Multi Inverter Air Conditioning Condensing Units - Summary Model Description Nominal Max of Cooling Inverter No. Heating of (kw) Fan Condensing (kw) Coils Unit ECO18MS2 Twin Multi Inverter 5kW 5.2 6.1 Detailed Specification ECO30MS3 Triple Multi Inverter 8kW 7.8 8.75 Detailed Specification ECO30MS4 Quad Multi Inverter 8kW 7.9 8.8 Detailed Specification ECO36MS4 Quad Multi Inverter 11kW10.5 11.1 Detailed Specification Note: Due to our policy of innovation some specifications may be changed without notification. These unit contain F-Gas and is govern by F-Gas regulations. All F-Gas must be handle by qualified F-Gas engineers. ECO18MS2 / ECO30MS3 specifications ECO30MS4 specifications ECO36MS4 specifications 1 / 21
7000~ Multi Inverter Air Conditioning - Condensing Units Outdoor Model ECO18MS2 ECO30MS3 Indoor Units CombinationSingle Twin Single Power supply Ph-V-Hz 1Ph,220-240V~,50Hz 1Ph,220-240V~,50Hz Cooling Capacity Btu/h 2 / 21
Capacity W -- 5200 Input W 1000~1200 1620 Rated current A 4.5~5.0 7.5 EER w/w -- 3.21 3 / 21
10000 Multi Inverter Air Conditioning - Condensing Units Heating Capacity Btu/h 4 / 21
Capacity W -- 6100 8750 Input W 1050~1250 1670 Rated current A 5.0~6.0 7.6 COP w/w -- 3.65 Max. input W 2150 3100 Max. current A 10.5 16.0 Compressor Type Rotary inverter Rotary inverter 5 / 21
126/10 Multi Inverter Air Conditioning - Condensing Units Capacity Btu/h 19277 22000 Input W 1610 1630 Rated current(rla) A 8.1 8.4 Locked rotor Amp(LRA) A 50 41 Outdoor fan motor Input W Capacitor uf 2.5 2.5 Speed r/min 760/600 760/600 Outdoor air flow m3/h 2500 2500 Outdoor noise level db(a) 53 55 6 / 21
845X6 2 X Multi Inverter Air Conditioning - Condensing Units Outdoor unit Dimension(W*H*D) mm Packing (W*H*D) mm 965X755X395 965X755X395 Net/Gross weight Kg 60/64 62/66 Refrigerant type and charge g R410A,1700 R410A, 2100 Design pressure(hi/lo) MPa 4.2/2.5 4.2/2.5 Refrigerant piping Liquid side/ Gas side mm(inch) 7 / 21
Transfer Connector (9.53 ~ 12.7) 2 Max. refrigerant pipe lengthm 30m total (20m per indoor 45m unit) total (20m per in Max. difference in level m 10(each indoor unit) 10(each indoor unit) Connection wiring No No Plug type No No Thermostat type Electronic control Electronic control Operation temp C 17-30 17-30 8 / 21
Ambient temp C 0~50(cooling); -15~24(heating) 0~50(cooling); -15~24(he Note: Due to our policy of innovation some specifications may be changed without notification. These unit contain F-Gas and is govern by F-Gas regulations. All F-Gas must be handle by qualified F-Gas engineers. ECO18MS2 / ECO30MS3 specifications ECO30MS4 specifications ECO36MS4 specifications Outdoor Model ECO30MS4 Indoor Units CombinationSingle Twin Triple Quad Power supply Ph-V-Hz 1Ph,220-240V~,50Hz Cooling Capacity Btu/h 9 / 21
7000~ Multi Inverter Air Conditioning - Condensing Units Capacity W -- -- Input W 1034~2054 1730~2803 2634~2977 Rated current A 4.7~9.4 7.92~12.8 12.0~13.5 10 / 21
8000~ Multi Inverter Air Conditioning - Condensing Units EER w/w / / Heating Capacity Btu/h 11 / 21
Capacity W -- -- Input W 1056~2220 1731~3010 2439~3155 Rated current A 4.8~11.0 8.0~13.6 11.2~14.4 COP w/w / / Max. input W 4800 Max. current A 21 Compressor Type Rotary inverter Capacity Btu/h 7130 Input W 2200 Rated current(rla) A 9.7 Locked rotor Amp(LRA) A 45 Outdoor fan motor Input W 12 / 21
144(H 895X8 Multi Inverter Air Conditioning - Condensing Units Capacitor uf 2.5uF/450V Speed r/min 780/600 Outdoor air flow m3/h 3500 Outdoor noise level db(a) 57 Outdoor unit Dimension(W*H*D) mm Packing (W*H*D) mm 1043X915X395 Net/Gross weight Kg 78/82 Refrigerant type and charge g R410A, 2400 Design pressure(hi/lo) MPa 4.2/2.5 Refrigerant piping Liquid side/ Gas side mm(inch) 13 / 21
4 x Multi Inverter Air Conditioning - Condensing Units Transfer Connector (9.53 ~ 12.7) 3 Max. refrigerant pipe lengthm 40m total (20m per indoor unit) Max. difference in level m 10(each indoor unit) Connection wiring No Plug type No Thermostat type Electronic control Operation temp C 17-30 Ambient temp C 0~50(cooling); -15~24(heating) Note: Due to our policy of innovation some specifications may be changed without notification. 14 / 21
These unit contain F-Gas and is govern by F-Gas regulations. All F-Gas must be handle by qualified F-Gas engineers. ECO18MS2 / ECO30MS3 specifications ECO30MS4 specifications ECO36MS4 specifications Outdoor Model ECO36MS4 Indoor Units CombinationSingle Twin Triple Power supply Ph-V-Hz 1Ph,220-240V~,50Hz Cooling Capacity Btu/h 15 / 21
Capacity W -- -- Input W 1334~2384 1730~3403 2 Rated current A 5.8~7.8 7.5~10.7 9 EER w/w / / 16 / 21
Heating Capacity Btu/h 17 / 21
Capacity W -- -- Input W 1656~2520 1931~3519 2 Rated current A 7.2~11.0 9.3~14.9 1 COP w/w / / Max. input W 4900 Max. current A 22.5 Compressor Type Rotary inverter Capacity Btu/h 9860 Input W 3080 Rated current(rla) A 13.5 Locked rotor Amp(LRA) A 67 Outdoor fan motor Input W 18 / 21
Capacitor uf 10uF/450V Speed r/min 760/620 Outdoor air flow m3/h 5800/4800 Outdoor noise level db(a) 61 Outdoor unit Dimension(W*H*D) mm Packing (W*H*D) mm 1120X1100X435 Net/Gross weight Kg 86/90 Refrigerant type and charge g R410A, 2700 Design pressure(hi/lo) MPa 4.2/2.5 Refrigerant piping Liquid side/ Gas side 19 / 21
Transfer Connector (9.53 ~ 12.7) Max. refrigerant pipe length m 20(each indoor unit) Max. difference in level m 10(each indoor unit) Connection wiring No Plug type No Thermostat type Electronic control Operation temp C 17-30 Ambient temp C 0~50(cooling); -15~24(heating) 20 / 21
Note: Due to our policy of innovation some specifications may be changed without notification. These unit contain F-Gas and is govern by F-Gas regulations. All F-Gas must be handle by qualified F-Gas engineers. 21 / 21