FX FIRE ALARM SYSTEM (ALC) Planning Instructions

Similar documents
FX FIRE DETECTION SYSTEM

FX NET FIRE DETECTION SYSTEM Installation and commissioning manual

Installation, Operating and Maintenance Manual

CONTROL PANELS. Tech Data Sheet D01688GB1 10/2012 Fire Detection. Control Panels of the FX 3NET (ALC) Fire Detection System

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

On the job around the clock 24/7: Fire detection systems

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

System 800 Addressable Fire Detection & Alarm System

Application, Installation, Operation & Maintenance Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Planning Instructions MEW01090 Revision 4

BSR Addressable Fire Detection control panel. Installation operation manual

Esmi Sense FDP Fire detection panel with ALC2 loop controller

Conventional Fire Alarm System 2014 V1.2

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

Planning Instructions MEW01776 Revision -

FEC400 Series. Installation Manual

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

Intelligent Addressable Fire Alarm System

CODESEC FIRE ALARM SYSTEMS. security technologies

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Intelligent addressable fire alarm control panel

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Model 17A00 Expansion Enclosure

Touch Screen 1 loop Addressable Fire Alarm Panel

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

Addressable Fire Alarm Control Panel

SET-2000 Hi Level/Oil

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

Consultant Specification AGILE Wireless Fire Detection System

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Intelligent Security & Fire Ltd

OPERATION AND INSTALLATION MANUAL

Fire alarm system EBL512 G3

Pioneer-R16 Gas Monitor Operator s Manual

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide

LaserFOCUS VLF-250 Engineering Specification

Analogue addressable devices

XP95/Series 90 Test Set

Interface and EOL Modules 8

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

The EN54 Part 2 & 4 Fire System

Excel-EN Conventional Fire Control Panel

Control Panel User Guide

Flair 500 Series Annunciators

Fire Control Panel FS4000

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interface Modules for SENTRI

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

Vigilant MX4428 Fire Alarm System

Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel. Application Guide

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.

Wireless Fire & Security Solutions. Fire Product Showcase

Control/Communicator Installation Manual

1X-F Series Installation Manual

Sita200plus. 200detectors. Single loop analogue addressable System

The supplier and installer of the system should be approved by the local civil defence authority.

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

Planning Instructions MEW01472 Revision -

REPEATER FS5200R INSTRUCTION MANUAL

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Installation Instructions 4 Zone Fire Panel

MODEL 5100 VOTING LOGIC MODULE

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

Automatisk Branddetekterings- og Alarm-system Automatic Fire Detection and Alarm System

TABLE OF CONTENTS TABLE OF CONTENTS 1

user manual Document No , Revision 03 November 2015

HG Home Guardian Advanced Home Energy, Safety and Security Management

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

2018 Johnson Controls. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland DUO-CEL

Document No Issue 4 user manual

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

False Alarm Management

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

ACTIVE INFRARED BARRIER

The Kentec driver connects to the Kentec Syncro range of fire detection panels. Available for Commander and ObSys.

Fire detection and alarm

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

SOLO Single Loop Addressable Fire Control Panel

S2000-ASPT. Fire Alarm and Extinguishing Control Panel. Engineer s and User s Manual

Fire Control Panel FS4000

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

Remote NAC Power Supply D7038

Synova TM product catalog.

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

HART XL High Sensitivity Smoke Detection

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

Solution F2. Fire Alarm Control Panels one step ahead.

FEC403EN Installation Manual

ZXSe Range Data Sheet

Laptop / PC Programming Manual

2000 Series Sensors Installation Guide

Transcription:

FX FIRE ALARM SYSTEM (ALC) Planning Instructions These are the planning instructions for a FX fire detection and alarm system consisting of - FX-2(-4, -6, -8) control panels with Intellia products - Intelligent and conventional detectors - Addressable I/O modules - Audible and visual alarm devices. In this document FX refers to all FX-2, -4, -6 and 8 loop panels. Information specifically related to a specific panel model, that model type is indicated. We reserve the right to technical changes without notice. Information on Intelligent addressable components can be found in the instructions "Component installation manual: Intelligent/addressable components". Information on conventional components can be found in the instructions "Component installation manual: Conventional fire detection systems". NOTE! Instructions given by the local authorities must be followed when planning the system. 6657 1639GB1 Oy ESMI Ab 19-2006

1 General about planning the system...4 1.1 When is a fire alarm needed?...4 1.2 Planning an automatic fire alarm system...4 1.3 Example of a plan for the FX fire detection system...5 2 General description of an FX system...6 2.1 Standalone FX-2 (-4, -6, -8) fire detection system...6 2.2 FX as a part of a MESA fire detection system...8 3 System components...9 3.1 Control panel components...9 3.2 Intelligent/addressable components...9 3.3 Conventional components...12 3.4 Installation accessories...13 4 FX-2 (-4, -6, -8) construction... 14 4.1 FX cabinet...14 4.2 FXL cabinet...14 4.3 FX battery cabinet...15 5 FX-ALC addressable detection circuits, addresses, zones... 16 5.1 Addressable detection circuits and addresses...16 5.2 FX detection zones...18 5.3 FX control zones...18 5.4 FX-ALC addressable detection circuit structure...21 5.5 Number of devices between short circuit isolators...22 5.6 Number of devices in an addressable detection circuit...23 5.7 Addressable detection circuit length for various cable types...24 6 Conventional detection circuits... 25 6.1 Conventional detection circuit controllers (CLC)...25 6.2 Compatible conventional detectors and manual call points...25 6.3 Conventional detection circuit structure and End-Of-Line resistors...26 6.4 Configurable options...26 7 Special features to avoid nuisance alarms... 28 7.1 Day mode...28 7.2 Delayed alarm...28 7.3 Delayed signal inputs...28 7.4 Attenuation of signal input changes...29 8 Cabling... 30 8.1 General description of the cabling...30 8.2 Cabling table...31 9 FX-2( -4, -6, -8) connections, settings and fuses... 32 9.1 FX-2 (-4, -6, -8) panel external connections...32 9.2 Connectors on the MC board...33 9.3 Connectors on the PS board...34 9.4 Connectors on each ALC board...34 9.5 Connectors on each CLC board...35 9.6 Connectors on each IOC board...35 10 FX-2 (-4, -6, -8) Technical data... 36 10.1 FX-2 (-4, -6, -8) Technical data, standard panels...36 10.2 FX-2 (-4, -6, -8) Fuses...37 10.3 FX-2 (-4, -6, -8) Battery backup...38 10.4 Battery backup calculation...39 11 FX Settings and configuration... 41 6657 1639GB1 2/43 19-2006

