Technical Datasheet. P4 Pellet Boiler Models 8/15, 20/25, 32/38, 48/60, 80/100. Benefits at a Glance:

Similar documents
Technical Datasheet. P4 Pellet Boiler Models 8/15, 20/25, 32/38, 48/60. Benefits at a Glance:

Technical Datasheet. FHG-S Models 28, and 45. Benefits at a Glance: State Route 22 Salem, NY 12865

Technical Datasheet. Solo Innova Models 30 and 50. Benefits at a Glance: Solo Innova

Multi-Heat. Multi-Heat Datasheet Version Tarm Biomass 4 Britton Lane Lyme, NH 03768

Econoburn Technical Datasheet

HEATING WITH PELLETS Pellet Planning Guide.

PE1 Pellet. PE1 Pellet. Pellet boiler - Canada. PE1 Pellet APPROVED FOR EPA 2020 EMISSION LIMITS.

HEATING WITH WOOD Wood Boiler Planning Guide. Boiler Planning Plumbing Layouts Thermal Storage Clearances Wiring.

HEATING WITH WOOD Wood Boiler Planning Guide. Boiler Planning Plumbing Layouts Thermal Storage Clearances Wiring.

P4 Wood Pellet Boiler

Owner s Manual for. PennStoker

Boiler Technical Specifications (2013)

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

OWNERS MANUAL MODEL DO110 & DO180 IS CERTIFIED TO: Unit Serial # Purchased From Company Address

Bonus Plus. Installation and Operations Manual. Model 30. Wood-fired central heating boiler

Submittal Data GA Line AYF Series Commercial and Specialty Chiller-Heaters 2 or 4 pipe Gas Fired Absorption Chiller-Heater Cooling and Heating

CHIMNEY INSTALLATION. Technical Bulletin #1

SOLO PLUS. Installation and Operations Manual. Models 30, 40, and 60. Wood-fired central heating boiler

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

Operating Instructions

NY Thermal Inc. WF-200 Wood Fired Boiler

GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO.

1. GENERAL SAFETY RULES

CHIMNEYS AND VENTS CHAPTER 8

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

SOLO PLUS. Installation and Operations Manual. Models 30, 40, and 60. Wood-fired central heating boiler

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Vedo

C1050ES Tankless Water Heater

B.C.S. Shop Heaters 26, 30 & 36 (36 shown)

P4 Pellet. Pellet boiler. P4 Pellet.

Revitalize Building Mechanical Systems (4619)

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

CHAPTER 8 CHIMNEYS AND VENTS

PZ35RL BIOTECH THE FUTURE OF HEATING PZ 35 RL

CHAPTER 8 CHIMNEYS AND VENTS

P4 Pellet. Pellet boiler. P4 Pellet.

Technical Data Manual Model Nos. and pricing: see Price List

Project Name: Location: Engineer: Contractor: I. GENERAL

Owner s Manual. P4 Pellet Read and follow the operating instructions and safety information! Subject to technical change!

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

NAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA

P4000 Construction Heater

VF/VG700 Jumbo. Construction Heater. Installation and Maintenance Manual

BC Series II OIL-FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR US AND CANADIAN SALES

TABLE OF CONTENTS. Site preparation 2 Placement. 2 Chimney and stove pipe connections. 2

C1210ES Tankless Water Heater

Suggested Specifications Prestige Excellence 110

Fully-automatic Wood Pellet central heating

Biomass. Biomass solid fuel boiler range

MX 200. MX-200 Technical Specifications FEATURES:

RS Chimney Fan for Solid Fuel Applications

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

Mascot. Gas-Fired Residential and Commercial Wall-Mounted Boiler. Easy Installation, 96% Efficiency, Fully Condensing

INSTALLATION AND OPERATING INSTRUCTIONS. Ariterm 60+

Pellet boiler Electronic Modulation Automatic Cleaning Grinder system Easy Installation 4 power levels: 10, 16, 25, 43 kw

Computer Controller. The Bio-Burner has user regulated settings as well as built-in safety features to protect you and your burner.

mith Mills Smith Mills 6500A 6500A-4 OIL OR GAS CAST IRON BOILER/BURNER CAST IRON

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

Forced Draft Boiler Flue Gas Venting: Problems & Solutions. Presented by Steve Connor and Patrice Gouin January 27, 2016

Pellet Vent INSTALLATION INSTRUCTIONS

RS Chimney Fan for Solid Fuel Applications

Before selecting your stove, it is very important that you clearly identify what your needs are:

STARFIRE IV SERIES 4 WATER OIL FIRED CAST IRON BOILER

Raypak Residential Products

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...

