utomation omponents nc.

Similar documents
Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

PRODUCT OVERVIEW SM-501 AT-A-GLANCE

PRODUCT OVERVIEW. SL-2000 AT-A-GLANCE MODEL NUMBER: SL-2000-N 4-Wire Ionization Duct Smoke Detector SL-2000-P 4-Wire Photoelectric Duct Smoke Detector

You in Control PRODUCT OVERVIEW

You in Control PRODUCT OVERVIEW SM-501 AT-A-GLANCE

Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector

HS-100 AT-A-GLANCE MODEL NUMBER: HS-100-N 4-Wire Ionization Duct Smoke Detector HS-100-P 4-Wire Photoelectric Duct Smoke Detector

RT-3000 SERIES NEMA 4X TYPE 4X ENCLOSURE WATERTIGHT CORROSION RESISTANT DUCT SMOKE DETECTORS

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS

DH500ACDC Intelligent Air Duct Smoke Detector Housing

DH100ACDCI Ionization Air Duct Smoke Detector

INSTALLATION AND MAINTENANCE

DH100ACDCI Ionization Air Duct Smoke Detector

SK-Duct Air Duct Smoke Detector

DH500 Intelligent Air Duct Smoke Detector Housing

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH400 Air Duct Smoke Detector

D2E Duct Smoke Detector

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range

E-PDD Duct Smoke Detector Installation Sheet

DH100LP Air Duct Smoke Detector with Extended Air Speed Range

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

DNR Duct Smoke Detector

DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

D343. Installation Instructions. Air Duct Smoke Housing

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

FX-PDD Duct Smoke Detector Installation Sheet

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

DNRECL Eclipse Duct Smoke Detector

DNR Duct Smoke Detector

DUCTSD Duct Smoke Detector

7251DH Intelligent Air Duct Smoke Detector

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

TS93 EMR WITH SMOKE DETECTOR

Installation Instructions

8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION

DNRHS Intelligent Air Duct Smoke Detector

Wiring Instructions (01-09)

Duct smoke housing, 2-wire D340/D340P

DNR-AUS Duct Smoke Detector

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Application Data ! WARNING FACTORY INSTALLED SMOKE DETECTORS FOR SMALL AND MEDIUM ROOFTOP UNITS 2TO25TONS TABLE OF CONTENTS PART NUMBERS

INSTRUCTIONS. Duct Mount Kit Q900. Description. Operation

TrueAlarm Analog Sensing

Installation Instructions

Instructions. Duct Mount Accessory Q Rev: 11/

Installation Instructions Models FDBZ492, FDBZ492-R and FDBZ492-HR

, -9686, -9688, -9755, Duct Detector/Sensor Installation Instructions

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

MANUAL RESET ALARM RELEASE BOX

MANUAL RESET ALARM RELEASE

HEATER E L E CT R I C DUCT RENEWAIRE EVERYWHERE EVERY GEOGRAPHY, EVERY CLIMATE, EVERY HOME, EVERY BUILDING AND EVERY APPLICATION

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

MANUAL RESET ALARM RELEASE

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

Model 17A00 Expansion Enclosure

Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

Indirect gas-fired air heater

Installation Instruction Venturi-Air Duct Kit. (Part No. S )

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

SILENT KNIGHT. IntelliKnight Smoke Detector Cleaning and Testing Instruction. Equipment Needed. Testing Equipment. Cleaning Equipment

TrueAlarm Analog Sensing

AnaLASER II Detector. Protection Systems. A UTC Fire & Security Company. High-Sensitivity Smoke Detector (HSSD ) FEATURES DESCRIPTION

Duct and Rough Service Carbon Monoxide Sensor

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

PULL STATION SERIES DIE-CAST METAL MANUAL PULL STATIONS

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Filtrex A Smoke Detector for Difficult Environments

A GUIDE FOR PROPER USE OF SMOKE DETECTORS IN DUCT APPLICATIONS. Application Guide DUCT SMOKE DETECTORS

ENERVEX ADC100 DRAFT CONTROL

Addressable Detectors & Bases

Series. Access Power Controllers. Installation Guide

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

READ AND SAVE THESE INSTALLATION INSTRUCTIONS

DH100ACDCLPX Air Duct Smoke Detector with Extended Air Speed Range

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

DUCT SMOKE DETECTOR D4120

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

RELEASE DEVICE CONTROLS

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

Instructions for the BASIC BCRW Fan, Sizes General

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

Installation Guide for models:

LASER ASPIRATED SMOKE DETECTOR

Series 65 Product Guide MAN 3036

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Installation Smoke Detector ELQZ , GOLD

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

MR-2602 Two Zone Fire Alarm Control Panel

Field Start-Up Sheet Direct Fired Gas Equipment

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

Transcription:

A CI utomation omponents nc. P R ODUC T OV E R V IE W P R ODUC T A P P L IC AT ION: T he S L-00 S eries Duct S moke Detectors provide early detection of smoke and products of combustion present in the air moving through an VAC duct in commercial, industrial and residential applications. These devices are designed to prevent the recirculation of smoke in areas by the air handling systems, fans and blowers. C omplete systems may be shut down in the event of smoke detection. NOT E F or the correct installation of a duct smoke unit, please refer to the NF PA 72E (S tandard for Automatic F ire Detectors) and NF PA 90A (S tandard for Installation of Air C ondition and Ventilation S ystems.) This detector is not intended for open area protection nor should it be used for early warning detection or replace a regular fire detection system. Air P roducts and C ontrols Inc. provides a special U.L. 50 listed, NE MA 3R rated weatherproof enclosure separately (Model WP -00) which should be used in appropriate outdoor applications for protection from the elements. Other installations above the roof line (attics, banjo type roofs, etc.) do not require the special Model WP -00 weatherproof enclosure as long as the Air P roducts and C ontrols Inc. duct smoke detectors are not exposed to dripping water or other environmental elements. The Model WP -00 weatherproof enclosure should be used in all applications where environmental elements are a concern or local code requires a weatherproof enclosure for proper installation. All installations of our duct smoke detectors and weatherproof enclosures should be done in accordance with all applicable electrical and building codes. P R ODUC T DE S C R IP T ION: The S L-00 S moke Detector is fitted with a mounting base that will accept an Ionization Detector ead Model # 5500-225AP O or P hotoelectric Detector ead Model # 5500-328AP O. T he duct unit supports 2 sets of form C and form A Alarm C ontacts and form C Trouble C ontact. T he trouble contact supervises the presence of the input power and removal of the detector head. T E T R OUB L E C ONTA C T S (T E R MINA L S 4-5-5) A R E S OWN IN T E NON-E NE R G IZE D C ONDIT ION. T he trouble contact will not operate in the event of a smoke alarm. INS TALLAT ION INS T R UC T IONS F OR UNIV E R S AL DUC T S MOK E DE T E C TOR S MODE L S L-00-N Ionization MODE L S L-00-P P hotoelectric The S L-00 Duct Detector models S L-00-N and S L-00-P will operate on one of the following input voltage sources: 24VAC, 24VDC, 5VAC and 230VAC. T he duct smoke detector units are designed to operate in duct widths from 2 inches to 0 feet wide with an air velocity between 00 and 4,000 feet per minute. To verify correct installation, the pressure differential between the input and exhaust tubes should be measured using a Magnehelic pressure gauge or equivalent. An acceptable reading must be between 0.0 and.2 inches of water. F or a S moke Duct Detector unit to operate correctly, it must be installed 6 duct widths from any obstruction i.e. elbows, deflector plates, filters, dampers, etc. In situations where the criteria cannot be met, deviations are acceptable providing they meet the pressure differential requirements. S A MP L ING T UB E S : The principal of operation of a duct detector is based on the Venturi effect. Two tubes extend into the VAC duct. Air flowing through the duct is forced into the air intake tube via the air intake holes, and passes over the detector head. T he air will be drawn out via the exhaust tube back into the VAC duct. (7 exhaust tube provided in the installation kit.) When the particles of smoke suspended in the air stream reach the alarm threshold of the detector head, the unit will go into alarm. DUC T UNIT INS TA L L AT ION DUC T S MOK E L OC AT ION P R E -R E QUIS IT E S : This guideline contains general information on duct smoke detector installation, but does not preclude the NF PA documents listed. Air P roducts and C ontrols Inc. assumes no responsibility for improperly installed duct detectors. To determine the correct installation position for a S L-00 Duct S moke Detector, the following factors must be considered. ) A uniform non turbulent airflow of between 00 ft/min to 4,000 ft/min. must be present in the VAC duct. To determine the duct velocities examine the engineering specifications that define the expected velocities or use an Alnor model 6000P velocity/meter (or equivalent). 2) In order to prevent stratification, duct smoke units, where possible, must be located a minimum of six duct widths down stream from a source of turbulence i.e. elbows, deflector plates, filters, dampers, and inlets. In installations where it is impossible to adhere to the six duct width requirement, units can be installed closer but as far from inlets, bends or deflector plates as possible. S hould this situation arise, check velocity readings in the duct prior to the duct smoke unit installation. E nsure the duct smoke unit pressure differential complies with the unit specifications. The pressure differential between the input sampling tube and exhaust tube for the S L-00 series duct smoke unit should be greater than 0.0 inches of water and less than.2 inches of water. INS T AP -4;R ev.05/02