11.1 Settings in the FX panel...41 11.2 Configuration of the FX panel...43 6657 1639GB1 3/43 19-2006

1 General about planning the system 1.1 When is a fire alarm needed? Fire detection and alarm systems are installed mainly to protect human life. The early warning of smoke detectors alerts people to evacuate the building in an orderly manner. In hotels and similar, alarm bells or sirens provide sufficient noise to wake up people. Fire detection and alarm systems are also installed on premises where stocks, machinery or other property are to be protected. A fire detection system gives an early indication, making it possible to start and finalize the rescue work quickly thus allowing the normal activities to continue soon. A fire detection system often brings lower insurance rates. If getting a building permit requires installation of a fire alarm system, a sufficient degree of coverage must be provided. The extent of such coverage is specified in national and international regulations. 1.2 Planning an automatic fire alarm system The automatic fire detection system should be planned and installed in a way that guarantees that a starting fire in the area to be surveyed is detected as early as possible and a fire alarm indicating the location is activated. Faults that might jeopardize the reliability of the fire detection system should also be reported. If needed (for example for quotation purposes) a preliminary plan should be made as well as an installation plan for the detection system. Preliminary plan The preliminary plan can be made by the electric engineer, the contractor or the manufacturer's representative. Installation plan The installation plan is made by the manufacturer's representative or an authorized fire detection and alarm planning engineer. The planning includes: Selection of detector types and manual call points and specifying their location taking into consideration coverage, environment, building construction etc. Selection of types of alarm devices (bells, sirens, flash light beacons etc.) and specifying their location to ensure that everybody in the building is alerted. Selecting cable types and planning the routing of the cables within the building. Specifying any control functions needed for fire protection e.g. signals to extinguishing systems, ventilation systems, fire doors or shutters etc. Taking into consideration any additional requirements from the fire authorities. It may be a requirement by the local fire authorities that the plan is inspected and approved by a third party before the installation commences. 6657 1639GB1 4/43 19-2006

1.3 Example of a plan for the FX fire detection system 1/100 0 1 2 3 4 1 (m) O O O 2 O FX O O 3 R O O O I O Heat detector Manual call point Smoke detector End of line resistor Smoke detector, ionization Fire bell Short circuit isolator Zone number 6657 1639GB1 5/43 19-2006

2 General description of an FX system 2.1 Standalone FX-2 (-4, -6, -8) fire detection system Main features The modular design of the FX-2 (-4, -6, -8) control panel offers a competitive solution for small sized, as well as for medium sized projects. The address capacity of the detection circuits also offers a flexibility with regards to cabling, thus saving costs of installation work. A wide range of intelligent detectors provides solutions for all applications. In addition conventional detectors can be connected to interface modules or CLC boards in the panel, making an upgrade of a former conventional system flexible. The Intellia series of I/O-modules are both economic and space-saving in installation and provide monitoring and control functions. With the extensive configuration software all addresses and many control functions of the panel can be adopted to the requirements of the installation site. The serial communication port(s) makes it possible to connect a standard printer and additional alarm display panels. Application areas Protectable area up to 15 000 m² Business and office buildings Industrial sites Lodging houses Service centres Health and nursing centres Educational buildings FX-2 (-4, -6, -8) standalone system metrics 2... 8 addressable detection circuits 126 intelligent detectors and I/O-modules per detection circuit 250 detection zones 512 addresses (detectors and manual call points) 17 Ah, 34 Ah, 51Ah or 68Ah batteries 4,5 A total load in alarm condition 6657 1639GB1 6/43 19-2006

Parts of an FX system 6657 1639GB1 7/43 19-2006

2.2 FX as a part of a MESA fire detection system Application areas Protectable area up to 150 000 m² Business and office complexes Industrial sites Hotels Service centres Hospitals Educational buildings MESA system metrics 4 MESA user panels 16 FX control panels 99 addressable detection circuits 1000 zones 8 000 addresses (detectors and manual call points) Properties of the FX sub-system, see chapter 2.1 Parts of a MESA system 6657 1639GB1 8/43 19-2006

3 System components 3.1 Control panel components Control panel Loop Controller expansion kits, including all necessary hardware and instructions Loop Controller expansion for up to 16 conventional loops Serial communication Adapter, including all necessary hardware and instructions Input-Output Controller expansion kit, including all necessary hardware and instructions FX-2 FXL-2 FX-ALC FX-CLC FX-SAA FX-SAB FX-IOC Basic control panel 2 detection circuits. Expandable to max. 8 detection circuits in steps of 2. Expansion 2 - > 4 or 4 - > 6 or 6 - > 8 loops Maximum number of ALC s and CLC together is 4 Expansion with 16 conventional loops. Maximum number of ALC s and CLC together is 4 One RS485/422 serial communication port. Galvanically isolated for external communication with - FMP/MCO/REP or graphical alarm presentation devices Two RS485/422 serial communication ports. Galvanically isolated for external communication with - FMP/MCO/REP/ABC devices and systems - MESA panels For clean contact input monitoring, clean contact control outputs and alarm device line outputs. - 4 clean contact inputs - 2 clean contact outputs - 4 alarm device line outputs Mounting cabinet FX-CAB FX-2 control panel sized box for mounting of extra relays, modules etc. Chart cabinet FX_MAP FX-2 control panel sized box for orientation charts and other documentation. Also has space for alarm router equipment mounting. Battery cabinet, including fixing accessories for batteries and fuses FX-BAT Space for 4 x 17 Ah/12 V batteries, Total battery capacity 34 Ah/24 V Fire brigade panel FMP Operating unit for fire brigade or information display To be connected to the FX-SA RS485/Info-line Protocol repeater REP For duplication of the FX-SA RS485/Info-line Programmable controls MCO Programmable logic controller To be connected to the FX-SA RS485/Info-line 3.2 Intelligent/addressable components NOTE! Technical information for the components can be found in the document "Component installation manual, 2006 ". Ilmaisimien soveltuvuus eri tiloihin. A:n taulukko CO ilmaisimesta varoitus Ei savuilmaisin Intelligent detectors for mounting in bases EBI-10, EBI-11 and EBI-20 Ionisation smoke detector EDI-10 Ionisating smoke detector EN54-7/2000 Optical smoke detector EDI-20 Optical smoke detector EN54-7/2000 6657 1639GB1 9/43 19-2006

