Tag Data - Split System Air Conditioning Units (Large) (Qty: 6) Item Tag(s) Qty Description Model Number A1 20 ton vfd 6 6-25 Ton Unitary Split Systems ( SSC2 TTA24004H00-TWE240E404A TTA Air Condensing Outdoor Unit 20 Ton Nominal Cooling Capacity R410A Dual Compressors-R410A Microchannel 460 Volt 3 Phase 60 Hertz Hailguard factory installed Electromechanical controls TWE Air Handler Unit 20 Ton Nominal Cooling Capacity R-410A Dual Circuit - R410A 460 Volt 3 Phase 60 Hertz VFD Oversized Motor FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13
Performance Data - Split System Air Conditioning Units (Large) Tags 20 ton vfd MCA - cooling only unit (A) 47.00 MOP - cooling only unit (A) 60.00 Min. Cond. operating weight (lb) 762.0 Max. Cond. operating weight (lb) 904.0 Condensing unit type Cooling only unit Airflow (cfm) 8000 Elevation (ft) 5430.00 Cooling EDB (F) 90.00 Cooling EWB (F) 73.00 Ambient (F) 105.00 Gross total capacity (MBh) 256.59 Gross sensible capacity (MBh) 200.39 Latent capacity (MBh) 55.83 Net total capacity (MBh) 236.18 Net sensible capacity (MBh) 180.35 Cooling LDB (F) 68.42 Cooling LWB (F) 64.50 Saturated suction temp (F) 52.88 Discharge temperature (F) 127.05 Metering device Expansion valve External Static Pressure (in H2O) 2.000 Supply fan power (bhp) 6.48 Indoor motor RPM (rpm) 1236 MCA - A.H. (A) 11.30 MOP - A.H. (A) 25.00 Evaporator motor FLA (A) 9.00 Evaporator face area (sq ft) 21.65 Evaporator face velocity (ft/min) 370 Evaporator fin spacing (Each) 168.00 Evaporator rows (Each) 3.00 Indoor motor power (kw) 5.90 Condenser Fan Power (kw) 12.32 Compressor power (kw) 22.52 Total power (kw) 27.37 EER @ AHRI (with air handler) (EER) 10.0 EER @ AHRI (cond. unit only) (EER) 12.1 IPLV @ AHRI (with Air Handler) (IPLV) 11.1 Compressor 1 RLA (A) 18.60 Compressor 2 RLA (A) 18.60 Condenser motor 1 FLA (A) 2.50 Condenser motor 2 FLA (A) 2.50 Min. A.H. operating weight (lb) 818.0 Max. A.H. operating weight (lb) 891.0 Fan motor heat (MBh) 7.91 FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 4 of 13
Mechanical Specifications - Split System Air Conditioning Units (Large) General - TWE Completely Factory Assembled Convertible for Horizontal or Vertical Configuration Convertible for Cooling Only or Heat Pump Application Convertible for Left or Right External Connections (Refrigerant and/or Electrical) Convertible for Front or Bottom Air Return Nitrogen Holding Charge Certified and Rated in Accordance with AHRI and DOE Standards Certified to UL 1995 for Indoor Blower Coil Units Casing - TWE Zinc Coated, Heavy Gauge, Galvanized Steel Weather Resistant Baked Enamel Finish Access Panels with Captive Screws Completely Insulated with Foil Faced, Cleanable, Fire Retardant, Permanent, Odorless Glass Fiber Material Captured or Sealed Insulation Edges Electrical Connection Bushings or Plugs Refrigerant Connection Bushings or Plugs Withstand Elevated Internal Static Pressure Refrigeration System - TWE Single or Dual Circuit Distributor(s) Thermal Expansion Valves (TXVs) Evaporator Coil - TWE 3/8" Internally Enhanced Copper Tube Mechanically Bonded to Lanced Aluminum Plate Fins Factory Pressure and Leak Tested to 449 psig. Draw-Through Airflow Dual Circuits Are Interlaced/Intertwined Double Sloped, Removable, Cleanable, Composite Drain Pan Four Drain Pan Positions Indoor Fan - TWE Double Inlet, Double Width, Forward Curved, Centrifugal Type Fan Dual Fans On 10.4-20.912.5-25 Ton Air Handlers Adjustable Belt Drive Permanently Lubricated Bearings Indoor Motor - TWE Adjustable Motor Sheaves Fixed Motors Sheaves (SZVAV and 2-Speed VFD) Thermal Overload Protection Permanently Lubricated Bearings Meet Energy Policy of 1992 (EPACT) Optional Over Sized Motors for High Static Applications Controls - TWE Completely Internally Wired Numbered and Colored Wires Magnetic Indoor Fan Contactor Low Voltage Terminal Strip Single Point Power Entry Evaporator Defrost Control Filters - TWE Access From Side Coil Panels Filters Slide on Rack One Inch (1"), Throw-Away Filters on 4.6-8.335-10 Ton Units Filter Rack Convertible to Two Inch (2") Capability on 5-10 Ton Units FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 5 of 13
