INSTALLATION MANUAL. Domestic hot water tank with UK kit for air to water heat pump system EKHTS200AC EKHTS260AC EKHTSU200AC EKHTSU260AC EKUHWHTA

Similar documents
INSTALLATION MANUAL. Domestic hot water tank for air to water heat pump system EKHTS200A EKHTS260A EKHTSP200AA EKHTSP260AA

INSTALLATION MANUAL. Domestic hot water tank with option kit for air to water heat pump system EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 EKUHWB

INSTALLATION MANUAL. Domestic hot water tank for air to water heat pump system EKHWS150B3V3 EKHWS200B3V3 EKHWS300B3V3 EKHWS200B3Z2 EKHWS300B3Z2

INSTALLATION MANUAL. Domestic hot water tank for air to water heat pump system EKHWE150A3V3 EKHWET150A3V3 EKHWE200A3V3 EKHWE300A3V3

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

Unvented Electric Water Heater 10/15 litre Undersink

Powerflow Unvented water heater

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

BOILING UNIT REDITAP. Installation and User Guide. IMPORTANT: This booklet should be left with the user after installation and demonstration

INSTALLATION AND OPERATION MANUAL

INSTALLATION MANUAL. RD SERIES Digital Electric Water Heater Wall-hung Unvented

MW & EW 10 & 15 Litre Unvented Water Heaters HANDBOOK. IMPORTANT: This booklet should be given to the customer after installation and demonstration.

WH-TD20B3E5 WH-TD30B3E5

ZIP Varipoint III. Installation, Maintenance and User Instructions. Models VP303, VP503 VP803, VP953 direct unvented water heaters. Issued August 2008

Speedflow Undersink Unvented Water Heater. Models SF05K, SF10K and SF15K. Instruction Manual

TABLE OF CONTENTS EKHTS-A

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

SEALED THERMAL STORE

Zip Econoboil. On wall boiling water. Installation instructions & user manual. Model number: ,

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Thermostatic bar mixer valve with adjustable head Installation guide

Furrows Business Park, Haybridge Road Wellington, Telford, Shropshire TF1 2FE

TH100 Three in One Instant Hot Water Tap

Installation and User Instructions HS10U, HS15U.

Unvented water heater

Installation, Operating and Servicing Instructions

OPERATION MANUAL. Daikin Altherma indoor unit EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1

AUTOMATIC ICE-CUBE MAKER

1. Take the hoses and elbow out of the holders, depending on model. max. 100 cm. min. * cm

Mira Sport Max with Airboost

Unvented Direct & Indirect Hot Water Cylinders (400L L)

Alpha CombiMax 350 and 600

Unvented Direct & Indirect Hot Water Cylinders (400L L)

ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for unvented systems.

Tempest TP420/180 Electric Pressure Washer

UK-specific appendix to Installation instructions DHP-A DHP-A Opti DHP-AQ Maxi DHP-H DHP-H Opti DHP-H Opti Pro DHP-L DHP-L Opti DHP-L Opti Pro

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

BF5000NT BF5000 EF2604 SF2603 DF2603

Mira Reflex Thermostatic Bar Valve

Avensys Avensys FIN EST SLO RUS UAE

BEFORE USING THE DISHWASHER/CONNECTIONS

Installation and User Instructions Aquaheat Unvented Water Heaters Models: AH30H

Moisture inside the drum is due to final testing.

LC Series - Light Commercial Pump Station Installation and Operation Manual

Kinetic. Logic. Astin. THERMOSTATIC INLINE CONTROL SHOWER VALVES Installation & aftercare instructions. Please retain for future reference

User and Installation Instructions. Wall Mounted Water Boiler WMB3F/B and WMB3F/W IS435 ECN3461

Flow Factor ~

USER MANUAL. Fan coil units FWC06B7TV1B FWC07B7TV1B FWC08B7TV1B FWC09B7TV1B FWC06B7FV1B FWC07B7FV1B FWC08B7FV1B FWC09B7FV1B. Cover Cover.

WAIWELA SERIES-TWO WATER HEATERS

BL Series INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Inta City Concealed Shower Mixing Valve CT80010CP

SEA FROST BD 12 OR 24-VOLT D.C. AIR-COOLED SYSTEM

INSTALLATION MANUAL. Decoration Panel Provided with Filter Auto Cleaning Function Self Cleaning decoration panel BYCQ140D7GW1 BYCQ140D7GFW1

AUTOMATIC MODULAR ICE-CUBE MAKER

Closomat Lima Vita installation & user guide

541D19 SERIES. Technical Manual. A Division of Aquion Partners L.P.

