1 Advance Proof. Private to members Copyright 2007 The Institute of Refrigeration No publication or reprinting without authority THE INSTITUTE OF REFRIGERATION CARBON DIOXIDE FOR SUPERMARKETS by Campbell, A. 1,2, Missenden, J.F. 2,. and Maidment, G.G. 2 1 Tesco Stores Ltd. Cirrus Building B Shire Park Welwyn Garden City Al7 1AB 2 London South Bank University, 103 Borough Road, London, SE1 OAA, , maidmegg@lsbu.ac.uk (Session ) To be presented before the Institute of Refrigeration at the Institute of Marine Engineering, Science and Technology, 80 Coleman Street, London EC1 on 5th April 2007 at 5.45pm INTRODUCTION The effects of refrigerants on the environment are well documented. Supermarkets contribute both directly and indirectly to global warming. Directly, greenhouse gas emissions occur through the leakage of HFC refrigerants used in refrigeration systems for refrigeration of food. These refrigerants have very high global warming potential with GWP s in excess of However, supermarkets also indirectly produce CO 2 as they are large consumers of electricity, consuming as much as GWh (54 000TJ) per annum and approximately 40% of this is consumed by refrigeration equipment. Over the last 20 years, legislation has prohibited the use of many ozone-depleting refrigerants including CFCs and HCFCs, however, the use of HFC refrigerants is still legal and commonplace. In recent years natural refrigerants have been proposed as an environmentally friendly solution for the refrigeration industry. These refrigerants which include ammonia, hydrocarbons and carbon dioxide, do not contribute to ozone depletion and have low global warming potentials. Carbon dioxide offers a long-term solution suitable for many applications in refrigeration and heating, from domestic applications utilizing heat pumps, to providing hot water and heating to commercial applications for supermarket refrigeration. The technology is future proof requiring no further retrofitting to the next refrigerant solution promoted commercially. To investigate the performance of R-744 refrigeration, a prototype system was constructed and tested to demonstrate proof of principle. This Proc. Inst. R

2 73,6 +31 Deg.C Supercritical Critical point Liquid -10 o C 26 Bar Bar 5,2 Solid Solid -Liquid -28 o C 11Bar Liquid - vapour - 56,6 Deg.C Triple point Solid - Vapour Vapour - 78,4 Deg.C Enthalpy (kj/kg) Figure 1. Simplified P-H Diagram [1]. paper reports on a practical investigation of R-744 refrigeration in a commercial application and describes an investigation of its design, commissioning and energy performance. Also discussed are the practical experiences gained from building a R-744 system and the benefits of using such a natural refrigerant. The main characteristics of R-744 as a refrigerant are that the critical and triple points are relatively low at 31 o C (73 Bar) and o C (5.2 Bar) respectively. In order to remain below the critical temperature of 31 o C it is necessary to use a cascade system to provide a heat sink to allow the CO 2 to condense. The system restrictions in relation to temperature and pressure can be seen below in the simplified P-H diagram R-744 operates at a far higher pressure than standard refrigerants although this is not excessively high compared to similar engineering applications. Figure 2 demonstrates the differences in operating pressures of standard refrigerants and R-744. It can be seen from the graph that while R-744 operates at higher pressures than conventional refrigerants, the pressures relative to those say of automobile power steering systems (115 Bar) are low although power steering utilizes liquid rather than a gas. Power Steering 115 Bar Figure 2. Comparison of refrigerant pressures. Proc. Inst. R

3 1 2 R-404a COMPRESSOR 5 6 R-744 COMPRESSOR R-1270 CYCLE PHE PULSE VESSEL R-744 H.T CYCLE- 7 o C R-744 PUMP 4 R-744 L.T. CYCLE Figure 3. A Typical cascade supermarket refrigeration system using R1270/R-744. The reasons for the renewed interests in CO 2 as a viable natural refrigerant is the advantages associated with the properties of CO 2 over other natural refrigerants. CO 2 has a high volumetric refrigeration capacity, as a result of its high vapour density when compared to other refrigerants. As a consequence, refrigeration compressors using CO 2 are 6-8 times smaller than those of R22 systems in displacement terms. Further benefits of high vapour density are realised when applied to pipe-work suction pipe work and valves can be reduced by several sizes. This will result in a significant reduction in material used, not only in pipe and component sizes but also pipe gauge. CO 2 also possess improved heat transfer properties allowing the evaporator to operate at a higher temperature than competitive R404a evaporators. Evaporators may work at least 2K higher than conventional R404a evaporators. These improved heat transfer properties result in increased capacity in standard heat exchangers. Application of R-744 in supermarkets The excellent safety and environmental properties associated with R-744 enable its systems to offer real advantages to the retail food industry. Its non-toxic and non-flammable nature is important because large refrigerant charges are used in supermarkets and much of the refrigerant runs in pipes through the customer area. Since the Montréal protocol there has been much discussion about the use of natural refrigerants using ammonia and hydrocarbons in supermarkets. Although these refrigerants offer environmental benefits they can t be used in large volumes in such public spaces. However a number of systems have been installed and tested using a central ammonia / hydrocarbon chiller and a secondary distribution system using Tyfoxit, propylene glycol and other heat transfer fluids. The disadvantages with these fluids is that the safe, non toxic, non flammable fluids are expensive in terms of revenue and capital to implement for a variety of reasons at low temperature. These include high viscosity, low heat transfer and poor thermophysical properties, as well as practical complications through corrosion and material compatibility. The use of CO 2 as a distribution fluid was highlighted by Pearson to the Institute in 1993[2]. The use of CO 2 in conjunction with a hydrocarbon or ammonia primary chiller presents the opportunity to refrigerate retail food areas with a low carbon, safe and low GWP combination of refrigerants. Low GWP is important because of the potential refrigerant leakage rates that are a characteristic of the complexity and size of these systems. This is shown in Figure 3, which shows a typical cascade CO2 system which has been reported used in supermarkets [3]. This can be seen to comprise of medium- and low-temperature sections serving chilled and frozen food chillers and freezers respectively. Proc. Inst. R