TMB Baking TSV Gas Oven TAG Series. Contractor s Utility Requirements

MX 200. MX-200 Technical Specifications FEATURES:

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

Importance of a Draught Regulator

iq1001, Gen II Submittal Data

G124X - G234X - G334X Atmospheric Gas Boilers

PUSHING THE LIMITS OF WHAT IS POSSIBLE

AT SERIES C ELECTRIC BOILERS ABSOLUTE EFFICIENCY. TOTAL COMFORT! Save Money, Save Space, Save the Environment! RESIDENTIAL / LIGHT COMMERCIAL

Hubbell NX500 High Efficiency Gas Condensing Water Heater

Operation and Service Manual

Draft Control D R A F T C O N T R O L G U I D E w w w. f i e l d c o n t r o l s. c o m August 2007

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Before selecting your stove, it is very important that you clearly identify what your needs are:

PELLET STOVES & INSERTS. PELLET STOVES & INSERTS

2015 MECHANICAL CODE REQUIREMENTS

AFUE 95% Heating Input 50,000 to 200,000 Btuh

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E

iq251, Gen II Submittal Data

Copper Finned Gas-Fired Volume Water Heaters, Boilers and Commercial Pool Heaters. Low NOx, Quiet, Efficient, Space-Saving

Operating Instructions

HDG K SERIES. Wood pellet boiler. The perfect alternative to fossil fuels. Receive up to

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

INSTALLATION AND SERVICE MANUAL. Hot Water Heating Boilers Domestic Hot Water Supply Boilers 399, ,000 Btu/hr Models

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES

St. Croix Greenfield Installation Manual

940ES Tankless Water Heater

APPUZO RANGE HOOD INSTALLATION

Utica Boilers MAC Submittal

Commercial Gas Water Heaters

DOMESTIC WATER HEATER OIL FIRED

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

HERZ ECO-Line Heating with logs or wood pellets

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT

Transcription:

Boiler Models 8/15, 20/25, 32/38, 48/60, 80/100 Technical Datasheet FrÖling Boiler The P4 is a patented, wood pellet boiler available in five sizes with outputs from 35,800341,000 Btu/hr (cascaded systems up to1.4mm Btu/hr.) For both residential and commercial applications. Benefits at a Glance: Automatic ignition. Automatic sliding grate in combustion chamber. Automatic fuel feed. Automatic ash removal. Virtually selfcleaning Can be used with hot water baseboard, radiant floor, or hot air systems. Overall efficiencies of over 85%. Insulated cleaning door for heat retention. Soundproofing for almost silent operation. Covered by a 20year limited warranty. Model 80/100 built to ASME pressure vessel standard. Boiler Datasheet 18007829927 Version 0513

Boiler InformationBoiler Overview 1 2 3 4 5 8 6 7 9 10 11 12 13 1. Insulated cleaning door for heat retention. 2. EOS technology (Efficiency Optimization System) for high efficiency with automatic drive for continuous cleaning. 3. Lambdatronic P3200 microprocessor control. 4. Speed regulated induced draught fan for highest operating efficiency. 5. Spacious store container with automatic pellet feed. 6. Insulated cleaning door for excellent heat retention. 7. Easy access ash container for easy emptying of ash. Large container size for a longer emptying interval. 8. The larger boilers have ash removal screws which transport the ash to two closed ash boxes. 9. Patented multiplepass heat exchanger for variable boiler operation. The 3pass heat exchanger guarantees the highest possible ash separation. 10. Automatic sliding grate for ash removal. Almost maintenancefree operation. 11. Tested sealed slider guarantees safe operation of the boiler. 12. Automatic ignition 13. Special cyclone fitment with integrated silencer for quiet operation. Boiler Datasheet 18007829927 Version 0513 1

