Installation, Operating and Maintenance Manual for F Modul plus Calorifiers

Size: px
Start display at page:

Download "Installation, Operating and Maintenance Manual for F Modul plus Calorifiers"

Transcription

1 Installation, Operating and Maintenance Manual for F Modul plus Calorifiers By Appointment to Her Majesty the Queen Boiler Manufacturers & Engineers Hoval Ltd Newark Revision No.2 Dated: November

2 2 Table of Contents Contents Page Introduction Description of F Modul plus Calorifier Technical and Performance Details Delivery / Positioning Instructions Assembly Instructions Installation and Piping Layouts Unvented Systems Commissioning & Operation Inspection and Maintenance Anode Protection Immersion heaters Immersion heater wiring diagrams Fault Finding Chart Wiring Diagrams for Open Vented Calorifiers Wiring Diagrams for Unvented Calorifiers Notes These instructuctions should be read and understood before attempting to install, commission or operate this unit. Material in this publication may not be reproduced without Hoval s written permission. Hoval reserve the right to change specifications without notice.

3 Introduction Introduction These instructions have been written to give a brief description of the F Modulplus Calorifier, its installation, commissioning, operation and subsequent maintenance. The installation of calorifiers and their ancillary equipment is normally carried out by a heating engineer. For the purpose of this manual he is regarded as the installer, and, as such, it is his responsibility to ensure that he has read and understood the contents of this manual before installing the calorifier. It is essential that each calorifier has all services permanently connected to it before commissioning is requested. The installation should be in accordance with current I.E.E. regulations, relevant British Standard and Codes of Practice, Building Regulations and Local Authority Bylaws. Commissioning/Combustion Report Commissioning should be arranged via the heating engineer. Hoval engineers are available to carry out this work if requested. Where the calorifier installation is part of a Hoval boiler package it will normally be commissioned at the same time and entry made on the report opposite A note should be entered below by the person responsible for the plant, giving the boiler, calorifier model and its output and reference serial number, as indicated on the nameplate. For completion by Plantroom Attendant Calorifier Model: Boiler type / Model: Output l/hr: Serial Number: Date of installation: For technical, servicing or parts enquiries, telephone, fax or to Hoval Ltd quoting the calorifier(s) serial number, as above.

4 4 Description of F Modul Calorifier Description of F Modul plus Calorifier Applications F Modul plus calorifiers are designed to operate with the full range of Hoval boilers up to 4.5 Bar (standard model) and 6.90 Bar (high pressure model) primary pressure, and are intended for the production and supply of DHW to commercial and industrial premises. The F Modul-plus is available in seven model sizes with high performance outputs up to 10,000 litres per hour. General Details The construction of the F Modul plus is in the form of a series of horizontal bottles, linked in modular fashion, and comprising a high grade stainless steel inner vessel with a rippled wall to enhance heat exchanger efficiency. This is surrounded by a mild steel primary water jacket, which is encased with steel sheet insulated panels. The assembly is mounted on two base channels running from front to back. On all seven models, the secondary flow and primary inlet are from the top and the secondary return, cold feed and primary outlet connections are at the bottom. Performance of the seven F Modul plus models covers a range of outputs up to an hourly rating of 10,000 litres/hour. Higher outputs can be provided by arranging the units in modular formation. For most typical applications (other than process water generation) the key requirement is for adequate quantities of hot water over a relatively short period. On this basis, the F Modul plus will provide significantly higher flow rates than its continuously hourly rate. A drain must be fitted in the secondary cold feed site pipework to fasciliitate draining and flushing out. (CIBSE TM 1:2000 Recommendations to prevent Legionella Bacteria Contamination). Very low primary and secondary resistances. Electric immersion heaters can be fitted by prior arrangement. Large heating surface, suitable for operation with lower temperature primary feed from condensing boilers. (Duty reduced - contact Hoval). See later section for unvented systems and the additional equipment required. Where access is a problem the bottles can be split (flanged), This is an optional extra. Suitable for primary flow temperatures upto 90 Deg C. Suitable for secondary pressures upto 9.66 Bar. Internal view of F Modul plus Calorifier F42 Modul plus Calorifier Key Features Minimum floor area, fits through standard doorway. Suitable for use with any make of boiler High efficiency heat transfer for rapid D.H.W. regeneration. Recirculation design removes danger of temperature stratification. Optimum D.H.W. storage - sufficient for quick draw-off but with lower standing losses than conventional large volume calorifiers.

5 Technical and Performance Details 5 Technical Data. Model Primay Details Secondary outputs at 60 o C based on 10 o C cold feed Contents Flow rate Resistance Contents o At 90 o Resistance peak continuous peak continuous litres l/s mbar litres l/10 mins l/hour l/10 mins l/hour mbar # F F F F F * Resistance is for primary ow rate listed + For DHW outputs below 60 o C, external blending to a lower temperature is recommended. # Resistance at the peak 10 minute draw off rate. For resistance at other draw off rates See Graphs on page 6. Pressures Standard Model Pressures High Pressure Model Pressures** System Operating Test Pressures Operating Pressures Test Pressures Pressure Bar Bar Bar Bar Primary Side Secondary Side ** To meet the requirements of M&E, high pressure primary water units can be tted with a bursting disc. Weights Model Dry Weight kg Dry weight Excl. Casings kg Total weight kg F F F F2 605 F Chloride. The maximum allowable chloride content of DHW cold feed water is 100mg/litre, (or up to 200 mg/litre where optional tted). To calculate the load on the boiler. Rating kw = Q x S.H. x (T 2 - T 1 ) 600 Q = Calori er hourly output - Litres (kg) T 1 = Temperature cold feed - o C T 2 = Temperature DHW ow - o C S.H. - kj/kg o C Note for Hydraulic Testing: The primary jacket should not be pressurised without steel vessel. An adjustable secondary thermostat has a sensing point which ensures that the main body of water is held uniformly, pre-set level, normally 60 o C - 65 o C. Legionellae The safe temperature for storage is now considered to be a minimum of 60 o C to prevent the risk of legionella bacteria contamination. For kitchen and similar duties requiring 60 o C water, the supply can be direct from the calori er o C supply, mixing or blending with cold water, external to the calori er, is required and will increase the secondary output listed on page 5 by about 25%. When temporarily operating the primary side only, the pressure should not exceed 1 bar g and the secondary side should be vented. November 2015

6 6 Technical and Performance Details Hydraulic Resistance (Primary) Hydraulic Resistance (Secondary) M / h /.6 = l/s

7 Technical and Performance Details 7 Dimensions T ype F21, F41, F4 Type F21, F41, Type F4 2. Dimensions 2 T & P on Unvented Systems Height b Width a Type F21 F1 F41 F51 F2 F42 F F52 F2, Type F51 F1, Type F2, F51, Type F1, F52 4 T & P on Unvented Systems Connections 1. Secondary Flow 2 BSP Male F51 = NW 50 F52 = NW Cold Feed 2 BSP Male. Circulation 1 BSP Male 4. Primary Flow F21-F51 = DN50 PN6 5. Primary Return } { F2-F52 = DN65 PN6 6. Control panel 7. Electrical Connection Hot water 2" Cold water 2" Circulation 1" feed F21 - return F2 - Electrical box Electrical connection } Rear View Side View Front View

8 8 Delivery Positioning Instructions Delivery and Positioning Instructions Transport Dimensions Delivery Positioning / Clearance Position the calorifiers as required, ensuring that side and inspection opening clearances are adequate. At least 400mm side clearance is required for fitting the casings. If this space is not available, the calorifier insulation and casings must be fitted before positioning the calorifier. Ensure that the calorifier is level using a spirit level along the top calorifier bottle. The F Modul plus calorifiers are delivered in three pieces:- - The Modul bottles and frame. - The casings and lagging in a cardboard box. - The Calorifier control panel in a box.

9 Assembly Instructions 9 Assembly Instructions Mounting the support rails Ensure that the dimensions between the top casing rails and the base channels are as per H. Before fitting the insulation and casings, fix the bottom guide rails (1) to the base channels. For types F2, F42 and F52 use Hole A. For types F21, F1, F41 and F51 use Hole B. Hole A. Hole B.