Multi-criteria detector EDI-30 Combined detector, smoke and thermal EN54-7/2000 EN54-5/2000 class A1 Heat detectors EDI-50 Heat detector class A1S (EN54-5/2000) Configurable class Installation bases for intelligent / addressable detectors Installation base EBI-10 Base with short circuit isolator EBI-11 Base with relay contacts EBI-20 Includes a relay output with a single pole switch over contact Duct detector housing EBI-50 Detector (e.g. EDI-20) is not included Intelligent detectors for special applications Beam detector Carbon monoxide gas detector 55000-268APO 55000-273APO EDI-60 Intelligent infrared beam detector and reflector providing for supervision of up to 700 m 2 (14m x 50m). EN54-12/2002. Intelligent beam detector with laser beam and reflectors providing for supervision of up to 1400 m 2 (14m x 100m). EN54-12/2002. See separate application document. Note! CO detectors are not replacements for smoke detectors! Exi area devices The intelligent Exi - area smoke detectors are mounted in 45681-215APO base and connected to the addressable loop through a protocol converter and galvanic isolator. Optical smoke detector 55000-640APO Optical smoke detector EEx ia IIC T5 Ionisation smoke detector 55000-540APO Ionisation smoke detector EEx ia IIC T5 Heat detector 55000-440APO Heat detector (A2S) EEx ia IIC T5 Manual call point 55000-940APO Manual call point EEx ia IIC T5 Protocol converter 55000-855APO Single channel protocol converter Protocol converter 55000-856APO Dual channel protocol converter Galvanic isolator 29600-098APO EEx ia IIC T5 Manual call points Call point EPP-10 EPP-20 55100-950APO Manual call point Manual call point with short circuit isolator IP67, surface mounting Short circuit isolators and addressable I/O modules, surface mounted Short circuit isolator ECI-30 Short circuit isolator EBI-30 Base for short circuit isolator Conventional zone module EMI-310/CZ Address module for standard conventional detectors and manual call points as well as for beam detectors, flame detectors and other special detectors. Monitor modules EMI-310 Addressable module with one contact input. 6657 1639GB1 10/43 19-2006

For available programmable functions see chapter 11 Control module For available programmable functions see chapter 11 Combined monitor and control modules For available programmable functions see chapter 11 EMI-310+ 55000-833APO 55000-832APO EMI-301 EMI-311 EMI-311/240 Addressable module with one contact input incl. delay Mini switch monitor module. To be mounted inside the device to be monitored. Mini switch monitor module with interrupt function. To be mounted inside the device to be monitored. Address module with one relay output Address module with one contact input and one voltage free relay output. Address module with one contact input and one relay output for controlling 240Vac circuits. 6657 1639GB1 11/43 19-2006

3.3 Conventional components NOTE! Information of the components can be found in the instructions Component installation manual, 2006 Detectors for mounting in base EBC-10 for connection to a EMI-310/CZ conventional zone module Multi-criteria detector EDC-30 Combined detector, smoke and thermal EN54-7/2000 EN54-5/2000 class A1 Smoke detectors EDC-20 Optical smoke detector (EN54-7/2000) Heat detectors EDC-50/A1R Heat detector class A1R (EN54-5/2000) EDC-50/A2S Heat detector class A2S (EN54-5/2000) EDC-50/BR Heat detector class BR (EN54-5/2000) EDC-50/BS Heat detector class BS (EN54-5/2000) EDC-50/CR Heat detector class CR (EN54-5/2000) EDC-50/CS Heat detector class CS (EN54-5/2000) Manual call points for connection to a EMI-310/CZ Conventional call points MCP?? MCP?? MCP?? Flush mounting in device box Surface mounting in mounting box SR2G Waterproof IP67 for surface mounting Alarm devices, flash lights and alarm indication panels Alarm devices, Flash lights MBF-6EV MBA-6+BBX4 ESI-20 ESI-30 ESI-40 ESI-50 ESI-60 ESI-70 Bell for indoor use Bell for outdoor use, IP57 Sounder, for mounting beneath the detector base, with isol. Sounder, for mounting beneath the detector base Sounder, for wall mounting, IP66 (100dB) Sounder, for wall mounting, IP42 (100dB) Sounder Beacon, for mounting beneath the detector base, with isolator Sounder Beacon, for mounting beneath the detector base Alarm indication panels LEDFF01 Indicators for fire alarm and fault warning Remote indicator NLY-91200 Surface mounting To be used with both addressable and conventional detectors 6657 1639GB1 12/43 19-2006

3.4 Installation accessories End-of-line resistors and End-of-line capacitors End-of-line resistors 4,7 kω ± 5%, 0,5 W for alarm device lines 3,9 kω ± 5%, 0,5 W for the sub-detection circuit of M512ME modules 47 kω ± 5%, 0,5 W, EOL resistor for Base mounting accessories Conduit box 45681-204APO Mounting box for damp sites Ceiling tile adaptor for 45681-309APO Flush mounting accessory for lowered ceilings detectors Ceiling tile adaptor for 45681-310APO Flush mounting accessory for lowered ceilings sounders Socket gasket MS2000 For detector bases?? MS2001 For detector bases?? Esmi do supply also special detectors, not mentioned in this document, like other types of flame detectors, heat sensing cables, wireless detectors and aspiration systems. Please contact the sales department for further information. 6657 1639GB1 13/43 19-2006

4 FX-2 (-4, -6, -8) construction The FX panel is a modular construction, facilitating easy expansion and selection of needed modules. The panel consists of a back plate in sheet metal, specially designed racks that holds the electronic boards and a cover in plastic. Two different cabinet types are available for housing the control panel and in addition a cabinet with blank cover is available for housing of batteries or auxiliary equipment. The electronics are distributed on boards as follows: - FX-UI the User Interface board contains an LCD display, LEDs and buttons - FX-MC the Main Controller contains the main processor and basic mandatory inputs and outputs - FX-PS the Power Supply unit is responsible for standby battery charging, voltage regulation and power supply to the panel and external circuitry. - FX-ALC the Loop Controller takes care of power distribution to the detection circuits (loops), communication with the addressable devices connected to the loops and monitoring and control of the loop cabling. - FX-IOC the Input/Output Controller provides clean contact signal inputs, clean contact signal outputs and alarm device outputs. - FX-SA the Serial Adapter contains the circuitry for galvanically isolated serial data communication. Signalling between the boards goes through a motherboard between the racks. 4.1 FX cabinet The FX cabinet has space for the following - 1 x UI - 1 x MC (+SA) - 1 x PS - 5 x ALC or CLC(max. 4) or IOC (max. 4) - 2 x Battery 12V / 17Ah MC PS 4.2 FXL cabinet The FXL cabinet has space for the following - 1 x UI - 1 x MC (+SA) - 1 x PS - 4 x ALC or CLC - 4 x IOC MC PS 6657 1639GB1 14/43 19-2006

