1 A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513) JM AEROFOIL FANS Installation, Operation and Maintenance Instructions Site Storage The fan must be stored in clean, dry conditions in a vibration-free area. Before installation, the resistance to ground should be measured. If this is less than 1 mega ohm the motor should be dried out before applying main voltage. The impeller should be rotated monthly (minimum) to prevent hardening of the grease and corrosion of the bearings. Supply The details of the site supply must be checked to ensure that the voltage, frequency, power rating and number of phases comply with the details given on the motor nameplate. Installation The Aerofoil fan is supplied completely assembled and is tested at the factory. Weatherproof motors are provided with drain holes and in humid or wet conditions, must be mounted with the drain holes at the lowest point. If the drain holes are plugged the plugs must be removed before commissioning. When installing the fan, sharp bends in the ductwork should be avoided in the vicinity of the fan. For optimum performance, the connection to the ductwork should be by means of a smooth transformation duct with a 60 maximum effective included angle when the diameter decreases in the direction of the airflow, or a 15 maximum effective included angle when it increases in the direction of the airflow. The height of the fan supports should be adjusted so that no undue distortion of the fan casing or mounting occurs. When vibration isolators are used, flexible connectors and electrical conduit should also be used. The flexible connectors should be fitted so that they are almost taut and completely overlap the spigot on the matching flange. The fan should be aligned closely with the inlet and outlet ductwork and must be fitted in accordance with the airflow direction and rotation arrows shown on the nameplate. Typical installations are shown on figures 1 and 2. When installing multi-stage fans, refer to duct nameplate for stage number, stage 1 is installed in the upstream position, and comply with airflow direction and rotation arrows. Aerofoil bifurcated fans when mounted horizontally should have the motor inlet/outlet tunnel positioned at 3 o clock, 9 o clock or vertically downwards (not upwards). Page 1 of 12

2 Connection The wiring must be connected in accordance with the wiring diagram in the terminal box. The direction of rotation is marked on the casing to comply with the form of running required. Single-phase motors are shipped correctly connected. Three phase motors require a trial connection to the supply; if the rotation is incorrect, interchange any two phases of the three-phase supply. Warning - Disconnect and lock out electrical supply before servicing. Failure to do so may result in injury or death. Grounding The fan must be grounded in accordance with the requirements of the local supply authority or code of practice. A separate ground continuity conductor should be connected to the grounding screw in the terminal box. Conduit Wiring should be in accordance with the local regulations and code of practice. For explosion proof motors, see separate section. Balance and Vibration All fan impellers are dynamically balanced prior to installation in the fan assembly. After assembly, fans supplied with motors are test run and fine-tune balanced to reduce vibration levels to acceptable limits as shown in table below (from AMCA Standard ). After field installation, fans will need to be checked prior to commissioning, to assure that the vibration levels do not change significantly from those achieved at the factory. It is recommended that the velocity values in the table below are not exceeded by more than 10% when field installed. Fan Application Category Rigid Mounted Flexible Mounted mm/sec. (in./sec.) mm/sec. (in./sec.) BV (0.15) 5.1 (0.20) The installed vibration level of any fan is not solely dependent on the balance grade. Installation factors such as the mass and stiffness of the supporting system, will influence the as installed vibration level (Refer to AMCA Publication 202, Troubleshooting). Therefore, the as installed fan vibration level is not the responsibility of the fan manufacturer unless specified in the purchase contract. Page 2 of 12

3 Starting Starting of the fan may be carried out manually or automatically. The number of starts in a given time should be limited as follows: 4 direct on line starts/ hour 2 reversals per hour with a run-down time of 15 seconds before reversal 2 starts in quick succession followed by 30 minutes cooling, which may be achieved either by running or switching off Protection Any fuses in the circuit should be regarded as protecting the wiring against the effects of short circuits or ground faults only. They are not suitable for overload protection. To provide protection against a blown fuse or a bad contact, a starter with single phasing protection should be used. The overload current setting should be up to 1.15 times the nameplate current. Motors fitted with thermistor or thermostatic overheat protection should be wired in accordance with the instructions given. Operating Conditions Standard fans are suitable for use in an ambient temperature of -40 C to +40 C, except for the belt driven fans that may be used up from 0 to 80 C, provided the motor is in ambient from -20 to 40 C. The maximum ambient temperature in which an individual fan may be used is given on the nameplate. When fans are operating in ambient temperatures below 0 C icing up must be avoided. Standard fans are not suitable for handling air containing free moisture or corrosive fumes. Routine Maintenance After three months, and thereafter as experience dictates, the fan should be inspected to ensure that there is no build-up of dirt or other matter that would cause overheating of the motor or obstruct the impeller track. The belt tension of Belt Driven Aerofoils should be checked after the first few hours running and thereafter at 3 monthly intervals or as experience dictates. Lubrication The fan is supplied lubricated at the factory and should be lubricated periodically per instructions affixed to the fan. Motors with Lubricators and Bearing Housings Details of the relubrication period and the quantity of lubricant are given on Figures 5 and 6. When carrying out relubrication it is essential that every trace of dirt and water is removed from around the grease nipple and that a clean grease gun is used. Only a low pressure should be required to inject the specified quality. If a high pressure is required the cause should be investigated. Page 3 of 12