10 10 Assembly Instructions Fitting the insulation Wrap the insulation matress (1,2,,4 & 5) around the calorifier(black side outwards), join the insulation at the top using tension springs (8). Secure with the plastic straps (6). These plastic straps are secured using the strap fastener (7). Do not fasten too tightly as this will effect the insulation properties of the matress. Fit the pipe insulation (9) and secure using tension springs. Fit the bottle end covers (10) at both ends.

11 Assembly Instructions 11 For instructions on how to fit the casings please see page 12.

12 12 Assembly Instructions Fitting the Casings (i) Fit the front base panel (11) from the front. Then the middle and rear base panels (12) are placed in position from the side, between the plinth channels. (ii) The front side panels (1) are first placed in the bottom guide rails (Fig. A) and then attached to the top casing rails. Push the side panels (1) back against the casing rails as far as it goes.(fig B) (iii) Fit the other side panels (14,15). Join the front side panels (1) to the bottom guide rails with spring clips (16, Fig. C). Push the side panels (14,15) up against the front side panels so that there isn t a gap and then fix the panels at the back to the bottom guide rails with the spring clips. (iv) Fit the C-clips (17, Fig. D) to the cubicle retaining rails. (v) Now the front lids (18.19) (on the F1, 2, 51, 52 models) or the front lid (on the F21, 41, 42 models) should be put in place. Then fit the other lids (20). Do not tighten the fixing screws at this stage. (vi) Fix the back panel (21) in position using the self-tapping screws. (vii) Fit the support panel for the electrical control panel (22) and fix to the mounted screws with dome nuts (2). (viii) Mount the cable gland (24) in the support panel with the plastic counter-nut. Blank off the other holes with blank grommets (25). (ix) Push into position the electrical control panel (26). Beforehand, please route the capillaries to the rear, through the opening in the support panel (22). (x) Carefully Insert the thermometer and thermostat sensors into the immersion pocket (27) of the corresponding bottle. Do not remove the plastic clip until the sensor bundle is inserted half way into the immersion pocket. The sensor for a limit thermostat (on unvented systems) must be mounted in the topmost bottle. Do not kink the capillaries. (xi) Then push the retaining spring (28, Fig. E) on the immersion pocket to prevent the thermometer and thermostat sensors from slipping out. (xii) Finally fit the front panel (29) and fix it with the dome nuts (2).

13 Assembly Instructions 1 Wiring up the unit. A copy of the wiring diagram is both in the control panel and at the back of this manual. Unvented systems require a hand reset limit stat. Vented DHW calorifiers only require a control stat. The electrical installation should conform with all relevent British Standards / I.E.E. Regulations. This diagram should be checked for correct application. To gain acess to the back of the control panel, remove the two dome screws and remove the orange support casing which houses the control panel. There are also two screws which can be removed to get inside the control panel. Ensure that the thermostats and the thermometer capiliaries are fitted in the pocket in the calorifier bottle. Before attempting to wire the unit, always refer to the relevant wiring diagram.

14 14 Installation and Piping Layouts Installation and Piping Layouts Installation Fit unions to all pipe connections ensuring that joint seals are fitted. Fit isolating valves to all pipework. Note: The F Modul plus calorifier isn t fitted with a DHW or primary drain tapping. Therefore the primary drain must be fitted in the site pipework off the primary outlet connection and the DHW drain should be fitted in the cold feed. To facilitate venting during drain down, ensure that a manual vent valve is fitted in both the primary inlet and the secondary flow between the calorifier and the isolating valves. On open vented systems the vent should be taken from the same place. Piping layout For the general design of water circuits refer to current British Standards and Codes of Practice. A simple pumped primary flow and return, adequately vented, is all that is needed. Secondary connections are quite conventional. Connect the calorifier(s) to the rest of the system according to the chosen layout. Examples of both primary and secondary systems are shown below: Recommended primary Primary systems Systems (open vented). A Primary Connections Connections from Main Headers. Temperature control from by pump. Main Headers. Temperature control by pump. AAV 1 2 B Primary Connections from Main Headers. Temperature control by diverting valve. 1 4 (if Required) Secondary Water Primary Water 5 4 AAV Primary Water Secondary Water 5 AAV 7 6 Anti-thermal loop 6 Key (1) Safety recommended if not on adjacent boiler or system. (2) Spring loaded non-return valve. () Isolating valves. (4) Primary pump (For diagram B the main circulating pump may be used if sufficient head is available). (5) Thermostat (linked to primary pump to control calorifier DHW temperature, for Diagram A).For diagram B the thermostat controls the diverting valve. On Unventedsystems there is also a limit stat fitted. (6) Drain cock. (7) Diverting valve (use 0 second motor).

15 Installation and Piping Layouts 15 Recommended Primary Systems (open vented) Continued Recommended Primary Systems Continued. C Primary Connections direct from boiler. Temperature control by pump. AAV 2 5 Primary Water 4 Flow 1 D Primary Connections direct from boiler. Temperature control by diverting valve. AAV Primary Water Secondary Water 5 4 (if Required) Secondary Water Boiler 7 Flow 1 6 Anti-thermal loop Return 6 Return Boiler Key (1) Safety recommended if not on adjacent boiler or system. (2) Spring loaded non-return valve. () Isolating valves. (4) Primary pump (For diagram D the main circulating pump may be used if sufficient head is available). (5) Thermostat (linked to primary pump to control calorifier DHW temperature, diagram C). For diagram D the thermostat controls the diverting valve. On Unventedsystems there is also a limit stat fitted. (6) Drain cock. (7) Diverting valve (use 0 second motor). Recommended Secondary Systems. Secondary Connections OPEN VENTED. 4 AAV 6 Vent 1 Primary Water Secondary Water 1 Cold Feed 2 Secondary Circulating Pump Cold water mains Secondary Return Secondary Connections Unvented Secondary Connections UNVENTED. Unvented kits available on request. Manual See page 17. Vent Cold water mains Cold Feed T & P Relief in socket provided Primary Primary Water Secondary Secondary Water Water Secondary Circulating Pump 4 Secondary Return Key (1) Relief valve adjacent to calorifier. (2) Spring loaded non-return valve. () Isolating valves. (4) Open vent. (5) Unvented system kit. (6) Secondary drain valve. Key 1. Expansion Relief adjacent to calori er 2. Spring loaded non return valve. Isolating valves 4. Temperature and pressure relief valve 5. Strainer 6. Pressure reducing valve 7. Double check valve 8. Expansion vessel 9. Lock shield valve 10. Drain valve 11. Manual vent valve 12. Secondary circulating pump

16 16 Unvented Systems Unvented Systems Definition An unvented hot water system differs from conventional open vented systems in that no vent pipe is provided and it is connected to the mains water supply, eliminating the need for the provision of cold water storage tanks in the roof space. The functions, therefore, of the open vents and cold feeds have to be performed in other ways. There are two basic types of unvented system: (1) Direct off the mains, (2) Boosted water supply. An expansion relief valve should be fitted in the cold feed between the expansion vessel and the calorifier. No means of isolating the calorifier from this valve should be installed. A temperature and pressure relief valve should be fitted directly in the calorifier as a thermal protection to prevent the DHW reaching 100 deg C. A hand reset limit stat should be fitted in the calorifier to prevent the DHW overheating. Direct off the mains Where mains pressure is sufficient the system can be connected straight off the mains. However, between the cold water supply and the DHW generator (i.e. the F Modul plus calorifier) there must be an unvented system kit fitted. Unvented System kit Kit. T & P Relief. Hand reset limit stat. Expansion relief valve c/w tundish. Expansion Vessel. Check valve. PRV. Key Strainer. Cold Feed Cold water mains 1. Expansion Relief 2. Manual vent valve *. Isolating valves * 4. T & P relief valve 5. Strainer in control panel As shown in the above diagram, an unvented system kit comprises of the following components:- Strainer (this is optional, but good practice, to prevent debris passing through the valves) Pressure regulating valve (PRV), this allows the pressure to be reduced and controlled at a preset pressure. A pressure gauge is supplied to indicate system pressure. Double check valve, this prevents the expanded water back-feeding into the mains supply and additionally seals the system. An expansion vessel should be fitted between the non return valve and the calorifier to take up expanded water during heat-up Pressure reducing valve 7. Double check valve 8. Expansion vessel 9. Lock shield valve 10. Drain valve* * Not Hoval supply. 4 Boosted water supply Where mains water pressure is insufficient a cold water booster set can be fitted. Normally these sets have integral pressure controls, in the form of either pressure transducers, pressure switches, and or pressure regulating valves. They also have a non return valve which prevents back-feeding. Systems where a booster set is installed should not have a vent and as such are unvented. Boosted systems should have an unvented system kit fitted down-stream from the booster set. This kit should contain a minimum of the following items:- An expansion vessel should be fitted between the non-return valve and the calorifier to take up expanded water during heat-up. Warning: Some pressure booster sets have an accumulator (expansion vessel). This is to reduce the amount of pump starts and should not be confused with the system expansion vessel. An expansion relief valve should be fitted in the cold feed between the expansion vessel and the calorifier. No means of isolating the calorifier from this valve should be installed. A temperature and pressure relief valve should be fitted directly in the calorifier as a thermal protection to prevent the DHW reaching 100 deg C. A hand reset limit stat should be fitted in the calorifier to prevent the DHW overheating. Balanced Unvented Systems Some systems may be fitted with blending valves or mixers that require a balanced hot and cold water supply. When sizing the strainer, the PRV, and check valve care must be taken to ensure they can pass the flow rates at the required pressure. Hoval standard unvented system kits are sized to reduce incoming pressure to bar at a flow rate that meets the peak output of the calorifier only.