4.3 FX battery cabinet The FX battery cabinet has space for the following - 4 x battery 12V / 17Ah - Fire alarm and Fault warning router 6657 1639GB1 15/43 19-2006

5 FX-ALC addressable detection circuits, addresses, zones 5.1 Addressable detection circuits and addresses The cables that connect the detectors and the I/O-modules to the panel are called detection circuits (or loops in some ESMI documentation). The detection circuits are identified by a two-digit number and are by default: 01 02 for an FX panel with two detection circuits (one ALC Loop Controller) 01 04 for an FX panel with four detection circuits (two ALC Loop Controllers) 01 06 for an FX panel with six detection circuits (three ALC Loop Controllers) 01 08 for an FX panel with eight detection circuits (four ALC Loop Controllers) With the configuration software the detection circuit identifications can be changed to any consecutive range of numbers with a maximum value of 99. The detectors and the I/O-modules are individually assigned a number (address) during installation and can therefore be identified by the panel, using a proprietary communication protocol. The address setting for detectors is simply done by inserting an address card in the base of the detector. Prepared (address set) cards are available as a series with addresses 1.. 126. Each base also comes with a blank card that can easily be set to a certain address at the installation site. The address setting for IO-modules is done with binary coded address switches. Within the system a detector (or I/O-module) is identified by the detection circuit and the setting of the address. This identification is expressed in the FX (and MESA) displays as dc.add, where dc is the detection circuit and add is the address setting, e.g. 05.037. Max. 126 addresses (detectors and IO-modules) in free order. System capacity System type Detection circuits Max det. addresses FX 2 (one ALC) 2 252 FX 4 (two ALC) 4 504 FX 6 (three ALC) 6 512* FX 8 (four ALC) 8 512* System type Detection circuits Addresses MESA(16 FX panels) 99 8000 * The maximum number of detectors and manual call points has to be kept as 512 for compliance with the EN54 standard. For other purposes the full address range of 126 addresses per loop can be used. NOTE! In a MESA system the MESA user panels and the FX control panels must be configured before they are connected to each other. A stand-alone FX system can be commissioned and used without configuration, however, the following has to be considered: Every time the system is started, the presence of all addresses has to be manually verified. The zone assignments of the addresses are according to a default scheme. 6657 1639GB1 16/43 19-2006

6657 1639GB1 17/43 19-2006

5.2 FX detection zones Detectors of a fire detection system are usually grouped to detection zones. In conventional systems the detection circuit coincides with a detection zone, but in addressable systems like the FX, the detectors are grouped by the software. The zones are identified by a four-digit number in the range 0001 9999 and they have to be consecutive within an FX panel. In a standalone FX system the addresses are by default assigned to zones according the following scheme, but this assignment can easily be changed with the configuration software. When configured, any detector within the FX panel, even in different detection circuits, can be assigned to any zone. All addresses have to be assigned to some zone. Default assignment of addresses into detection zone s Detection circuits (Loops) Addresses 1 st Loop Controlle r 2 nd Loop Controller 3 rd Loop Controller 4 th Loop Controller L 1 L 2 L 3 L 4 L 5 L 6 L 7 L 8 001 012 1 11 21 31 41 51 61 71 013 024 2 12 22 32 42 52 62 72 025 036 3 13 23 33 43 53 63 73 037 048 4 14 24 34 44 54 64 74 049 060 5 15 25 35 45 55 65 75 061 072 6 16 26 36 46 56 66 76 073 084 7 17 27 37 47 57 67 77 085 096 8 18 28 38 48 58 68 78 097 108 9 19 29 39 49 59 69 79 109 126 10 20 30 40 50 60 70 80 5.3 FX control zones The concept of control zones in an FX panel is a way of grouping the various inputs of the panel to facilitate activation of outputs. The control zones are defined separately from the detection zones, although they are the same as default. Control zone inputs are not limited to the detectors and other addressable devices on the loop, also monitoring inputs in the panel can be members of control zones. Control zone outputs can just as well be both addressable outputs on the loop as relay outputs in the panel. Control zones goes hand in hand with events. There are two kinds of events, input events and output events. Input events are the type of signals that the control logic reacts on, e.g. when a detector gives a fire signal we say that the input event is a fire event. Output events are events activated (triggered) by the logic. Certain input events have corresponding output events, e.g. a fire input event corresponds to an alarm device output event. To say it with one sentence: When an input event for a specified control zone occurs, the corresponding output events for the same control zone are activated. There are 250 specific control zones in an FX panel and one general control zone. In this document these are identified with the numerical values 1... 250 and the word General, respectively. For input events, two control zones can be assigned, in this document referred to as In-Zone-1 and In-Zone-2. For output events, up to all 250 specific control zones or the General zone can be assigned, in this document referred to as Out-Zones. An input event is signalled to both In-Zone-1 and In-Z one-2 immediately when the event occurs, except if the device is set up for delayed alarm. If the input device is set up for delayed alarm the event is signalled to In-Zone- 1 immediately, but to In-Zone-2 after the delay. 6657 1639GB1 18/43 19-2006

An output device, that is configured to belong to the Gener al control zone, responds to its corresponding input event from any input devices, regardless of the control zone assignments of that input device. An output device, that is configured to belong to any one, or combination of, of the specific control zones (1 250), responds to its corresponding input event, only from input devices with a matching control zone assignment. C ontrol zone inputs and events Following is a list of devices that can create input events Device Input event Fire alarm Prewarning Fault warning Detectors Maintenance warning Disablement Comment When the user makes an address disablement, or the address is disabled due to day mode (see 7.1 ). Monitor module or control module regardless of configured function Fault warning Maintenance warning Disablement If the module stops responding to the panel, an address fault warning is issued by the panel. When the user makes an address disablement, or the address is disabled due to day mode (see 7.1 ). Monitor modules configured with function: - Manual Call Point / A l m Switch - Manual Call Point - Beam detector Fire alarm - Conv. Heat Detector - Fire Alarm Input - Prewarning Input Prewarning - Fault warning Input Fault warning Maintenance - Maintenance Input warning - Technical Alarm Input Technical alarm - Silent Tech Alarm Input - Zone Disablement Input Disablement - Day Mode Activation Input - - Delayed Alarm Enable Input - - Day Mode and Delayed Alarm Enable Input - - Delayed Alarm Zonal Silence Fire alarm silence - Delayed Alarm Zonal Reset Fire alarm reset If any address is set to be disabled during day mode, a disablement event for that address will occur. If Delayed Alarm is set to be indicated as a disablement, a general disablement event will occur. See previous Day Mode Activation Input and Delayed Alarm Enable Input Affects only fire alarm signals from the same detection zone 6657 1639GB1 19/43 19-2006

