Installation Instructions

Similar documents
Comparative Enthalpy Kit

Installation Guide. Wind Baffle for Outdoor Units VRF-SVN079A-EN. VRF Single-Phase and C-Series Systems. October 2015 SAFETY WARNING

Combination Cooling/Gas Heat Package Units

Variable Refrigerant Flow (VRF) System Simple Touch Remote Control SAFETY WARNING

Packaged Rooftop Air Conditioners Precedent - Cooling, Gas/Electric, Heat Pump 3-5Ton Standard and High Efficiency 3 Phase Rooftop Units

Packaged Cooling 20 Ton Rooftop Units with ReliaTel Controls, 50 Hz

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance

Installation Owner Diagnostics

Installation Instructions Remote Blowers

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance

Y_C-SVE002B-EN. Wiring Manual. Packaged Gas/Electric with ReliaTel Controls 3-10 Tons. Models: (60 Hz) YSC036A*R - YSC120A*R YHC033A*R - YHC120A*R

Split System Heat Pump Condensers

Installation Instructions

Installation, Operation, and Maintenance

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Installation Instructions

Installation, Operation, and Maintenance

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER

Installation Instructions

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

Installation Instructions

Installation Instructions

Installation Instructions

Installation, Operation, and Maintenance

Installation Instructions

Installation Operation Maintenance

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Submittal. 1 1/2 Ton Convertible Air Handler TEM3A0B18S21SA TEM3A0B18-SUB-1C-EN. July 2014 TAG:

Submittal. 2 Ton Convertible Air Handler TEM3A0B24S21SA TEM3A0B24-SUB-1C-EN. July 2014 TAG:

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

INSTALLATION GUIDE Dual Fuel Ranges

Service Facts. Split System Cooling 3.0 Ton 4A7A6036J-SF-1B-EN. January A7A6036J1000A

INSTALLATION INSTRUCTIONS

Installation Instructions

INSTALLATION INSTRUCTIONS

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Installation, Operation and Maintenance

Submittal. 5 Ton Convertible Air Handler TEM3A0C60S51SA TEM3A0C60-SUB-1C-EN. July 2014 TAG:

Installation, Operation, and Maintenance

Installation in Standard & Variable Speed Indoor Air Handlers IMPORTANT

Installation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324

Installation, Operation, and Maintenance

Installation Instructions Dual Fuel Ranges

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

Installation, Operation & Maintenance: Field-Installed Electric Heater for RXT Series Units

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

Dryer. User manual DV22K6800** DV22K A-00_EN (US)_ indd :15:41

Installation & Maintenance Instructions

Installation Instructions

USER S MANUAL AND INSTALLATION INSTRUCTIONS IMPORTANT

SM Field Installed Electric Heat Kit

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

Installation Instructions for Models: HES232U, HES236UHES246U, HES247U, HES245U, HES242U, HES256U, HES255U, HES252U

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

Installation, Operation, and Maintenance

Installation Instructions

Cased Aluminum "Convertible" Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC**

INSTALLATION INSTRUCTIONS

Installation, Operation, and Maintenance

T-Series Air Conditioner T15 Model

FAN POWERED VAV TERMINALS

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AN

Installer's Guide. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE YCC-IG EB23D1-12

INSTALLATION INSTRUCTIONS

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

C7 Series Split System Uncased Indoor Coils

Water Boilers ME10EN, ME15EN. Table of Contents

Installation Instructions

Surna 25-Ton Chiller Operating & Maintenance Manual

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

GAS COOKTOP INSTALLATION INSTRUCTIONS

Installation Instructions

DRAFT INSTALLATION INSTRUCTIONS. Solid-State Series !! NOTE!! Covers the following models: Refer to INSERT for additional information

CLe-series Dishwashers

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

KR Series Air Defrost Unit Coolers Operating and Installation Manual

Installation Instructions T 9822 Gas Dryer. en - US, CA. To prevent accidents

Electric Heat Accessory Installation Instructions

Variable Speed Convertible Air Handler 5 Ton

Installation Instructions

Table of Contents. Important Safety Instructions. WARNING: If the instructions contained in this manual are not followed

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Installation Instructions

The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury.