Installation Instructions

MIX Boiler & Font Range Service Manual

Moisture inside the drum is due to final testing.

OWNER S MANUAL. How to install, operate and maintain your. EcoWater Systems Automatic Sediment Filter. EcoWater Systems Poland

INSTALLATION GUIDE NZ AU C

Beautifully Traditional

KYROS INSTALLATION MANUAL KYROS. Digital Electric Water Heater Wall-hung Unvented

INTA ION MODERN BAR / BATH SHOWER MIXER CP

CONTENTS CONSIDERATIONS. General Plumbing Component Connection ILLUSTRATION. Control System CONFIGURATION. Voltage Verification CONNECTION

MIDAS. Installation instructions 110/220

s y ens Av Avensys FIN EST RUS SLO RUS UAE

WC2 & WC3 Installation & Maintenance Instructions

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:

Aquamixa. Thermo. Thermostatic shower valve with manual bath fill

Enzo Concealed Shower Mixing Valve

IMPORTANT SAFETY INFORMATION

Thermostatic mixing valves with interchangeable cartridges

Food Waste Disposer Instruction Manual

installation INSTRUCTIONS

NEPTUN I Sole cleaning unit Art.-No.:

INSTALLATION MANUAL ESM9+ / ESM11+ / ESM15+

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

ADVANCE STAINLESS STEEL UNVENTED HOT WATER SYSTEMS

Quantum. Installation, User and Service Manual. Hot Spring

INSTRUCTION MANUAL Model: SU3022

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions

General safety precautions English

16 OUTDOOR MISTING FAN

Safety, Operation and Maintenance Manual with Parts List

Parasitic Cysts - Cryptosporidium and Giardia, Chemicals, Heavy Metals, Dissolved Salts, Offensive Tastes and Odours, Sediment, Dirt,

Autofill wall mounted water. boiler. Getting the best from your water. boiler. Please read and keep these instructions

Dyna-Form Air. Alternating Pressure Relief Overlay System

DOUBLE DISHDRAWER TM DISHWASHER

Installation Manual CARBONATOR With Plain-Water Booster

Powerstock Storage Tank

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd

Viking Installation Guide

Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS

Transcription:

INSTALLATION MANUAL Domestic hot water tank with UK kit for air to water heat pump system EKHTS00AC EKHTS0AC EKHTSU00AC EKHTSU0AC EKUHWHTA

x x x 0 mm x x x B A C 0 H 0 Ø0 0 0 0 00 00 0 0 >0 >0 A EKHBRD* EKHVMR/YD* EKHVH/X* A >0 >0 >00 >00

EKHTSU00AC EKHTSU0AC EKUHWHTA Domestic hot water tank with UK kit for air to water heat pump system CONTENTS Page INTRODUCTION Introduction... General information... Scope of this manual... Model identification... Accessories... Accessories supplied with the domestic hot water tank... Accessories supplied with the EKUHWHTA kit for the domestic hot water tank... Optional equipment... Overview of the unit... Main components... Outlook diagram... Installation of the EKHTSU domestic hot water tank... Installation guidelines... Installing and commisioning the domestic hot water tank... Installation of the EKUHWHTA kit on the domestic hot water tank.. Piping requirements... Installation procedure of the EKUHWHTA kit... Maintenance... Descaling... Draining... Troubleshooting... General guidelines... General symptoms... Technical specifications... Domestic hot water tank specifications... READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE. PLEASE LEAVE THIS MANUAL WITH THE EKHWSU DOMESTIC HOT WATER TANK AFTER INSTALLATION. IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL. IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION. THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED FOR INDOOR INSTALLATION ONLY AND FOR AMBIENT TEMPERATURES RANGING C~0 C. General information Thank you for purchasing this domestic hot water tank. The domestic hot water tank must be installed by a licensed technician and be installed in compliance with instructions as of subject in this manual, all current legislation, codes of practice and regulations governing the installation of unvented hot water cylinders in force at the date of installation. This installation is subject to building regulation approval, notify Local Authority of intention to install. The EKHTS domestic hot water tank can be connected to EKHBRD, EKHVMRD, EKHVMYD, EKHVH and EKHVX indoor units. The domestic hot water tank is available in two sizes: approximately 00 and 0 litre. All models can be mounted on top of the indoor unit. For installation of the domestic hot water tank on the floor next to the indoor unit, the dedicated EKFMAHTB connection kit is required. In case of EKHBRD*AA* indoor unit, the kit EKMKHT is required. Scope of this manual This installation manual describes the procedures for installing and connecting the EKHTSU domestic hot water tank together with the EKUHWHTA kit. Model identification Domestic hot water tank EK HTS U 00 AC Series Identification of type U = Special version for United Kingdom only Hot water Tank Stainless steel European Kit The English text is the original instruction. Other languages are translations of the original instructions. EKHTSU000AC EKUHWHTA PW0-0.00

