1 BERKELEY DAVIS IRVINE LOS ANGELES MERCED RIVERSIDE SAN DIEGO SAN FRANCISCO SANTA BARBARA SANTA CRUZ OFFICE OF THE ASSIST ANT VICE CHANCELLOR CAMPUS ARCHITECT- FACILITIES DESIGN & CONSTRUCTION TEL : (858) FAX : (858) GILMAN DRIVE #09I6 LA JOLLA, CALIFORNIA December 8, 2014 TO: ALL HOLDERS OF BIDDING DOCUMENTS TELECOM BLDG. HVAC UPGRADES Enclosed is the following: 1. Addendum No.2 dated December 8, 2014, to the Construction Documents. NOTE: THE BID DATE REMAINS 2:00P.M., WEDNESDAY, DECEMBER 17,2014. Gillie Senior Director of Construction Services Facilities Design and Construction.. -dim:ie's~. Enclosure

2 PROJECT NO.: 4606/MS-024/ General: ADDENDUM NO. TWO TO THE CONSTRUCTION DOCUMENTS December 8, 2014 The following changes, additions or deletions shall be made to the following documents; all other conditions shall remain the same. I. Item# CLARIFICATIONS 1. Question: What are the requirements for temporary cooling (i.e. load, electrical)? Answer: a. Requirements for temporary cooling are as listed below and the phasing is only a suggestion. The activities of the building must be maintained at all times and the noise disruption kept to a minimum. Rooms 108, 113, and 114 must be operational at all times. Employees in rooms 109, 110, and 112 can be relocated to allow for construction activities but must be coordinated with the owner regarding duration. Room 111 is vacant and can be used temporarily as an office, break room, or conference room depending on the sequence of work set by the contractor. Most of the work outlined can be conducted during regular business hours, but noise must be kept to a minimum and may need to be conducted after regular business hours if the owner decides the work is too disruptive: i. Phase 1 Scope of work: (E) AC-1 demo, AC-1A/18 install, MECHANICAL ROOM work (except FC-1 system), SWITCH ROOM work Temp cooling: (1) 5-ton unit for MECHANICAL ROOM. To avoid electrical overload, the temporary 5 ton moving cool unit may run simultaneously with either AC-1A or AC-18, but not both. Under no circumstance, should temporary 5 ton moving cool and new AC-1A and AC-18 be run simultaneously. User Requirements: Complete the work for rooms 113 and 114 and keep existing FC-1 running. ii. Phase 2 Scope of work: FC-3 install, FC-4 install, LOUNGE work, RECEPTION work, CONFERENCE ROOM work. Temp cooling: (1) 314-ton unit for RECEPTION, (1) 314-ton unit for CONFERENCE ROOM, (1) 112-ton temporary unit for MANAGER (used as temporary lounge space). To avoid electrical overload, temporary units should not be run simultaneously with new permanent units that serves the same space(s). User Requirements: Install FC-3 and FC-4 before demolition of existing FC-1. UCSD- FD&C Page 1 of 3

3 UCSD MEDICAL CENTER- HILLCREST iii. Phase 3 Scope of work: (E) FC-1 demo, EF-1 install, COPY ROOM work, SUPERVISOR work, MANAGER work, ANALYST work. Temp cooling: (1) 112-ton unit for SUPERVISOR, (1) 112-ton unit for MANAGER (used as temporary technical work space), (1) 112-ton unit for ANALYST. To avoid electrical overload, temporary units should not be run simultaneously with new permanent units that serves the same space(s). User Requirements: Complete all work for office spaces and restrooms before demolition of existing FC-1. One restroom at a time can be shutdown. iv. Phase 4 Scope of work: FC-1 install, TECHNICAL work, OPERA TORS work. Temp cooling: (3) 112-ton units for OPERA TORS. To avoid electrical overload, temporary units should not be run simultaneously with new permanent units that serves the same space(s). 2. Question: Can we hoist equipment and materials over the building, and if so what are the restrictions if any? Answer: Avoid hoisting equipment over the building. If this is too difficult, then alternate techniques can be discussed to minimize schedule disruptions. 3. Question: What are the working hours of each area? Answer: See item 1 above. 4. Question: It was mentioned on the walk that some of the racks that are currently in the way are to be removed at some point. For bidding purposes, can we assume that they will be gone? Answer: No racks will be removed. However, there will be another vendor hired separately by the owner that will be working inside of room 113 and possibly other rooms at the time of construction. The contractor will be required to coordinate work activity and allow access to the job site for this vendor. 5. Question: Does the BC Controller get insulated and does it need a condensate pan underneath it? Answer: BC-1 branch circuit controller comes factory-installed with insulation and secondary condensate removal. No additional insulation or condensate drip pan required on BC-1 unit. Insulation of refrigerant piping and condensate drain connected to BC-1 unit is still required. UCSD-FD&C Page 2 of 3