4 Additional Instructions for Explosion Proof Motors Explosion proof motors must only be wired by qualified electricians familiar with all local and national codes for wiring of explosion proof motors. Joints should be made though special explosion proof junction boxes or unions throughout the hazardous area. At a point outside the hazardous area, the explosion proof conduit system must be sealed off by a special junction box having an explosion proof barrier. Glands and flexible cable should be used to connect to the fan when it is supported on resilient mountings. Operating Conditions Provided the motor is not allowed to become coated with dirt, dust, or other solid matter that would restrict surface cooling, the carcass temperature will never exceed 80 C when operating in the maximum ambient temperature of 40 C. It is incumbent on users to satisfy themselves that this carcass temperature is safe under the conditions of use and with respect to the particular flammable media in the vicinity. Warning: Failure to comply with these instructions may result in injury or death. Safety When installing or using products the following precautions must be taken. 1. No work may be carried out without switching off and locking out the electrical supply. 2. If it is necessary to carry out any assembly operations before installing the fan, ensure that all fasteners are tightened securely and that any lifting points provided are used. 3. The security of fasteners and the integrity of components should be checked regularly as part of the routine maintenance operation. Particular attention should be paid to impeller fastening screw. 4. Do not re-use locking devices such as lock washers or wedge-lock screws. 5. If the unit is installed where there is a reasonable possibility of persons or objects coming into contact with the impeller, a guard must be fitted. It is the responsibility of the installer and the user to ensure that the installation complies with all OSHA regulations. Where a unit is installed so that a failure of components could result in injury to personnel, precautions should be taken to prevent such an injury. Motor Maintenance Lubricate motor bearings to the manufacturer s recommendations. Lubrication recommendations are included with the packet attached to the fan. Should this packet be missing, the following will apply: Page 4 of 12

5 A. Fractional Horsepower Sleeve Bearing Motors: Under normal operation at ordinary temperatures and clean surroundings, these motors will operate for three years without re-lubrication. Then lubricate annually with electric motor oil or SAE 10 oil. Under continuous operation higher temperatures (but not to exceed 104 F ambient) re-lubricate annually. B. Fractional Horsepower Ball Bearing Motors: Under normal conditions, ball bearing motors will operate for five years without relubrication. Under continuous operation at higher temperatures, (but not to exceed 104 F ambient) re-lubricate after one year. To re-lubricate where motors are not equipped with pressure fittings, disassemble motor and clean the bearings thoroughly. Repack each bearing one-third full with ball bearing grease. C. Integral Horsepower Ball Bearings Motors: Motors having pipe plugs or grease fittings should be re-lubricated while warm and at standstill. Replace one pipe plug on each end shield with grease fitting. Remove other plug for grease relief. On low pressure, grease, run and lubricate until new grease appears at grease relief. Allow motor to run for ten minutes to expel excess grease. Replace pipe plugs. Motors not having pipe plugs or grease fittings can be re-lubricated by removing end shield, cleaning grease cavity and refilling three-fourths or circumference of cavity. Recommended re-lubrication intervals (General guide only) H.P Standard Duty Severe Duty Extreme Duty Range 8 Hr./Day 25 Hr./Day Very Dirty Dirty-Dusty High Ambients 1 ½ - 7 ½ 5 Yrs. 3Yrs. 9 Mos Yrs. 1 Yr. 4 Mos Yr. 9 Mos. 4 Mos. Recommended Motor Greases Polyrex EM Exxon Oil Company SRI #2 Chevron Oil Company FAN MOTORS USED WITH VARIABLE FREQUENCY DRIVES 1. Specify Inverter Duty Motors whenever possible. If this is not practical, premium efficiency motors must be specified. 2. Specify motors with inverter spike resistant magnet wire when possible. 3. Specify insulated bearings or provide shaft grounding to prevent shaft currents from causing bearing damage and premature failure. This is critical on motors that are 50 HP and larger since the cost of downtime and bearing replacement is typically much greater on larger motors, than the initial cost of one of these preventative measures. Note: Shaft currents can occur on any motor HP rating when used with a variable frequency drive. 4. Specify the same manufacturer for both the motor and variable frequency drive, if possible, for single-source responsibility. Page 5 of 12