ACCESSORIES Main components Accessories supplied with the domestic hot water tank See figure. Flexible hose of heat exchanger coil Hot/cold water flexible hose Clamp Knockout hole assembly (grommet tie-wraps screws) Unpacking instruction sheet -way valve assembly (body motor clamps ) T-piece B Accessories supplied with the EKUHWHTA kit for the domestic hot water tank B x x x x x 0 x x x x x N M F Pressure reducing valve Expansion relief valve Blind stop plastic screw-on closing caps for pressure reducing valve Reducing coupler mm - mm Expansion vessel of litres Tundish Elbow/Drain valve mm x / Male BSP Adaptor mm x / Female BSP T-piece mm x mm x mm 0 Instruction sheet Optional equipment EKFMAHTB Connection kit for installation of the domestic hot water tank on the floor next to the indoor unit. Refer to the installation manual of the kit for more details. EKMKHT In case the EKHTS*AC domestic hot water tank is to be installed on top of an EKHBRDAA series indoor unit, the additional EKMKHT kit is required. Refer to the instruction sheet of the kit for more details. P G J G J H L E A K A E K OVERVIEW OF THE UNIT The total system (indoor unit and outdoor unit) is designed for combination with a Daikin domestic hot water tank. In case another tank is being used in combination with the Daikin indoor unit, Daikin cannot guarantee neither good operation nor reliability of the system. For those reasons Daikin cannot give warranty of the system in such case. A B E F G Hot water out connection (G /" Female) Temperature and pressure relief valve H J Heat exchanger coil Return outlet connection to the mainindoor unit at the bottom of the tank (quick coupling) Recirculation connection (G /" Male) K Cold water in connection (G /" Female) Thermistor socket Flow inlet connection from the main indoor unit at the bottom of the tank (quick coupling) L M N P Thermistor Anode Casing Knockout holes for water piping EKHTSU000AC EKUHWHTA PW0-0.00

Safety devices The domestic hot water tank relief valve connections may not be used for other purpose. This domestic hot water tank can only be used with an EKHBRD, EKHVMRD, EKHVMYD, EKHVH or EKHVX indoor unit. Temperature and pressure relief valve The temperature and pressure relief valve prevents excessive water temperature (> C) and excessive water pressure ( 0 bar) in the domestic hot water tank. Expansion relief valve (EKUHWHTA kit) The pressure relief valve prevents excessive water pressure ( bar) in the water circuit. Thermal protector The indoor unit is equipped with a thermal protector. The thermal protector is activated when the temperature becomes too high. When activated, the protector has to be reset on the indoor unit by pressing it (for access, remove the decoration panels like indicated in the manual of the indoor unit). Switch off the power supply before opening the decoration panels of the indoor unit. NOTE Refer to "Installation of the EKUHWHTA kit on the domestic hot water tank" on page for connection of other safety devices in accordance with relevant local and national regulations. Outlook diagram 0 B >0 0 D C >0 >0 A >00 H 0 Ø0 0 0 H 0 00 00 Hot water out connection (G /" Female) Cold water in connection (G /" Female) Hot water out connection at the bottom of the tank (quick coupling) Cold water in connection at the bottom of the tank (quick coupling) Recirculation connection (G /" Male) Flow inlet connection from the main indoor unit (quick coupling) Return outlet connection to the main indoor unit (quick coupling) -way valve Flow inlet connection from the main indoor unit at the bottom of the tank (quick coupling) 0 Return outlet connection to the main indoor unit at the bottom of the tank (quick coupling) Knockout holes for water piping Levelling feet Temperature and pressure relief valve ( mm Male) Domestic hot water tank model H H EKHTSU00AC 00 mm mm EKHTSU0AC mm 0 mm EKHTSU000AC EKUHWHTA PW0-0.00