4 Figure 4. PH chart showing operation of Cascade Refrigeration System. The ph chart in figure 4 shows the cascade subcritical cycle using a primary refrigerant together with a cascade CO 2 system. A number of these systems have now been tested and it is reported that energy savings of between 11% -15 [4] have been achieved compared with a typical R-404a reference cycle. In terms of carbon the savings will be greater since direct emissions will be several orders of magnitudes lower due to the low GWP of the natural refrigerants. Alternatively CO 2 has been used in a transcritical cycle in retail applications [5]. A number of systems have been reported and the conceptual schematic and PH chart are shown in figures 5 and 6. It can be seen that the high pressure condition is above the critical point and as such heat rejection occurs without change of phase in the gas cooler. One key advantage of this cycle is the availability of high temperature energy at the compressor PULSE VESSEL Figure 5. A schematic of a transcritical CO 2 refrigeration system. Proc. Inst. R

5 Figure 6: A PH chart of a transcritical CO2 refrigeration system. discharge which offers potential for high grade heat recovery. One further advantage of the system is it s simplicity with a single refrigerant and compression cycle. However it can be seen that the intermediate gas is returned to the compressor suction and this re-expansion at low pressure presents an avoidable and significant reduction in COP. pulse vessel, which acts as liquid receiver and separation vessel. The high temperature R-744 evaporator is fed from the pulse vessel via a A Pilot Commercial System The R-744 systems that have been proposed and installed in supermarkets are generally industrial in nature and this is shown in figure 7. The consequence of this higher specification is capital cost. It has been estimated, that compared with conventional R-404a systems capital costs are in the region of 20% higher [6]. As a consequence initial work carried out has been to develop a commercial CO 2 system that is more economic, but retains safety and integrity features. This pilot system is shown in Figure 8. The pilot system was designed as a dual temperature cascade arrangement with refrigerant R-404A as the heat rejecting/ condensing medium for the R-744 two-stage cycle. This arrangement enables the R- 404a system to be a small compact unit, with minimal charge and leakage risk. The R-404A cycle evaporates at -15 o C and condenses at 36 o C and uses two scroll compressors. The evaporator is a plate heat exchanger, which acts as the condenser for the R-744 cycle. It condenses the discharge gas from the R-744 compressor serving the LT system and the flash gas from the wet suction on the high temperature (HT) R-744 evaporator at. The R-404A evaporator was sized to remove the heat from both the LT and HT R-744 cooling systems. At the HT condition the R-744 is condensed and held in the Figure 7. Danish Supermarket Pack Installed at ISO Roskilde Denmark. Figure 8. Pilot R-744 system. Proc. Inst. R

6 Figure 9. CAD drawing of pilot commercial system. refrigerant pump, which feeds the refrigerant at a 4:1 circulation ratio. The R-744 at -10 o C acts as a volatile secondary refrigerant in respect to sensible and latent cooling making the evaporator more efficient. The refrigerant returns to the pulse vessel from the evaporator as a saturated liquid via the wet suction where it is re-condensed. The flash gas leaves the vessel and enters the condenser to liquefy and then return to the vessel at -10 o C. The low temperature liquid R-744 also leaves the pulse vessel at -10 o C and feeds its evaporator where it is expanded to boil at -28 o C, returning via the dry suction to the R-744 compressor, thus completing the cycle. A detailed as built drawing can be seen in figure 9 complete with control system. Performance of the Pilot Commercial System The performance of the pilot system was calculated and measured. The table below shows the calculations based on the performance expected by the manufacturers and the results gained from the readings on the test rig. The COP is the standard form, where COP = Q cooling / P input and the COP of the system is COSP = Q e M.T. + Q e L.T. P 404A + P cond fans + P pump +P CO2 Where Q e M.T. is the medium temperature load Q e L.T. is the low temperature load P 404a is the power input to the R404a compressors P cond fans is the power input to the condenser fans P pump is the power in to the refrigerant pump P CO2 is the power in put to the CO 2 compressor Using the various manufacturers software to establish the expected power input and performance parameters the design output is shown in table 1. This also shows the measured and computed Proc. Inst. R

7 CoolPack CYCLE ANALYSIS : COMBINATION OF ONE-STAGE CYCLES > TWO-STAGE CASCADE SYSTEM, DX EVAPORATORS LOG(p),h-DIAGRAM T 4,HT : 33.6 [ C] T 2,HT : 55.7 [ C] T 5,HT : 33.6 [ C] Q 4-5,HT : 0.00 [kw] 5 HT 4HT Q C,HT : 40.5 [kw] m HT : [kg/s] T C,HT : 36.0 [ C] 2 HT 3 HT SUB-DIAGRAM WINDOWS T 4,LT : [ C] T 5,LT : [ C] Q 4-5,LT : 0.00 [kw] W HT : [kw] T 2,LT : 33.4 [ C] 5 LT 4 LT Q C,LT : 11.6 [kw] T C,LT : [ C] 2 LT Q E,HT : 29.6 [kw] T E,HT : [ C] 7 HT 3 LT Department of Mechanical Engineering Technical University of Denmark Version 1.46 TOOL C.10 6 HT X 6,HT : 0.40 [kg/kg] m LT : [kg/s] Q E,LT : 10.0 [kw] T E,LT :-28.0[ C] 6 LT X 6,LT : 0.12 [kg/kg] REFRIGERANT HT : R404A COP HT :2.399 COP* HT : REFRIGERANT LT : R744 COP LT :6.349 COP* LT : T 8,HT : -6.0 [ C] 8 HT 1 HT T 1,HT : [ C] 7 LT W LT : [kw] 9 T 8,LT : [ C] 8 LT 1 HT T 1,LT : [ C] η CARNOT,HT : 0.47 η CARNOT,LT : 0.47 Figure 10. Cycle Prediction for Low Temperature System from Cool Pack Software. ACTUAL design High Side High Side Copeland ZB45KCE-TFD x 2 Copeland ZB45KCE-TFD x 2 T c 36 C T c 36 C T e -15 C T e -15 C Q e 17.8kW Q e 15.0kW P 404A 7.0kW P 404A 8.0kW P cond fans 0.5kW P cond fans 1.7kW THR 24.8kW THR 23.0kW COP 404A 2.39 COP 404A 1.5 M.T. M.T. T e -10 C T e -10 C Q e 4.7kW Q e 4.7kW P pump 0.8kW P pump 1.0kW COP CO2 MT 5.7 COP CO2 MT 4.7 L.T. L.T. Bitzer 2KC-3.2 K Bitzer 2KC-3.2 K Tc -10 C Tc -10 C T e -28 C T e -28 C Q e 10.0kW Q e 10.0kW P CO2 1.8kW P CO2 1.5kW THR 11.8 THR 11.5 COP CO2 LT 5.6 COP CO2 LT 6.7 SYSTEM SYSTEM P total 10.1kW P total 12.2kW COP Total 1.5 COP Total 1.2 Table 1. Pilot system s recorded and design performance. Proc. Inst. R