6 5. A load reactor should be installed in series in the power leads between the VFD and the motor, located as closely as possible to the VFD. This is an inexpensive preventative measure, especially if the VFD is more than 75 feet from the motor. 6. The switching frequency of the IGBT s in the VFD should be kept as low as practical to prevent higher temperatures in the motor and the VFD. However, lower switching frequencies cause higher noise levels in the motor. Therefore, the application noise level versus the higher temperature must be carefully weighed. Generally, 2.5 Khz is optimal. 7. Good industrial wiring practices, including proper grounding, that meet local and national electric codes must be followed. 8. It is best to limit the minimum frequency to the motor to 10 Hz or more for extended periods of time. Note: These are general recommendations only. As each application is different, you must consult the motor and drive manufacturer for specific requirements as they apply to your installation. WARNING! Shaft currents are phenomena created by the interaction between motors and variable frequency drives that can cause premature motor bearing failures. The occurrence of shaft currents is common and cannot be predicted. American Fan Company has experienced many motor bearing failures that have been positively identified as 'shaft current' problems due to the distinctive failure pattern seen in the failed bearings. American Fan Company recommends the adoption of the above list of design constraints for any fan/motor/vfd combination. Regardless if any or all precautions are taken, American Fan Company accepts no responsibility for shaft current related motor bearing failures and will extend only the warranties of the motor and/or variable frequency drive manufacturer (when supplied by American Fan Company). Further, American Fan Company will not be held liable for any consequential damages under any circumstances resulting from premature bearing failures due to shaft currents. V-Belt Drive Maintenance If belts squeal at start-up, they are too loose and should be tightened. Periodically check belt and sheave wear, alignment, and tension. When belts show wear, replace all belts at once with a new matched set of belts. New belts will not work properly in conjunction with used belts due to difference in length. Belts and sheaves should be clean and free from grease. After installing new belts, check tension midway between sheaves. Belts should deflect about 1/64 per inch of span length with approx. 20-lb. force. Allow unit to run for 4 6 hours, then it will be necessary to re-tighten belts again because new belts tend to stretch initially. Vibration Level of Replacement Impellers All replacement impellers are dynamically balanced at our factory prior to shipment. Occasionally, an impeller that has been factory-balanced will yield poor balance/vibration results when installed and operated. This does not mean that the impeller was incorrectly Page 6 of 12

7 balanced at the factory. It can result from differences between test-stand conditions and operating conditions. A factory test stand has different bearings, bearing spans, structural response, stiffness, mechanical impedance, and by necessity, running speed. The test stand cannot duplicate the actual fan system and its response. For these reasons, the fan system vibration levels must be checked after installing a replacement impeller. Refer to page 4 for acceptable vibration levels. NOTE: All illustrations used in this Operation Manual are for Reference Only. Contact your local American Fan Representative if further assistance is needed. ORDERING SPARE PARTS Service and Parts: Phone: (513) , Dial 2 Fax: (513) greg.robinson@flaktwoods.com Page 7 of 12

8 Contact the local American Fan Co. sales representative or AFC Service and Parts Department and supply the following information: 1. Fan serial number stamped on nameplate. 2. Fan code and model stamped on nameplate. 3. Fan arrangement. 4. Description of part required. 5. Part number if part is a casting. 6. Special materials, paints or coatings. WHEEL Be sure to indicate direction of rotation as viewed from drive side, type of wheel and the operating speed. SHAFT Length and diameter. MOTORS The name of the motor manufacturer, motor model number, and serial number from the motor nameplate must be supplied to the factory for repairs or replacement. BEARINGS The following information should be indicated when ordering various types of bearings: ANTI-FRICTION BEARINGS 1. State whether ball or roller. 2. Manufacturer. 3. Size and number. 4. Fixed or floating. RECOMMENDED SPARES: 1. V-belts on V-belt driven fans. 2. Fan bearings 3. Wheel (s) 4. Motor (if blower is critical to your operation). Page 8 of 12

9 Page 9 of 12

10 Page 10 of 12

11 Page 11 of 12

12 AMERICAN FAN COMPANY TERMS OF SALE AND WARRANTY For details, please contact factory: American Fan Company 2933 Symmes Road Fairfield, OH Phone: (513) Fax: (513) Page 12 of 12

Aerofoil Axial - Flow Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions Part No.416421 CONTENTS Paragraphs Safety Introduction And Purpose 1 General 1.1 Storage

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch. IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch. IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Please read and save these instructions. Read carefully before

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION & MAINTENANCE MANUAL CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid

More information

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL SWP (Models SWP08 through SWP20) OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS PART # 538 Model BCF Belt Drive Centrifugal Cabinet Fans Installation, Operation, and Maintenance Manual Please read and save these instructions for future reference. Read

More information

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) Our Expertise, Your Air-Moving Solution ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) PART# 0601710001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference.