17 A separate Strainer and PRV can be fitted to both the hot and cold water services to give balanced system pressures. Alternatively, a larger Strainer and PRV can be installed to cope with both hot and cold water demands. Cold water booster sets tend to be sized on the total demand of the system and subsequently give a balanced condition. Hoval Unvented System Kits Hoval have carefully sized and selected a range of standard unvented system kits suitable for installation with the F Modul plus range of calorifiers. The various valves and fittings should be installed in the sequence shown on the right. The size of the standard unvented kits are shown in the table below. Please note that these kits are only sized for the cold feed going into one of the F Modul plus calorifiers. Using the PRV from a standard Hoval unvented kit to provide a balanced hot and cold water supply may cause pressure and water flow problems. Ensure that the PRV can cope with the demand from both the hot and cold water services. Unvented Systems Warning: On balanced systems with a common PRV, Strainer and Double check valve, ensure that the valves are sufficiently sized to cope with both hot and cold water demand. Unvented System Kit. Unvented System kit T & P Relief. Hand reset limit stat. Expansion relief valve c/w tundish. Expansion Vessel. Check valve. PRV. Strainer. Cold Feed Key Key Cold water mains Cold water mains 1. Expansion Relief 2. Manual vent valve *. Isolating valves * 4. T & P relief valve 5. Strainer 1. Expansion Relief 2. Manual vent valve *. Isolating valves * 4. T & P relief valve 5. Strainer in control panel Pressure reducing valve 7. Double check valve 8. Expansion vessel 9. Lock shield valve 10. Drain valve * Not Hoval supply Pressure reducing valve 7. Double check valve 8. Expansion vessel 9. Lock shield valve 10. Drain valve* * Not Hoval supply Strainer P.R.V. Double Check Expansion Vessel Expansion Relief & Tundish T & P Relief * F litre ¾ HP80-1 1½ F litre ¾ HP F41 1.1/2 1.1/2 1.1/2 150 litre ¾ HP150-1½ 2½ F51 1.1/2 1.1/2 1.1/2 150 litre ¾ HP150-1½ 2½ F2 1.1/2 1.1/2 1.1/2 150 litre ¾ HP150-1½ 2 x 2 F litre ¾ HP x 2½ F litre ¾ HP x 2½ *Supplied factory fitted with unvented calorifier (discharge pipe(s) by others - not supplied November 2015 by Hoval)

18 18 Unvented Systems Multi-calorifier Installations Shared Unvented System Kits Feeding Two or More Calorifiers. Temperature and Pressure Relief Temperature and Pressure Relief Two or more calorifiers can be installed with individual unvented system kits. Where the expansion vessels have been sized to share the total system expansion, the two feed lines can be joined by a pipe to allow both vessels to be used when one calorifier is isolated. Cold Feed Isolation valve Strainer Pressure Reducing Double Check Expansion Vessel Expansion Vessel Drain cock by installer Drain Cock By the Installer Isolating Expansion Vessel Expansion Relief and Tundish Drain cock by installer Isolating Expansion Relief and Tundish Cold Feed Isolation valve Strainer Pressure Reducing Double Check Drain Cock By the Installer Joining Pipe. Common Unvented System Kit. Temperature and Pressure Relief Temperature and Pressure Relief More than one calorifier can be installed off a single common cold feed. Each calorifier must have it s own T & P valve and expansion relief valve. No means of isolating these safety valves from the calorifier should be installed. Cold Feed Strainer Isolation valve Pressure Reducing Double Check Expansion Vessel Drain Cock By the Installer Drain cock by installer Isolating Expansion Relief and Tundish Drain cock by installer Isolating Expansion Relief and Tundish

19 Unvented Systems 19 Balanced Hot and Cold water supplies. Unvented System with balanced hot and cold water services. Temperature and Pressure Relief The hot and cold water supplies can be balanced by utilizing the same strainer and PRV to control the two supply lines. Note it may be necessary to increase the size of these two fittings in comparison to the nonreturn valve in the calorifier cold feed line. Cold Feed Isolation valve Strainer Isolation valve Pressure Reducing Balanced Cold Water Supply Double Check Expansion Vessel Drain Cock By the Installer Drain cock by installer Isolating Expansion Relief and Tundish Balanced hot and cold water services using two PRVs. Temperature and Pressure Relief The hot and cold water supplies can be balanced using two separate PRVs. Balanced Cold Water Balanced Supply Cold Water Supply Expansion Vessel Drain cock by installer Cold Feed Isolation valve Strainer Pressure Reducing Strainer Pressu Reduc Double Check Drain Cock By the Installer Isolating Expansion Relief and Tundish

20 20 Unvented Systems Fitting the Unvented System Kit. Fit the components as indicated. In the suggested schematics detailed on previous pages. All components must be installed in a frost free area. Installation of the Expansion Vessel. Expansion Vessel Ensure that valves and fittings are fitted correctly to suit the direction of flow. Set the Pressure reducing valve (PRV) to bar. Pipe off expansion relief valve via the tundish provided to a gulley. Pipe expansion vessel into cold feed. Fit a lock shield valve and drain between the vessel and the cold feed line. This will allow the expansion vessel gas charge to be checked during maintenance. This is shown on the right. Fit a lock shield valve and drain to allow the expansion vessel to be isolated and drained for periodic inspection. Cold Feed Isolation valve Strainer Pressure Reducing Double Check Drain Cock (By the Installer) Lock Shield (By the Installer) Isolation valve Maintenance of Unvented System Kit. Expansion Vessel Sizing. Clean out strainer on commissioning and annually. Check Expansion relief valve setting annually by twisting the cap on top of the valve. Check expansion vessel gas charge pressure, isolate the vessel, drain off any water in the vessel and test the gas pressure using a tyre gauge. Expansion Vessel Volume = System content (l) x C.o.E. Vessel Efficiency Vessel Efficiency = Max Pressure (Bar Abs) - Min Pressure (Bar Abs) Max Pressure (Bar Abs) Where: Max Pressure is final desired working pressure + 1. Min Pressure is pressure setting on PRV + 1. C.o.E. at 60 Deg C is approx 0.02 Fault Finding. Symptom Possible Cause(s) Remedial Action (A) Reduction in water flow Blockage in strainer Clean out strainer. Blockage in PRV Clean out secondary strainer in PRV. Wrong PRV pressure setting Check PRV pressure setting alter if necessary. (B)Discharge from expansion Debris on valve seat Twist test knob and replace if necessary. Relief valve. Wrong incoming pressure Adjust the pressure setting on PRV. Expansion vessel diaphram Check expansion vessel gas charge. Failure. Insufficient Expansion vessel Check expansion vessel size. volume.