3) Identify a location for the installation of the duct unit that will permit easy access for viewing and serviceability. 4) Install duct units in the return air side of an VAC unit prior to the air being exhausted from the building or diluted with outside air. 5) When installing duct smoke units down stream of filters, fires occurring in the filters will be detected, but if the filters become blocked insufficient air flow through the duct unit will prevent the correct operation of the duct detector. 6) Where possible, install duct detectors upstream of air humidifiers and downstream of dehumidifiers. 7) To prevent false alarms, the duct detector should not be mounted in areas of extreme high or low temperatures, in areas where high humidity exists or in areas where the duct may contain gases or excess dust. Tube Support ole Only for Ducts Greater than 3 Feet Wide. Bend or Other Obstruction Air Flow Insert Red Stopper This End of Inlet Tube Duct Width Air Flow Direction 6 Duct Widths Minimum Inlet Tube oles Face Air Flow Set Screw Exhaust Tube Installed Downstream of Air Flow. Do Not Insert Red Stopper. SL-00 2650 Duct Duct Smoke Detector Smoke Detector SAMPLING TUBE ASSEMBLY: Sampling tubes are to be ordered separately in one of the 3 standard lengths. STN-2.5 For duct widths of.0 TO 2.5 STN-5.0 For duct widths of 2.5 TO 5.0 STN-0.0 For duct widths of 5.0 TO 0.0 The standard sampling tubes are steel tubes with air intake holes drilled down the entire length of the tube. These tubes must be cut to length and must span the entire width of the duct. Sampling tubes over 3.0 feet must be supported on the opposite side of the duct. To ensure the correct operation of the sensing tube, the red end cap (red stopper in installation kit) must be inserted in the end of the air intake sampling tube. DUCT PREPARATION: For ease of duct unit installation, remove mounting template from the installation kit. Remove paper backing from the mounting template and affix it to the duct at the desired location. Using the template as a guide, drill 2 mounting holes (3/32 diam.) for the 2 X /2 sheet metal screws packaged in the installation kit. Drill or punch /4 holes for sampling tubes, using the template as a guide. Clean all holes. MOUNTING DUCT SMOKE DETECTOR Mount the housing to the duct using 2 #2 x /2 sheet metal screws. Install the intake tube making sure the holes are facing the air flow. Tighten the latch screw to secure the tube. Install the exhaust tube. Tighten the latch screw to secure the tube. AIR SAMPLING VERIFICATION: To ensure correct operation of the duct unit use a Magnehelic differential pressure gauge or Dwyer model 4000 to determine the differential pressure between the inlet and exhaust tubes. The differential pressure between the two tubes should be greater than 0.0 inches of water and less than.2 inches of water. This duct smoke detector is shipped with a separate velocity adapter insert, found in the installation kit. Installing this adapter will allow the duct detector to operate at extremely low air velocities - outside of the range referred to in the attached installation instructions. To use the adapter, simply insert it into the slots provided inside the detector housing so that the adapter fits snugly over the smoke detector head. Unless your system is consistently operating in the slower velocity range, we recommend that the adapter not be inserted. If you experience false alarms at higher velocities with the adapter in place, the adapter should be removed. Please use the following chart for guidance on when the velocity adapter should be used. For reference, the speeds indicated are intended to represent the velocity of air within the duct under normal operational conditions. 2650-760 2650-76 00 ft/min 300 ft/min 500 ft/min,000 ft/min 2,000 ft/min 3,000 ft/min 4,000 ft/min UL Listed without insert installed (300-4,000 ft/min) UL Listed with insert installed (00-2,000 ft/min) UL Listed without insert installed (,000-4,000 ft/min) UL Listed with insert installed (00-4,000 ft/min) INST AP-4;Rev.05/02 2