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble,

More information

Fan Motor. user manual INSTALLATION - OPERATION - MAINTENANCE

Fan Motor. user manual INSTALLATION - OPERATION - MAINTENANCE user manual Fan Motor INSTALLATION - OPERATION - MAINTENANCE Z0239042_B ISSUED 8/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT installation Receiving Storing A motor

More information

JM Aerofoil Fans Bulletin JMA60-05

JM Aerofoil Fans Bulletin JMA60-05 www.howden.com JM Aerofoil Fans Bulletin JMA60-05 Introduction The high performance JM Aerofoil Fan Benefits of the JM Aerofoil Fan include compactness, low cost, high efficiency and rugged design. Availability

More information

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer)

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) Galvanized Panel Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) 52" Belt Drive, Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before

More information

FAN ENGINEERING. Fan Installation, Operation & Maintenance

FAN ENGINEERING. Fan Installation, Operation & Maintenance FAN ENGINEERING Information and Recommendations for the Engineer FE-500 Fan Installation, Operation & Maintenance How to Avoid Problems with Your Fan Introduction This document presents ways to avoid the

More information

FAN ENGINEERING. Fan Installation, Operation & Maintenance

FAN ENGINEERING. Fan Installation, Operation & Maintenance FAN ENGINEERING Information and Recommendations for the Engineer FE-500 Fan Installation, Operation & Maintenance How to Avoid Problems with Your Fan Introduction This document presents ways to avoid the

More information

EC Box Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions CONTENTS Paragraphs Safety 1 Handling/Storage 2 Installation (Mechanical) 3 Fig. 1: Fig. 2: Tilt Mechanism

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

A. Codes and Standards that are Standard at the University:

A. Codes and Standards that are Standard at the University: PART 1: GENERAL 1.01 Purpose: 1.02 References: 1.03 Requirements: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The

More information

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS Installation & Operating Manual 3001806 03.02 USA CAN BESF Box Ventilator READ AND SAVE THESE INSTRUCTIONS 1200 Northmeadow Parkway, STE 180 Roswell, GA 30076 (770) 587-3238 (800) 255-2923 Fax (770) 587-4731

More information

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A CS 2 Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual Form No. 6120A TABLE OF CONTENTS Page Inspection... 2 Shipment of Units... 2 Handling... 2 Installation...

More information

BESB Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4

BESB Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4 Installation & Operating Manual BESB Box Ventilator USA CAN Product Information... Chapter 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...

More information

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004) High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust

More information

User Manual Box Exhaust Fan Series (Belt Drive)

User Manual Box Exhaust Fan Series (Belt Drive) User Manual Box Exhaust Fan Series (Belt Drive) 36" Box Exhaust Fan with Three Wing Blade Box with Aluminum Shutter 54" Box with Cone 800-779-3267 sales@schaeferfan.com www.schaeferfan.com 2013 Schaefer

More information

HB CDA SERIES WITH TEMPERATURE SETBACK

HB CDA SERIES WITH TEMPERATURE SETBACK HB CDA SERIES WITH TEMPERATURE SETBACK 2013 NOVATEC, Inc. All Rights Reserved Document: HB CDA IM 7-24-2013 NOTES: Please record the following information, which is specific to this piece of equipment,

More information

57" Fiberglass Exhaust Fan with Cone

57 Fiberglass Exhaust Fan with Cone OPERATORS MANUAL Fiberglass Exhaust Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate or service the product described. Failure

More information

Installation of Glass Lined Equipment

Installation of Glass Lined Equipment Installation of Glass Lined Equipment Information given herein is for guidance only and may not be complete. It is important that only trained and competent personnel are permitted to handle glass lined

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual MPA Modular Plenum Array Installation, Operation, and Maintenance Manual This publication contains the installation, operation and maintenance procedures for standard units of the MPA: Modular Plenum Array.

More information

USER'S MANUAL PGE Single Package Rooftop

USER'S MANUAL PGE Single Package Rooftop USER'S MANUAL PGE Single Package Rooftop Gas Heating/Electric Cooling Units Sizes 036-150 3 to 12-1/2 Tons NOTE TO INSTALLER: This manual should be left with the equipment owner. WARNING: If the information

More information

VFB SERIES INDUSTRIAL DEHUMIDIFIER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

VFB SERIES INDUSTRIAL DEHUMIDIFIER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Total Environmental Conditioning Solutions VFB SERIES INDUSTRIAL DEHUMIDIFIER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS REACT OUTLET PROCESS OUTLET REACT INLET PROCESS INLET Bry-Air Part Number

More information

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

A. General: Refer to paragraph entitled SUBMITTAL in Section Include the following data: SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL

More information

Belt Driven Mixed Flow Fans

Belt Driven Mixed Flow Fans www.howden.com Belt Driven Mixed Flow Fans 500 to 1600mm Diameter Bulletin MXF 09-08 A product of the latest computerized design techniques, improving upon already proven designs, the MX-PLUS Mixed Flow

More information

BESF Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4

BESF Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4 Installation & Operating Manual BESF Box Ventilator USA CAN Product Information... Chapter 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...