4 6. Question: For the split systems, can factory flexible ACR pre-insulated line-sets be used or does piping need to be rigid? Answer: Per manufacturer's instructions, 112H or H hard copper refrigerant gas and liquid piping with brazed connections is required between the outdoor condensing unit and branch circuit controller. Type 0 soft copper prefabricated linesets with flared connections are permissible between branch circuit controller and indoor fan-coil units. See attached PDF. UCSD- FD&C Page 3 of 3

5 9. Refrigerant piping installation The pipe is connected via a tenninal-branch type connecuon in which refrigerant piping from the outdoor un~ is branched at the tenninal and is connected to each of the indoor units The method of pipe connection Is as follows: flare connection for the indoor units, low-pressure pipes and high-pressure pipes for outdoor units, brazed connection. Note that the branched sections are brazed ~Warning: Do not use refrigerant other than the type Indicated In the manuals provided with the unit and on the nameplate. - Doing so may cause the unh or pipes to burst, or resuh in explosion or fire during use, during repair, or at the Ume of disposal of the uml. - It may also be In violauon of applicable laws. - MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant. Always use extreme care to prevent the refrigerant gas from leaking while using fire or flame. If the refrigerant gas comes In to contact with a flame from any source, such as a gas stove, It breaks down and generates a poisonous gas which can cause gas poisoning. Never weld In an unventilated room. Always conduct an Inspection for gas leakage after Installation of the refrigerant piping has been completed Caution This unit uses refrigerant R41 DA. Follow the local regulations on materials and pipe thickness when selecting pipes. (Refer to the table on the below.) I 1 ' Use the following materials for refrigeration piping Material: Use copper alloy seamless pipes made of phosphorus deoxidized copper. Ensure the Inner and outer surfaces of the pipes are clean and free from hazardous sulfur, oxide. dusts, shaving particles. oils, and moisture (contamination) Size: Refer to Hem 9.2 for detailed lnfonnation on refrigerant piping system. ~ Always observe the restrictions on the refrigerant piping (such as rated length, height difference, and piping diameter) to prevent equipment failure or a dedlne in heaung/cooling perfonnance. I~ Do not Install outdoor unit piping when It Is raining. 4 Commercially available piping often contains dust and other materials Always blow it dean with a dry inert gas. ~ t Use care to prevent dust. water or other contaminants from entering the piping dur1ng Reduce the number of bending portions as much as possible, and make bending radius as big as possible. tv For Indoor and outdoor branching and merging section, be sure to use the following twinning pipe sets and merge pipe sets (sold separately). Indoor TwiMing Pipe Kit model Line branch Lower stream unh model Less than 3D In total CMY-Y1D2SS-G2 Indoor Junction Pipe Kit model Total indoor model P36- P96 CMY-R16DC-J Outdoor Twinning Kit model Total outdoor model Total outdoor model P144YSKMU, P216 - P288TIYSKMU P168, P192T/YSKMU CMY R 1 OOCBK2 CMY-R1DDXLCBK Copper pipe size and radial thickness for R41 DA CITY MULTI Size(mm) Size (Inch) Radial thickness Radial thickness (mm) (mil) Pipe type a6.35 a1/4" DB 32 Type-0 a9.52 a3/b" D.8 32 Type-0 a12 7 a1/2" DB 32 Type-0 a15 88 as/8" 10 4D Type-0 "a19.d5 a3/4" 12 4B Type-0 'a19.d5 a3/4" 1 D 4D Type-1/2H or H a22.2 a7/8" 1 D 4D Type-1/2H or H a25.4 a1 " 1 D 4D Type-112H or H 1112B /8" 1 D 4D Type-112H or H /4" Type-112H or H /8' 12 4B Type-1/2H or H " Type- 1/2H or H that of a branching pipe, (i!,. Braze only with non-oxide brazing material for piping. Failure to do so may damage the