21 Commissioning & Operation 21 Commissioning & Operation Commissioning Instructions Pre-commissioning: Important: Always fill the secondary side of the calorifier before the primary. Pressurising the primary when the secondary is empty may cause the secondary bottle to collapse. Flush all swarf, filings and other debris out of the system, preferably using a proprietary flushing agent. Do not wash particles into the calorifier, this could cause subsequent corrosion. Once the secondary side is fully flooded and sealed, fill the primary system completely and treat the water with a good corrosion inhibitor (e.g. Fernox). Corrosion inhibitors are not used in secondary (tap) water. Ensure that all joints are water tight and all pipework is vented. Check that all electrical connections are complete and correct. Ensure that the thermostat(s) are wired up and the sensor probes are fitted in the stat pocket. The thermostat may be wired into the boiler controls to activate the pumps or a motorised valve. The control thermostat can be adjusted to operate between 0 deg C and 80 deg C and is usually set to 60 deg C. Warning: To avoid Legionellae, ensure the calorifier control stat is set at a minimum of 60 deg C. Commissioning (1) Light the boiler (refer to the appropriate boiler operating instructions). (2) Adjust the calorifier thermostat to the required operating temperature. () Check that the thermostat is operating correctly. (4) Ensure that the primary pump is working or primary primary circuit is established. (5) Check that the operating temperature remains constant. Operating Instructions The calorifier thermostat when wired to the primary circulating pump or diverting valve provides completely automatic control. It is necessary only to adjust the thermostat if the occasion demands.

22 22 Inspection and Maintenance Inspection and Maintenance Periodic Inspection The user is advised to carry out periodic inspection between main servicing periods and it is recommended that the specialist servicing company also carries them out. Note: Before opening the inspection covers always ensure you have a new inspection cover joint. Each bottle has two covers (one at each end, (e.g. 20 on a F52 calorifier). Model Joint Cat No. ALL F Modul plus Inspect the calorifier casing for obvious signs of damage, corrosion or deterioration. Inspect the calorifier siting for signs of crack ing or settling. Inspect all pipes and connections for obvious damage or deterioration. Remove calorifier front/rear panel and exam ine interior for corrosion and deterioration. If anodes are fitted, check for deterioation. Draining Down Note: The primary side of the calorifier MUST always be drained before the secondary. The secondary MUST always be filled before the primary. FOLLOW THE PROCEDURE BELOW: (1) Ensure that both primary and secondary pumps are switched off. (2) Isolate the primary inlet and outlet. () Fit hose to primary drain which should be installed in primary outlet and run the hose to a gulley. (4) Open primary vent valve. (5) Open primary drain. (6) Isolate all secondary connections. (7) Fit hose to the secondary drain which is lo cated underneath the calorifier and run the hose to a gulley. (8) (On sealed systems) Open manual secondary vent valve (this should be fitted in secondary flow between calorifier and isolating valve). (9) Open secondary drain valve. When filling the calorifier follow the above procedure but in reverse. Cleaning The period between cleaning will depend on operating temperature and hardness of water. Local conditions will serve as a guide. Normally descaling will be required less often than with conventional calorifiers. The following procedure should be adopted: (1) Remove calorifier front / rear casing panel. (2) Remove cleanout cover for calorifier internals. () Scrape the inside surface with a non ferrous scraper when deposits of scale are found. Note: Chemical cleaning can be carried out if required, but such work should be undertaken in accordance with the instructions of the de-scaling compound manufacturer. We recommend chemical treatment specialist such as Aquazur. After chemically cleaning the DHW calorifier internal, ensure that the unit is thorougly flushed out with clean water. Following cleaning, replace inspection cover using a new gasket to prevent leaks.

23 Inspection and Maintenance 2 Inspection and Maintenance Periodic Inspection Units fitted with sacrificial magnesium anodes should be checked on a twice yearly basis to assess the deterioration of the anode. To inspect the anodes follow the procedure be- low:- () Carefully rest the new anode in the slot on the plastic support pipe. (4) Screw the new anode to the socket in the inspection cover and replace rubber gaskets and carefully fit the covers. Note: Before opening the inspection covers always ensure you have a new inspection cover joint. Each bottle has two covers (one at each end, (e.g. 20 on a F52 calorifier). Example - F1 (1) Drain the calorifier down. Magnesium Anode Note: Follow the draining down procedure on page 22. (2)Carefully undo the nut holding the inspection cover in place. Support the inspection cover by holding the fixing stud. Carefully remove the inspection cover bracket and allow the inspection cover to rest on the stud. Plastic Support Pipe Rubber Door Joint Inspection Cover () Using a torch assess the state of the anode. Note when the anode is about 10mm in diameter new anodes should be fitted. (4) If the anodes are greater than 10mm in diameter, replace the rubber gaskets and carefully refit the covers. (5) Once all of the covers have been fitted, refill the calorifier, (Secondary side first, then the Primary side). Fitting New Anodes If new anodes are required: (1) Unscrew the old anodes off the inspection covers. (2) Carefully remove the old anode, making sure that you do not dislodge the plastic support pipe at the other end. Part Description Cat Number Magnesium Anode Inspection Cover Rubber Door Joint Plastic Support Pipe Please note you will need one of each of the above per bottle. Please contact our spares department to order replacement parts.

24 24 Immersion Heaters Immersion Heaters General All work should be carried out by suitably qualified personnel. Heaters must be handled with care and stored in dry conditions. Adequate withdrawal space must be provided to allow the removal of the heater assembly. Carefully remove all protective packaging and visually inspect unit for any transit damage. All prevailing rules, regulations and bylaws in force at the time and place of installation must be observed. Heaters must only be immersed in the fluid they are designed to heat. The introduction of alternative fluids even in small concentrations for purposes such as sterilising may cause serious damage to the heater and will invalidate the warranty. Any modification not carried out by Heatex Limited or its approved agent will invalidate certification and warranty. Precautions must be taken to prevent damage to enclosure seals. Installation The heater should be securely fixed in position and all terminal connections checked for tightness before energising. The installed orientation of horizontally mounted heaters must be such that any thermostats or other temperature sensors are uppermost. Sealing gaskets must be undamaged. The terminal box must not be used for tightening heater into tank or vessel. Electrical Supply Connection Refer to wiring diagram on page 25. The cable entry or gland plate is positioned on the side of the terminal box. Before connection ensure that the supply corresponds with that specified on the rating label. Ensure that the sizes and types of cables to be used are suitably rated for the load and temperature of the unit. Each heater must be protected by a suitably rated over current device. The cables must enter the heater terminal box via a suitable cable gland to maintain the IP rating and be fitted by a qualified person. Earth Connection THESE HEATERS MUST BE EARTHED An earth connection is provided inside the terminal box. Operation Ensure that the active sections of all the heating elements are fully immersed in the fluid to be heated at all times whilst energized. Heat is transferred by means of electric heating elements. Control of the heater is facilitated by thermostats, thermocouples or RTDs and reference should be made to the wiring diagram inside cover to ensure that these are correctly connected and set prior to energising the heater. Where a manual reset thermostat or cut-out is installed, the terminal box cover will have to be removed after isolating the heater to enable a reset to be carried out. Maintenance All prevailing site safety regulations shall be adhered to at all times. Equipment is to be fully isolated from the electrical supply and locked off before and whilst any work is being carried out. Routine Maintenance Monthly Generally inspect the equipment for external damage or leaks. 6 Monthly Isolate the electrical supply and remove the cover. Ensure the terminal box is clean and dry internally. Ensure the electrical terminals are intact and secure. Check that the heating element insulation resistance is at least 2 mega ohms. Check the continuity of all elements. Refit cover with new gasket if required. Ensure that earth continuity is maintained between all exposed conductive material and main site structure. Annually Carry out all monthly and 6 monthly checks as above. Check for element failure or low insulation resistance. If heaters are being left unused for a period greater than months, carry out 6 monthly maintenance before energizing.