CONTENTS CONSIDERATIONS. General Plumbing Component Connection ILLUSTRATION. Control System CONFIGURATION. Voltage Verification CONNECTION

Dishwasher Installation Manual

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

Transcription:

Installation Instructions Factory Installed Options (FIOPs) FIYTUBE008AA,009AA Supply Air Sensing Tube for Heat/Cool Units FIYDFPS005AA Clogged Filter Switch FIYDFPS006AA Fan Fail Switch FIYENTH007AA Reference Enthalpy FIYENTH008AA Comparative Enthalpy FIYUCB* Factory Mounted Unit Circuit Breaker FIYUDC* Factory Mounted Unit Disconnect FIYCOPO* Powered Convenience Outlet FIYCOUP* Unpowered Convenience Outlet FIYTBUG101AA Through the Base Gas Utility Option FIYSMDT* Return Air Smoke Detector T/YC*150F, 151F, 180F, 181F, 210F, 211F, 240F, 241F, 300F, 301F WC*150E, 180E, 240E, 151E, 181E, 211E, 241E, 301E Voyager Options Wiring Schematics Novar Interface 2024 ETM (T/YC* 150-301F) Novar Interface 3051 ETM (T/YC* 180F, 181F, 210F, 211F, 240F, 241F, 301F) SAFETY Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. November 2011 ACC-SVN81F-EN

Warnings, Cautions, and Notices Warnings, Cautions, and Notices. Note that warnings, cautions, and notices appear at appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions. ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout this literature. Read these carefully: CAUTIONs NOTICE: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices. Indicates a situation that could result in equipment or property-damage only accidents. Important Environmental Concerns! Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine, and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs. Responsible Refrigerant Practices! Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering, and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them. Personal Protective Equipment (PPE) Required! Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards. Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE. When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations. If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. Failure to follow recommendations could result in death or serious injury. 2011 Trane All rights reserved ACC-SVN81F-EN

Warnings, Cautions, and Notices Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Inspection 1. Unpack all components of the kit. 2. Check carefully for any shipping damage. If any damage is found it must be reported immediately and a claim made against the transportation company. 3. Visually inspect the components for shipping damage as soon as possible after delivery, before it is stored. Concealed damage must be reported within 15 days. 4. If concealed damage is discovered, stop unpacking the shipment. 5. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery. 6. Notify the carrier s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee. Note: Do not attempt to repair any damaged parts until the parts are inspected by the carrier s representative. ACC-SVN81F-EN 3

Table of Contents Supply Air Sensing Tube for Heat/Cool Units.............................. 5 Switches............................................................... 6 Clogged Filter Switch............................................... 6 Fan Fail Switch.................................................... 7 Enthalpy............................................................... 8 Reference Enthalpy................................................ 8 Comparative Enthalpy............................................. 10 Factory-Mounted Unit Options.......................................... 11 Circuit Breaker (FIYUCB) & Unit Disconnect (FIYUDC).................. 11 Powered and Unpowered Convenience.................................. 13 Powered Convenience Outlet Powered Option (FIYCOPO).............. 13 Unpowered Convenience Outlet Unpowered Option (FIYCOUP)......... 13 Through the Base Gas Utility Option.................................... 14 Factory-Installed Economizer Set-Up.................................... 16 12½ Through 25 Ton Units......................................... 16 Return Air Smoke Detector............................................. 20 FIYSMDT* - TC*/YC*150-301F, WC*150-240E......................... 20 High Pressure Option.............................................. 24 Novar Interface 2024-ETM.......................................... 25 NOVAR Interface 3051-ETM........................................ 26 4 ACC-SVN81F-EN

Supply Air Sensing Tube for Heat/Cool Units FIYTUBE008AA,009AA The supply air sensing tube is designed to sense the supply air temperature downstream of the heat exchanger or electric heater Figure 1. (L) horizontal unit-illustration only and (R) downflow unit-illustration only Tube Mounting Bracket Insertion Hole Horizontal Unit (Illustration Only) Downflow Unit (Illustration Only) Sensor See Inset "A" Sensing Tube Plug Button Fan Discharge Sensor See Inset A Tube Mounting Bracket Sensing Tube Plug Button Figure 2. Sensor illustration Inset "A" Insulation Sensor Wire Ties Sensor Insertion Hole Insulation Wire Ties Note: Pull wire ties tight enough to seal ends around the tube. ACC-SVN81F-EN 5