More information

OPERATING MANUAL Gfp 255C Please read this manual carefully before operating!

OPERATING MANUAL Gfp 255C Please read this manual carefully before operating! OPERATING MANUAL Gfp 255C Please read this manual carefully before operating! Unpacking, assembly, and operating videos are available at www.gfpsmoothstart.com 1 Table of Contents Gfp 255C March 2015 Contents

More information

Industrial Fans & Blowers

Industrial Fans & Blowers Industrial Fans & Blowers IN-LINE FANS ADD DIRECT DRIVE TUBEAXIAL FANS FEATURES & BENEFITS Spark resistant, cast aluminum airfoil axial impeller Aerodynamically efficient performance Factory set adjustable

More information

Enviro KES INSTALLATON MANUAL

Enviro KES INSTALLATON MANUAL Enviro KES INSTALLATON MANUAL Spring Air Systems Inc., Oakville, Ontario Phone (905) 338-2999, Fax (905) 338-0179, info@springairsystems.com www.springairsystems.com KES Installation Manual. This publication

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Air Handler Unit. Installation & Operations Manual. Table of Contents. Bulletin No. H-IM-AH August 2002 Part Number 4346B001

Air Handler Unit. Installation & Operations Manual. Table of Contents. Bulletin No. H-IM-AH August 2002 Part Number 4346B001 Bulletin No. HIMAH August 2002 Part Number 4346B001 (Replaces HIM71A, August 2002) Installation & Operations Manual Air Handler Unit Table of Contents Inspection...2 Shipment of Units Handling Suspended

More information

SECTION (15833) - HVAC POWER VENTILATORS

SECTION (15833) - HVAC POWER VENTILATORS PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted

More information

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and

More information

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit Packaged Gas/Electric Units Owner s Guide to Operating and Maintaining Your Gas/Electric Unit ELECTRICAL SHOCK HAZARD. FIRE OR EXPLOSION HAZARD Disconnect power at fuse box or service panel before performing

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

HMD Heated Makeup Direct: A Direct Fire Make-Up Air Unit INSTALLATION, OPERATION AND MAINTENANCE MANUAL

HMD Heated Makeup Direct: A Direct Fire Make-Up Air Unit INSTALLATION, OPERATION AND MAINTENANCE MANUAL HMD Heated Makeup Direct: A Direct Fire Make-Up Air Unit INSTALLATION, OPERATION AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance procedures for standard units

More information

READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS

READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS Bifurcated Axial Fan Installation and Wiring Instructions 220-240V/1/50Hz & 380-415V/3/50Hz RAD INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLAS SAV THS INSTRUCTIONS Installation and Wiring Instructions

More information

LC Series - Light Commercial Pump Station Installation and Operation Manual

LC Series - Light Commercial Pump Station Installation and Operation Manual LC Series - Light Commercial Pump Station Installation and Operation Manual Please keep this manual with the pump station Content Rain Bird LC Series Overview... Safety Instruction... Operation... 3 Pump

More information

Electrical Preventive Maintenance (EPM) Program

Electrical Preventive Maintenance (EPM) Program Electrical Preventive Maintenance (EPM) Program Only qualified and properly trained persons may work on electric circuit parts or equipment. Such persons shall be capable of working safely and shall be

More information

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - fans@coolair.com MNEFDD54 & MNBCDD54 GALVANIZED

More information

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP DS series Industrial End Suction Pumps ISO/DP 5199 www.sterlingpumps.com.au DS series Capacities from: Heads from: 340 to 5,680 m3/h (1,500 to 25,000 USPGM) 21 to 106 metres (70 to 350 feet) Power range

More information

DC Motor Blower Kit Frames DC180ATZ and C180ATZ thru C400ATZ Installation & Operating Manual

DC Motor Blower Kit Frames DC180ATZ and C180ATZ thru C400ATZ Installation & Operating Manual DC Motor Blower Kit Frames DC180ATZ and C180ATZ thru C400ATZ Installation & Operating Manual 10/11 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2 3002239 RSIF 2014-04-04 Installation and operation manual RSIF power venter READ AND SAVE THESE INSTRUCTIONS! Product information Chapters 1 + 2 Mechanical installation Chapter 3 Electrical installation