INSTALLATION OF THE EKHTSU DOMESTIC HOT WATER TANK Installation shall be done by a licensed technician, the choice of materials and installation shall comply with local and national regulations. The equipment is not intended for use in a potentially explosive atmosphere. Domestic hot water quality must be according to EU directive / EC. For safety reasons, it is not allowed to add any kind of glycol to the water circuit. To avoid stagnation of water, it is important that the storage capacity of the domestic hot water tank meets the daily consumption of domestic hot water. In cases where during longer periods of time there is no consumption of hot water, the equipment must be flushed with fresh water before usage. The disinfection function provided on the equipment is specified in the operation manual of the indoor unit. It is advised to avoid long runs of piping between the domestic hot water tank and the hot water end point (shower, bath,...) and to avoid dead ends. The installation must be in compliance with local and national regulations and may require additional hygienic installation measures. For compliance with UK Building Regulations, thermostatic mixing valves must be installed. Immediately after installation, the domestic hot water tank must be flushed with fresh water. This procedure must be repeated at least once a day the first consecutive days after installation. If required by relevant local and national regulations, connect a recirculation pump in between the hot water end point and the recirculation connection of the domestic hot water tank. Installing and commisioning the domestic hot water tank Installing the hot water tank on top of the indoor unit Unpack the domestic hot water tank according to the instructions mentioned on the unpacking instruction sheet. Check if all domestic hot water tank accessories are enclosed (see "Accessories" on page ). Remove the decoration panels and top plates of the indoor unit. Take away the decoration panels by removing the bottom screws and then unhitching the panel. Mount the top plate of the indoor unit on the domestic hot water tank module. x x x Connect the -way valve A Only for EKHBRD and EKHVMR/YD units. Remove both parts of the drain plate on top of the indoor unit before installing the -way valve. x x x Recirculation connection Hot water connection Shower Recirculation pump Installation guidelines Keep in mind the following guidelines when installing the domestic hot water tank: The installation location is frost-free. Standard installation location of the domestic hot water tank is on top of the indoor unit. B Only for EKHVH/X indoor units. Remove the indoor unit switch box by unscrewing fixations and by then sliding the switch box aside without disconnecting any wiring connections. If available service space to left and/or right side is limited, carefully consider all indoor module installation steps first. The domestic hot water tank can be floor mounted as well. In that case, the dedicated EKFMAHTB connection kit for installation of the domestic hot water tank next to the indoor unit is required and to be ordered separately. Locate the domestic hot water tank in a suitable position to facilitate ease of maintenance. Refer to the grey-coloured zones indicated in the outlook diagram figure and to the installation manual of the indoor unit. To avoid back siphonage it is advised to install a non-return valve on the water inlet of the domestic hot water tank in accordance with local and national regulations. Take care that in the event of a leak, water can not cause any damage to the installation space and surroundings. If installing an EKHTSU* domestic hot water tank, installing the kit EKUHWHTA is obligatory. Refer to the UK Building Regulation G. x MAX. cm EKHTSU000AC EKUHWHTA PW0-0.00

Installation position. The -way valve must be installed in the indoor unit. From indoor unit To domestic hot water tank To room heating Install the -way valve body in the pipework. Avoid contact between hot piping and electrical wiring at all time. Refer to the figure below before making the connection. For EKHBRD indoor units only. Unpack the -way valve body and -way valve motor. Verify that following accessories are provided with the motor. A B 0 Sleeve Screw Valve motor cover Turn knob Put the sleeve on the valve and turn the valve so that the sleeve is positioned according to the figure below. C If the valve is not positioned in this way before mounting the motor, the valve will give way to both domestic water and room heating during operation. EKHTSU000AC EKUHWHTA PW0-0.00

For EKHVMRD indoor units only. For EKHVMYD indoor units only. A A EKHTSU000AC EKUHWHTA PW0-0.00