Switches Clogged Filter Switch FIYDFPS005AA This accessory kit detects static pressure differentials across the filters to indicate a clogged or dirty filter condition. When it detects such a filter problem, it causes the "Service" light LED on the zone sensor to glow steady, but not shut down unit operation. Settings The pressure switch is factory preset at 0.45" WC. After a failure situation is detected and corrected, reset the zone sensor service light. This is done by either setting the mode switch to "OFF" for 5 seconds, then back to the desired mode or by cycling the power "OFF" then "ON" at the unit disconnect switch. Figure 3. View for TC/WC/YCH150-301 Detail B Front Fitting (Stamped P1, + ) Rear Fitting (Stamped P2, - ) Detail A Wire 100A Connects to front fitting on clogged filter switch stamped + High Side Low Side Wire 58J See Detail B Mount cogged filter switch on fan board wall with fittings to bottom of unit. (Use lower set of holes) Secure tubing to suction tubes with two wire ties See Detail A Connects to rear fitting on clogged filter swith stamped - 6 ACC-SVN81F-EN

Switches Figure 4. View for TC/WC/YCD150-301 Front Fitting (Stamped P1, + ) Detail A Wire 100A Rear Fitting (Stamped P2, - ) High Side Low Side Wire 58J See Detail A Fan Fail Switch FIYDFPS006AA This accessory kit detects static pressure differentials if the indoor fan should fail. Fan Fail This condition shuts down operation of the unit and causes the "Service" light LED of the zone sensor to flash. Settings This device is factory preset at 0.07" WC. After a failure situation is detected and corrected, reset the zone sensor service light. This is done by either setting the mode switch to "OFF" for 5 seconds, then back to the desired mode or by cycling the power "OFF" then "ON" at the unit disconnect switch. ACC-SVN81F-EN 7

Enthalpy Reference Enthalpy FIYENTH007AA An outdoor humidity sensor located in the economizer is used to measure and communicate outdoor humidity. The unit receives and uses this information to provide improved comfort cooling while using the economizer. Figure 5. Reference enthalpy 139A (PR) 140A (PR) Route harness over edge protector Apply edge protector #140 #139 8 ACC-SVN81F-EN

Enthalpy Figure 6. Fan fail view for TC/WC/YCD150-301 Detail A Wire 102A Wire 101A See Detail A Figure 7. Fan fail view for TC/WC/YCH150-301 Wire 102A Detail A See Detail A Wire 101A Reference Enthalpy Settings Economizer enthalpy changeover is field selectable to five (5) points. See Table 1, p. 9 for potentiometer settings. The selection is made on the ECA. Table 1. Potentiometer settings Potentiometer Setting Dry Bulb Enthalpy A 73ºF (22.8ºC) 27 Btu/lb (63 kj/kg) B 70ºF (21.1ºC) 25 Btu/lb (58 kj/kg) C (a) 67ºF (19.4ºC) 23 Btu/lb (53 kj/kg) D 63ºF (17.2ºC) 22 Btu/lb (51 kj/kg) E 55ºF (12.8 C) 19 Btu/lb (44 kj/kg) (a) Factory Setting ACC-SVN81F-EN 9