Silence of the - General Silence Input currently highest alarm priority Alarm priority order is (from highest priority): Fire alarm, Prewarning, Technical alarm, Fault warning, - General Reset Input Reset of the currently Maintenance warning highest alarm priority - Extinguisher Activated Input - Has no control input event, only lights up the Extinguisher Activated LED in the panel. - Smoke ventilation Activated Has no control input event, only lights up the Smoke - Input ventilation Activated LED in the panel. - Customer LED 1 Activation - Has no control input event, only lights up the Customer LED 1 LED in the panel. - Customer LED 2 Activation - Has no control input event, only lights up the Customer LED 2 LED in the panel. - Internal Logic Input Logic control - External Logic Input - - Evacuation input Evacuation Control output devices and events Event Fire alarm Evacuation Prewarning Fault warning Maintenance warning Disablement Main power break Technical alarm Logic control Activates outputs Fire Alarm Router Equipment Fire Alarm Devices Fire Alarm Devices Non- Silenceable Fire Alarm Output Fire Door Output Extinguisher Output Fire Alarm Devices Fire Alarm Devices Non- Silenceable Prewarning Output Fire Door Output Fault warning router equipment Fault Warning Output Fire Door Output Maintenance Warning Output Disablement Output Fire Door Output Fire Door Output Technical Alarm Output Internal Logic Output 6657 1639GB1 20/43 19-2006

5.4 FX-ALC addressable detection circuit structure The detection circuit cabling can be arranged in a variety of lay-outs, being flexible for all applications. However, following has to be considered when selecting a cable lay-out. The cable resistance between the panel and any detector may not exceed 60 Ω. If a large number of sounders, powered from the detection circuit, are used, the maximum resistance may be further restricted to ensure sufficient voltage to all devices (see chapter 5.6). The cable capacitance may not exceed 360 nf. Not more than one zone (max. 32 detectors and/or manual call points) may drop out of operation in case of a fault in the cable. There are limitations on number of devices between short-circuit isolators (see chapter 5.5). Closed detection circuit (highly recommended) A closed detection circuit gives the highest safety, because the panel can still communicate with all addresses even if the cable is cut. To minimise the effect of a short-circuit, isolators are available which reduces the number of dropped-out addresses to the addresses between the isolators that are closest to the short-circuit. The rule of max 60 Ω between panel and any detector has to be considered even if the cable is cut in either end of the detection circuit. The cable capacitance in this layout is normally not an issue of concern. Closed detection circuit with branches (recommended with reservations) Branches are allowed if the length of the branch is kept short (< 100 m) and if the number of addresses that may drop out in case of a cable failure is less than 32. Again the rule of cabl e resistance has to be considered in any case of cable cut. The capacitance may be an issue if there are several branches. Check with the cable manufacturer and calculate the total capacita nce. Open-end detection circuit (not generally recommended) This is least efficient utilization of the cable, since only 32 addresses can be use d on the circuit. With that restriction in mind, it can still provide the longest distance between the panel and the farthest address. Closed detection circuit Open-end detection circuit <60 Ω <60 Ω Closed detection circuit + addressable branches Short circuit isolator <60 Ω <60 Ω <60 Ω 6657 1639GB1 21/43 19-2006

5.5 Number of devices between short circuit isolators Using short circuit isolators and returning the detection circuit to the panel, the full capacity of the detection circuit can be used. Short circuit isolators have to be installed at the boundary of each zone to comply with the requirement that not more than one zone falls out of operation in the case of a single cable fault. It may be necessary to use additional short circuit isolators if the current consumption of the devices between two isolators otherwise exceeds the following specification. During start-up of the detection circuit (before the isolators have connected all segments) current is fed from the already powered-up side of the isolator to the other side through a circuit that limits the current to 50 ma. If the voltage on the others side reaches 14 V, the isolator by-passes the current limiter and connects full supply to the other side. If there is a short circuit or if the load on the other side is too high, the isolator will cut off the current and try again after approx. 5 seconds. All devices have a surge current that can be significantly higher than the standby current. The sum of the surge current for all devices between the isolators has to be less than 45 ma to assure a proper startup. Following table shows the load factors of the addressable devices. The corresponds to the 45 ma limit. total load factor can not exceed 20, which Load factor x Pcs = Load factor EDI-10 Ion Smoke Detector 1 EDI-20 Optical Smoke Detector 1 EDI-30 Photo-Thermal Detector 1 EDI-50/xx Heat Detector 1 EDI-60 Carbon Monoxide Detector 1 55000-268APOBeam Detector 20 55000-280APO Flame Detector 20 EPP-10 Manual Call Point 1 EPP-20 Manual Call Point 1 EMI-301 Single Output Module 3 EMI-301/S Sounder control module 3 EMI-310 Switch Monitor module 3 EMI-310+ Switch Monitor+ module 3 EMI-310/CZ Conventional Zone Monitor Module 3 EMI-311 Input/Output Module 4 EMI-311/240 240V Relay Output Module 4 EMI-333 Three channel Input/Output module 12? EMI-401 Single Output Module 3 EMI-401/S Sounder control module 3 EMI-410 Switch Monitor module 3 EMI-410+ Switch Monitor+ module 3 EMI-410/CZ Conventional Zone Monitor Module 3 EMI-411 Input/Output Module 4 55000-640APO Optical smoke detector 1 55000-540APO Ionisation smoke detector 1 55000-440APO Heat detector 1 55000-940APO Manual call point 1 55000-855APO Protocol converter 1 55000-856APO Protocol converter 1 29600-098APO Galvanic isolator 0 ESI-10 Ancilliary Base Sounder 1 ESI-20 Addressable Base Sounder with Isolator 1 ESI-30 Addressable Base Sounder 1 ESI-40 Standalone Sounder IP 66 (100dB) 1 ESI-50 Standalone Sounder IP 42 (100dB) 1 ESI-60 Loop Powered Sounder Beacon with Isolator 1 ESI-70 Loop Powered Sounder Beacon 1 Total load factor 6657 1639GB1 22/43 19-2006