8 performance for the actual system under similar conditions. It can be seen from the comparison that there is reasonable agreement between design and measured performance. Discrepancy between the two is due to transient measurement conditions and manufactures tolerances. The calculated comparative COP for a similar R-404a system was below 1 and the relative improvement in performance of the CO 2 system is similar to that reported by others [4] This was achieved using a more commercial style of pack. Case Studies To reduce the carbon footprint of their stores, of which circa 40% is due to refrigeration, Tesco commissioned C0 2 installations at Swansea, Wick and Shrewsbury. The store at Swansea was located in Llansamlet in an urban environment and comprised 60,000ft 2 / 5574 m 2 of nett retail area, with 354 kw of chilled food and 57 kw of frozen food. The systems consisted of one sub-critical system serving 19.5 m (14.98kW) of frozen food cabinets and one transcritical system serving 22.5 m (38.5kW) of dairy and produce chilled food cabinets. The motivation for both schemes was to test their operational and energy performance in a live application, with a view to making a generic corporate system specification for future stores. The sub-critical system was chosen specifically as an energy efficient and low carbon alternative to conventional a R-404A single stage system. The transcritical system was chosen as a low carbon alternative to a HFC system. Although transcritical systems are normally designed to operate more efficiently with a heat reclaim facility, this system was installed without this, primarily to avoid the additional complexity associated with the control of heating and cooling output. This feature and its impact are subject to further study. Consequently from an energy perspective the transcritical system may be optimized for significant performance improvements. In addition the store also had four R-404a (2 x HT,2 x LT) single stage systems serving the remainder of the chilled and frozen food. Schematics for the sub-critical and transcritical systems are shown in figures 11 and 12. The sub-critical system in figure 11 consists of a two R-290 H.T. close coupled air cooled liquid chillers each with 2kg of refrigerant charge. Each pack includes brazed plate heat exchanger evaporators, R- 22 charged Danfoss TEV s, Bitzer semi hermetic reciprocating compressors and brazed plate heat exchanger condensers, connected to a dry air cooler. This configuration was chosen to optimise system output for refrigerant charge. The low temperature R-744 circuit for the DX frozen cabinets consists of Bitzer Octagon compressors specifically produced for sub-critical applications. The evaporator output was controlled by AKV electronic evaporation devices linked to a pressure transducer rather than Figure 11. Cascade system installed at Swansea. Proc. Inst. R

9 PULSE VESSEL Figure 12. Transcritical System installed at Swansea. temperature probes. This is a critical part of the system performance, inherently complicated by the properties of C0 2 causing conventional expansion control to be unsuitable. The transcritical system consisted of two Dorin semi hermetic reciprocating compressors running with 2 pole motors at 2980rpm. The system was configured to run in trans and sub-critical operation depending on the ambient temperature and therefore condensing temperature. When the ambient is below 22 o C the system runs as a standard sub-critical refrigeration system when the ambient reaches 22 o C the system is driven into transcritical mode through the use of an automatic control valve. System Performance The systems have now been operating for one year, without failure. System performance has been compared against like for like HFC systems installed as a control. Figure 13 demonstrates a better COP COP R290/R-744 VER R-404a COP Jun-06 Jul-06 Aug-06 Sep-06 R-404a R-744 Figure 13: Comparative measured COP of Cascade R-744 cycle and control R-404a. Proc. Inst. R

10 for the R-744 cascade L.T. system against the HFC control. Observation from site showed this to be partly due to the reduced temperature lift associated with the improved heat transfer within the R-744 heat exchanger, and also reduced system pressure drop. It was observed on start up that the increase heat transfer resulted in ice build up on the food on the CO 2 cabinets only. This was rectified by raising the evap temp which consequently raised the COP. The data taken from the transcritical system needed further clarification and could not be reported at this point. Operational Factors Other observations relate to the operational characteristics associated with the systems. The compressors selected for the transcritical system used 2 pole motors which were particularly noisy, however subsequent versions have overcome this limitation. Also standard in store maintenance procedures have been successfully followed with all systems. Specifically and not previously covered in the literature is the in store cleaning of C0 2 cabinets using hot water at 60 C. This was successfully achieved because all shut off valves had been eliminated within the cabinet vicinity allowing safe expansion of the C0 2 back to the compressors. Overall the installation was simply and efficiently executed within normal Tesco construction time frames. Capital was greater for both systems, however we expect with economies of scale there to be no significant difference in system cost between R-744 and R-404a technology. Carbon savings In order to evaluate the potential carbon saving associated with direct and indirect emissions, system performance was evaluated based upon the Shrewsbury store. Comprising of 342 kw of H.T. and 69kW of L.T. load, this store will utilise 2 cascade systems for the whole store, using R-1270 as the primary refrigerant and R-744 as both the L.T. DX refrigerant and the H.T. secondary volatile refrigerant. When the store is complete the refrigeration system will be the largest supermarket natural refrigerant solution installed in the UK to date. In order to justify this system a TEWI investigation to compare the systems with a standard reference using typical industry performance parameters was carried out. The results of this investigation are shown in table 2. The key headline from this is the significant carbon reduction associated with the R-744 scheme which is due primarily to the avoidance of HFC emissions with a high GWP factor of Future Developments The potential for transcritical systems has not as yet been fully explored using monitored data. Also there is considerable potential for use of high grade waste heat to drive an integrated sorption cooling system and other heat demand applications. A hybrid system using either series compressors or intermediate feed would produce better COP for transcritical applications comprising of DX L.T. and flooded H.T. as can be seen from figure 14. Further work and modelling will be carried out using this system and the research will include investigations into using the rejected heat to provide heating and System and period of assessment Standard R-404a system TEWI 1 year Cascade system TEWI 1 year Difference between systems over 1 year CO TONNES OF CO TONNES OF CO TONNES OF CO2 Standard R-404a system TEWI 10 year Cascade system TEWI 10 year Difference between systems over 10 year TONNES OF CO TONNES OF CO TONNES OF CO2 Based on 61% run time Table 2. Results of TEWI comparison of standard versus Natural cascade systems. Proc. Inst. R