Enthalpy Table 2. Economizer control options Control Option Enable Conditions (a) Optional Sensors Required (b) Dry Bulb (standard) See Table 1, p. 9 None Reference Enthalpy (ReliaTel Only) See Table 1, p. 9 Outdoor Humidity (BAYENTH007AA) Comparative Enthalpy (ReliaTel Only) Outdoor Air Enthalpy 3.0 BTU/lb. less than Return Air Enthalpy Outdoor Humidity Return Humidity Return Temperature (BAYENTH008AA) (a) - Economizing is enabled when these conditions are met. (b) - Conditions level will be self configured when optional sensors are connected. Comparative Enthalpy FIYENTH008AA An outdoor humidity sensor located in the economizer and a return humidity sensor located in the barometric hood are used to provide maximum occupant comfort by maximizing the use of the economizer based on the outdoor and the indoor air conditions. By utilizing a humidity sensor and a temperature sensor in both the return air stream and the outdoor air stream, the economizer control acturator (ECA) will be able to establish which conditions are best suited for maintaining the zone temperature, i.e. indoor conditions or outdoor conditions. Figure 8. Comparative enthalpy Reversed View Grommet Economizer Control Box Sheet Metal Cross Member Actuator Outdoor Humidity Sensor Sensor Air Scoop Return Air Humidity Sensor View Grommeted Hole Barometric Hood Back Panel Sensor Air Scoop Return Humidity Sensor Temperature Sensor View Inward Hood Panel Outward Hood Panel Free Swinging Relief Door Barometric Hood Back Panel Return Air Temperature Sensor Kit Provided Grommet 10 ACC-SVN81F-EN

Factory-Mounted Unit Options Circuit Breaker (FIYUCB) & Unit Disconnect (FIYUDC) Hazardous Voltage w/capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Important: All phases of this installation must comply with NATIONAL, STATE, and LOCAL CODES. In addition to local codes, the installation must comply with National Electric Code - ANSI/NFPA NO. 70 LATEST REVISION. 1. Field connections are made by first removing all access panels on the front of the unit. Unscrew the assembly around the outside of the disconnect switch or circuit breaker. This assembly is located between the evaporator and heat section of the unit (Figure 9, p. 12). For downflow configurations, the hole in the base section is for both high and low voltage power wiring on down flow units. Horizontal units will route through the front plate located directly under the circuit breaker or disconnect panel. The hole is sized for 1 1/2" conduit. Horizontal units will use the front plate located directly under the circuit breaker panel. 2. If the conduit required for your application is larger, remove the termination plate and connect to the larger hole using field supplied reducing washers. 3. Route the power wires and ground conductor through conduit and into the bottom of the factory installed disconnect switch or circuit breaker. Connect the power conductors to the lugs provided. Connect the ground wire to the unit ground lug. Note: Wire size for the length of run should be determined using the circuit ampacity found on the unit nameplate and the N.E.C. 4. Route low voltage (class II), control wiring through hole in base of unit but not through high voltage conduit. Feed control wiring through bushing provided on side panel and into the flexible conduit provided in the heat section of the unit (Figure 9, p. 12). Route wires through loose wire ties provided in unit as in Figure 9, p. 12. 5. Tighten the wire ties. Secure the excess wire bundle under the wire ties in the outdoor section. Do not leave excess wire in the electrical enclosure. Use the unit wiring diagram to make the low voltage connections. ACC-SVN81F-EN 11

Factory-Mounted Unit Options Figure 9. Main power entrance for units with factory mounted disconnect or circuit breaker Wire Ties 12 ACC-SVN81F-EN

Powered and Unpowered Convenience Hazardous Voltage w/capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Powered Convenience Outlet Powered Option (FIYCOPO) When the powered convenience outlet option is installed, the unit will include a dedicated transformer located in the evaporator section of the unit. Additionally, a service receptacle disconnect switch will be provided on the side wall of the evaporator section. The service receptacle switch is shipped in the OFF position. The powered outlet comes completely wired from the factory except for 208 volt applications. 1. For 208 volt applications, disconnect and tape the blue 230 volt wire. 2. Then connect the brown 208 volt wire. Unpowered Convenience Outlet Unpowered Option (FIYCOUP) 1. When the unpowered convenience outlet option is installed, remove the receptacle. 2. The field wiring should be routed through the hole in the base for downflow applications or front panel for horizontal applications then through holes provided in the J box (bottom for EMT and top for flexible conduit). 3. Connect the three (3) wires to terminals inside outlet box. Figure 10. Power options A - Powered B - Powered ACC-SVN81F-EN 13