compressor. Be sure to perform the non-oxidation brazing with a nitrogen purge. Do not use any commercially available anti-oxidizing agent since It may cause pipe corrosion and degrading of the refrigerant oil. Please contact Mltsublshl Electric for more details. (Refer to item 1D.2. for details of the piping connection and valve operation) (j_ii Always Insulate the piping properly. Insufficient Insulation will resuh In a decline in heating/cooling perfonnance. water drops from condensation fanning and other such problems (Refer to Hem 1 D.4 for thennal insulauon of refrigerant When connecting the refrigerant piping. make sure the valve ofthe outdoor unh Is completely dosed (the factory sehing) Do not operate ft unuithe refrigerant piping for the outdoor, indoor unfts and BC controller has been connected, a refrigerant leakage test has been perfonned, and the evacuation process has been completed. ii Never use refrigerant to perform an air purge. Always evacuate using a vacuum pump 13 Be sure to charge the system using liquid refrigerant 1'1.' Either a lack or an excess of refrigerant causes the unit to make an emergency stop Charge the system with an appropriate amount of refrigerant. When servicing, always check the notes concerning pipe length and amount of additional refrigerant at both locations, tha refrigerant volume calculation table on the back of the service panel and the additional refrigerant section on the labels for the combined number of indoor units (Refer to Item 9.2. for detailed lnfonnation on refrigerant piping system) ~Warning: When Installing and moving the unit, do not charge the system with any other refrigarant other than the refrigerant specified on the unit Mixing of a different refrigerant, air. etc. may cause the refrigerant cyde to malfunction and may result in severe damage. ~Caution: Use a vacuum pump with a reverse flow check valve. - If the vacuum pump does not have a reverse flow check valve, the vacuum pump oil may flow back into the refrigerant cyde and cause deteriorauon of the refrigerant oil Do not use the tools shown below used with conventional refrigerant. (Gauge manifold, charge hose, gas leak detector, check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment) - Mixing of convenuonal refrigerant and refrigerant oil may cause the refrigerant oil to deteriorate.. Mixing of water will cause the refrigerant oil to deteriorate.. R41DA refrigerant does not contain any chlorine. Therefore. gas leak detectors for conventional refrigerants will not react to it. Manage the tools used for R410A more carefully than normal.. If dust, dirt, or water gets in the refrigerant cycle, the refrigerant oil will deteriorate. Never use exlsung refrigerant piping. The large amount of chlorine in convenuonal refrigerant and refrigerant oil in the existing piping will cause the new refrigerant to deteriorate Store the piping to be used during Installation Indoors and keep both ends of the piping sealed until just before brazing.. If dust, dirt. or water gets Into the refrigerant cyde. the oil will deteriorate and the compressor may feil Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate. Do not use special detergents for washing piping. Both pipe types can be used for pipe size D5 (3/4 inch) for R41DA air -(a Use an adapter If a specified refrigerant pipe has a different diameter from I - I

KSGD-01W/S SEMI CONDUCTOR STAND ALONE REFRIGERANT LEAK DETECTOR. Instructions for :- KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector

KSGD-01W/S SEMI CONDUCTOR STAND ALONE REFRIGERANT LEAK DETECTOR. Instructions for :- KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector Issue 1 KSGD-01W/S SEMI CONDUCTOR STAND ALONE REFRIGERANT LEAK DETECTOR Installation Manual Instructions for :- For safe and correct use please read the installation manuals supplied with the equipment.