11 115 BAR AMBIENT ABOVE 31 oc GAS COOLER EXPANSION INTERMEDIATE PRESSURE 26 BAR PULSE VESSEL COMPRESSOR EXPANSION L.T. EVAPORATOR Figure 14. Future Transcritical Dual Temperature Pack. cooling for the store using LTHW and sorption cooling. Results will be reported at a later date. CONCLUSION The investigation has clearly demonstrated there are considerable energy savings to be made by using a R- 744 system. The calculations demonstrate that the R- 744 system reduces substantially CO 2 emissions when compared with traditional systems. The practical experience gained from building and commissioning R-744 systems has shown that there are no insurmountable problems with using R-744 as a refrigerant. The problems associated with the procurement of equipment will diminish with growth in the use of R-744. The benefits of R-744 are: Smaller compressors Smaller pipe work and valves Smaller heat exchangers Greater energy efficiency Environmentally more friendly Reduction in green house gas emissions Cheaper refrigerant With the imminent arrival of the F-gas regulations, the running costs of systems can be further reduced by the avoidance of inspections, with the use of R There is no reason to delay the design of new plants using R-744 as the components and technology are now available. The only hindrance to wider use is the unfamiliarity of designers with these types of systems and available trained staff to service and install these systems. References [1] Danfoss. CO 2 Refrigerant for industrial Refrigeration, Danfoss 2002 Arhus [2] Pearson S.F., Development of improved secondary refrigerants, Institute of Refrigeration 1993 [3] Van Riessen G., NH 3 /CO 2 Supermarket refrigeration systems with CO2 in the cooling and freezing section, 6 th IIR Gustav Lorentzen Natural Working Fluids Conference. Glasgow [4] Pachai A.C., Experiences with CO 2 as a refrigerant in supermarkets, 6 th IIR Gustav Lorentzen Natural Working Fluids Conference. Glasgow [5] Heinbokel B., Gernemann A., One year experiences with the first CO2-DX system for medium and low temperature refrigeration at Swiss megastore, C-dig meeting 22/ Zurich [6] Girotto S., et al, Commercial refrigeration system using CO2 as the refrigerant, International journal of refrigeration Pearson A., Carbon Dioxide Short Course 6 th IIR Gustav Lorentzen Natural Working Fluids Conference. Glasgow Acknowledgements The authors would like to thank Tesco Stores Limited for their permission to publish this paper. Proc. Inst. R

A refrigeration system for supermarkets using natural refrigerant CO 2

A refrigeration system for supermarkets using natural refrigerant CO 2 A refrigeration system for supermarkets using natural refrigerant CO 2 A. Campbell 1,2, G. G. Maidment 2 and J. F. Missenden 2 1 Tesco Stores Ltd, Shire Park, Welwyn Garden City 2 London South Bank University,

More information

HFCs or the Old Refrigerants - what is the best Choice?

HFCs or the Old Refrigerants - what is the best Choice? HFCs or the Old Refrigerants - what is the best Choice? Hermann Halozan Institute of Thermal Engineering, Graz University of Technology Inffeldgasse 25 / B, A-8010 Graz, Austria, Phone: +43 316 873-7303

More information

Trends and Perspectives in Supermarket Refrigeration

Trends and Perspectives in Supermarket Refrigeration Trends and Perspectives in Supermarket Refrigeration Prof. Dr.-Ing. Michael Kauffeld Karlsruhe University of Applied Sciences Mechanical Engineering and Mechatronics Department Institute of Refrigeration,

More information

July 2012 was a significant date for the HVAC and Refrigeration industry as it saw the introduction of the Carbon Tax and the HFC Levy.

July 2012 was a significant date for the HVAC and Refrigeration industry as it saw the introduction of the Carbon Tax and the HFC Levy. Parilla Thermal Storage Project In 2013 Glaciem Cooling Technologies undertook the commercialisation of its Thermcold Thermal Storage system, the system which has been operating now for over two years

More information

Parilla Thermal Storage Project Case Study. May Page 1 of 11

Parilla Thermal Storage Project Case Study. May Page 1 of 11 Parilla Thermal Storage Project Case Study May 2014 Page 1 of 11 BACKGROUND Parilla Premium Potatoes is a large refrigerated storage facility (Figure 1) located in South Australia; the facility consists

More information

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications Commercial CO2 Refrigeration Systems Guide for Subcritical and Transcritical CO2 Applications 2 Contents Chapter 1. Introduction 4 Chapter 2. CO 2 Basics and Considerations as a Refrigerant 5 Section 1.

More information

Commercial CO 2 Refrigeration Systems

Commercial CO 2 Refrigeration Systems Commercial CO 2 Refrigeration Systems Guide for Subcritical and Transcritical CO 2 Applications 2 Contents Chapter 1. Introduction 4 Chapter 2. CO 2 Basics and Considerations as a Refrigerant 5 Section

More information

Environmentally friendly refrigeration systems for industrial use

Environmentally friendly refrigeration systems for industrial use compindustri Environmentally friendly refrigeration systems for industrial use CO ² refrigeration systems of the future GENERAL INFORMATION compindustri More than 10 years of development of refrigeration

More information

Current use of HFCs and HCFCs. Trends, alternatives and climate impact. YEREVAN, Armenia, May 18-19, International Institute of Refrigeration

Current use of HFCs and HCFCs. Trends, alternatives and climate impact. YEREVAN, Armenia, May 18-19, International Institute of Refrigeration Current use of HFCs and HCFCs. Trends, alternatives and climate impact YEREVAN, Armenia, May 18-19, 2009 Didier COULOMB, Director of the IIR, d.coulomb@iifiir.org Institut du Froid (IIF) - www.iifiir.org

More information

SUBCRITICAL & TRANSCRITICAL SYSTEMS

SUBCRITICAL & TRANSCRITICAL SYSTEMS R744 CO2 SYSTEMS SUBCRITICAL & TRANSCRITICAL SYSTEMS ORIGINAL MANUFACTURED EQUIPMENT R744 CO2 Systems BA-508-3 AUS In 2004 BITZER Australia introduced the Enviro-Cold CO 2 System to the Australian Refrigeration

More information

System Design, Commissioning, Operation

System Design, Commissioning, Operation PART 3: CO 2 as a Refrigerant System Design, Commissioning, Operation Service This series continues with the introduction of transcritical, cascade and secondary systems; how each system works; and compares