Two Inch (2"), Throw-Away Filters on 10.4-20.912.5-25 Ton Units TTA Microchannel - General Weatherproofed steel mounting/lifting rails Hermetic scroll compressors Microchannel condenser coils on select models Plate fin condenser coils Fans and motors Standard operating range 50-125 F (min. 0 F with low ambient accessory) Nitrogen holding charge Certified and rated in accordance with AHRI and DOE standards Certified to UL 1995 TTA Microchannel - Casing Zinc coated, heavy gauge, galvanized steel Weather resistant baked enamel finish Meets ASTM B117, 672 hour salt spray test Removable single side maintenance access panels Lifting handles in maintenance access panels Unit base provisions for forklift and/or crane lifting TTA Microchannel - Condenser Coil (Microchannel) Microchannel coils burst tested by the manufacturer Coils shall be leak tested to ensure the pressure integrity Factory pressure and leak tested to 660 psig Perforated steel hail guards available (factory installed option or field installed accessory) TTA Microchannel - Condenser Fan 26" or 28" propeller fan(s) Direct drive Statically and dynamically balanced TTA Microchannel - Condenser Motor(s) Permanently lubricated totally enclosed or open construction Built-in current and thermal overloads Ball or sleeve bearing type TTA Microchannel - Controls Choice of electromechanical or microprocessor Completely internally wired Numbered and colored wires Contactor pressure lugs or terminal block Unit external mounting location for disconnect device Single point power entry TTA Hail Guards Condenser coil protection from hail, vandals, etc. Perforated, painted galvanized steel Factory installed FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 6 of 13
Unit Dimensions - Split System Air Conditioning Units (Large) SEE NOTE 2 NOTES: 1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72". RECOMMENDED SERVICE CLEARANCE 48" 2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT 3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING) SEE NOTE 3 HAIL GUARD (OPTIONAL) SERVICE CLEARANCE 48" (SEE NOTE 1 FOR CLEARANCE) DETAIL A 95 7/16" WITH HAIL GUARD 41 7/16" SERVICE PANEL 46" WITH HAIL GUARD 44" HAIL GUARD (OPTIONAL) HAIL GUARD (OPTIONAL) 45 1/8" SERVICE PANEL 6 5/8" 3 3/8" 41 3/8".16".8" 9" 25 11/16" 9" 93 5/16" 9 1/4" 6 13/16" 7/16" DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES - 4 PLACES) LINE VOLTAGE 1 3/16" CONTROL WIRING SERVICE PANEL SIDE SUCTION LINE REFRIGERANT ACCESS 39 7/8" 41 5/8" BOTTOM OF UNIT 36 7/8" 41 1/2" 18 3/4" 14 5/8" 12 9/16" 5 9/16" 4 3/8" LIQUID LINES 3" 2 3/16" 6 13/16" 87" 93" SUCTION LINE FRONT DETAIL A DIMENSIONAL DETAIL 6 5/16" 3 11/16".96" 20 TON COOLING CONDENSER (DUAL COMPRESSOR) DIMENSIONAL DRAWING FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 7 of 13
Unit Dimensions - Split System Air Conditioning Units (Large) ELECTRICAL DATA CONDENSER ELECTRICAL DATA COMPRESSOR MOTOR CONDENSER FAN MOTOR Model: Unit Operating Voltage: Minimum Circuit Ampacity: Maximun Fuse Size: Maximun Circuit Breaker: TTA240H4 414-506 47.0 60.0 60.0 No.: Volts: Phase: Amp-RLA: Amp-LRA: 2 460 3 18.6 142.0 No.: Volts: Phase: Amp-FLA: Amp-LRA: 2 460 1 2.5 5.8 GENERAL DATA CONDENSER COOLING PERFORMANCE (1)(2)(3)(4)(5) Matched Air Handler: Condensing Unit Only: ARI Net Cooling Capacity: Matched Air Handler (EER): Condensing Unit Only (EER): System Integrated Part Load Value (IPLV): Condensing Unit Only (IPLV): System KW Condensing Unit KW: Systern IEER: 256000 248000 248000 10.0 12.1 - - 24.8 20.5 11.1 COMPRESSOR Number: Motors/HP (each): Motor RPM: No. Compressor / Tons: SYSTEM DATA (7) No. Refrigerant Circuits: Suction Line (in.) OD: Liquid Line (in.) OD: 2 - - 2/10.0 2 1 3/8" 1/2" OUTDOOR COIL OUTDOOR FAN Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI 13/16" 44 5/16" 1/23 No. Used/Diameter (in.): Drive Type/No. Speeds: CFM: No. Motors/HP: Motor RPM: 2 / 28" DIRECT / 1 15500 2 / 1 1,100 REFRIGERANT CHARGE (Fld Supplied) (7)(8) TYPE: (Circuits #1): (Circuits #2): R-410A 11.6 lb 12" NOTES: 1. Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Ratings shown are tested and certified in accordance with AHRI 2. Standard 340/360 or 365 certification program. 3. Condensing Unit Only Gross Cooling Capacity rate at 45 F saturated suction temperature and at 95 F ambient. 4. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft. of OD interconnecting tubing. EER is rated at AHRI conditions and in accordance with DOE test procedures. 5. Integrated Part Load Value is based on AHRI Standard 340/360 or 365. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at AHRI rated CFM. 6. Sound Rating shown is tested in accordance with AHRI Standard 270. 7. Refer to refrigerant piping program for line sizing and line length. 8. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft. of interconnecting refrigerant lines. All units are shipped with a small nitrogen holding charge only. FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 8 of 13
Unit Dimensions - Split System Air Conditioning Units (Large) 31 1/8" SUPPLY OPENING 16 5/16" 5" 18 7/8" NOTES: 1 PANEL DEPTH 1/2" (TYP.ALL PANELS). 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT. 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT. 4. 1" FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 5. 1" FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION. 92 9/16" 54 15/16" DUCT FLANG 1" HIGH 21" SIDE RETURN SIDE RETURN 20 15/16" BOTTOM RETURN BOTTOM RETURN 3" 2 15/16" CONTROL WIRING 31 1/8" 4 3/4" 83 1/8" 4 3/4" 83 1/8" LINE VOLTAGE CONTROL BOX ACCESS PANEL 12 13/16" DRAIN CONNECTION FOR HORIZONTAL (SEE NOTE 2,3,5) REMOTE BULB TXV SUCTION LINE COPPER LIQUID LINE FIELD CONNECTION COPPER SUCTION LINE FIELD CONNECTION 21 3/8" 21 13/16" 15 7/8" 18 3/8" 19 1/8" 12 7/8" 25 1/2" 25 1/2" 21 13/16" 19 1/8" 18 3/8" 15 7/8" FILTER ACCESS PANEL 22" MIN. DISTANCE BOTH SIDE LIQUID LINES SEE NOTES 2,3,4 1 11/16" 1 15/16" 3 3/8" 4" 92 9/16" (4) - HOLE FOR HORIZONTAL SUSPENSION 1 9/16" 1 7/8" 3 1/4" 3 7/8" SEE NOTES 2,3,4 1 11/16" 89 3/16" 9 5/8" SUPPLY OPENING SIDE RETURN (4) HOLE FOR HORIZONTAL SUSPENSION 71 7/8" 50 13/16" SIDE RETURN FILTER 11 7/16" BOTTOM RETURN SUPPLY VERTICAL - RETURN HORIZONTAL / RETURN VERTICAL BOTTOM RETURN SUPPLY HORIZONTAL - RETURN VERTICAL / RETURN HORIZONTAL 20 and 25 TON AIR HANDLER (DUAL CIRCUIT) DIMENSIONAL DRAWING FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 9 of 13
Unit Dimensions - Split System Air Conditioning Units (Large) AIR HANDLER ELECTRICAL DATA CONDENSER ELECTRICAL DATA Model: Unit Operating Voltage: Minimum Circuit Ampacity: Maximun Fuse Size: Maximun Circuit Breaker: TWE240 414-506 11.0 15.0 15.0 EVAPORATOR FAN MOTOR (9) No.: Volts: Phase: Motor HP: Amp-FLA: Amp-LRA: SYSTEM DATA GENERAL DATA INDOOR COIL - TYPE No. Refrigerant Circuits Suction Line (in.) OD Liquid Line (in.) OD 2 1 3/8" 5/8" Tude Size: Face Area: Row/FPI Refrigerant Control Drain Connection Size 3/8" 21 11/16" 3 / 14 EXPANSION VALVE 1" PVC INDOOR FAN FILTER Type: No. Used/Diameter x Width: Drive Type/No. Speed: CFM: No. Motor: Motor HP - Standard/Oversized: Motor RPM: Motor Frame Size: CENTRIFUGAL 2 / 15"X15" Belt/VFD Variable 8000 1 5.0 / 7.5 3450/3470 56HZ/184T Type: Furnished: No. Size Recommended: THROWAWAY YES (4) 16"X25"X2" (4) 16"X20"X2" HEATER DATA ELECTRICAL DATA Heat Rating (kw): Control Stages: Power Supply: Minimum Circuit Ampacity: Maximun Fuse Size: Maximun Circuit Breaker: Notes: 1. KW ratings are at: 208/240V for 208-230V air handlers 480V for 460V air handlers 600V for 575V air handlers For other than rated voltage, capacity = ( Voltage Rated Vpltage ) x 2 Rated Capacity 2. Any power supply and circuits must be wired and protected in accordance with local electrical codes. 