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL No. OCH468 REVISED EDITI-A HFC utilized R4A June 2 [Model name] MXZ-8B48NA PAC-AKA5BC PAC-AKA3BC (Indispensable

More information

Installation Manual PMV Kit RBM-PMV0363E RBM-PMV0903E

Installation Manual PMV Kit RBM-PMV0363E RBM-PMV0903E EB99802801-1 Installation Manual RBM-PMV0363E RBM-PMV0903E Installation Manual English OUTDOOR UNIT SIDE UPPER INDOOR UNIT SIDE Thank you very much for purchasing TOSHIBA Air conditioner. Please read this

More information

Split Air Conditioner

Split Air Conditioner Split Air Conditioner Owner's Manual Residential Air Conditioners Thank you for choosing Residential Air Conditioners,please read this owner s manual carefully before operation and retain it for future

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

UNIVERSITY OF CALIFORNIA, SAN DIEGO

UNIVERSITY OF CALIFORNIA, SAN DIEGO UNIVERSITY OF CALIFORNIA, SAN DIEGO BERKELEY DAVIS IRVINE LOS ANGELES MERCED RIVERSIDE SAN DIEGO SAN FRANCISCO SANTA BARBARA SANTA CRUZ CAMPUS PLANNING 9500 GILMAN DRIVE # 0074 TEL: (858) 534 6515 LA JOLLA,

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL October 202 No. OCH446 REVISED EDITION-E HFC utilized R40A [Model name] PUMY-P00VHMB PUMY-P25VHMB PUMY-P40VHMB PUMY-P00VHMB-BS

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

REFRIGERANT ON-VEHICLE INSPECTION AC 14

REFRIGERANT ON-VEHICLE INSPECTION AC 14 14 REFRIGERANT ON-VEHICLE INSPECTION 1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET (a) This is a method to specify trouble areas by using a manifold gauge set. Read the manifold gauge pressure

More information

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

Cased Aluminum Coils Dedicated Upflow / Downflow Convertible to horizontal with separately purchased kit 18-AD32D1-3 Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit Upflow models: 4PXCAU24BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCBU36BS3HAA

More information

5.07 Air Replenishment Systems

5.07 Air Replenishment Systems 5.07 Air Replenishment Systems Reference: 2010 SFFC, Section 511.2 Definitions: CERTIFIED COMPRESSOR. A compressor used by a contractor for maintenance and testing of air replenishment systems that is

More information

Chapter 6. Do s & Don ts in Refrigeration & Air-Conditioning Servicing

Chapter 6. Do s & Don ts in Refrigeration & Air-Conditioning Servicing Do s & Don ts in Refrigeration & Air-Conditioning Servicing Who is Better? OR Common Practices that are damaging to the Refrigeration & Air-conditioning Systems Brazing with Cu electrode for brazing Cu

More information

1. BEFORE INSTALLATION

1. BEFORE INSTALLATION ENGLISH SPLIT-TYPE AIR CONDITIONERS INSTALLATION MANUAL REFRIGERANT JG79Y335H01 Model names are indicated in 1-3. When installing multi units, refer to the installation manual of the multi unit for outdoor

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3B54VA MXZ-4B71VA. English

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3B54VA MXZ-4B71VA. English Split-type Air-Conditioner MXZ-3B54VA MXZ-4B71VA INSTALLATION MANUAL English Refer to the installation manual of each indoor unit for indoor unit installation. IMPORTANT NOTES TO COMPLY WITH THE REQUIREMENTS

More information

HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B COUNTER SHOWCASE MODEL SERVICE MANUAL HOSHIZAKI

HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B COUNTER SHOWCASE MODEL SERVICE MANUAL HOSHIZAKI NO. S051-800 ISSUED: MAR. 26, 2010 REVISED: HOSHIZAKI COUNTER SHOWCASE MODEL HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B SERVICE MANUAL IMPORTANT This manual should be read carefully

More information

Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy)

Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy) Indiana University Northwest Environmental Health & Safety Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy) Applies to: Issue Date: Latest

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

C7 Series Split System Uncased Indoor Coils

C7 Series Split System Uncased Indoor Coils Installation Instructions C7 Series Split System Uncased Indoor Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

Installation manual. Branch kit 1:3 RBC-TRP100E AIR CONDITIONER (SPLIT TYPE) Model name: Installation manual. Air conditioner (Split type) 1 English