Through the Base Gas Utility Option FIYTBUG101AA Field Installed Connections This section contains the instructions for making field connections to the Through the Base Gas Utility Option. For gas piping, supply, and manifold pressure information see the unit installation, operation, and maintenance guide. Hazardous Voltage w/capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Important: All phases of this installation must comply with NATIONAL, STATE, and LOCAL CODES. In absence of local codes, the installation must conform with American National Standard-Z223.1a- National Fuel Gas Code Latest Revision. 1. Field connections are made by first removing the access panel for the heat section on the front of the unit, Figure 12, p. 15. 2. The gas piping assembly ships inside this section and includes the shut-off valve, a pressure tap for testing, and the necessary unions for field connection. For through the base access, remove the factory-provided cap from the base pan opening. See Figure 11, p. 15. 3. Route field piping through this hole to the dimension shown in Table 3, p. 14. Outlet Pressure Check Required! This unit uses a negative pressure gas valve. At start-up, the outlet pressure should be checked and adjusted if required to a negative -0.2 inches of water column. Never adjust the regulator to a positive pressure. Failure to follow instructions could result in death or serious injury or equipment damage. 4. Place the assembly through the cabinet opening as shown in Figure 12, p. 15 and make the union connection to the field piping and to the gas train. Refer to the unit IOM for checkout procedures. Table 3. Piping hole dimension Model Dimension YC* 150-301 1 3/16" 14 ACC-SVN81F-EN

Through the Base Gas Utility Option Figure 11. Through the base opening Figure 12. Gas piping ACC-SVN81F-EN 15

Factory-Installed Economizer Set-Up 12½ Through 25 Ton Units Each economizer ships inside the unit and requires partial assembling and setup. The following steps are illustrated throughout this section. Refer to the illustrations as the steps are performed. Hazardous Voltage w/capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. 1. Remove the filter/fan compartment access panel. 2. Remove the five (5) lower screws in the end panel, as illustrated. Note: Do not remove the three (3) screws in the upper row of the end panel. 3. Grasp the bottom of the end panel and pull the economizer assembly outward into the operating position, as illustrated with the arrow. 16 ACC-SVN81F-EN

Factory-Installed Economizer Set-Up 4. Remove approximately 3" of gasket material from the bottom of each corner post to expose the holes used to attach the economizer assembly to the unit, as illustrated. 5. With the screws provided, secure both sides of the economizer assembly by inserting the screws, through the clearance holes in the bottom of the corner post, into the engagement holes in the economizer assembly. 6. From inside the evaporator fan compartment, remove the following parts: Clearance Hole a. Block-off angle (located underneath the evaporator fan assembly) b. Plastic bag containing: i. One tube of sealant ii. Screws c. Barometric relief hood 7. The barometric relief hood ships in two (2) sections and is secured with brackets. Discard the brackets after removing the hood and install it, as follows: Note: If barometric relief is desired, remove the shipping screw from the barometric relief damper and ensure that it swings freely before attaching the barometric hood. a. Attach the larger section of the barometric relief hood to the back of the economizer assembly using two (2) screws at the top, as illustrated. Outer Hood Section b. Attach the outer section of the hood to the larger section, previously installed. c. With both sections assembled together, secure the completed hood at the top with two (2) screws provided, as illustrated. ACC-SVN81F-EN 17

Factory-Installed Economizer Set-Up 8. Install the block-off underneath the economizer, as illustrated. The blockoff is designed to close the opening created, between the economizer and the base, when the economizer assembly is in its operating position. a. Holding the block-off with the holes at the bottom and the bottom angle outward, tilt the top forward and insert it into the opening between the economizer and the unit base. b. Press the bottom of the block-off against the unit and line up the holes. Using the provided screws, secure it into place. Seal along these Areas 9. Using the sealant that shipped with the economizer, seal along each side, bottom, and any other areas that could be a potential air leak, as illustrated. 10. Replace the filter/fan access panel. 11. Complete the setup and checkout procedures in the "Final Economizer Setup" section. Economizer Setup Minimum Position Setting Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. To adjust the minimum position setting and check out the economizer, the power must be connected. 1. Close the unit disconnect and place the zone sensor fan selector in the fan "ON" position and the heat/cool selector in the "OFF" position. This will place the damper in the minimum ventilation position. 2. To adjust the minimum position setting for the required ventilation air, turn the potentiometer (on the ECA) clockwise to "open" (to increase the amount of ventilation) or counterclockwise to "close" (to decrease the amount of ventilation). The damper will open to this setting each time the blower circuit is energized. 3. When adjusting minimum position, the damper may move to the new setting in several small steps. Once the damper has remained in position for 10-15 seconds without movement, it can be assumed it is at the new position. 4. Replace the filter access panel. 5. The damper will close when the blower circuit is de-energized. 18 ACC-SVN81F-EN