More information

INLET DAMPER WALL FAN UNIT

INLET DAMPER WALL FAN UNIT FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - agfans@coolair.com INLET DAMPER WALL FAN UNIT

More information

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST S Model TCBS CATALOG AX220 May 2013 TubeaxialFans Model TCBS The Twin City Fan & Blower model TCBS is a belt driven tubeaxial fan that is

More information

APW PSI PRESSURE WASHER

APW PSI PRESSURE WASHER APW5001 1300 PSI PRESSURE WASHER 1300 PSI PRESSURE WASHER Please carefully read this manual which has been specifically designed to provide all the necessary information for the correct use of the machine,

More information

OWNERS GUIDE TO INSTALLATION AND OPERATION

OWNERS GUIDE TO INSTALLATION AND OPERATION OWNERS GUIDE TO INSTALLATION AND OPERATION SPM SERIES HIGH POWER CENTRIFUGALS READ THESE INSTRUCTIONS CAREFULLY Read these installation instructions in detail before installing your pump. Be sure to check

More information

568X, 587X, 588X Series

568X, 587X, 588X Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance TOP ECOSMART TWINFANS (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use Installation and Maintenance The EMC Directive 2014/30/EU The Low Voltage directive 2014/35/EU INDOOR USE ONLY Introduction

More information

Selecting the Correct Fan

Selecting the Correct Fan Selecting the Correct Fan Ryan B. Johnson Air Purification Company Sales Engineer Member, ASHRAE Pikes Peak Chapter rjohnson@airpurificationcompany.com 1 Your Speaker circa 1998 Fan Types Applications

More information

DBF 4XL Dryer Booster Fans

DBF 4XL Dryer Booster Fans Installation and Operation Manual Item #: 401315 Rev Date: 050814 DBF 4XL Dryer Booster Fans DBF4XL Kit Includes: Dryer Booster Fan, 1 pc Fan Mounting Bracket and Hardware, 1 pc Wall Label (Mount on wasll

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RFEC/U/2017-1 (EN) (valid since 18.08.2017) ROOF FANS RF/EC...-... / RFV/EC...-... Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the

More information

SELF-PRIMING JET PUMPS

SELF-PRIMING JET PUMPS SS Anti-Rust SS Shaft Copper & Cold-rolled SELF-PRIMING JET PUMPS CONTENTS 1. Applications.... Model Description.... Technical Data... 4. Implementation Standards... 5. Safety Precautions... 6. Product

More information

AEROFOIL AXIAL FLOW FANS

AEROFOIL AXIAL FLOW FANS FIRE SAFETY AIR MOVEMENT AEROFOIL AXIAL FLOW FANS» SAFETY, INSTALLATION AND MAINTENANCE INSTRUCTIONS PART NO. 416421 CONTENTS PARAGRAPH SAFETY 1 INTRODUCTION & PURPOSE - GENERAL 2 STORAGE & HANDLING 3

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

Packaged Air Conditioning Units. Owner s Guide to Operating and Maintaining Your Air Conditioner. This manual should be left with the owner.

Packaged Air Conditioning Units. Owner s Guide to Operating and Maintaining Your Air Conditioner. This manual should be left with the owner. Packaged Air Conditioning Units Owner s Guide to Operating and Maintaining Your Air Conditioner ELECTRICAL SHOCK HAZARD. Failure to follow this warning could result in personal injury, Disconnect power

More information

Aquatower User Manual

Aquatower User Manual Aquatower User Manual OM-3800/4800B Manual 92-1311G 1 Contents Tower Installation... 3 Piping to Tower... 4 Mechanical Equipment Installation... 5 Motor Electrical Connections... 8 Starting and Operating

More information

ENERVEX GSV GREASE FAN

ENERVEX GSV GREASE FAN ENERVEX GSV 200-450 GREASE FAN 3001391 12.16 Installation & Operating Manual READ AND SAVE THESE INSTRUCTIONS! ENERVEX Inc. 1685 Bluegrass Lakes Parkway Alpharetta, GA 30004 USA P: 770.587.3238 F: 770.587.4731

More information

Installation and Wiring Instructions

Installation and Wiring Instructions Powerline (TDF) Installation and Wiring Instructions TDF32014 TDF38014 TDF42014 TDF48014 TDF38034 TDF42034 TDF48034 TDF52034 TDF52036 TDF60034 TDF60036 PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE STARTING

More information

Long Case Axial Fan. Installation and Wiring Instructions V/1/50Hz & V/3/50Hz

Long Case Axial Fan. Installation and Wiring Instructions V/1/50Hz & V/3/50Hz Long Case Axial Fan Installation and Wiring Instructions 220-240V/1/50Hz & 380-415V/3/50Hz RAD INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLAS SAV THS INSTRUCTIONS Installation and Wiring Instructions