Installation manual. Branch kit 1:3 RBC-TRP100E AIR CONDITIONER (SPLIT TYPE) Model name: Installation manual. Air conditioner (Split type) 1 English EH99862001-2 AIR CONDITIONER (SPLIT TYPE) Installation manual Branch kit 1:3 Model name: RBC-TRP100E Installation manual Air conditioner (Split type) 1 English Please read this Installation Manual carefully

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

ADVANCED TRAINING INSTITUTE, HYDERABAD PR04/F01

ADVANCED TRAINING INSTITUTE, HYDERABAD PR04/F01 Revision: 00 LEARNING CONTENT Page 1 of 6 III COURSE CODE RAC-01 COURSE TITLE INSTALLATION REPAIR & MAINTENANCE OF A/C WINDOW & SPLIT TYPE On completion of the course, the learner will be able to understand

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS C8DA Series Split System Uncased Indoor Coils - Downturn IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

Daikin Direct Expansion (DX) Cooling Coils

Daikin Direct Expansion (DX) Cooling Coils Installation and Maintenance Manual IM 902 Daikin Direct Expansion (DX) Cooling Coils Group: Applied Air Part Number: IM 902 Date: February 2008 Types EN, EF, ER, EJ, EK 2008 Daikin Applied Contents Introduction...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS C7BA & C7BH Series Split System Indoor Cased Coils INSTALLATION INSTRUCTIONS IMPORTANT It is your responsibility to know this product better than your customer. This includes being able to install the

More information

Service Manual. Air Conditional

Service Manual. Air Conditional Air Conditional Service Manual Большая библиотека технической документации http://splitoff.ru/tehn-doc.html каталоги, инструкции, сервисные мануалы, схемы. -2 - MODEL: AC-FR30CM -3 - CONTENTS SPECIFICATION...

More information

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e 5.07 Air Replenishment Systems (2016) Reference: SFFC, Section 511.2. Purpose: The purpose of this bulletin is to describe the requirements for air replenishment systems intended to be used to fill firefighters'

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

PURY-WP-YJM-A (-BS) For use with R410A. Air-Conditioners For Building Application OUTDOOR UNIT

PURY-WP-YJM-A (-BS) For use with R410A. Air-Conditioners For Building Application OUTDOOR UNIT ir-onditioners For uilding pplication OUTOOR UNIT PURY-WP-YJM- (-S) For use with R410 INSTLLTION MNUL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner

More information

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT HVAC MAINTENANCE TECHNOLOGY. Test Code: 5937 Version: 01

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT HVAC MAINTENANCE TECHNOLOGY. Test Code: 5937 Version: 01 CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT HVAC MAINTENANCE TECHNOLOGY Test Code: 5937 Version: 01 Specific competencies and skills tested in this assessment: Introduction to HVAC Identify HVAC systems Demonstrate

More information

Installation Instructions

Installation Instructions 38MPRA Outdoor Unit Single Zone Ductless System Sizes 09 to 12 Installation Instructions NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes

More information

MXZ-4B80VA MXZ-5B100VA INSTALLATION MANUAL

MXZ-4B80VA MXZ-5B100VA INSTALLATION MANUAL Split-type Air-Conditioner MXZ-4B80VA MXZ-5B100VA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Deutsch Français Nederlands Español Italiano

More information

Installation Instructions

Installation Instructions 38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes

More information

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems 12 In Row Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents Table of Contents... 3 Site

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS C7BA Series Split System Indoor Cased Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH789

SERVICE MANUAL OUTDOOR UNIT. No. OBH789 OUTDOOR UNIT SERVICE MANUAL HFC utilized R32. Models MUZ-AP25VG - E1, ET1 MUZ-AP25VGH - E1 MUZ-AP35VG - E1, ET1 MUZ-AP35VGH - E1 MUZ-AP42VG - E1, ET1 MUZ-AP42VGH - E1 MUZ-AP50VG - E1, ET1 MUZ-AP50VGH -

More information

Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi , Ph. No.

Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi , Ph. No. Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi -110003, Ph. No. 011-49854100 TENDER NOTICE Sealed tender in two separate bids a) Technical bids,

More information

power Describe the purpose of lockout/tag-out devices Demonstrate use of lockout/tagout

power Describe the purpose of lockout/tag-out devices Demonstrate use of lockout/tagout c. All contestants are required to remain in the contest area until the contest has been torn down and excused by the Chairperson. Note: Your contest may also require a hard copy of your résumé as part

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

INSTALLATION MANUAL SPLIT TYPE ROOM AIR CONDITIONER (PART NO )

INSTALLATION MANUAL SPLIT TYPE ROOM AIR CONDITIONER (PART NO ) SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION MANUAL (PART NO. 9312791019-01) This air conditioner uses new refrigerant HFC (R410A). The basic installation work procedures are the same as conventional refrigerant

More information

Split-type Air-Conditioner

Split-type Air-Conditioner Split-type Air-Conditioner MXZ-2C52VA Installation Manual For INSTALLER This manual only describes the installation of outdoor unit. When installing the indoor unit, refer to the installation manual of

More information

Split-type Air-Conditioner

Split-type Air-Conditioner Split-type Air-Conditioner MXZ-2D52VA Installation Manual For INSTALLER This manual only describes the installation of outdoor unit. When installing the indoor unit, refer to the installation manual of

More information

AIR CONDITIONER (SPLIT TYPE) Installation manual. Outdoor Unit. English. Model name: For commercial use

AIR CONDITIONER (SPLIT TYPE) Installation manual. Outdoor Unit. English. Model name: For commercial use AIR CONDITIONER (SPLIT TYPE) Installation manual Outdoor Unit For commercial use Model name: RAV-SM2244AT7 RAV-SM2244AT7Z RAV-SM2244AT7ZG RAV-SM2244AT8-E RAV-SM2244AT8Z-E RAV-SM2244AT8ZG-E RAV-SM2804AT7

More information

METHOD STATEMENT INFORMATION REQUIRED

METHOD STATEMENT INFORMATION REQUIRED METHOD STATEMENT Prepared for : DSG Retail Ltd Maylands Avenue Hemel Hempstead Hertfordshire HP2 7TG Project details : Split Air Conditioning condenser relocation Site : Dixons Wandsworth Date : 7 th March

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

SERVICE BULLETIN A

SERVICE BULLETIN A 1. PLANNING INFORMATION A. Effectivity: Dassault Falcon 10 aircraft which have installed R-134a Upgrade Kit SZ59K-R134 before August 8, 2002. B. Reason: Upgrade kits before August 8, 2002 did not include

More information

1. BEFORE INSTALLATION

1. BEFORE INSTALLATION ENGLISH SPLIT-TYPE AIR CONDITIONERS INSTALLATION MANUAL REFRIGERANT JG79B528H01 Model names are indicated in 1-3. Phillips screwdriver Level Scale Utility knife or scissors 75 mm hole saw Torque wrench

More information

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS DLCSRA INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes only.

More information

SERVICE MANUAL MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG OUTDOOR UNIT. No. OBH767. Models HFC R32

SERVICE MANUAL MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG OUTDOOR UNIT. No. OBH767. Models HFC R32 OUTDOOR UNIT SERVICE MANUAL HFC utilized R32. Models MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG - E1, ER1, ET1 - E1, ER1, ET1 - E1, ER1, ET1 - E1, ER1, ET1 Indoor unit service manual MSZ-LN VGW/V/B/R

More information

Residential Piping and Long Line Guideline

Residential Piping and Long Line Guideline AC / HP R-410A Refrigerant Systems Single-Stage, Two-Stage and Variable Speed Models Residential Piping and Long Line Guideline TABLE OF CONTENTS Safety Considerations... 2 Definitions... 2 Introduction...

More information

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES 11-AC11D2-5 INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Models: Condensing Units 2A7A5024-048, 2A7A4018-060, 2A7A2018-060 & 2A7A1018-060 IMPORTANT

More information

1. ACCESSORIES SUPPLIED WITH THE AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNIT 3. INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 4.