ELECTRICAL INSTALLATION WIRING Prior to connecting power to the SL-00-N and SL-00-P duct units, determine the correct input voltage and ensure it is connected to the correct terminals. (Refer to power connections) 24VAC/DC,Terminals (9, 0); 5VAC, Terminals (5,, G); 230VAC, Terminals (2,, G). TERMINAL CONNECTIONS: RESET INPUT (+) PILOT OUT 24 VDC COM (-) 0A *TROUBLE S NC NO C 0A POWER INPUT 24 VAC/VDC NC NO (-) (+) C GROUND POWER INPUT 2/240 VAC VAC 2 3 4 5 6 7 8 9 0 G 2 5 2 5 6 7 8 L NO C NC C (-) (+) (+) 2A AUX 0A POWER OUT *TROUBLE S ARE SOWN IN NON-ENERGIZED CONDITION. UNDER NORMAL OPERATION S WILL BE REVERSED. CAUTION: For terminals (7, 8, 8), (6, 6, 7), (, ) do not use looped wire under terminals. Break wire run to provide supervision of connections. To test the correct operation of the duct smoke unit, excluding the detector head (see functional testing page 3) remove detector head and connect one of the appropriate dedicated power sources to the applicable terminals (See above). Replace detector head and cover, the unit will be energized (The green LED will be illuminated). When pressing the test/reset button the red alarm LED will be illuminated. In the event of a fire alarm, certain equipment may have to be shut down. A shut down will be achieved by interrupting the supply source to that particular piece of equipment when wired as indicated below. EXAMPLE: FAN Fan Supply Source 7 8 8 In alarm, 7 and 8 will open, interrupting supply to fan NC C NO RELAY SL-00 Duct Unit TEST PROCEDURES OPERATIONAL TESTING To determine the correct operation of the SL-00 Duct Smoke Detector, ensure power is connected and the green pilot LED is illuminated. The LED on the detector head flashes during the standby mode. The LED on the detector head will be permanently illuminated when smoke is detected and the head is in alarm. With the air handling unit shut down, and the clear cover removed, press and hold the test/reset button and the cover removal switch on the SL- 00 Duct Unit. The red alarm LED on the circuit board will be illuminated and the alarm relay outputs will change state. Using a multimeter set to OMS (or continuity buzzer function on the meter) place the meter probes on the following terminals and ensure the contacts are closed (continuity) (8, 8), (6,7) when releasing the test/reset button these contacts will open. INST AP-4;Rev.05/02 3

The trouble contacts (4, 5, 5) will not change state in the event of a fire alarm, operational or functional testing. The trouble contacts can be tested by rotating the Apollo detector head counter-clockwise and removing the detector head. This action will extinguish the pilot (green) LE D and cause the trouble contacts to change state, (4, 5) will be closed (continuity) (5, 5) will be open circuit. R eplacing the detector head and rotating it clockwise until it locks, will cause the green pilot LE D to be illuminated and the unit will be operational, terminals (4, 5) will be open circuit and (5, 5) will be closed (continuity). F UNC T IONA L T E S T ING Once operational testing is concluded the unit requires functional testing to determine the correct operation of the detector head. MA G NE T T E S T ING : P lace the magnet provided with the instruction kit on top of the housing between the raised sections above the detector head (as indicated on the unit cover). Allow at least five (5) seconds for alarm initiation. R emove magnet and reset detector. S MOK E T E S T ING : Using smoke test canister with testing nozzle (available from Air P roducts and C ontrols Inc. P art Number T G -0), insert the test gas nozzle into the test point on the unit cover. P ress can against cover to release gas into chamber. C AUT ION: Do not spray gas for more than /2 second. Overuse of test gas facility will result in detector contamination. After 5 to seconds the detector head will go into alarm, illuminating the detector head LE D and causing the duct unit functions to operate, relays will change state and the remote accessories if attached will function. P lease allow several minutes for the gas to evacuate the chamber before the detector may be reset. If no test gas is available to conduct the testing, remove cover and, while holding the cover removal switch, blow smoke from a cotton wick or punk directly at the head to cause alarm. T he alarm indicator will illuminate within one minute. S hould testing be required for simulated fire conditions, smoke bombs placed in the duct may not be suited for the particular detector head selected and installed. Ionization Detector ead 5500-225AP O utilizes a radioactive source as its means of detection and will detect smoke particles of between. and micron in size. P hotoelectric Detector ead 5500-328AP O operates on the principle of light scatter and will detect smoke particles of between and 0 microns in size. When purchasing smoke bombs for functional testing, ensure smoke particle sizes comply with the criteria as described above. MAINTE NANC E E ach installation location must be assessed on its own merits. If the protected area is of a very dirty nature then the S L-00 Duct units will have to be checked and cleaned on a Quarterly basis or when cleaning is required. As a guideline the detector head should be cleaned every six months or as required. The best methods of cleaning are to vacuum the detector head thoroughly or to blow the detector head out using compressed air. Do not use chemicals to clean the detector head housing as this could contaminate the detector head and damage the casing. S ensing tubes must be inspected and cleaned in accordance with the schedule as determined above, to allow the free flow of air through the sensing tube. Model Number: P R ODUC T S P E C IF IC AT IONS S L-00-N Ionization 24V AC /DC, 5V AC, 230V AC S L-00-P P hotoelectric 24V AC /DC, 5V AC, 230V AC Detector Model Number: S 65 Ionization Detector ead 5500-225AP O S 65 P hotoelectric Detector ead 5500-328AP O P OWE R R E QUIR E ME NT S QUIE S C E NT C UR R E NT A L A R M C UR R E NT 24V AC 39.4mA 24V AC 28.7mA 24V DC.5mA 24V DC 59.3mA 5V AC.8mA 5V AC 27.0mA 230V AC 7.9mA 230V AC 6.0mA R E L AY C ONTA C T R AT ING S : Alarm contacts: 2 form C rated at 0AMP S @ 5V AC resistive, F orm A @ 2AMP S Trouble contacts: S et form C rated at 0AMP S @ 5V AC resistive Air velocity: 300 to 4000 ft/min Ambient temperature: Model S L-00-N 32 o F to 55 o F (0 o C to 68 o C ) : Model S L-00-P 32 o F to 00 o F (0 o C to 38 o C ) umidity: 0% to 85% R.. no condensation Material: G ray plastic backbox with clear plastic cover Dimensions: L- /2, X -4 /2, Depth - 2 /4 Max. net wt.: 3 lbs. R adioactive element: F or S L-00-N (Ionization model) Americium 24, 0.9 micro curie Do not expose to corrosive atmospheres. INS T AP -4;R ev.05/02 A CI utomation omponents nc. 4 2305 Evergreen Road Middleton Industrial Park Middleton, WI 53562 (608) 83-2585 Phone (608) 83-7407 Fax or TOLL FREE @ -888-WORK-ACI 9675224