More information

English CNA-CNB. Centrifugal fans Installation and maintenance

English CNA-CNB. Centrifugal fans Installation and maintenance 916505-0 English CNA-CNB Centrifugal fans Installation and maintenance 916505-0 GB Centrifugal fans types CNA, CNB, CNA-M and CNB-M installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2

More information

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS 6720 Columbus Road Mississauga, Ontario Canada, L5T 2G1 Tel: (905) 670 3595 Fax: (905) 670 3592 Web: www.temspec.com TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS INSTALLATION AND MAINTENANCE

More information

GRIND PRO DUAL OR DISC SANDER. Operator Manual

GRIND PRO DUAL OR DISC SANDER. Operator Manual GRIND PRO DUAL OR DISC SANDER Operator Manual 2 GRIND PRO DUAL OR DISC ORTHO-SANDER INTRODUCTION The Grind Pro Dual or Disc Sander is a compact, durable machine designed for fast, complete finishing work.

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

Series V VCA Evaporative Condenser

Series V VCA Evaporative Condenser Series V VCA Evaporative Condenser Table of Contents...Page Recommended Maintenance Services.....................................................N83 Operation and Maintenance.............................................................N83

More information

Republic Blowers. Ring Blower Side Channel Blower Regenerative Owner s Manual

Republic Blowers. Ring Blower Side Channel Blower Regenerative Owner s Manual Ring Blower Side Channel Blower Regenerative Blower Systems www.republicsales.com Revised 7.08 2006 Sales & Manufacturing Regenerative Blowers Criteria Use Criteria Use only clean, dry air. Do not use

More information

Installation/Instruction Manual

Installation/Instruction Manual 1510876HC8902 Pressurized ventilators (for device cooling) Model Blade diameter (cm) Indoor or outdoor EF-20UYS-UL EF-25UAS-UL EF-30UBS-UL 20 25 30 Indoor Installation/Instruction Manual For customers

More information

238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual

238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual 238 Series Industrial/Commercial Electric Unit Heater Owner s Manual This manual covers installation, operation and maintenance. Read carefully before attempting to install, operate or service the 238

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR MODEL RH REMOTE HORIZONTAL AIR COOLED HEAT EXCHANGERS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR MODEL RH REMOTE HORIZONTAL AIR COOLED HEAT EXCHANGERS INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR MODEL RH REMOTE HORIZONTAL AIR COOLED HEAT EXCHANGERS 9845 South 57 th Street Franklin, WI 53132 Telephone: (414) 421-4666 Fax: (414) 421-0712 MODEL RH

More information

User s Information Manual

User s Information Manual 48AJ,AK,AW,AY020-060 Single-Package Rooftop Gas Heating Units with COMFORTLINK Controls and Scroll Compressors User s Information Manual NOTE TO INSTALLER This manual should be left with the equipment

More information

PORT700CF Portable Fume Collector

PORT700CF Portable Fume Collector 11975 Portland Ave. S. Suite 104 Burnsville, MN 55337 Phone: 952-894-6637 Fax: 952-894-0750 Email: info@ventaire.com Website: www.ventaire.com PRODUCT GUIDE FOR PORT700CF Portable Fume Collector REV:110314

More information

EYS SEPARATOR EYS 01 G. USER MANUAL for EYS SCREW-PRESS SEPARATOR MODEL EYS 01 G. User Manual for EYS 01G Screw-Press Separator

EYS SEPARATOR EYS 01 G. USER MANUAL for EYS SCREW-PRESS SEPARATOR MODEL EYS 01 G. User Manual for EYS 01G Screw-Press Separator USER MANUAL for EYS SCREW-PRESS SEPARATOR MODEL EYS 01 G User Manual for EYS 01G Screw-Press Separator Table of Contents Page 1. Introduction 2 2. General Safety Instructions 3 3. Installation 5 4. Start-up

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions ! Condensate Return Systems General Installation, Operation, & Service Instructions INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. SAFETY INSTRUCTIONS This safety alert symbol will be used in this

More information

BELT DRIVEN STATIONARY AGITATOR

BELT DRIVEN STATIONARY AGITATOR BELT DRIVEN STATIONARY AGITATOR INSTRUCTION MANUAL www.usfarmsystems.com 2955 S. K Street Tulare, CA. 93274 (559)685-0340 (800)811-9462 Fax (559)685-9160 Revision Date 9/7/2017 TABLE OF CONTENTS How to

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

MXI Mixed Flow Inline Fan

MXI Mixed Flow Inline Fan MXI Mixed Flow Inline Fan PRODUCT GUIDE PennBarry Your Single Source for Commercial & Industrial Supply & Exhaust Fans www.pennbarry.com TABLE OF CONTENTS INTRODUCTION 3 CERTIFICATIONS & LISTINGS 4 MIXED

More information

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ... Installation & Operating Manual RSIF Power Venter USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration... Chapter

More information

KCC Centrifugal Fan Air Cooled Condensers

KCC Centrifugal Fan Air Cooled Condensers PRODUCT DATA & INSTALLATION Bulletin K50-KCC-PDI-10 KCC Centrifugal Fan Air Cooled Condensers Air Cooled Models from 103 Thru 164 Four to ninety Ton 1064435 We are on the Internet www.keepriterefrigeration.com

More information

I.O.M. #116 7/10 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE. Covers Models from 25 to 100 tons.