3. The HACR circuit breaker is for U.S.A. installations only. NOTES: 1. Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. 2. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Ratings shown are tested and certified in accordance with AHRI Standard 340/360 or 365 certification program. 3. Condensing Unit Only Gross Cooling Capacity rate at 45 F saturated suction temperature and at 95 F ambient. 4. AHRI Net Cooling Capacity is calculated with matched blower coil and 25 ft. of OD interconnecting tubing. EER is rated at AHRI conditions and in accordance with DOE test procedures. 5. Integrated Part Load Value is based on AHRI Standard 340/360 or 365. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at AHRI rated CFM. 6. Sound Rating shown is tested in accordance with AHRI Standard 270. 7. Refer to refrigerant piping program for line sizing and line length. 8. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft. of interconnecting refrigerant lines. All units are shipped with a small nitrogen holding charge only. 9. Second Column data Coverable to 460 volt FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 10 of 13
Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Large) SERVICE PANEL SERVICE ACCESS SIDE 1 1/4" DIA. LIFTING HOLES ( 4 PLACES) SERVICE PANEL SERVICE ACCESS SIDE SERVICE PANEL #1 #2 WEIGHTS AND CORNER WEIGHTS Shipping: Net Corner 1: Corner 2: Corner 3: Corner 4: 904.0 lb 762.0 lb 239.0 lb 218.0 lb 149.0 lb 156.0 lb #4 #3 WEIGHTS AND LOAD POINT LOCATION FOR CONDENSOR WEIGHT AND RIGGING FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 11 of 13
Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Large) #4 #1 WEIGHTS AND CORNER WEIGHTS B C Shipping: Net VERTICAL Corner 1: Corner 2: Corner 3: Corner 4: HORIZOTNAL Corner A: Corner B: Corner C: Corner D: 891.0 lb 818.0 lb 258.0 lb 168.0 lb 161.0 lb 231.0 lb 256.0 lb 181.0 lb 146.0 lb 235.0 lb #3 #2 A D AIR FLOW HORIZONTAL RETURN AIR FLOW HORIZONTAL RETURN VERTICAL RETURN VERTICAL RETURN VERTICAL APPLICATION HORIZONTAL APPLICATION WEIGHTS AND LOAD POINT LOCATION FOR CONDENSOR WEIGHT AND RIGGING FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 12 of 13
Field Wiring - Split System Air Conditioning Units (Large) TO POWER SUPPLY PER LOCAL CODES SUPPLY HEATER CONTROL BOX SEE NOTE 8 STAGE 1 HEAT STAGE 2 HEAT FAN SEE NOTE 9 24 VAC COMMON TO OUTDOOR UNIT J W1 W2 G BX B1 B2 SEE NOTE 5,6 & 7 EDC AIR HANDLER TO POWER SUPPLY PER LOCAL CODES INTER-COMPONENT WIRING 24 VOLT LINE VOLT 24 VOLT LINE VOLT FACTORY WIRING FIELD WIRING NOTES: 1. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES. 2. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT NAMEPLATE. 3. LOW VOLTAGE WIRING TO BE 18 A.W.G. MINIMUM CONDUCTOR. 4. USE COPPER CONDUCTORS ONLY. 5. IF TWO STAGE ELECTRIC HEATERS AND THERMOSTAT ARE USED, REMOVE JUMPER BETWEEN W1 AND W2. 6. FOR SINGLE STAGE ELECTRIC HEATER, OMIT WIRE BETWEEN W2 AND THERMOSTAT AND W2 AND ELECTRIC HEATER. 7. FOR COOLING ONLY, OMIT WIRES BETWEEN W1,W2 AND THERMOSTAT AND OMIT ELECTRIC HEATER. 8. WHEN ELECTRIC HEATER ACCESSORY IS USED SINGLE POINT POWER ENTRY OR DUAL POINT POWER ENTRY IS FIELD OPTIONAL. SINGLE POINT POWER ENTRY OPTION IS THROUGH ELECTRIC HEATER ONLY. 9. WHEN ELECTRIC HEATER ACCESSORY IS USED, A FIELD SUPPLIED JUMPER MUST BE PLACED BETWEEN "B1" AND "BX" ON THE THE INDOOR SECTION LOW VOLTAGE TERMINAL BOARD. FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 13 of 13