5.6 Number of devices in an addressable detection circuit It is necessary to make careful calculations of load on, and resistan ce of, the detection ci rcuit especially if addressable sounders are installed on the detection circuit. The resistance from the panel to any device has to be less than 60 Ω and this is to be the case even if there s one cut anywhere in the detection circuit. It may be necessary to further decrease the resistance and thus the voltage drop, by u sing thicker cable, if the alarm load is high. Maximum peak current The current consumption of the components in the detection ci rcuit indicated in dat a sheets and other documentation is the mean value and is good for battery backup ca lculation. However, the planning of the detection circuits should take into consideration also the following: A short circuit isolated by two isolators = 2 x 50 ma pulses every 5 seconds = 100 ma peaks Additional pulsating current drawn by the devices during communic ation = 20 ma The current of the detection circuit is limited to 600 ma by the panel. The total load (including above mentioned 120 ma) of all devices connected to the detection circuit in normal condition as well as in alarm condition can not exceed 600 ma. Voltage drop calculation The more symmetrically (with respect to the centre of the cable) the load is distributed, the better with respect to voltage drop. On the contrary, the more the load is concentrated close to either end of the cable (no matter which, because the system has to operate from either end, even if the other end is cut) the worst it is with respect to voltage drop. The v oltage drop can be calculated with the formula where Itot * Rtot * a Itot = total current (in alarm condition and including above mentioned 120 ma) Rtot = total resistance a = correcting factor for load distribution With a perfectly symmetrical distribution of t he load, the voltage drop is only half (b = 0,5) com pared with all load being at ei ther end (b = 1). A generally safe v alue to use is b = 0,85 that corresponds to an evenly distributed load over half of the cable (0, 75) + a safety margin of 0,1. The highest minimum voltage for the addressable devic es is 17V, and since the loop provide a m inimum voltage of 27 V, we can use 10 V as the maximum allowed voltage drop in the loop cabling. Subsequently the formula for calculating max allowed detection circuit cable resistance is Rmax = 10 V / (Itot * a) NOTE! * In the following table the alarm current for the detectors are included for your information only and should not be used for the voltage drop calculation. The alarm current for the detectors is increased only by the LED s and the FX panel restricts the number of lit LED s to 5. Therefore the alarm current for the detectors are added at the end of the table as 5 times 3 ma. Device Standby Alarm X pcs = current EDI-10 Ion Smoke Detector 0,5 (3,5)* EDI-20 Optical Smoke Detector 0,4 (3,4)* EDI-30 Photo-Thermal Detector 0,5 (3,5)* EDI-50 Heat Detector 0,5 (3,5)* EDI-60 CO Detector 0,5 (3,5)* 55000-268APO Beam Detector 5,0 (9,0)* 55000-273APO Beam Detector 5,0 (9,0)* 55000-280APO Flame Detector 2,2 (4,2)* 6657 1639GB1 23/43 19-2006

ESI-10 Ancillary Base Sounder 0,1 3,0 ESI-20 Addressable Integrated Base Sounder with isolator 0,3 5,0 ESI-30 Addressable Integrated Base Sounder 0,3 5,0 ESI-40 Standalone Sounder IP66 (100dB) 1,2 5,0 ESI-50 Standalone Sounder IP42 (100dB) 1,2 5,0 ESI-60 Loop Powered Sounder Beacon with isolator 0,3 8,0 ESI-70 Loop Powered Sounder Beacon 0,3 8,0 EMI-310 or EMI-410 1,3 3,5 EMI-310+ or EMI-410+ 1,3 4,4 EMI-310/ CZ or EMI-310/CZ 4,0 21 EMI-311 or EMI-411 1,3 5,5 EMI-333 EMI-301 Single Output Module 0,4 1,8 EMI-301/S Sounder Output Module 2,0 1,7 EMI-311/240 EMI-401 0,7 3,3 EMI-401/S 1,9 1,7 Sum Additional curren t for LED s of 5 detectors (5 x 3 ma) + 15,0 = Correction for load distrib ution x 0,85 = Allowed cable resistance for 10V voltage drop (10V divided by previous current value) NOTE! The cable resistance may never, because of other reasons, exceed 60 Ω 5.7 Addressable detection circuit length for various cable types In the following table the max. lengths for some generally used cables are calculated taking into account maximum voltage drop of 10V and a correction factor for load distribution of 0,85. Load current Cable length (A= cross-section area, Ø= diameter) Mean value (for Peak value (for Allowed cable A=0,5 mm² A=0,8 mm² A=1,0 mm² A=1,5 mm² battery voltage drop resistance Ø=0,8 mm Ø=1,0 mm Ø=1,1 mm Ø=1,4 mm calculation) calc.) R pair =74Ω/km R pair =47Ω/km R pair =38Ω/km R pair =25Ω/km [ma] [ma] [Ω] [m] [m] [m] [m] 50 170 60 * 811 1277 1579 2400 100 220 53 723 1138 1407 2139 150 270 59 589 927 1147 1743 200 320 44 497 782 967 1471 250 370 35 430 677 837 1272 300 420 29 379 596 737 1120 350 470 25 338 533 659 1001 400 520 22 306 481 595 905 450 570 21 279 439 543 826 * NOTE! The resistance may not, because of other reasons, exceed 60Ω 6657 1639GB1 24/43 19-2006