I.O.M. #116 7/10 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE. Covers Models from 25 to 100 tons. I.O.M. #6 7/0 INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE Covers Models from 25 to 00 tons. 525 East Stop 8 Road Greenwood, IN 4642 37-887-0729 fa: 37-88-277 Service Department fa: 37-885-8683

More information

Owners Manual. SM-HP A SM-HP8-10 Meter. Manual D

Owners Manual. SM-HP A SM-HP8-10 Meter. Manual D DuraCore TM Fan Owners Manual SM-HP8-64-360A SM-HP8-10 Meter Manual 9-1473D 1 4 5 7 8 9 6 MONEL HARDWARE 7 8 9 STAINLESS HARDWARE 00 FAN BLADE FAN HUB 3 Fan Components Marley Order No. Trial Pitch Angle

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RF/U/2017 (ENGLISH) (valid since 13.10.2017) ROOF FANS RF / RFV Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the right to modify this

More information

Packaged Heat Pumps. Owner s Guide to Operating and Maintaining Your Heat Pump

Packaged Heat Pumps. Owner s Guide to Operating and Maintaining Your Heat Pump Packaged Heat Pumps Owner s Guide to Operating and Maintaining Your Heat Pump NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the spaces

More information

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use TOP INDOOR USE ONLY Introduction Units are rectangular in section and have circular/rectangular rigid spigots at each end. Four matching mounting feet are supplied with the unit. Full size access panels

More information

MODEL 652A MODEL 654A MODEL 652A MODEL 653A MODEL 651A AURORA. 650 Series SINGLE STAGE SOLIDS HANDLING PUMPS

MODEL 652A MODEL 654A MODEL 652A MODEL 653A MODEL 651A AURORA. 650 Series SINGLE STAGE SOLIDS HANDLING PUMPS MODEL 652A MODEL 654A MODEL 652A MODEL 651A MODEL 653A AURORA 650 Series SINGLE STAGE SOLIDS HANDLING PUMPS WWW.AURORAPUMP.COM 2 AURORA 650 Series Single Stage Solids Handling Pumps Capacities to 2000

More information

How about Savings in Time, Money, Energy and Longer Life?

How about Savings in Time, Money, Energy and Longer Life? Chapter 17: The Value of Maintaining Evaporative Cooling Equipment 97 The Value 17 of Maintaining Evaporative Cooling Equipment 1. Cooling Tower Maintenance and Upgrades... What s in it for You? How about

More information

MAXI PUMP INSTRUCTION MANUAL NE6151B /NE6171B READ THIS MANUAL CAREFULLY BEFORE USING YOUR MAXI PUMP

MAXI PUMP INSTRUCTION MANUAL NE6151B /NE6171B READ THIS MANUAL CAREFULLY BEFORE USING YOUR MAXI PUMP MAXI PUMP INSTRUCTION MANUAL NE6151B /NE6171B READ THIS MANUAL CAREFULLY BEFORE USING YOUR MAXI PUMP 8104 MAXI-PUMP PARTS BREAKDOWN Re f # 1 2 3 4 5 6 7a 7b 8 9 10 11 12 13 14 15 16 2 Part # NEP2134 NEP2135

More information

Lo-Carbon Quadra Centrifugal Fan

Lo-Carbon Quadra Centrifugal Fan Lo-Carbon Quadra Centrifugal Fan Installation and Wiring Instructions Stock Ref. N Quadra TP Quadra TM Quadra HTP 439251A 439253A 439181A 220-240V~50Hz IPX4 PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH

More information

12 VELOCITY OWNER S MANUAL OPERATING INSTRUCTIONS - MAINTENANCE - SAFETY - TROUBLESHOOTING

12 VELOCITY OWNER S MANUAL OPERATING INSTRUCTIONS - MAINTENANCE - SAFETY - TROUBLESHOOTING 12 VELOCITY OWNER S MANUAL OPERATING INSTRUCTIONS - MAINTENANCE - SAFETY - TROUBLESHOOTING This manual contains very important safety warnings and information. Read and save these instructions for future

More information