Factory-Installed Economizer Set-Up Dry Bulb Settings Reference Enthalpy Settings Standard economizer dry bulb changeover is field selectable to four (4) outdoor temperatures. See Table 4, p. 19 for potentiometer settings.the selection is made on the ECA. Economizer enthalpy changeover is field selectable to five (5) points. See Table 4, p. 19 for potentiometer settings. The selection is made on the ECA. Table 4. Potentiometer settings Economizer Control Options Potent. Setting Dry Bulb Enthalpy A 73ºF(22.8ºC) 27 Btu/lb (63 kj/kg) B 70ºF (21.1ºC) 25 Btu/lb (58 kj/kg) C (a) 67ºF (19.4ºC) 23 Btu/lb (53 kj/kg) D 63ºF (17.2ºC) 22 Btu/lb (51 kj/kg) E 55ºF (12.8ºC) 19 Btu/lb (44 KJ/Kg) (a) Factory Setting Table 5. Economizer control options Control Option Enable Conditions (a) Optional Sensors Required (b) Dry Bulb (standard) See Table 4, p. 19 None Reference Enthalpy (ReliaTel Only) See Table 4, p. 19 Outdoor Humidity (BAYENTH007A) Comparative Enthalpy (ReliaTel Only) Outdoor Air Enthalpy 3.0 BTU/lb. less than Return Air Enthalpy (a) Economizing is enabled when these conditions are met. (b) Conditions level will be self configured when optional sensors are connected. Outdoor Humidity Return Humidity Return Temperature (BAYENTH008A) ACC-SVN81F-EN 19

Return Air Smoke Detector FIYSMDT* - TC*/YC*150-301F, WC*150-240E Pre-Requisite Smoke Detector Installation Note: The following field installation instructions apply to downflow only. Horizontal return air smoke detectors require no field installation. When a unit is ordered with a downflow economizer and a return air smoke detector as factory installed options, the return air smoke detector cannot be completely installed because the economizer, when it is in the shipping position, is occupying the space where the return air smoke detector is to be installed. The partial assembly and set-up required for each factory installed economizer must be completed up to the point where the barometric relief hood is to be installed into the unit. Prior to this operation, go to Step 5 of this instruction and perform the operations described there. After this is completed, the economizer installation is to be completed in its entirety as outlined in the installation guide. Important: The shipping screw that holds the barometric relief damper must be removed before proceeding with the smoke detector installation. After completion of the economizer installation as outlined above, proceed with the installation of the return air smoke detector as follows: Hazardous Voltage w/capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. 1. Remove the smoke detector assembly from its shipping position in the indoor fan compartment. This assembly is attached with three screws to the indoor fan board near the top of the unit. 2. Remove and discard the shipping bracket from the smoke detector assembly. This is the angled piece of sheet metal that secured the smoke detector assembly to the interior parts of the unit during shipment. 3. Place the end of the smoke detector 16 inch metal exhaust tube provided into the bottom hole in the back of the smoke detector. Line up the tab in the exhaust tube with one of the slots in the detector and insert the tube until the tube can be rotated. Rotate the tube 45 degrees to lock it in place. 20 ACC-SVN81F-EN