More information

Energy Performance of Low Charge NH3 Systems in Practice. Stefan S. Jensen

Energy Performance of Low Charge NH3 Systems in Practice. Stefan S. Jensen Energy Performance of Low Charge NH3 Systems in Practice Stefan S. Jensen Introduction Central type, dual compression stage, ammonia vapour compression systems. Main Design Features: Reciprocating Compressors

More information

CO2 TRANSCRITICAL BOOSTER SYSTEMS

CO2 TRANSCRITICAL BOOSTER SYSTEMS CO2 TRANSCRITICAL BOOSTER SYSTEMS William Katz Sr. Technical Writer Hillphoenix 2016 Gees Mill Road Conyers, GA 30013 Tel: 678-613-9364 Email: william.katz@hillphoenix.com Refrigeration systems for supermarkets

More information

From the Field to the Supermarket

From the Field to the Supermarket From the Field to the Supermarket Post Harvest Cooling Part 4 of 4 By Andy Butler Retail Market Manager Star Refrigeration Ltd., Glasgow, Scotland This is the fourth and final part of a series of articles

More information

Brazed Plate Heat Exchanger for CO Applications

Brazed Plate Heat Exchanger for CO Applications Brazed Plate Heat Exchanger for CO Applications www.kaori-bphe.com CO 2 (R744) Due to global warming, climate change phenomenon, and rising restriction on the use of high GWP synthetic refrigerant; replacing

More information

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 200 Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid Haruhisa

More information

Campbell Soup Company Extends Use of CO2 Systems Into Their Operations

Campbell Soup Company Extends Use of CO2 Systems Into Their Operations Campbell Soup Company Extends Use of CO2 Systems Into Their Operations The Campbell Soup Company needed to expand their frozen operations at one of their Pepperidge Farm manufacturing plants in Pennsylvania

More information

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants Purdue University Purdue e-pubs nternational Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1996 Modelling of an ntegrated Supermarket Refrigeration and Heating System Using

More information

Alternatives in the AC & Chiller Sectors. Sukumar Devotta and Lambert Kuijpers OORG Refrigeration

Alternatives in the AC & Chiller Sectors. Sukumar Devotta and Lambert Kuijpers OORG Refrigeration Alternatives in the AC & Chiller Sectors Sukumar Devotta and Lambert Kuijpers OORG Refrigeration 1 Outline ASHRAE position paper summary which marks a difference in the US approach dealing with various

More information

FACT SHEET 6 Transport Refrigeration

FACT SHEET 6 Transport Refrigeration UNEP Ozone Secretariat Fact Sheets on HFCs and Low GWP Alternatives UNEP Ozone Secretariat Background Material on HFC Management October 205 FACT SHEET 6 Transport Refrigeration. Description of market

More information

Postprint.

Postprint. http://www.diva-portal.org Postprint This is the accepted version of a paper presented at IEA Annex 27 Workshop: Selected Issues on CO2 as Working Fluid in Compression Systems. 2000. Trondheim, Norway.

More information

PRICE CHOPPER SARATOGA, NY. First cascade supermarket system in North America Installed and Started March of 2008

PRICE CHOPPER SARATOGA, NY. First cascade supermarket system in North America Installed and Started March of 2008 PRICE CHOPPER SARATOGA, NY First cascade supermarket system in North America Installed and Started March of 2008 Why did we choose CO2? Meets Corporate sustainability initiatives Looking for ways to reduce

More information

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou Condensers ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM A. Hadawey, Y. T. Ge, S. A. Tassou 4 7 8 5 3 2 6 1 Produced by: The Centre for Energy and Built Environment

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION 1.1 CFC REFRIGERANTS Since the 1930s, chlorofluorocarbons (CFCs) have been widely used as foam blowing agents, aerosols and especially refrigerants due to their pre-eminent properties

More information

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications. TECHNICAL DATA SHEET R434A () Features and uses of R-434A () is a non-flammable HFC mixture. ODP = 0, compatible with traditional mineral lubricants, alkyl benzene and also with synthetic POE, so there

More information

Energy Efficiency Considerations in Refrigeration Systems

Energy Efficiency Considerations in Refrigeration Systems Energy Efficiency Considerations in Refrigeration Systems Donall O Brien Industrial Energy Consultant Why Focus on Refrigeration? Refrigeration & Cooling is responsible for approx. 20% of all Electricity

More information

R&D ON HEAT PUMPS WITH NATURAL WORKING FLUIDS IN JAPAN

R&D ON HEAT PUMPS WITH NATURAL WORKING FLUIDS IN JAPAN R&D ON HEAT PUMPS WITH NATURAL WORKING FLUIDS IN JAPAN E. Hihara, Professor, Institute of Environmental Studies, The University of Tokyo, 7-3-1 Hongo, Bunkyo-ku, Tokyo, Japan The conventional refrigerant

More information

NATURAL REFRIGERANTS FOR HEAT PUMPS AND AIR-CONDITIONING SYSTEMS. Bernard Thonon Greth

NATURAL REFRIGERANTS FOR HEAT PUMPS AND AIR-CONDITIONING SYSTEMS. Bernard Thonon Greth NATURAL REFRIGERANTS FOR HEAT PUMPS AND AIR-CONDITIONING SYSTEMS Bernard Thonon Greth bernard.thonon@greth.fr Artificial or Natural Refrigerants? Performances COP Capacity Cost Safety Pressure, Temperature

More information

PREPARE FOR CHANGE LOW GWP ALTERNATIVES. November 17

PREPARE FOR CHANGE LOW GWP ALTERNATIVES. November 17 PREPARE FOR CHANGE LOW GWP ALTERNATIVES November 17 F-GAS PHASE DOWN Where we are now F-Gas regulation places restrictions on the use of some HFC refrigerants of high GWP. This is indirectly achieved by

More information

NATURAL REFRIGERANT SYSTEMS

NATURAL REFRIGERANT SYSTEMS R744 CO 2 SYSTEMS NATURAL REFRIGERANT SYSTEMS SINGLE & MULTIPLE COMPRESSOR SYSTEMS SUB-CRITICAL / TRANS-CRITICAL ORIGINAL MANUFACTURED EQUIPMENT R744 CO2 SYSTEMS In 2004 BITZER Australia introduced the

More information

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology Refrigeration Cycles MOHAMMAD FAISAL HAIDER LECTURER Department of Mechanical Engineering Department of Mechanical Engineering Bangladesh University of Engineering and Technology Objectives Introduce the