For EKHVH/X indoor units only. Push the motor on the sleeve. Make sure not to rotate the sleeve during this action, so as to maintain the valve position as set during step. Put the turn knob on the valve motor cover as shown below. A Room heating Domestic hot water tank Make sure that the turn knob is completely pushed in to allow the turn knob being operated automatically by the unit. If the turn knob is lifted slightly, manual operation is possible. Perform the wiring in the indoor unit switch box in accordance with the following figure: (make sure power supply is switched off) 0 EKHBRD / EKHVMR/YD EKHVH/X B 0 XM XM 0 -way valve -way valve BLU BLK BRN BRN BLU BLK N Y L L N Y C Make sure to follow the appropriate wiring routing inside of the unit (this wiring routing can be found in the installation manual of the indoor unit). Refer also to the wiring diagram delivered with the indoor unit. Remove the top front decoration panel of the tank module as indicated in the figure. x Mount the tank module on top of the indoor unit using the lifting holes. Because of the weight of the domestic hot water tank, it is advised to handle and lift it with two persons. Refer to the figure below and make sure that the positioning guides on all four corners of the domestic hot water tank bottom perfectly match on the four positioning guides of the indoor unit top when mounting the tank module. EKHTSU000AC EKUHWHTA PW0-0.00

Connect the flexible hoses as indicated in figure, figure, figure and figure. The flexible hoses with quick coupling connections on both sides must be connected to the coil connection as indicated (for EKHBRD units see figure, for EKHVH/X units see figure, for EKHVMRD units see figure, for EKHVMYD units see figure ). The flexible hoses with quick coupling connection on one side and threaded connection coupling on the other side must be connected to the hot water outlet and cold water inlet (they have to be routed out from the rear plate as indicated in figure, figure, figure and figure ). Depending on the installation location (left or right side installation), punch the required right or left knockout holes out of the rear plate. Apply the grommet to the edges of the knocked out holes to protect the flexible hoses. If the recirculation connection is used, connect a tube with threaded connection to this hole and guide it through a hole in the rear plate too (for EKHBRD units see figure, for EKHVH/X units see figure, for EKHVMRD units see figure, for EKHVMYD units see figure ). 0 Connect the thermistor wire to the indoor unit switch box. Make sure power supply is switched off. Refer to the wiring diagram delivered with the indoor unit. For EKHBRD and EKHVMR/YD units only For EKHVH/X units only Hot water out connection (G /" Female) Cold water in connection (G /" Female) Hot water out connection at the bottom of the tank (quick coupling) Cold water in connection at the bottom of the tank (quick coupling) Recirculation connection (G /" Male) Flow inlet connection from the main indoor unit (quick coupling) Return outlet connection to the main indoor unit (quick coupling) -way valve Flow inlet connection from the main indoor unit at the bottom of the tank (quick coupling) 0 Return outlet connection to the main indoor unit at the bottom of the tank (quick coupling) It is recommended to install a shut off valve to the cold water inlet. Close this shut off valve during periods of absence to avoid damage to the surroundings in case water should leak. Fix the side bottom decoration panels of the domestic hot water tank to the indoor unit. x x x x Decoration panel Quick fixation hole Fasten with screws Connect the accessories supplied with the EKUHWHTA kit as explained in "Installation of the EKUHWHTA kit on the domestic hot water tank" on page. EKHTSU000AC EKUHWHTA PW0-0.00

The distance between the thermistor cable and power supply cable must always be at least mm to prevent electromagnetic interference on the thermistor cable. Plug the thermistor cable connector in the socket XA (EKHBRD EKHVMR/YD (AP)) or XA (EKHVH/X (AP)) on the PCB. ~ > mm -way valve NYL BLU BLK BRN Fix the cables to the cable tie mountings with cable ties to ensure strain relief. When routing out cables, make sure that these do not obstruct mounting of the indoor unit cover. Note: only relevant field wiring is shown. For EKHBRD indoor units only. XM ~ > mm -way valve NYL BLU BLK BRN XM AP XA XA AP For EKHVMR/YD indoor units only. >0 mm -way valve N YL BLU BLK BRN XA AP XM AP XM EKHTSU000AC EKUHWHTA PW0-0.00