25 Immersion heater Electrical Diagrams 25 Immersion heater Electrical Diagrams

26 26 Fault finding Fault Finding Chart Please carry out checks as per the list below when faults occur. If you cannot rectify the fault, contact Hoval Customer Services or your installer. Telephone number and address are shown on the rear cover. Symptom Possible Cause Action A. Primary Water Circuit Inefficient (1) Leakage in system. (2) Pump faulty or inoperative. () Boiler faulty or inoperative. (4) Circuit not properly vented. (5) Pump not of sufficient duty. (1) Check pipe connection. Renew if required. (2) Refer to appropriate pump part document. () Refer to appropriate boiler part document. (4) Vent primary system. (5) Change pump speed or pump. Symptom Possible Cause Action A. Secondary water temperature not as setting on thermostat. (1) Leakage in system. (2) Pump faulty or inoperative. () Thermostat faulty. (4) Electrical fault in control system. (5) Calorifier scaled up. (6) Calorifier not large enough for load imposed. (7) Low primary temperature. (8) Diverting valve bypassing. (1) Check pipe connection. Renew if required. (2) Refer to appropriate pump part document. () Check and replace if required. (4) Refer to appropriate control system part document. (5) Mechanically / chemically descale as necessary. (6) Change calorifier or add calorifier / buffer vessel. (7) Turn up boiler thermostats / increase primary flow rate. (8) Check primary pipe cools when hot water not required.

27 Electrical Diagrams 27 Wiring Diagrams for Open Vented Calorifiers

28 28 Electrical Diagrams Wiring Diagrams for Unvented Calorifiers

29 Notes 29

30 Conservation of Energy Protection of the Environment Hoval Limited, Northgate, Newark, Notts NG24 1JN Telephone: Service Desk Spares Desk Fax service@hoval.co.uk and spares@hoval.co.uk Web Site: November 2015

Powerstock Storage Tank

Powerstock Storage Tank Powerstock Storage Tank Models ST300, ST500, ST750 & ST1000 INSTALLATION, COMMISSIONING AND SERVICING INSTRUCTIONS THE POWERSTOCK STORAGE TANK IS INTENDED FOR USE AS A COMMERCIAL APPLIANCE. PUBLICATION

More information

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION SOLARCYL IM/SC INSTALLATION MANUAL This manual gives detailed advice for installation and should be read carefully prior to fitting any unvented

More information

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION 0 RD 0 RI 0000-06 IM/ IM/a INSTALLATION MANUAL This manual gives detailed advice for installation and should be read carefully prior to fitting

More information

Installation, Operation and Maintenance Instructions for Electric Storage Calorifier

Installation, Operation and Maintenance Instructions for Electric Storage Calorifier OM004 Installation, Operation and Maintenance Instructions for Electric Storage Calorifier The operating and maintenance instructions contained within this package are for standard electric storage calorifiers

More information

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION Ecoline Geo RI HP INSTALLATION MANUAL The Ecoline GEO is an indirect unvented cylinder designed and approved for use with a heat pump. The

More information

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual POWERFLOW Series Unvented Electric Storage Water Heaters Installation & Operating Instructions Manual These Instructions must be left with the user after installation. Version 3.0 June 2009 Hyco POWERFLOW

More information

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier OM001 Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier These operating and maintenance instructions are for standard semi-storage calorifiers (vessels fitted with

More information

SEALED THERMAL STORE

SEALED THERMAL STORE ISSUE 3 0717 INSTALLATION AND USER GUIDE ENERGYMANAGER SEALED THERMAL STORE ADVANCE APPLIANCES LTD PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE. SCHEMATIC DIAGRAM OF ENERYMANAGER THERMAL

More information

Technical information Installation instructions. Modul-plus (F21-52) High performance calorifiers

Technical information Installation instructions. Modul-plus (F21-52) High performance calorifiers Technical information Installation instructions Modul-plus (F21-52) High performance calorifiers These instructions apply to the following types: 5/6-Modul-plus F (21) 5/6-Modul-plus F (31) 5/6-Modul-plus

More information

OPERATING & MAINTENANCE INSTRUCTIONS FOR EXHEAT RFA-OS TYPE FLAMEPROOF OVERSINK WATER HEATER

OPERATING & MAINTENANCE INSTRUCTIONS FOR EXHEAT RFA-OS TYPE FLAMEPROOF OVERSINK WATER HEATER OPERATING & MAINTENANCE INSTRUCTIONS FOR EXHEAT RFA-OS TYPE FLAMEPROOF OVERSINK WATER HEATER 1 1.0 GENERAL 1.1 All work should be carried out by suitable qualified personnel. 1.2 Heaters must be handled

More information

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT FLR TYPE FLAMEPROOF RADIATORS

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT FLR TYPE FLAMEPROOF RADIATORS INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT FLR TYPE FLAMEPROOF RADIATORS Please read these instructions thoroughly before installation and ensure they are passed on to the end-user 1 1.0

More information

Powerflow Unvented water heater

Powerflow Unvented water heater Product Instruction Manual Powerflow Unvented water heater 30, 50 and 90 litres v15.6/5 Thank you for purchasing a Powerflow series unvented electric water heater. The Powerflow is suitable for hand washing

More information

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500 Unvented Calorifier Range. Operating and Maintenance Manual. For Models 125 300 & 500 Telephone 08456 448802 Fax 08456 448803 Emial info@mhgheating.co.uk Web www.mhgheating.co.uk TABLE OF CONTENTS. Section

More information

Hoval Cosmo Combination boilers. High efficiency heating combined with economic DHW generation. Boiler outputs from 100 to 1450kW.

Hoval Cosmo Combination boilers. High efficiency heating combined with economic DHW generation. Boiler outputs from 100 to 1450kW. boilers. High efficiency heating combined with economic DHW generation. Boiler outputs from 00 to 0kW. DHW output to,00 litres per hour. Where quality and reliability cannot be compromised, select the

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information

Unvented Electric Water Heater 10/15 litre Undersink

Unvented Electric Water Heater 10/15 litre Undersink Unvented Electric Water Heater 10/15 litre Undersink Fitting Instructions and User Guide 1 CONTENTS SECTION PAGE 1.0 INTRODUCTION 2 2.0 TECHNICAL SPECIFICATION 3 3.0 INSTALLATION 4 4.0 COMMISSIONING 9

More information

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 COMPACT PLUS 10 and 15 Litre Unvented Under and Over Sink Water Heater INSTALLATION AND USER GUIDE 1 DIMENSIONS 10L - 250mm 15L - 310mm 100mm 80mm 410mm

More information

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No 53 416 06 Publication No. ZZ 180/17 May 2000 These appliances are tested and certified by B G Technology for

More information

Puro Mini Dual Control Shower Mixer PU90010CP

Puro Mini Dual Control Shower Mixer PU90010CP Puro Mini Dual Control Shower Mixer PU90010CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept

More information

Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to 8 bar. Heatpack boilers. to 2900kW.

Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to 8 bar. Heatpack boilers. to 2900kW. Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to bar. Heatpack boilers to 2900kW. Whether your application is for single, multiple or space saving heatpack boilers, Hoval always

More information

Inta City Shower Mixing Valve CT20010CP

Inta City Shower Mixing Valve CT20010CP Inta City Shower Mixing Valve CT20010CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept any responsibility

More information

Alpha CombiMax 350 and 600

Alpha CombiMax 350 and 600 Installation and Servicing Instructions Alpha CombiMax 350 and 600 Unvented Hot Water Store for use with the Alpha 240/280 Range of Gas Fired Combination Boilers For Technical help or for Service call...

More information

Inta City Concealed Shower Mixing Valve CT80010CP

Inta City Concealed Shower Mixing Valve CT80010CP Inta City Concealed Shower Mixing Valve CT80010CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept

More information

Installation and User Instructions HS10U, HS15U.