Specification DataTechnical Specifications Component Unit 8 15 20 25 32 38 48 60 80* 100* Rated heat output 35,800 50,800 68,200 85,300 109,000 129,650 163,780 200,000 273,000 341,000 Heating efficiency range Btu/ hr 10,500 35,800 10,500 50,800 20,500 68,200 25,600 83,300 30,400 109,000 30,400 129,650 57,300 163,780 57,300 200,000 82,000 273,000 102,000 341,000 Electrical Connection 240V / 60Hz fused 15A Electrical Consumption W 96 123 110 110 110 110 120 120 120 120 Weight of boiler 1) lbs 772 772 948 948 1168 1168 1676 1676 2425 2425 Water contents Gals 18.5 18.5 21 21 33 33 45 45 74 74 Maximum boiler temperature setting Minimum boiler temperature setting F 176 176 176 176 176 176 176 176 104 104 104 104 104 104 104 104 190 104 190 104 Boiler test pressure Psi 65 65 65 65 65 65 65 65 65 65 Recommended buffer tank size Gals 60 120 150 200 250 300 380 475 650 800 Permitted fuel Wood pellets Ø (1/4 5/16 ) 6mm. Must have a PFI Quality Rating of Premium or Super Premium. The pellets must be made from natural wood. *Built to ASME pressure vessel standard. Boiler Datasheet 18007829927 Version 0513 2

Specification DataComponents and Connections 3 5 1 G E F 4 D 2 B A C Pos. Description Unit 8 / 15 20 / 25 32 / 38 48/60 80/100 A Boiler supply connection 1 1½ 1½ 1½ 2 B Boiler return connection Inch 1 1½ 1½ 1½ C Drain ½ ½ ½ ½ D Air vent ½ ½ ½ ½ E Pellet suction line F Returnair line inch 2 2 2 2 G Flue gas pipe connection 5 5 6 6 2 1 1 2 8 1 Lambdatronic P 3200 control system 2 Switch box 3 Safety temperature limiter STL 4 Induced draught fan 5 Service interface Boiler Datasheet 18007829927 Version 0513 3

Specification DataDimensions A Dimensions Description Unit 8 / 15 20 / 25 32 / 38 48/60 80/100 L Length, boiler 1) inches 29⅛ 29⅛ 32¼ 35½ 39⅜ L1 Total length inc. induced draught fan 37 37 40⅛ 43¼ 42⅛ B Width, boiler 23⅝ 30⅜ 33¾ 40½ 48⅝ B * Width, boiler, inc. support for positioning unit 2) inches 27¾ 34½ 38 50¼ Total width, inc. suction B1 cyclone H Height, boiler 3) 46⅝ 53⅜ 56¾ 70½ 50⅜ 50⅜ 56⅜ 62⅜ H1 Total height, inc. suction cyclone 65⅜ 65⅜ 74⅞ 74⅞ H2 Height, flue pipe connection 53⅛ 53⅛ 60¼ 66⅜ H3 Height, supply connection 18⅛ 18⅛ 18⅛ 20¼ H4 Height, return connection inches 37 37½ 42¾ 48⅞ H5 Height, drainage connection 18⅛ 18⅛ 18⅛ 20¼ H6 H8 H15 Height, ventilation connection Height, induced draught fan connection Height, suction system connection 40½ 40½ 45½ 51½ 43 43 47⅞ 54⅛ 58¼ 58¼ 67¾ 67¾ A Flue pipe diameter inches 5 5 6 6 58¼ 82 67⅜ 74⅞ 70¼ 20½ 53½ 20½ 56¼ 58⅞ 67¾ 8 1) Corresponds to the minimum positioning length. 2) Corresponds to the minimum positioning width after removing the stoker assembly, suction cyclone and positioning unit. 3) Corresponds to the minimum positioning height after removing the stoker assembly, suction cyclone and positioning unit. Boiler Datasheet 18007829927 Version 0513 4

Specification DataSupply Air Connection Dimensions 9¼ 9 1 /16 8½ 12 12½ 4 4½ 4½ 6⅝ 7½ Description Unit 8 / 15 20 / 25 32 / 38 48/60 80/100 Supply air connection (external diameter) inches 3⅛ 4 5 6¼ 7⅞ Outside air kit connection (external diameter) inches 4 4 6 6 8 Specification DataFlue Pipe Position Description Unit 8 / 15 20 / 25 32 / 38 48/60 80/100 ALateral Distance inches 16½ 23 25½ 32 39⅜ BDepth Distance inches 3½ 3½ 3⅜ 3½ 3⅛ Boiler Datasheet 18007829927 Version 0513 5