For EKHVH/X indoor units only. Only for EKHBRD and EKHVMR/YD units: reattach the drain plate on the indoor unit. > mm -way valve N YL BLU BLK BRN Commisioning The domestic hot water tank coil must be filled with water at the indoor unit water inlet. This to avoid that dirt enters the system. Follow the next steps to fill up the tank: Open each hot water tap in turn to expel air from the system pipe work. XM Open the cold water supply valve. Make sure the decoration panels of both the domestic hot water tank and the indoor unit are aligned. Close all water taps after all air is expelled. Check for leaks. XM 0 Manually operate the temperature and pressure relief valve to ensure free water flow through the discharge pipe (turn knob counterclockwise). Refer to "Main components" on page for location of the temperature and pressure relief valve. Reattach the temperature and pressure relief valve insulation piece, and both front decoration panels of the domestic hot water tank. x XB XA AP Reattach the front decoration panel of the indoor unit. x x Decoration panel Insulation piece Temperature and pressure relief valve insulation piece Installing the hot water tank by the side of the indoor unit Refer to the manual delivered with the kit EKFMAHTB. 0 EKHTSU000AC EKUHWHTA PW0-0.00

INSTALLATION OF THE EKUHWHTA KIT ON THE DOMESTIC HOT WATER TANK All pipework and fittings must be flushed free of all flux and debris prior to the fitting of controls of this kit. Failure to do this may cause irreparable damage to the controls. All cautions as under chapter "Installation of the EKHTSU domestic hot water tank" on page remain of extreme importance and are equally valid in this chapter. 00 mm 0 D >00 mm D H C >00 mm 00 mm D D Fixed grating Trapped effluent water Piping requirements Tundish Install the tundishes in a vertical position within a maximum of 00 mm away from the temperature and pressure relief valve on the domestic hot water tank and the expansion relief valve included in the EKUHWHTA kit. Tundish pipework Tundish pipework must be mm metal pipe with a minimum vertical length of 00 mm below the tundish. Maximum permitted (equivalent) length of mm pipework is m. Each bend or elbow is equivalent to 0. m of pipework. All pipework must have a continuous fall. Sizing of copper discharge pipe D for common temperature relief valve outlet sizes Valve outlet size Discharge pipe size D Discharge pipe size D from tundish Maximum resistance allowed, expressed as a length of straight pipe (i.e. no elbows or bends) Resistance created by each elbow or bend mm mm mm up to m 0. m EKHTSU000AC EKUHWHTA PW0-0.00

Requirements to discharges Discharge piping, tundish, drain valves, etc. must be positioned away from any electrical components. The discharge pipe away from the tundish must terminate in a safe, visible position without forming any risk to persons in the vicinity. NOTE If in any doubt, refer to Building Regulation G. Installation procedure of the EKUHWHTA kit Locate the domestic hot water tank in a suitable position to facilitate the installation of water supply, discharge fittings and pipework. It is therefor recommended to first read through this whole procedure. Refer to the figure on the facing page at the start of this chapter for full understanding of next procedure steps. Pre-assembly To access the tundish connected to the temperature and pressure relief valve, the front decoration panels need to be removed. Do not install any valves between the domestic hot water tank and relief valves/expansion vessel. Pre-assemble the pressure reducing valve (part of this kit, refer to page ) by mounting the blind stop and the black plastic screw-on closing caps (part of this kit), so that the pressure reducing valve is ready for installation. The black plastic plugs in the pressure reducing valve body are pressure gauge connections to enable pressure monitoring to be carried out, should the system develop a fault. It is recommended that these be accessible (the pressure reducing valve has two - only one need be accessible). Mount the reducing coupler (part of this kit) in between the pressure reducing valve and the expansion relief valve (part of this kit) using a length of copper tube Ø mm (to the pressure reducing valve) and a length of copper tube Ø mm (to the expansion relief valve). Water main in Fit the elbow/drain valve (part of this kit) in the cold water flexible hose coming out of the rear plate. Pay attention to position the drain valve in such a way that 0% of the domestic hot water tank can be drained. Position both, the pressure reducing valve with integrated non return valve and line strainer and the expansion relief valve (parts and of this kit - see also procedure step ) as high as possible and connect it to the water mains inlet. The expansion relief valve must be installed with a horizontal discharge. If fitted inverted, debris may be deposited on the seat and cause fouling of the seat when the valve operates. Check direction of flow arrows. Fit a length of copper tube Ø mm (field supply) in between the elbow/drain valve (procedure step ) and the pressure reducing valve. Make sure to provide for a connection on this pipe to the expansion vessel (part of this kit). Fit a length of copper tube Ø mm (field supply) inbetween the T-piece (part of this kit) and the pre-assembled expansion vessel (procedure steps and ). Discharge Remove the front decoration panels of the domestic hot water tank. Install the first tundish (part of this kit) in a vertical position within a maximum of 00 mm away from the temperature and pressure relief valve. Use the foreseen space inside the domestic hot water tank module as indicated in the figure. Use tie-wraps to firmly fix the tundish. 0 Connect a metal discharge pipe Ø mm (field supply) from the temperature and pressure relief valve to the tundish ( 00 mm). Install the second tundish (part of this kit) in a vertical position within a maximum of 00 mm away from the expansion relief valve. Connect a metal discharge pipe Ø mm (field supply) from the expansion relief valve to the tundish ( 00 mm). Connect discharge pipes from both tundishes. Refer to paragraph "Tundish pipework" on page. All pipework must have a continuous fall and be fitted conform to the requirements of the Building Regulation G. Ø mm Ø mm After completing the installation After completing the installation, the installer has to fill in the warning label on the tank with indelible ink. The warning label is located on the lower front decoration panel inside. Pre-assemble the adaptor and expansion vessel (parts and of this kit) so that the expansion vessel is ready for installation. Remove the insulation piece to get acces to the factory fitted temperature and pressure relief valve. Manually operate the temperature and pressure relief valve to ensure free water flow through discharge pipe. Turn knob left. Do not remove Contact the installer. Should the system develop a fault, switc contact the installer. This installation is subject to building regulation approval, notify Local Authority of intention to install. Use only manufacturer's recommended spare parts. Contact your local Daikin dealer. Installed by name address tel. No. completion date EKHTSU000AC EKUHWHTA PW0-0.00