Installation and User Instructions HS10U, HS15U. Installation and User Instructions HS10U, HS15U. MULTIPOINT Please read and understand these instructions before starting work. Please leave this leaflet with the user following installation PACK CONTENTS

More information

Hoval SR-plus heating boilers Outputs from 350 to 4000kW Working pressures to 8 bar

Hoval SR-plus heating boilers Outputs from 350 to 4000kW Working pressures to 8 bar Hoval SR-plus heating boilers Outputs from 30 to 4000kW Working pressures to 8 bar ...built in the UK where high quality and reliability have been a way of life for generations. Hoval SR-plus Simplicity

More information

Deluge Shower Mixing Valve 10045CP

Deluge Shower Mixing Valve 10045CP Deluge Shower Mixing Valve 10045CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept any responsibility

More information

Quantum. Installation, User and Service Manual. Hot Spring

Quantum. Installation, User and Service Manual. Hot Spring Hot Spring Domestic Hot Water Cylinder Storage Capacities 90, 125, 150, 170, 200, 250 and 300 Litres 1 Important - This Manual should be left with the householder after installation Index Section Page

More information

Telo Shower Mixing Valve TL10016CP

Telo Shower Mixing Valve TL10016CP Telo Shower Mixing Valve TL10016CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept any responsibility

More information

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL STREBEL GENEVA CE ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL INDEX TABLE 1 TECHNICAL DATA SECTION 1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION 6 SECTION 7 SECTION 8 SECTION

More information

Installation, Operation and Maintenance Instructions Electric Flow Heater OM009

Installation, Operation and Maintenance Instructions Electric Flow Heater OM009 Installation, Operation and Maintenance Instructions Electric Flow Heater OM009 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail: sales@gmsthermal.co.uk

More information

Installation, Operating and Servicing Instructions

Installation, Operating and Servicing Instructions Installation, Operating and Servicing Instructions Wall Mounted Water Boiler WMB3F/B,WMB3F/W Please make a note of your product details for future use: Date Purchased: Model Number: Serial Number: Dealer:

More information

MW & EW 10 & 15 Litre Unvented Water Heaters HANDBOOK. IMPORTANT: This booklet should be given to the customer after installation and demonstration.

MW & EW 10 & 15 Litre Unvented Water Heaters HANDBOOK. IMPORTANT: This booklet should be given to the customer after installation and demonstration. MW & EW 10 & 15 Litre Unvented Water Heaters HANDBOOK IMPORTANT: This booklet should be given to the customer after installation and demonstration. Description of water heater 1) Hot water outlet 2) Temperature

More information

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT INDUSTRIAL FLR & FLRA TYPE FLAMEPROOF RADIATORS

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT INDUSTRIAL FLR & FLRA TYPE FLAMEPROOF RADIATORS INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT INDUSTRIAL FLR & FLRA TYPE FLAMEPROOF RADIATORS Please read these instructions thoroughly before installation and ensure they are passed on to

More information

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FAW, FAW-C & FAW-C-T TYPE AIR WARMERS FCR & FCR-A TYPE CONVECTORS

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FAW, FAW-C & FAW-C-T TYPE AIR WARMERS FCR & FCR-A TYPE CONVECTORS INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FAW, FAW-C & FAW-C-T TYPE AIR WARMERS FCR & FCR-A TYPE CONVECTORS STW & STW-T SAFE AREA AIR WARMERS HFT, AFT & SAT TYPE AIR THERMOSTATS Please read these

More information

Installation and Servicing Instructions. Alpha FlowSmart

Installation and Servicing Instructions. Alpha FlowSmart Installation and Servicing Instructions Alpha FlowSmart Hot Water System incorporating an Alpha InTec 30/40GS Condensing Combination Boiler with Integrated Flue Gas Heat Recovery Device and wall mounted

More information

Plus Bath Shower Mixing Valve CP and PL30020CP

Plus Bath Shower Mixing Valve CP and PL30020CP Plus Bath Shower Mixing Valve 920000CP and PL30020CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot

More information

Mio Concealed Shower Mixing Valve MI40010CP

Mio Concealed Shower Mixing Valve MI40010CP Mio Concealed Shower Mixing Valve MI40010CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept any

More information

T E C H C A L EBS-1 T High technology heating

T E C H C A L EBS-1 T High technology heating IMPORTANT FOLLOW COMMISSIONING INSTRUCTIONS OBSERVE THE WARRANTY CONDITIONS READ THE WHOLE MANUAL CAREFULLY NO SAFETY DISCHARGE TO BE REDUCED IN SIZE. CONDENSE TO BE 32 mm PVC T E C H NI C A L I N ST EBS-1

More information

Sema thermostatic bar mixer Installation and operating instructions

Sema thermostatic bar mixer Installation and operating instructions Sema thermostatic bar mixer Installation and operating instructions Installers please note these instructions are to be left with the user 2180579A September 2006 CONTENTS Page Introduction 1 Safety warnings

More information

User and Installation Instructions. Wall Mounted Water Boiler WMB3F/B and WMB3F/W IS435 ECN3461

User and Installation Instructions. Wall Mounted Water Boiler WMB3F/B and WMB3F/W IS435 ECN3461 User and Installation Instructions Wall Mounted Water Boiler WMB3F/B and WMB3F/W IS435 ECN3461 Dear Customer Thank you for purchasing this Lincat product. With correct use and careful maintenance as described

More information

TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw /17 Subject to modification

TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw /17 Subject to modification TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw Subject to modification Contents 1. Important Information 4 1.1. Documentation 4 1.2. Guarantee

More information

NENE. Installation and Operating Instructions. Thermostatic bar mixer shower PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER

NENE. Installation and Operating Instructions. Thermostatic bar mixer shower PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER NENE Thermostatic bar mixer shower Installation and Operating Instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER 2180430B October 2005 CONTENTS Page Introduction 1 Safety

More information

Thermostatic bar mixer valve with adjustable head Installation guide

Thermostatic bar mixer valve with adjustable head Installation guide Bar valve Thermostatic bar mixer valve with adjustable head Installation guide Index Introduction p.3 - Safety information p.3 - Product specification p.3 Connection to supplies p.3 - Flushing p.4 - Filters

More information

MEGAFLO HE Iss 1

MEGAFLO HE Iss 1 MEGAFLO HE 1 36 00 5843 Iss 1 Contents Contents SECTION PAGE 1 INTRODUCTION... 3 2 GENERAL REQUIREMENTS... 4 3 INSTALLATION - GENERAL... 5 4 INSTALLATION - DIRECT UNITS... 8 5 INSTALLATION - INDIRECT UNITS...

More information

REDRING POWERSTREAM UNVENTED INSTANTANEOUS WATER HEATER. Installation and User Guide

REDRING POWERSTREAM UNVENTED INSTANTANEOUS WATER HEATER. Installation and User Guide : GUARANTEE AND CONTACT DETAILS REDRING POWERSTREAM UNVENTED INSTANTANEOUS WATER HEATER Installation and User Guide APPLIED ENERGY PRODUCTS LIMITED MORLEY WAY, PETERBOROUGH PE2 JJ TEL: +44 (0) 844 372

More information

Enzo Concealed Shower Mixing Valve

Enzo Concealed Shower Mixing Valve Enzo Concealed Shower Mixing Valve EZ40010CP, EZ40013CP & EZ40014CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible.

More information

Technical and Installation manual All Models

Technical and Installation manual All Models WATER CONTROL setting the standards Technical and Installation manual All Models CONTENTS CONTENTS Section 1 Introduction 1-1 Introduction ---------------------------------------------- 2 1-2 System Layout

More information

Installation, Operation and Maintenance Instructions for PlantPac Steam Plate Heat Exchanger Package

Installation, Operation and Maintenance Instructions for PlantPac Steam Plate Heat Exchanger Package OM014 Installation, Operation and Maintenance Instructions for PlantPac Steam Plate Heat Exchanger Package The operating and maintenance instructions contained within this package are for PlantPac packaged

More information

THE REMEHA HIU RANGE Installation, operation and maintenance manual December 2017

THE REMEHA HIU RANGE Installation, operation and maintenance manual December 2017 Installation, operation and maintenance manual December 2017 CONTENTS The following instructions are for the E70/5, E70/9, T60/5 & T60/7. Introduction... 3 Declaration of conformity... 3 Symbol key...