6 Conventional detection circuits 6.1 Conventional detection circuit controllers (CLC) The FX panels can also be equipped with Conventional Loop Controllers (CLC). The CLC board takes one loop controller place in the panel. Thus the following combinations are possible: ALC s CLC s Comment 1 No addressable loops, 1 to 16 conventional lines 2 No addressable loops, 17 to 32 conventional lines 0 3 No addressable loops, 33 to 48 conventional lines 4 No addressable loops, 49 to 64 conventional lines 0 2 addressable loops (each 126 addresses) 0 conventional lines 1 2 addressable loops (each 126 addresses) 1 to 16 conventional lines 1 2 2 addressable loops (each 126 addresses) 17 to 32 conventional lines 3 2 addressable loops (each 126 addresses) 33 to 48 conventional lines 0 4 addressable loops (each 126 addresses) 0 conventional lines 2 1 4 addressable loops (each 126 addresses) 1 to 16 conventional lines 2 4 addressable loops (each 126 addresses) 17 to 32 conventional lines 0 6 addressable loops (each 126 addresses) 0 conventional lines 3 1 6 addressable loops (each 126 addresses) 1 to 16 conventional lines 4 0 8 addressable loops (each 126 addresses) 0 conventional lines Note! The total number of detectors and manual call points, connected to one FX panel, may not exceed 512, to fulfill the EN54 standard. The FX panel handles internally the who le CLC board as one addressable loop and each conventional line as an address of that loop. Each conventional line can therefore be configured and used just as the conventional zone modu le connected to an addressable detection circuit. It also means that the conventional lines are handled by the user in the same way as the conventional zone modules, e.g. for disablement/re-enablement. Ea ch line is by default in its own detection zone. 6.2 Compatible conventional detectors and manual call points Compatibility of detectors with the CL C conventional line is determined by the following factors: - Supply voltage range - Current consumption in standby condition - Vo ltage across the detector in alarm condition - Series resistance (either in the detector or in the base) - End-Of-Line resistor The voltage supplied by the CLC to the c onventional line is 21Vdc to 24Vdc. The maximum allowable voltage drop in the cable is 21V minus the lowest operating voltage of the connected devices. If the line goes through an Exi barrier, the maximum allowed cable resistance and current consumption is less than for a normal line. The following table shows the required series resistor for a number of detector voltages (in alarm condition), the two allowed EOL types and whether or not a Exi barrier is connected to the loop. EOL resistor, Exi 4k7, 5%, not Exi 2k94, 1%, not Exi 4k7, 5%, Exi 2k94, 1%, Exi Ma x cable resistance 100Ω 100Ω 50Ω 50Ω Max detector load 1,8 ma 4,0 ma 1,5 ma 3,0 ma 8V 50 1000Ω 50-550Ω 10-700Ω 10-320Ω 5V 110-1300Ω 110-750Ω 150-1050Ω 170-550Ω 6657 1639GB1 25/43 19-2006

3V 140-1500Ω 150-880Ω 250-1250Ω 280-710Ω 1V 180-1700Ω 190-1010Ω 340-1500Ω 380-880Ω 0V 200-1800Ω 210-1070Ω 390-1600Ω 440-960Ω 6.3 Conventional detection circuit structure and End-Of-Line resistors Each line (conventional detection circuit) of the CLC is terminated with an End-Of-Line resistor. The value of this resi stor can be either 4k7 or 2k94, depending on the type of detectors connected to the line and the alarm series resi stor the detector or its base has. Max 32 detectors and manual call points together. The number may further be reduced by the current consumption of the devices. See table in chapter 6.2 for required series resistors and EOL resistors. 6.4 Configurable options For different applications the operation of the conventional line can be modified through the configuration tool WinFX. Following items can be configured: Detection zone identification The conventional line can be a member of any detection zone of the panel Control zone 1 and control zone 2 Control zones are used to group detectors, manual call points, signal inputs and (see chapter 5.3) also conventional lines for common control output functions Functional type In addition to Manual call point line and Detection line items selectable for addressable monitor modules are selectable EOL resistor Whether the line is Normally Open (NO) or Normally Closed (NC) 4k7 (default) or 2k9 NO (default) usually used for manual call point lines and detection lines. NC may sometimes be useful for signal inputs Whether the line is monitored for A break in the line is by default indicated as a fault. In special cases it may be breaks or not useful not to have break monitoring on Whether a short circuit should be indicated as fault or as alarm Whether the line is used in an intrinsically safe area (Exi-area) A short circuit is by default indicated as a fault. To interface with old style conventional loops, it may be necessary to indicate a short circuit as an alarm condition The barrier that is used at the entry to the Exi area is seen as an increased resistance in the line. This setting compensates. Alarm mode Special alarm modifiers, like co-incidence, delayed alarm output, prealarm only or local alarm only Whether the line should have a double-knock feature or not Filter value for avoiding disturbances Whether the line should be disabled by Day Mode or not Whether the line should be disabled by a zone disablement or not Double-knock means that the panel resets the line for a few seconds and if there is an alarm signal still after this reset the panel indicates the alarm. Used to avoid false alarms. The default setting of 2 means that 2 verifying measurements are taken from the line before an alarm condition is raised To avoid false alarm it may be necessary to disable parts of the fire alarm system during day mode Zone disablements are typically made to avoid false alarms and it is usual to only disable smoke detectors. Lines with manual call points and/or heat detectors should not be disabled Text to be displayed in any alarm Any descriptive text of the area covered by the line 6657 1639GB1 26/43 19-2006