More information

Use of transcritical CO 2 in industrial applications

Use of transcritical CO 2 in industrial applications Use of transcritical CO 2 in industrial applications Why CO 2 in industrial? Commercial needs customer needs it Customers want natural solutions (NH3 not always wanted) Customers want non-toxic solutions

More information

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA Daniel Giguère, Technology Expert Georgi Pajani, Engineer Sophie Hosatte, Section Head, Buildings CETC-Varennes, Natural

More information

Ammonia. Background on ammonia as a refrigerant

Ammonia. Background on ammonia as a refrigerant Ammonia Danfoss Industrial refrigeration has written a technical paper on things to consider when changing from HFC/HCFC s to ammonia. It outlines some of the main differences between the different plant

More information

THE BIG FIVE NATURAL REFRIGERANTS IN DIFFERENT INDUSTRIAL APPLICATIONS. MAYEKAWA EUROPE S.A.,Leuvensesteenweg 605, 1930 Zaventem, Belgium

THE BIG FIVE NATURAL REFRIGERANTS IN DIFFERENT INDUSTRIAL APPLICATIONS. MAYEKAWA EUROPE S.A.,Leuvensesteenweg 605, 1930 Zaventem, Belgium THE BIG FIVE NATURAL REFRIGERANTS IN DIFFERENT INDUSTRIAL APPLICATIONS Jan Boone MAYEKAWA EUROPE S.A.,Leuvensesteenweg 605, 1930 Zaventem, Belgium Tel. 32-2-757-9075, Fax. 32-2-757-9023, e-mail : jan.boone@mayekawa.eu

More information

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72 International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Q. Which hydrocarbons can be used as a refrigerant? The following hydrocarbons can be used as a refrigerant in cooling & heating applications:

Q. Which hydrocarbons can be used as a refrigerant? The following hydrocarbons can be used as a refrigerant in cooling & heating applications: Basic Facts About Hydrocarbons Q. What are hydrocarbons? Hydrocarbon refrigerants are environmentally friendly, non-toxic, non-ozone-depleting replacement for chlorofluorocarbons (CFCs), hydrochlorofluorocarbons

More information

R718 TURBO CHILLERS AND VACUUM ICE GENERATION TWO APPLICATIONS OF A NEW GENERATION OF HIGH SPEED, HIGH CAPACITY R718 CENTRIFUGAL COMPRESSORS

R718 TURBO CHILLERS AND VACUUM ICE GENERATION TWO APPLICATIONS OF A NEW GENERATION OF HIGH SPEED, HIGH CAPACITY R718 CENTRIFUGAL COMPRESSORS TURBO CHILLERS AND VACUUM ICE GENERATION TWO APPLICATIONS OF A NEW GENERATION OF HIGH SPEED, HIGH CAPACITY CENTRIFUGAL COMPRESSORS Marcus HONKE, Mathias SAFARIK, Ralf HERZOG Institute of Air Handling and

More information

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Global Solutions for Ammonia Industrial Refrigeration

Global Solutions for Ammonia Industrial Refrigeration Global Solutions for Ammonia Industrial Refrigeration MAYEKAWA s lineups and results of Natural Refrigerants Atmosphere 2009 October19th 2009 Mayekawa Mfg. Co., Ltd. Kuniaki Kawamura 1 Founded: 1924 Location:

More information

Chapter 2. Alternatives to HCFCs and their Characteristics

Chapter 2. Alternatives to HCFCs and their Characteristics Alternatives to HCFCs and their Characteristics Refrigerant - General Chemical used in a cooling system, such as an air conditioner or refrigerator, as the heat carrier which changes from vapour to liquid

More information

Natural Refrigerant Market Trends

Natural Refrigerant Market Trends Natural Refrigerant Market Trends Bangkok Technology Conference, June 30, 2013 Marc Chasserot, Managing Director shecco about shecco market development company for natural refrigerants accelerate transition

More information

Ammonia Refrigeration & Scenario in Industrial Refrigeration. By Ramesh Paranjpey ASHRAE Fellow Life member

Ammonia Refrigeration & Scenario in Industrial Refrigeration. By Ramesh Paranjpey ASHRAE Fellow Life member Ammonia Refrigeration & Scenario in Industrial Refrigeration By Ramesh Paranjpey ASHRAE Fellow Life member 5 th March 2014 Basic Components Of A Refrigeration System Refrigerant Flow Path Refrigerant?

More information

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 Ameya P. Shrivastava 1, Choudhari Chandrakishor S. 2 1,2 Mechanical Department, AISSMS College of Engineering, Pune 411001, (India) ABSTRACT HCFC

More information

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER University of Maiduguri Faculty of Engineering Seminar Series Volume 6, december 5 ASSESSMENT OF REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R34A REFRIGERANT IN LARGE CAPACITY FREEZER S. Shodiya*, M.B. Oumarou

More information

Refrigerants & Cooling in renovation buildings

Refrigerants & Cooling in renovation buildings Refrigerants & Cooling in renovation buildings 01 Basics Refrigeration circuit. 1 Refrigeration Basics LP HP Mollier Diagram A-C Evaporation B-C Superheat C-D Compression D-E Desuperheat D-G Condensation

More information

Oyelami S., Bolaji B. O.

Oyelami S., Bolaji B. O. International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-2015 1158 Experimental Investigation of the Performance of Liquefied Petroleum Gas (LPG) Refrigerant in A Vapour Compression

More information

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,

More information

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming 88 KENJI UEDA *1 YOSHINORI SHIRAKATA *2 YASUSHI HASEGAWA *3 NORIYUKI MATSUKURA *4 NAOYA MIYOSHI

More information

FACT SHEET 9 Large Air-Conditioning (air-to-air)

FACT SHEET 9 Large Air-Conditioning (air-to-air) FACT SHEET 9 Large Air-Conditioning (air-to-air) UNEP Ozone Secretariat UNEP Ozone Secretariat Background Workshop Material for on HFC HFC Workshop, management: 205 technical issues Bangkok, 20 and 2 April

More information

Thermodynamics I. Refrigeration and Heat Pump Cycles

Thermodynamics I. Refrigeration and Heat Pump Cycles Thermodynamics I Refrigeration and Heat Pump Cycles Dr.-Eng. Zayed Al-Hamamre 1 Content Introduction The Reversed Carnot Cycle The Ideal Compression Refrigeration Systems Deviation from the ICRS Selection