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION 142039-02 GEO 9-2015 Ecoline Geo RI HP INSTALLATION MANUAL The Ecoline GEO is an indirect unvented cylinder designed and approved for use with

More information

SERVICE MANUAL. Bradford White ElectriFLEX HD (Heavy Duty) Commercial Electric Water Heater CEHD SERIES Immersion Thermostat Models

SERVICE MANUAL. Bradford White ElectriFLEX HD (Heavy Duty) Commercial Electric Water Heater CEHD SERIES Immersion Thermostat Models Bradford White ElectriFLEX HD (Heavy Duty) Commercial Electric Water Heater CEHD SERIES Immersion Thermostat Models SERVICE MANUAL Troubleshooting Guide and Instructions for Service (To be performed ONLY

More information

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION SLIMLINE INSTALLATION MANUAL This cylinder is manufactured and approved in accordance with EN 897:006. This manual gives detailed advice for

More information

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION 09-0 05-05 INSTALLATION MANUAL This cylinder is manufactured and approved in accordance with EN 897:006. This manual gives detailed advice

More information

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE:

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE: TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE: 560955 CE Directive 2006/95/CEE British Standard EN 60335-1 (C 73800) 1 CONTENTS Page 1) INTRODUCTION 1.1) Description 3 1.2) Dimensions & connections

More information

Installation and Commissioning Manual

Installation and Commissioning Manual Manual Advance Buffer Vessels for Ground Source Heat Pump Systems Installation and Commissioning Manual Copyright 2015 Kensa Heat Pumps Ltd Page 1 of 12 Contents Page Section Description Page 1... Safety

More information

Enzo Safe Touch Thermostatic Shower EZ10010CP & EZ10014CP

Enzo Safe Touch Thermostatic Shower EZ10010CP & EZ10014CP Enzo Safe Touch Thermostatic Shower EZ10010CP & EZ10014CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot

More information

OPERATING AND MAINTENANCE MANUAL FOR VERTICAL IMMERSION HEATED STEAM BOILERS. Technical Control Systems Limited MODELS "VIHS"

OPERATING AND MAINTENANCE MANUAL FOR VERTICAL IMMERSION HEATED STEAM BOILERS. Technical Control Systems Limited MODELS VIHS OPERATING AND MAINTENANCE MANUAL FOR VERTICAL IMMERSION HEATED STEAM BOILERS Technical Control Systems Limited MODELS "VIHS" Technical Control Systems Ltd Treefield Industrial Estate Gildersome, Leeds

More information

USER MANUAL INSTALLATION INSTRUCTIONS WARRANTY REGISTER

USER MANUAL INSTALLATION INSTRUCTIONS WARRANTY REGISTER USER MANUAL INSTALLATION INSTRUCTIONS WARRANTY REGISTER GREENGLO MAINS PRESSURE INTEGRATED WATER HEATER SINGLE COIL SERIES & DOUBLE COIL SERIES GREENGLO SAVER Customer Congratulations for choosing a GreenGlo

More information

Unvented water heater

Unvented water heater Unvented water heater Description of water heater 1)Hot water outlet 2)Temperature and pressure relief valve (30 litre only) 3)Cold water inlet 4)Control cover 5)Regulation knob 6)Heating neon Over-sink

More information

AIRE. Thermostatic bath shower mixer. Installation and Operating Instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER

AIRE. Thermostatic bath shower mixer. Installation and Operating Instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER AIRE Thermostatic bath shower mixer Installation and Operating Instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER 2180427C October 2005 CONTENTS Page Introduction 1 Safety

More information

Speedflow Undersink Unvented Water Heater. Models SF05K, SF10K and SF15K. Instruction Manual

Speedflow Undersink Unvented Water Heater. Models SF05K, SF10K and SF15K. Instruction Manual Speedflow Undersink Unvented Water Heater Models SF05K, SF10K and SF15K Instruction Manual Version 3.0 June 2010 HYCO SPEEDFLOW UNVENTED WATER HEATER MODELS SF05K (5 Litres) SF10K (10 Litres) AND SF15K

More information

IMPORTANT: PLEASE READ ALL THESE INSTRUCTIONS BEFORE COMMENCING INSTALLATION

IMPORTANT: PLEASE READ ALL THESE INSTRUCTIONS BEFORE COMMENCING INSTALLATION AIR TO WATER HEAT PUMP SYSTEM HOT WATER CYLINDER INDIRECT HEATING METHOD CLOSED OUTLET (UNVENTED) INSTALLATION AND SERVICE MANUAL HWS-1501CSHM3-UK HWS-2101CSHM3-UK HWS-3001CSHM3-UK 36006030_Issue_H 1 INSTALLATION

More information

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc Mikrofill Ethos Condensing combination boiler Maintenance Instructions 24cc IMPORTANT Benchmark Installation, Commissioning and Service Record Log Book is enclosed in your customer information pack. This

More information

INTA ION MODERN BAR / BATH SHOWER MIXER CP

INTA ION MODERN BAR / BATH SHOWER MIXER CP INTA ION MODERN BAR / BATH SHOWER MIXER 910000CP INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS PLEASE LEAVE THESE INSTRUCTIONS WITH THE USER Page 1 of 10 INTRODUCTION This installation guide has

More information

Installation & Technical Guide. Domestic & Commercial.

Installation & Technical Guide. Domestic & Commercial. Installation & Technical Guide Domestic & Commercial www.challisbooster.com www.challisboosterplus.com Installation and Technical Guide Domestic and Commercial Challis Water Controls Europower House, Lower

More information

Installation and User Instructions Aquaheat Unvented Water Heaters Models: AH30H

Installation and User Instructions Aquaheat Unvented Water Heaters Models: AH30H Installation and User Instructions Aquaheat Unvented Water Heaters Models: AH30H Please read and understand these instructions before starting work. Please leave this leaflet with the user following installation

More information

THERMflow Thermal Store Cylinders

THERMflow Thermal Store Cylinders THERMflow Thermal Store Cylinders Technical Manual Tel: (01592) 611123 www.mcdonaldwaterstorage.com September 2018 THERMflow Thermal Store Tank Technical Manual Manual must be completed by Installer and

More information

Enzo and Enzo Deluxe Safe Touch Thermostatic Shower EN10031CP & EN10035CP

Enzo and Enzo Deluxe Safe Touch Thermostatic Shower EN10031CP & EN10035CP Enzo and Enzo Deluxe Safe Touch Thermostatic Shower EN10031CP & EN10035CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as

More information

Kiko Bath Shower Mixing Valve KK90015CP

Kiko Bath Shower Mixing Valve KK90015CP Kiko Bath Shower Mixing Valve KK90015CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept any responsibility

More information

Deluge Concealed Shower Mixing Valve DL40010CP

Deluge Concealed Shower Mixing Valve DL40010CP Deluge Concealed Shower Mixing Valve DL40010CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept

More information

Unvented Direct & Indirect Hot Water Cylinders (400L L)

Unvented Direct & Indirect Hot Water Cylinders (400L L) Unvented Direct & Indirect Hot Water Cylinders (400L - 2500L) Important Please read & understand all these instructions before commencing installation. Please leave this manual with the customer for future

More information

MIX Boiler & Font Range Service Manual

MIX Boiler & Font Range Service Manual MIX Boiler & Font Range Service Manual 1000870# 1000871# 1000875# 1000880# 1000887# 1000878 1000879 2300268 www.marcobeveragesystems.com Ireland Tel: +353 (1) 295 2674 UK Tel: +44 (0207) 2744577 Service

More information

REDRING POWERSTREAM UNVENTED INSTANTANEOUS WATER HEATER. Installation and User Guide

REDRING POWERSTREAM UNVENTED INSTANTANEOUS WATER HEATER. Installation and User Guide REDRING POWERSTREAM UNVENTED INSTANTANEOUS WATER HEATER Installation and User Guide IMPORTANT: This booklet should be left with the user after installation and demonstration. It should be kept in a safe

More information

Multi-Elec COMPACTE BOILER

Multi-Elec COMPACTE BOILER Multi-Elec COMPACTE BOILER TECHNICAL MANUAL 03/2013 CODE: 560956 CE Directive 2006/95/CEE British Standard EN 60335-1 (C 73800) FOR TECHNICAL HELP/ADVICE Call 0161 621 5960 or email info@atlanticboilers.com

More information

Installation, Operating and Servicing Instructions

Installation, Operating and Servicing Instructions EN 0 / 0 / 00 / 800 Installation, Operating and Servicing Instructions excellence in hot water EN Y000.D EN INDEX Warnings Who should read these instructions Symbols Recommendations Applicable standards