condition 6657 1639GB1 27/43 19-2006

7 Special features to avoid nuisance alarms It is a well k nown fact that fire detection and alarm systems, while operating fully according to standards and specificat ions, may initiate alarms in situations that are not really fire situations. These alarms are called nuisance alarms and are mostly the result of activities in the building that create physical phenomena that resembles those that the fire detection system is designed to react upon. These activities includes, as examples, - construction work (may create smoke or fine particle dust that looks like smoke) - welding (creates smoke) - cooking (creates steam that may look like smoke, or heat from an open owen) - tobacco smoking - operating heavy machinery (may create electrical fields well beyond what a system is required to withstand) The selection of detector type and the lo cation of the detector should always be carefully considered as the first step to avoid nuisance alarms. If the selection of detector type and the loca tion of the detector do not give a satisfactory result, the FX system provides features to minimize the risk of nuisance alar ms while still providing the safety against real fire incidents as required by the standards. Since the usage of these measures against nuisance alarms may delay the signalling of real fire incidents, it is mandatory to carefully assess the need of these measures, and agree upon the usage of them with local fire authorities, insurance companies and the owner of the building. 7.1 Day mode It is a common practice to prevent nuisance alarms by disabling detectors in areas where the normal activities in the building create phenomena resembling a fire. This is often done by ma king the disablement at the panel or by a special device, giving a disablement command to the panel. The device can for example be a timer switch that the worker turns to a number of hours and a specified detection zone is disabled for the time set. Although this functionality is available in the FX system, it also introduces an automation of this action and an alternative to complete disablement. Day mode, as the term implies, is an operational mode of the system, used during day time, where certain settings reduces the risk of nuisance alarm. The settings that are selectable during day mode are: - disablement of selected detectors and addressable IO modules (or addresses in general) - decreased sensitivity of selected intelligent detectors The settings are selectable individually for each address in the system. Day mode is activa ted and deactivated, for example, by a contact in the central clock system, ensuring that the workers do not forget to turn it on and off. 7.2 Delayed alarm Delayed alarm is anoth er way of preventing nuisance alarms, acknowledged by the standard, and widely adopted in some European countries. It is, and should be, used only when trained personnel is at the site. The function involves an initial delay of alarm router and/or alarm devices and/or other control output functions. During this delay (typically 60 seconds) the person, trained and responsible, reacts on the alarm and gives a signal to the system that he is aware of the alarm and investigating it. This signal activates an additional delay time (typically 5 minutes) during which the person investigates the situation and resets the system if the alarm was a nuisance alarm. If the situation is a real fire incident, the delay can be terminated immediately from the nearest manual call point. If a timeout of either the initial delay or the additional delay occurs, all delayed control functions are activated. The Delayed alarm function is enabled with a signal input, either together with the day mode input or separately. The initial delay time and the additional delay time are set in 10 seconds increments and are limited by the standard to a maximum of 5 minutes and 10 minutes, the total delay time being furthe r restricted to a maximum of 10 minutes. Delayed alarm mode is selected individually for each address (normally only fo r smoke detectors). Delay is terminated by a non- delayed alarm signal (normally heat detector or manual call point). Delay termination can also be selected to occur when a se cond (delayed alarm) detector gives a fire signal. 7.3 Delayed signal inputs A third way to avoid nuisance alarms is to use delayed signal inputs. The time can be set in 10 seconds increments up to 60 seconds and is typically set to 20 or 30 seconds. The function requires that the signal from the detector remains above alarm level for the selected time before an alarm is issued by the panel. If the signal Kommentti: Feasible with Intellia detectors? 6657 1639GB1 28/43 19-2006

goes below the alarm level, the timer is stopped. This effectively filters out transients in the detectors or in the communication between the panel and the detectors. Because of the internal operation of the detectors and the way the panel schedules measurement requests (polling) from the detectors, this function works best for loops with less than 50 detectors, while Attenuation of signal input changes works best for loops with more than 50 detectors. 7.4 Attenuation of signal input changes Attenuation of signal i nput changes is a way to smooth rapid changes in the signals from the detectors. It effectively reduces the difference betw een the last received signals and previous calculated signal value to the fraction difference/(1+ n) where n is the selected attenuation factor in the range 0..4. Because of the internal operation of the detectors and the way the panel schedules measurement requests (polling) from the detectors, this function works best fo r loops with more than 50 detectors, while Delayed signal inputs works best for loops with less than 50 detectors. Kommentti: Feasible with Intellia detectors? 6657 1639GB1 29/43 19-2006

8 Cabling 8.1 General description of the cabling Open collector control lines 2 x 0,5 mm 2 Regional alarm centre 1 1' 8 8' Main detection circuit 2 x 0,5 mm 2 (+ shield) or 2 x 1,0 mm 2 (+ shield) Main supply 230 ± 10 VAC, 50-60 Hz Max. power 160 VA Own circuit fuse 10 A 7 6 Detection circuit branch 2 x 0,5 mm 2 (+ shield) Alarm lines 2 x 0,5 mm 2 or 2 x 1,0 mm 2 or 2 x 2,5 mm 2 depending on load Conventional zone module Power supply to the units 2 x 1,0 mm 2 or 2 x 2,5 mm 2 depending on load Monitor module Monitored lines 2 x 0,5 mm 2 Control module E.g. from extinguishing Clean contact relay output 2 x 0,5 mm 2 Alarm line 2 x 0,5 mm 2 or 2 x 1,0 mm 2 or 2 x 2,5 mm 2 depending on load Conventional detection circuit 2 x 0,5 mm² (+ shield) 6657 1639GB1 30/43 19-2006

8.2 Cabling table Cable connection Conductors x Max. length Comments area ax. allowed voltage drop defines cable to be 2 x 0, 5 mm 2 + 810 m Th e cable resistance of the loop is max. 60 Ω and the capacitance Addressable detection shield (60 Ω) m ax. 180 nf between conductor and shield, 360 nf between circuit cables 2 x 1, 0 mm 2 + 1580 m conductors. Max. voltage drop is 10V. See chapter 0 for more shield (60 Ω) information. 2 x 0, 5 mm 2 + 1200 m Conventional detection shield (100 Ω) Th e cable resistance of the loop is max. 50Ω, if an Exi barrier is connected to the loop, otherwise max 100Ω. circuits of a CLC board 2 x 1, 0 mm 2 + 2400 m The max. allowed capacitance of the cable is 0.5µF. shield (100 Ω) Sub-detection circuits 2 x 0, 5 mm 2 + 625 m Conventional zone module EMI-310/CZ or EMI-410/CZ and of conventional zone shield co modules (50 Ω) nventional detectors or conventional manual call points Printer connection 2x2x0,5 mm 2 + - Serial data shield 15 m RS232 Serial connections - INFO - MESA/FX 2 x 0, 5 mm 2 + shield or 2 x 0, 5 mm 2 1000 m RS485 FX clean conta ct input lines 2 x 0, 5 mm 2 2000 m The equipment receiving the contact signal may have restrictions FX clean conta 2 x 0, To be ct 5 mm 2 or on cable properties. calculated output lines 2 x 1, 0 mm 2 separately Load controlled by the relay output may restrict allowed resistance and length per cross section FX alarm device lines - 2 x 0,5 mm2 or To be fire bell, siren line 2 x 1, 0 mm 2 or calculated M used. - fault buzzer line 2 x 2, 5 mm 2 separately Addressable monitor 2 x 0, 5 mm modules + 1200 m Monitor modules EMI-310, EMI-310+, EMI-311, EMI-333, EMI410, shield (100 Ω) EMI-410+, EMI-411 - monitor lines Addressable control modules 2 x 0,5 mm 2 or To be Control modules EMI-301, EMI-311, EMI-333, EMI-411 2 x 1, 5 mm - power supply or calculated Number and distances of the relay control modules define the 2 x 2, 5 mm conductor area and length of the power supply cable. - alarm line separately Mains connection: Mains supply cable 3 x 1,5 mm 2-230 ±10% V AC, 50-60 Hz - maximum power 160 VA - own circuit fuse 10 A 6657 1639GB1 31/43 19-2006