ] Submitter Information Verification Submitter Full Name: Organization:

CHAPTER 15 REFERENCED STANDARDS SECTION MC 1502 STANDARDS. Number Title section number Manual D 95 Residential Duct Systems

DUCT SYSTEMS CHAPTER 6

Throughout standard remove references to the following and replace with the following:

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

First Revision No. 1-NFPA [ Chapter 2 ]

Technical Committee on Record Protection (REA-AAA)

Technical Committee on Portable Fire Extinguishers

Public Comment No. 10-NFPA [ Chapter 2 ]

Committee Input No. 60-NFPA [ Sections , ]

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

CHAPTER 15 REFERENCED STANDARDS. Air-Conditioning, Heating and Refrigeration Institute 4100 North Fairfax Drive, Suite 200 Arlington, VA 22203

Resolution: FR-1-NFPA Statement: When tests are conducted for fire reconstruction or research the items excluded above can be included.

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ]

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009.

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

Transcription:

Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation, 2011., ASTM D93, Standard Test Methods for Flashpoint by Pensky-Martens Closed Cup Tester, 2012., ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2013a 2016., ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials, 2012a., ASTM E136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C, 2012., ASTM E2231, Standard Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning Characteristics, 2009., ASTM E2652, Standard Test Method for Behavior of Materials in a Tube Furnace with a Cone-Shaped Airflow Stabilizer, at 750 C, 2012. Submittal Date: Tue Sep 27 14:36:55 EDT 2016 : date updates Response Message: Public Comment No. 32-NFPA 90A-2016 [Section No. 2.3.2]

Second Revision No. 2-NFPA 90A-2016 [ Section No. 2.3.6 ] 2.3.6 UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors, 2013. ANSI/UL 181A, Standard for Safety Closure Systems for Use with Rigid Air Ducts, 2013. ANSI/UL 181B, Standard for Safety Closure Systems for Use with Flexible Air Ducts and Air Connectors, 2013. ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2011, Revised revised 2015. ANSI/UL 555, Standard for Safety Fire Dampers, 2006, Revised revised 2014. ANSI/UL 555C, Standard for Safety Ceiling Dampers, 2014. ANSI/UL 555S, Standard for Safety Smoke Dampers, 2014. ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, Revised revised 2013. ANSI/UL 867, Standard for Safety Electrostatic Air Cleaners, 2011, Revised revised 2013. ANSI/UL 900, Standard for Safety Air Filter Units, 2015. ANSI/UL 1598, Luminaires, 2012. ANSI/UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics, 2004, Revised revised 2013. ANSI/UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and Smoke Characteristics, 2004, Revised revised 2013. ANSI/UL 1995, Standard for Safety Heating and Cooling Equipment, 2015. ANSI/UL 2024, Standard for Safety for Cable Routing Assemblies and Communications Raceways, 2014, Revised revised 2015. ANSI/UL 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces, 2013. UL 2518, Outline of Investigation for Air Dispersion System Materials, 2005. ANSI/UL 2846, Fire Test of Plastic Water Distribution Plumbing Pipe for Visible Flame and Smoke Characteristics, 2005. ANSI/UL 2846, Standard for Fire Test of Plastic Water Distribution Plumbing Pipe for Visible Flame and Smoke Characteristics, 2014. ANSI/UL 60335-2-40, Standard for Safety of Household and Similar Electrical Appliances, Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers, 2012.

Submittal Date: Tue Sep 27 14:37:49 EDT 2016 Committee Statement: Response Message: A reference to ANSI/UL 60335-2-40 is being added as it is anticipated that ANSI/UL 1995 will be withdrawn by UL and replaced by ANSI/UL 60335-2-40 by the year 2020. Public Comment No. 36-NFPA 90A-2016 [Section No. 2.3.6]

Second Revision No. 8-NFPA 90A-2016 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2016 edition. NFPA 90B, Standard for the Installation of Warm Air Heating and Air-Conditioning Systems, 20152018 edition. NFPA 101, Life Safety Code, 2015 2018 edition. NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances, 20132016 edition. NFPA 5000, Building Construction and Safety Code, 2015 2018 edition. Submittal Date: Tue Oct 04 11:31:06 EDT 2016 : Update to current editions Response Message:

Second Revision No. 3-NFPA 90A-2016 [ Section No. 4.2.4.2.1 ] 4.2.4.2.1 The requirements of 4.3.3.1 and 4.3.3.2 shall not apply to equipment tested and listed in accordance with ANSI/UL 1995, Standard for Safety Heating and Cooling Equipment, or ANSI/UL 60335-2-40, Standard for Safety of Household and Similar Electrical Appliances, Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers. Submittal Date: Tue Sep 27 14:38:18 EDT 2016 Committee Statement: Response Message: The additional reference to ANSI/UL 60335-2-40 is being added as it is anticipated that ANSI/UL 1995 will be withdrawn by UL by the end of 2020 and replaced by ANSI/UL 60335-2-40. The reference to ANSI/UL 60335-2-40 has been added to 2.3.6, UL Publications. Public Comment No. 37-NFPA 90A-2016 [Section No. 4.2.4.2.1]

Second Revision No. 7-NFPA 90A-2016 [ Section No. 4.3.3.1 [Excluding any Sub-Sections] ] Pipe and duct insulation and coverings, duct linings, vapor retarder facings, adhesives, fasteners, tapes, and supplementary materials added to air ducts, plenums, panels, and duct silencers used in duct systems, unless otherwise provided for in 4.3.3.1.1 or 4.3.3.1.2, shall have, in the form in which they are used, a maximum flame spread index of 25 without evidence of continued progressive combustion and a maximum smoke developed index of 50 when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or with ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials. Pipe and duct insulation and coverings, duct linings and their adhesives, and tapes shall use the specimen preparation and mounting procedures of AASTM ASTM E2231, Standard Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning Characteristics. Submittal Date: Tue Sep 27 14:48:15 EDT 2016 : Editorial correction of document title. Response Message:

Second Revision No. 5-NFPA 90A-2016 [ Section No. A.3.3.9 ] A.3.3.9 Air Inlet. For further discussion of various types of air inlet devices, see ASHRAE Handbook Fundamentals, Chapter 32 20, Space Air Diffusion., in the 2013 edition of ASHRAE Handbook Fundamentals. Submittal Date: Tue Sep 27 14:40:57 EDT 2016 Committee Statement: Response Message: Correction to latest version of referenced publication ASHREA Fundamentals. Chapter changed from 32 to 20. Public Comment No. 38-NFPA 90A-2016 [Section No. A.3.3.9]

Second Revision No. 6-NFPA 90A-2016 [ Section No. C.1.2.3 ] C.1.2.3 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2015a 2016. ASTM E136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C, 2012 2016. AASTM ASTM E2231, Standard Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning Characteristics, 2015. ASTM E2652, Standard Test Method for Behavior of Materials in a Tube Furnace with a Cone-Shaped Airflow Stabilizer, at 750 C, 2012 2016. Submittal Date: Tue Sep 27 14:44:02 EDT 2016 : date updates Response Message: Public Comment No. 33-NFPA 90A-2016 [Section No. C.1.2.3]