More information

Ca 6s and BCa 6s kw INSTALLATION AND OPERATING INSTRUCTIONS. Page 1 31/07/00

Ca 6s and BCa 6s kw INSTALLATION AND OPERATING INSTRUCTIONS. Page 1 31/07/00 Ca 6s and BCa 6s 33-64 kw INSTALLATION AND OPERATING INSTRUCTIONS Page 1 CONTENTS: General specification Dimensions for Ca6s and BCa6s boilers. Boiler room clearance requirements Boiler block assembly

More information

Oltis thermostatic bar mixer

Oltis thermostatic bar mixer Oltis thermostatic bar mixer Installation and operating instructions Installers please note these instructions are to be left with the user 2180564E February 2009 CONTENTS Page Introduction... 1 Safety

More information

Atmos EasySolar. Installation Instructions for. In-roof and flat roof installation with flat plate collectors

Atmos EasySolar. Installation Instructions for. In-roof and flat roof installation with flat plate collectors Atmos EasySolar Installation Instructions for Atmos EasySolar In-roof and flat roof installation with flat plate collectors Atmos Heating Systems West March Daventry Northants, NN11 4SA Tel: 01327 871990

More information

Crown Boiler Company

Crown Boiler Company Crown Boiler Company 1 Phantom Boiler System Combi Kit Instruction Manual I Product Description This kit adds the ability to generate DHW, as well as heat, ( combi capability) to select Phantom models

More information

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l Installation instructions for contractors VIESMANN Vitocell 300-B Type EVBA-A Dual mode DHW cylinder, 300 and 500 l VITOCELL 300-B 1/2017 Dispose after installation. Safety instructions Please follow these

More information

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5 4 ±0.5 12.0 Servicing 12.2 Annual Servicing Inspection (Cont) Flame Sensing 5 ±1 10 ±1 Position Fig. 45 Spark Ignition 5. Remove the clip securing the gas feed pipe to the air/gas venturi. Disconnect the

More information

Enzo Safe Touch Thermostatic Shower EZ20011CP & EZ20012CP

Enzo Safe Touch Thermostatic Shower EZ20011CP & EZ20012CP Enzo Safe Touch Thermostatic Shower EZ20011CP & EZ20012CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot

More information

User and Installation Instructions. Opus 700 Electric Wet Well Bain Marie OE7601 IS195 ECN2396

User and Installation Instructions. Opus 700 Electric Wet Well Bain Marie OE7601 IS195 ECN2396 User and Installation Instructions Opus 700 Electric Wet Well Bain Marie OE7601 IS195 ECN2396 Please read the following carefully before using this appliance. Warnings and Precautions Please ensure that

More information

Osprey 2 CFL

Osprey 2 CFL Osprey 2 CFL 125-150 - 180-220 Gas Fired Floor Standing Boiler Installation and Servicing Instructions Please leave these instructions with the user Natural Gas Potterton Osprey 2 CFL 125 G.C.N o 41 590

More information

Rycroft Storage & Non-Storage Calorifiers. Installation, Operation & Maintenance Manual

Rycroft Storage & Non-Storage Calorifiers. Installation, Operation & Maintenance Manual Ormandy Rycroft Duncombe Road Bradford BD8 9TB England TEL +44 (0)1274 490911 FAX +44 (0)1274 498580 www.rycroft.com Rycroft Storage & Non-Storage Calorifiers Installation, Operation & Maintenance Manual

More information

INSTALLATION MANUAL. RD SERIES Digital Electric Water Heater Wall-hung Unvented

INSTALLATION MANUAL. RD SERIES Digital Electric Water Heater Wall-hung Unvented INSTALLATION MANUAL RD SERIES Digital Electric Water Heater Wall-hung Unvented WELCOME Dear Customer, Thank you for choosing the RD Series electric water heater, with an exclusive electronic temperature

More information

Clyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw

Clyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw 90 kw Clyde Alkon 90 LP Gas Floor standing condensing boilers Natural Gas 90 kw Contents General information Dimensions and Data Installation requirements Boiler wiring diagram Hydraulic systems Page Fully

More information

Dove Eco thermostatic bar mixer shower

Dove Eco thermostatic bar mixer shower Dove Eco thermostatic bar mixer shower Eco Statement This product has been fitted with a flow regulator to deliver a maximum flow rate of 6 litres per minute. Installation and operating instructions Installers

More information

Hamworthy. Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters. Exceeds Minimum Requirements

Hamworthy. Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters. Exceeds Minimum Requirements Exceeds Minimum Requirements Hamworthy Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters 18.9 kw to 20.1 kw, Natural Gas or LPG Continuous outputs 369

More information

Bar valve with fixed and adjustable shower heads. Installation guide. Midas Plus installation instructions Page 1

Bar valve with fixed and adjustable shower heads. Installation guide. Midas Plus installation instructions Page 1 Midas Plus Bar valve with fixed and adjustable shower heads Installation guide Midas Plus installation instructions Page 1 Midas Plus Midas Plus installation instructions Page 2 Components Literature not

More information

AquaFlo II. Issue 3 December Please read these instructions carefully before commencing installation of the AquaFlo unvented water heater

AquaFlo II. Issue 3 December Please read these instructions carefully before commencing installation of the AquaFlo unvented water heater Installation, Maintenance and User Instructions AquaFlo II Issue 3 December 2011 Please read these instructions carefully before commencing installation of the AquaFlo unvented water heater Please leave

More information

Intatherm Safe Touch Basin Tap IT1008CP

Intatherm Safe Touch Basin Tap IT1008CP Intatherm Safe Touch Basin Tap IT1008CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept any responsibility

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL T Edition 0 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 88 STRATFORD, CT 0665

More information

MIDAS. Installation instructions 110/220

MIDAS. Installation instructions 110/220 MIDAS Installation instructions 110/220 INDEX INTRODUCTION Page 3 Safety information Page 3 Product specification Page 3 Important information CONNECTION TO SUPPLIES Page 4 Flushing Page 4 Filters Page

More information

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data Electrical Details Connection Details Dimensions Standing Losses

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data Electrical Details Connection Details Dimensions Standing Losses INSPIRED H I G H H O T EF F ICIENCY E F F I C I E N C Y W A T E R S Y S T E M S E XT REME HIGH EFFICIENCY HO T W AT ER SY ST EMS w i th I N JECT I O N DYN A M I C S T ECHN I CAL DO CUME N TA T I O N I

More information

Vortex 15/21 Utility and Outdoor Module Vortex Combi 21 and Outdoor Vortex Combi 21

Vortex 15/21 Utility and Outdoor Module Vortex Combi 21 and Outdoor Vortex Combi 21 Part No. DOC 38 Rev. 02 January 2007 SUPPLEMENTARY INSTALLATION and SERVICING INSTRUCTIONS Vortex 15/21 Utility and Outdoor Module Vortex Combi 21 and Outdoor Vortex Combi 21 For use with Kerosene only

More information

ENERSTORE. Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER

ENERSTORE. Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER ENERSTORE Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER Newark Copper Cylinder Co Ltd Brunel Drive Newark Notts. NG24 2EG Tel: 01636 678437 Fax: 01636 678964 Internet: www.newarkcoppercylinder.co.uk

More information

Installation, Operating and Maintenance Guide

Installation, Operating and Maintenance Guide Installation, Operating and Maintenance Guide Part no. 780327-C Contents Exposed Exposed Shower Mixing Valve Wall Cover Plate (x2) Strainer (x2) Fixing Screw (x2) Hexagon Key wall Plug (x2) Green Limiter

More information

Part No. DOC 16 Rev. 09 December USER and INSTALLATION INSTRUCTIONS OUTDOOR MODULES 50/70, 70/90, 90/120 & 110/140

Part No. DOC 16 Rev. 09 December USER and INSTALLATION INSTRUCTIONS OUTDOOR MODULES 50/70, 70/90, 90/120 & 110/140 Part No. DOC 16 Rev. 09 December 2004 USER and INSTALLATION INSTRUCTIONS OUTDOOR MODULES 50/70, 70/90, 90/120 & 110/140 For use with Kerosene or Gas Oil After installing the boiler leave these instructions

More information