MAINTENANCE In order to ensure optimal availability of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals. NOTE The described checks must be executed at least once a year by a licensed technician. Checking for leaks To be able to check for leaks, first remove the front decoration panel of the indoor unit and then the front panels of the tank module. Temperature and pressure relief valve Check for correct operation of the temperature and pressure relief valve. Remove the front decoration panels and insulation piece. Manually operate the temperature and pressure relief valve to ensure free water flow through the discharge pipe. Turn knob left. Pressure reducing valve with integrated non return valve and line strainer Depending on local water conditions, annual inspection of the integral line strainer, pressure reducing valve cartridge and seating may be necessary. - Unscrew the retaining nut of the valve. The complete operating mechanism, including the strainer can be removed. - Clean the filter mesh and cartridge under running water. - Replace the cartridge, ensuring that the strainer is correctly located and reassemble the unit. Expansion relief valve Check for correct operation of the expansion relief valve. Manually operate the expansion relief valve to ensure free water flow through discharge pipe. Turn knob left. Depending on local water conditions, annual inspection of the expansion relief valve cartridge and seating may be necessary. - Unscrew the expansion relief headwork from valve body. - Clean valve seat face and seating - do not scratch or damage either seat face or seating. - Refit in reverse order. Do not over tighten. Descaling Each inspection has to be carried out by a licensed technician and not by the user. Before carrying out any maintenance or repair activity, always switch off the circuit breaker on the supply panel, remove the fuses or open the protection devices of the unit. Make sure that before starting any maintenance or repair activity, also the power supply to the outdoor unit is switched off. The flexible hoses are designed for a year lifetime. It is adviced to replace them after this period. Depending on the water quality and set temperature, scale can deposit on the heat exchanger inside the domestic hot water tank and can restrict heat transfer. For this reason, descaling of the heat exchanger may be required at certain intervals. When using means for descaling, it must be ensured that the water quality remains compliant with the requirements of EU directive //EC. Draining Follow the next steps to drain the tank: Switch off the power supply. Turn off the cold water supply valve. Open the hot water taps. Open the drain valve. TROUBLESHOOTING This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit. General guidelines Before starting the trouble shooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring. When carrying out an inspection on the supply panel or on the switch box of the unit, always make sure that the circuit breaker of the unit is switched off. When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it. Under no circumstances safety devices may be bridged or changed to a value other than the factory setting. If the cause of the problem cannot be found, call your local Daikin dealer. General symptoms Symptom : No water flow from hot taps POSSIBLE CAUSES The main water supply is off. The strainer is blocked. The cold water inlet pressure reducing valve is not fitted properly. Symptom : Water from hot taps is cold POSSIBLE CAUSES The thermal cut-out located in the indoor unit has operated The indoor unit (EKHBRD) is not operating. Symptom : Intermittent water discharge POSSIBLE CAUSES Thermal control failure (water will be hot). The expansion vessel is broken. CORRECTIVE ACTION Check that all shut off valves of the water circuit are completely open. Turn off the water supply, remove and clean the strainer (see "Pressure reducing valve with integrated non return valve and line strainer" on page on how to do this). Check and refit as required (see "Pressure reducing valve with integrated non return valve and line strainer" on page on how to do this). CORRECTIVE ACTION Check and find the cause of tripping and then reset button. Check if thermistor is correctly installed in thermistor socket. Procedure: remove front panel and insulation, replace or fix the sensor. Check the indoor unit operation. Refer to the manual delivered with the unit. If any faults are suspected, contact your local dealer. CORRECTIVE ACTION Contact your local dealer. Replace the expansion vessel. EKHTSU000AC EKUHWHTA PW0-0.00