Return Air Smoke Detector Figure 13. Brackets Figure 14. Return air smoke detector for downflow units TWO PIECE HOOD PLASTIC ELBOW METAL INTAKE TUBE SMOKE DETECTOR COPPER TUBE (FACTORY INSTALLED) VINYL TUBES (7-3/4 INCHES LONG) VINYL TUBES (2 INCHES LONG) METAL EXHAUST TUBE (16.34 INCHES LONG) TUBES INSTALL FROM BOTTOM, TOP DOES NOT NEED TO BE REMOVED FROM SMOKE DETECTOR 4. Slide one 2 piece of the vinyl tubing provided onto the short smoke detector inlet tube which protrudes out of the back side of the smoke detector. Push this piece of vinyl tubing onto the inlet tube until it contacts the end of the plastic extension on the backside of the smoke detector. 5. Slide the long piece of vinyl tubing provided onto one leg of the plastic barbed elbow provided. Slide the other end of this piece of vinyl tubing with the elbow attached approximately 1 onto the end of the copper sampling tube installed in the unit s return air opening. Position the leg of elbow without the vinyl tubing such that it points toward the front side of the unit (directly out of the unit toward the filter access panel). ACC-SVN81F-EN 21

Return Air Smoke Detector Airflow & Sampling 6. Mount the smoke detector assembly into the unit. Align the smoke detector (exhaust tube down) with the holes in the outer panel of the barometric relief hood and position the smoke detector flush on the panel. Note: On all units there is a hole with a plastic snap bushing located on the inner vertical side of the barometric relief hood that the long exhaust tube must pass through. Be sure that the exhaust tube is aligned with this hole before positioning the smoke detector flush on the outer panel of the barometric relief hood. 7. Secure the smoke detector to the hood with two #10-16 x 3/4 sheet metal screws provided. Note: In order to perform the last part of this operation, it will be necessary to remove the barometric relief filter, open the barometric relief damper, and reach inside through the barometric relief outlet to access and connect the copper exhaust elbow to the smoke detector exhaust tube. 8. Connect the leg of the plastic elbow without the vinyl tubing attached that was installed in Step 5 to the smoke detector inlet tube pushing it onto the piece of vinyl tubing attached to the inlet tube. 9. Refer to Figure 15, p. 23 for wire connections of return air smoke detector to the unit wiring harness. 10. This completes the installation of the return air smoke detector. If the unit s air filter(s) and/or barometric relief filter were removed to ease installation of the smoke detector, they need to be replaced at this time. Refer to the instructions provided below regarding unit airflow to assure that the return air smoke detector will function properly. Important: The return air smoke detector is designed to shut off the unit if smoke is sensed in the return air stream. This function is performed by sampling the airflow entering the unit at the return air opening. Follow the instructions provided below to assure that the airflow through the unit is sufficient for adequate sampling. Failure to follow these instructions will prevent the smoke detector from performing its design function. In order for the return air smoke detector to properly sense smoke in the return air stream, the air velocity entering the unit must be between 500 and 4000 feet per minute. Most models of equipment covered by this instruction will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance tables. Certain models, however, if operated at low airflow, will not develop an air velocity that falls within the required 500 to 4000 feet per minute range. For these models, the design airflow shall be greater than or equal to the minimum specified in Table 6, p. 22. Table 6. Minimum allowable airflow Unit Model Number T/YCD180F, 181F Minimum Allowable Airflow with Return Air Smoke Detector 5300 CFM Note: Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes and coil cleaning, is required. Note: Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit. 22 ACC-SVN81F-EN

Return Air Smoke Detector Important: Refer to the service literature provided for testing and other information about the smoke detector or if problems are encountered. Figure 15. Smoke detector wiring scheme ACC-SVN81F-EN 23

Return Air Smoke Detector High Pressure Option FIYHGPC003A Figure 16. cutout wiring Figure 17. Wiring schematic 12½ through 25 ton options 24 ACC-SVN81F-EN

Return Air Smoke Detector Novar Interface 2024-ETM Figure 18. Schematics for the following units only: T/YC* 150-301F ACC-SVN81F-EN 25

Return Air Smoke Detector NOVAR Interface 3051-ETM Figure 19. Schematics for the following units only: T/YC* 180F, 181F, 210F, 211F, 240F, 241F, 300F, 301F 26 ACC-SVN81F-EN

The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments,the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.irco.com. The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. 2011 Trane All rights reserved ACC-SVN81F-EN 30 Nov 2011 Supersedes ACC-SVN81E-EN (28 Jun 2011) We are committed to using environmentally conscious print practices that reduce waste.