Specification DataFlue Gas System Data Description Unit 8 15 20 25 32 38 48 60 80 100 Flue gas temperature ºF 284 302 302 302 320 320 320 338 320 338 Flue gas mass flow RL PL lb/hr 55 24 79 33 115 44 143 55 172 71 203 90 309 132 342 154 474 165 606 209 Required Draft RL PL inch WC Flue Pipe Diameter inch 5 5 5 5 6 6 6 6 8 8 RL=Rated Load, PL=Partial Load Specification DataBoiler Clearances E F G Dimensions Component Unit Distance A Minimum distance between suction cyclone and wall 12 B Maintenance range for ID fan 14 C Front of Appliance to Combustibles 36 D Minimum distance from side of boiler to wall inches 8 E Combustibles to Flue Pipe 18 F Ceiling to Appliance 18 G Ceiling to Suction Cyclone 12 Boiler Datasheet 18007829927 Version 0513 6

System Design Considerations Boiler Sizing It is critical to size the boiler properly. A proper, up to date heat load calculation is advised. An accurate history of building fuel usage over several years can help to calculate the proper size boiler. Be wary of using simple techniques based only on square footage. The heat load of a home can vary widely depending on age and type of heating system and location of the home. Boiler sizing is the responsibility of the installer. Tarm Biomass bears no responsibility for boiler sizing, but can provide sizing input. 1 Black Pipe or Stainless Chimney The chimney is the most critical factors in the successful operation of any solid fuel heater, including the P4 pellet boiler. A good chimney will provide a continuous and dependable draft to pull the exhaust gasses out of the building. The boiler must be connected to a stainless lined chimney (made with 316 or AL294C alloys) or to a FactoryBuilt Type UL 103 HT (ULC S629 in Canada) approved chimney. The chimney must be in good condition. If the boiler is connected to a dirty or inadequate chimney, it can present a serious fire hazard. All chimney connections must conform to NFPA standard #211. No other appliance should be connected to this flue unless allowed by the local code authority. Consult your local code inspector for chimney requirements and install the boiler in accordance with all applicable codes. The smoke pipe connecting to the chimney must be black or stainless (galvanized cannot be used), have a thickness of 24 gauge, and a rise of ¼ per foot toward the chimney connection. The installation of a barometric damper (1) is recommended. The barometric damper should be mounted under the mouth of the flue gas pipe, since an underpressure condition can always be found there. If mounted on smoke pipe connection, dust and ash could escape into the room. Outside Combustion Air Provision for outside combustion air may be necessary to ensure that fuelburning appliances do not discharge products of combustion into the house. Guidelines to determine the need for additional combustion air may not be adequate for every situation. If in doubt, it is advisable to provide additional air. The boiler has a connection for outside air. The boiler must not be installed in an area or room where there are flammable liquids or combustibles. Boiler Location The boiler is not suitable for outdoor installation. It must be located in a weathertight, protected space. The boiler must be placed on a level, noncombustible floor, such as a concrete slab on earth. If the boiler is placed near inhabited rooms, so that the flue gas can easily penetrate into these rooms, a carbon monoxide alarm must be installed that can give a warning regarding possible escapes of carbon monoxide into the inhabited rooms. Electrical For the P4 pellet boiler a 240 VAC, 60 hertz, 4 wire power supply is required. This electrical connection should be from a dedicated 15 amp, circuit breaker. A master service switch for the boiler, mounted on the wall in the proximity of the boiler, is recommended. Locally enforced electrical codes must be followed. Water Quality If water quality is poor, water treatment should be considered. Boiler system ph should be 8.08.6. An antifreeze can be utilized in areas where freezing could occur. Automotive or silicatebased antifreeze cannot be used. Use only anti freeze approved for heating systems. Using antifreeze can cause a loss in heating efficiency and some heating components within the system could be negatively impacted. Fuel The boiler is designed to burn low ash Premium or Super Premium wood pellets. The wood pellets must be made from natural wood and have a diameter 1/4 X 5/16 and a length 1½. A cyclone deduster is highly recommended on boilers larger than 32Kw to remove pellet dust. System Plumbing For the heating system piping, it is possible to use either copper or iron piping materials. The supply and return pipe should be insulated to avoid heat loss. In systems where plastic tubing is used, it must have an oxygen diffuser barrier. If nonoxygen barrier tubing is used, the boiler must be separated from the tubing by a heat exchanger. The boiler recommends a buffer tank to prevent short cycling of the boiler. Recommended sizing is listed under technical specifications. Boiler Datasheet 18007829927 Version 0513 7