REMOTE ACCESSORY WIRING 2 2 LED vvv _ AND OR _ ORN/ STROBE GREEN PILOT LED vvv (WEN NOT INTERCONNECTED) PILOT 4 KEY OR PUS BUTTON TEST/RESET SWITC JUMPER 5 YELLOW TROUBLE LED vvv TROUBLE S CANNOT BE CONNECTED TO FIRE PANEL WEN USING TIS OPTION TEST / RESET EAD OR COVER REMOVAL Fire Alarm Control Panel Wiring 5 5 5 5 UL Listed Fire Alarm Control Unit EOL End of Line Fig. SL-00 # SL-00 #2 Remote Accessories Approved For Use With This Detector MS-RA Remote Alarm MS-R/KA/P/R Remote Alarm, Pilot, orn, key-operated Test/Reset Switch MS-RA/R Remote Alarm, push button Test/Reset Switch MS-R/P/A Remote Alarm, Pilot, orn MS-RA/P/R Remote Alarm, Pilot, push-button Test/Reset Switch MS-R/KA/P/A/T Remote Alarm, Trouble, Pilot, orn, key-operated Test/Reset Switch MS-KA/R Remote Alarm, key-operated Test/Switch SP24-575R orn/strobe, red housing, clear cover MS-KA/P/R Remote Alarm, Pilot, key-operated Test/Reset Switch SP24-575O orn/strobe, white housing, opaque cover MS-RA/P Remote Alarm, Pilot SP24-575W orn/strobe, white housing, clear cover MS-R Remote Alarm orn INST AP-4;Rev.05/02 6

DETECTOR INTERCONNECTION WIRING COMMON FUNCTIONS Unit # Unit #2 Unit #3 Unit # Unit #2 Unit #3 2 2 2 2 2 2 ALL RELAYS OPERATE WIT SINGLE INDIVIDUAL ORN/STROBE OPERATE ON ED DETECTOR ONLY 30 DETECTORS MAX ALL RELAYS OPERATE WIT SINGLE ALL ORN/STROBES OPERATE WIT SINGLE 0 DETECTORS MAX Unit # Unit #2 Unit #3 Unit # Unit #2 Unit #3 2 2 2 NORMALLY OPEN RESET SWITC ALL RELAYS OPERATE WIT SINGLE 30 DETECTORS MAX COMMON TEST/RESET 30 DETECTORS ONLY INST AP-4;Rev.05/02 5