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

The R-404A Challenge. Commercial Opteon Refrigerant Solutions - The New Industry Standard

The R-404A Challenge. Commercial Opteon Refrigerant Solutions - The New Industry Standard Opteon Refrigerants The R-404A Challenge. Commercial Opteon Refrigerant Solutions - The New Industry Standard Mark Hughes Business Development Manager Opteon Refrigerants Agenda Intro Chemours The Chemical

More information

INDUSTRIAL REFRIGERATION. Position on refrigerant selection

INDUSTRIAL REFRIGERATION. Position on refrigerant selection INDUSTRIAL REFRIGERATION Position on refrigerant selection 1 Which Options door do you choose today? Retrofit HFC 2 Industrial customers What is of vital importance to industrial customers? The reliability

More information

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A ISSN: 2250-0138 (Online) NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A RANENDRA ROY a1, MADHU SRUTHI EMANI b AND BIJAN KUMAR MANDAL c abc Department

More information

Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto

Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto Kawasaki centrifugal chiller using water as a refrigerant Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto Contents 1. Introduction of MiZTURBO 2. Study of CO 2 emissions

More information

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications: TECHNICAL DATA SHEET Features and uses of is a non-azeotropic blend of HFC with zero Ozone Depletion Potential et low Global Warming Potential (GWP), formulated to meet the requirements of the F-Gas Regulation

More information

Guidance for Stationary Refrigeration & Air-Conditioning

Guidance for Stationary Refrigeration & Air-Conditioning Information Sheet RAC 2 - Usage Guidance for Stationary Refrigeration & Air-Conditioning This Information Sheet provides background information about the use of stationary refrigeration, airconditioning

More information

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP Paul Maina and Zhongjie Huan mainap@tut.ac.za and huanz@tut.ac.za Department of Mechanical Engineering, Tshwane University of Technology P.O Box Private Bag X680

More information

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant M. Honma, T. Tamura, Y. Yakumaru and F. Nishiwaki Matsushita Electric Industrial Co., Ltd. Living Environment

More information

compact BOOSTER RACK TRANSCRITICAL CO 2 Cooling capacity LT: from 2 to 130 kw Cooling capacity MT: from 20 to 300 kw

compact BOOSTER RACK TRANSCRITICAL CO 2 Cooling capacity LT: from 2 to 130 kw Cooling capacity MT: from 20 to 300 kw w w w. p r o f r o i d. c o m compact TRANSCRITICAL CO 2 BOOSTER RACK Cooling capacity LT: from 2 to 130 kw Cooling capacity MT: from 20 to 300 kw compact Refrigeration Rack Transcritical CO 2 booster

More information

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM Sachin Kumar 1, Vicky Ranga 2 1Assistant Professor, Department of Mechanical Engineering, Jagan Nath University Jhajjar, Haryana, India. 2Scholar.

More information

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A [1] Ranendra Roy, [2] Madhu Sruthi Emani, [3] Bijan Kumar Mandal [1], [2],[3] Department of Mechanical

More information

Refrigeration Technology in Building Services Engineering

Refrigeration Technology in Building Services Engineering Unit 70: Unit code: T/600/0459 QCF Level: 3 Credit value: 10 Guided learning hours: 60 Unit aim Refrigeration Technology in Building Services Engineering This unit develops an understanding of the principles,

More information

EVALUATION OF ALTERNATIVERS TO R404 THE MOST COMMON REFRIGERANT IN SWEDISH GROCERY STORES

EVALUATION OF ALTERNATIVERS TO R404 THE MOST COMMON REFRIGERANT IN SWEDISH GROCERY STORES EVALUATION OF ALTERNATIVERS TO R404 THE MOST COMMON REFRIGERANT IN SWEDISH GROCERY STORES Ola, Gustafsson M.Sc. a *, Lennart Rolfsman M.Sc. a, Sara Jensen B.Sc. a, Markus Lindahl M.Sc. a, a SP Technical

More information

Low GWP Refrigerants for Air Conditioning Applications

Low GWP Refrigerants for Air Conditioning Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta

More information

Sub-Critical Operation of the CO2 Expander/ Compressor

Sub-Critical Operation of the CO2 Expander/ Compressor Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2006 Sub-Critical Operation of the CO2 Expander/ Compressor Josef Riha Technical University

More information

investment in R&D, the commitment to - name.

investment in R&D, the commitment to - name. The Hillphoenix name is synonymous with innovative, sustainable and extremely efficient refrigeration systems in a variety of business segments. While much of the company s reputation has been built as

More information

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a ISSN (e): 0 00 Vol, 0 Issue, 8 August 0 International Journal of Computational Engineering Research (IJCER) Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants

More information

FACT SHEET 9 Large Air-Conditioning (air-to-air)

FACT SHEET 9 Large Air-Conditioning (air-to-air) UNEP Ozone Secretariat UNEP Ozone Secretariat Background Material on HFC Management Fact Sheets on HFCs and Low GWP Alternatives October 205 FACT SHEET 9 Large Air-Conditioning (air-to-air). Description

More information

1.1. SCOPE OF THE WORK:

1.1. SCOPE OF THE WORK: Chapter 1: Introduction 1 1. INTRODUCTION 1.1. SCOPE OF THE WORK: Multi-stage refrigeration systems are an area of growing industrial importance in large plants. These systems are known to be large power

More information

Chapter 11 REFRIGERATION CYCLES

Chapter 11 REFRIGERATION CYCLES Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Chapter 11 REFRIGERATION CYCLES Wan Rosli Wan Sulaiman Copyright The McGraw-Hill Companies, Inc.