Symptom : Continuous water discharge POSSIBLE CAUSES Cold water inlet pressure. Temperature and pressure relief valve. The expansion relief valve is not functioning properly. Symptom : Dirty water DISPOSAL REQUIREMENTS CORRECTIVE ACTION Check the pressure reducing valve. Replace the pressure reducing valve if the measured pressure is >. bar. Check and reset button. Check for correct operation of the pressure relief valve by turning the red knob on the valve counter clockwise: If you do not hear a clacking sound, contact your local dealer. In case the water keeps running out of the unit, close both the water inlet and outlet shut-off valves first and then contact your local dealer. POSSIBLE CAUSES CORRECTIVE ACTION Dirty water Flush or clean the domestic hot water tank after periods of standstill. It could occur that particles in the water deposit on the bottom of the tank. If this deposit layer becomes thick enough it could enter the hot water outlet and contaminate the hot water. The water has a smell of rotten eggs. Check if this phenomena also occurs with the cold water. If it does, this indicates that there is a problem with the water supply or with the water in the piping, but not with the domestic hot water tank itself. Contact your water supplier. If the problem is not solved, increase the domestic hot water tank temperature above C. If this action solves the problem, the smell is most probably caused by bacterial contamination. Contact your water supplier. If the problem is not solved, contact your local dealer. Dismantling of the unit and treatment of parts must be done in accordance with relevant local and national legislation. TECHNICAL SPECIFICATIONS Domestic hot water tank specifications EKHTSU00AC EKHTSU0AC Storage capacity (l) 00 0 Material Stainless steel Stainless steel Overall dimensions (h x l x w) (mm) x 00 x 0 x 00 x Operating pressure (bar).. Maximum primary working pressure (heating side) (bar) Expansion vessel pre-charge pressure (bar).. Preset opening pressure of expansion relief valve (bar) Preset opening temperature of temperature and pressure relief ( C) 0~ 0~ valve Set opening pressure of temperature and pressure relief (bar) 0 0 valve Connections Quick coupling/ G/ F Quick coupling/ G/ F Inspection access type G/ M Recirculation connection G/ M Recirculation connection Weight - empty (kg) 0 - when full (kg) 0 Mounting On top of EKHBRD or floor mounted On top of EKHBRD or floor mounted Maximum water supply pressure (bar) Supply temperature time (a) - EKHBRD0 (min) 0 0 - EKHBRD0 (min) 0 0 - EKHBRD0 (min) 0 0 - EKHVMR/YD0 (min) 0 - EKHVMR/YD0 (min) Re-heat time (b) - EKHBRD0 (min) 0 0 - EKHBRD0 (min) 0 0 - EKHBRD0 (min) 0 0 - EKHVMR/YD0 (min) - EKHVMR/YD0 (min) (a) The time it takes to increase the temperature from C to 0 C (b) The time it takes to increase 0% of the contents of the vessel back up to 0 C EKHTSU000AC EKUHWHTA PW0-0.00

NOTES

0 EKHBRD* 0 EKHVH/X*

0 0 0 0 0 0 EKHVMYD* EKHVMRD*

Copyright 00 Daikin PW0-0.00