More information

Refrigeration and Air Conditioning

Refrigeration and Air Conditioning Refrigeration and Air Conditioning 1. Pick up the wrong statement. A refrigerant should have (a) Tow specific heat of liquid (b) high boiling point (c) high latent heat of vaporisation (d) higher critical

More information

Comparative Performance of HFO Blends in a Condenser

Comparative Performance of HFO Blends in a Condenser The knowledge hub for refrigeration, air conditioning and heat pumps Nick Atkins MInstR Simon Jones MInstR Gary Bell Comparative Performance of HFO Blends in a Condenser Paper 2 research laboratory tests

More information

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India DESIGN OF HYBRID AIR COOLER USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Vimalkirti Shende 1, Sushil Borkar 2, Touseef Iqbal Qureshi 3 Asst. Prof. Nikhil Bhende 1 1,2,3 U.G. Student, Department of Mechanical

More information

2. CURRICULUM. Sl. No.

2. CURRICULUM. Sl. No. . CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration

More information

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit

More information

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning Available online at www.sciencedirect.com Systems Engineering Procedia () 6 International Conference on Risk and Engineering Management (REM) Thermodynamic analysis of air cycle refrigeration system for

More information

R744 (CO 2 ) Refrigerant Cooling Systems, the Finned Tube R744 (CO 2 ) Evaporator and Gas Cooler Design Principles

R744 (CO 2 ) Refrigerant Cooling Systems, the Finned Tube R744 (CO 2 ) Evaporator and Gas Cooler Design Principles R744 (CO 2 ) Refrigerant Cooling Systems, the Finned Tube R744 (CO 2 ) Evaporator and Gas Cooler Design Principles Fatih KASAP Hatice CANBAZ Mechanical Engineer Mechanical Engineer Mechanical Engineer

More information

A Comparison Between Refrigerants Used In Air Conditioning

A Comparison Between Refrigerants Used In Air Conditioning A Comparison Between Refrigerants Used In Air Conditioning Derya Özkan, Özden Agra and Özlem Çetin University of Yildiz Technical University, Turkey Corresponding email: tumer@yildiz.edu.tr SUMMARY It

More information

Hydrocarbons as refrigerants

Hydrocarbons as refrigerants Hydrocarbons as refrigerants Hydrocarbons convince with their environment-friendliness and economic feasibility. A developed society cannot function without refrigeration. At home, in food production and

More information

Development of CO2 Compressor and Its Application Systems

Development of CO2 Compressor and Its Application Systems Development of CO2 Compressor and Its Application Systems Hiroshi MUKAIYAMA, Tetsuya MASUDA, Kazuaki MIZUKAMI, Satoshi IMAI, Toshiyuki EBARA, Toshikazu ISHIHARA, Ichiro KAMIMURA, Kikuo TAKIZAWA SANYO Electric

More information

Energy efficient vacuum freezing ice slurry generation using a R718 compressor

Energy efficient vacuum freezing ice slurry generation using a R718 compressor Institute of Air-handling and Refrigeration (ILK Dresden) Energy efficient vacuum freezing ice slurry generation using a R718 compressor ATMOsphere Europe 2013 ILK Dresden R&D company Founded in 1964 Re-established

More information

Emerging Refrigeration Technologies

Emerging Refrigeration Technologies Emerging Refrigeration Technologies Brandon F Lachner, Jr Research & Technology Forum Madison, WI January 20-21, 2005 University of Wisconsin-Madison 1 Today Current Industrial Refrigeration Ammonia in

More information

Chapter 11 REFRIGERATION CYCLES

Chapter 11 REFRIGERATION CYCLES Thermodynamics: An Engineering Approach Seventh Edition in SI Units Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2011 Chapter 11 REFRIGERATION CYCLES Mehmet Kanoglu University of Gaziantep Copyright

More information

Alternative Refrigerants Part 1 Future and Current Options. Overview

Alternative Refrigerants Part 1 Future and Current Options. Overview Alternative Refrigerants Part 1 Future and Current Options Dr Michael Bellstedt is the Projects and Technology Officer of the Green Cooling Council (www.greencoolingcouncil.org.au), and the Principal of

More information

Commercial Refrigeration

Commercial Refrigeration Commercial Refrigeration A science of vague assumptions based upon debatable figures taken from inconclusive experiments performed with instruments of problematical accuracy by persons of doubtful reliability

More information

PHASE-IN of natural refrigerants. Prof. Dr. Armin Hafner NTNU Norway

PHASE-IN of natural refrigerants. Prof. Dr. Armin Hafner NTNU Norway Armin Hafner Professor Refrigeration Technology, NTNU Department of Energy and Process Engineering Professor Dr.-Ing. Armin Hafner has recently started at NTNU in Trondheim, Norway, as a professor in refrigeration

More information

Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant

Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant International Journal of Refrigeration 28 (2005) 1302 1307 www.elsevier.com/locate/ijrefrig Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant Tomoichiro

More information

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle. Refrigeration Cycle Reading Problems 10-1 10-5, 10-7, 10-9 10-11, 10-14, 10-39 Definitions a refrigeration system removes thermal energy from a low-temperature region and transfers heat to a high-temperature

More information

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS Int. J. Chem. Sci.: 14(S2), 2016, 665-674 ISSN 0972-768X www.sadgurupublications.com PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS J. THAVAMANI *, MARRIPUDAGALA KOMALI, SHAIK

More information

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser

More information

Thermodynamics II Chapter 5 Refrigeration

Thermodynamics II Chapter 5 Refrigeration Thermodynamics II Chapter 5 Refrigeration Mohsin Mohd Sies Fakulti Kejuruteraan Mekanikal, Universiti Teknologi Malaysia Objectives Introduce the concepts of refrigerators and heat pumps and the measure

More information

NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS

NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS - 1 - NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS S.J. Metcalf, Z. Tamainot-Telto (1) and R.E. Critoph School of Engineering, University of Warwick, Coventry CV4 7AL, UK Abstract: A new

More information

Comparison Ammonia / Secondary Refrigerant System against Direct Evaporation of HCFCs /HFCs

Comparison Ammonia / Secondary Refrigerant System against Direct Evaporation of HCFCs /HFCs Comparison Ammonia / Secondary Refrigerant System against Direct Evaporation of HCFCs /HFCs 1 Introduction In the following discussion, the attempt is made to emphasize the economic and ecological advantages

More information

Evaluation of HCFC Alternative Refrigerants

Evaluation of HCFC Alternative Refrigerants Evaluation of HCFC Alternative Refrigerants Shaobo Jia Global Innovation Heatcraft Worldwide Refrigeration shaobo.jia@heatcraftrpd.com Introduction It is well-known that HCFC refrigerants widely used in

More information

ADVANCES in NATURAL and APPLIED SCIENCES

ADVANCES in NATURAL and APPLIED SCIENCES ADVANCES in NATURAL and APPLIED SCIENCES ISSN: 1995-0772 Published BY AENSI Publication EISSN: 1998-1090 http://www.aensiweb.com/anas 2016 Special10(7): pages 112-122 Open Access Journal The Effect Of

More information