1. ACCESSORIES SUPPLIED WITH THE AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNIT 3. INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 4. 1. ACCESSORIES SUPPLIED WITH THE AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNIT 3. INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 4. INSTALLATION OF THE INDOOR UNIT 5. CONDENSATE HOSE CONNECTION

More information

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO AOYG8LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL For authorized service personnel only. English PART NO. 93778639 93778639_IM.indb /20/20 6:07:25 PM AIR CONDITIONER OUTDOOR UNIT INSTALLATION

More information

RAV-SM2246AT8-E RAV-SM2246AT8J-E RAV-SM2806AT8-E RAV-SM2806AT8J-E

RAV-SM2246AT8-E RAV-SM2246AT8J-E RAV-SM2806AT8-E RAV-SM2806AT8J-E AIR CONDITIONER (SPLIT TYPE) Installation Manual Outdoor Unit Model name: RAV-SM2246AT8-E RAV-SM2246AT8J-E RAV-SM2806AT8-E RAV-SM2806AT8J-E For commercial use English 1 Original instruction Regulation

More information

Summer Registrant File Third Week

Summer Registrant File Third Week Summer Registrant File Third Week October 30, 2015 Information Resources and Communications Office of the President University of California Overview 1. For purposes of clarity, summer period refers collectively

More information

YC ON-OFF SERIES. Service Manual

YC ON-OFF SERIES. Service Manual YC ON-OFF SERIES Service Manual CONTENTS 1. Precaution... 3 1.1 Safety Precaution... 3 1.2 Warning... 3 2. Model Lists... 6 3. Dimension... 7 3.1 Indoor Unit... 7 3.2 Outdoor Unit... 11 4. Refrigerant

More information

Safety Precautions WARNING

Safety Precautions WARNING Safety Precautions Before installing the unit, thoroughly read the following safety precautions. Observe these safety precautions for your safety. WARNING This symbol is intended to alert the user to the

More information

Service Handbook AIR CONDITIONER

Service Handbook AIR CONDITIONER AIR CONDITIONER 200 Service Handbook Model PUHY-P200, P250, P300, P350, P400, P450YJM-A PUHY-P500, P550, P600, P650, P700, P750, P800, P850, P900YSJM-A() PUHY-P950, P000, P050, P00, P50, P200, P250YSJM-A

More information

Installation Instructions

Installation Instructions Split System Indoor Coils Installation Instructions! CAUTION: Read the Installation Instructions supplied with furnace/air handler and observe all safety requirements outlined in instructions and/or furnace/air

More information

CONTENTS INSTALLATION MANUAL HFC FOR INSTALLER R410A. utilized 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY... 2

CONTENTS INSTALLATION MANUAL HFC FOR INSTALLER R410A. utilized 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY... 2 SPLIT-TYPE AIR CONDITIONER CONTENTS INSTALLATION MANUAL 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY... 2 Model MXZ-A26/32WV HFC utilized R410A 2. INSTALLATION DIAGRAM & ACCESSORIES... 2 3. SELECTING

More information

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies Pakistan s Largest Manufacturers of Air-Conditioners PACKAGE TYPE UNIT FOR MOBILE APPLICATIONS Provides Turnkey Projects Conceptual Planning to Commissioning of HVACR Projects THE LARGEST MANUFACTURER

More information

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire

More information

38GL...G / 38GLS...G 38YY...G / 38YYS...G

38GL...G / 38GLS...G 38YY...G / 38YYS...G LLOYD'S REGISTER QUALITY ASSURANCE 38GL...G / 38GLS...G 38YY...G / 38YYS...G I S O 9 00 1 INSTALLATION MANUAL 38GL...G / 38GLS...G / 38YY...G / 38YYS...G Cooling only and heat pump split system outdoor

More information

DAIKIN AIR CONDITIONER

DAIKIN AIR CONDITIONER 3P226011-1A M07B242A DAIKIN AIR CONDITIONER Two-dimensional bar code is a code for manufacturing. Safety Precautions (1) Read these Safety Precautions carefully to ensure correct installation. This manual

More information

OWNER S MANUAL (English)

OWNER S MANUAL (English) TRS600 IGNITION PROOF SERIES Refrigerant Recovery Machines OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TRS600, TRS600K, TRS600S Evaluated for performance

More information

REFRIGERANT PIPING SYSTEM

REFRIGERANT PIPING SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The requirements of this section apply to the refrigerant piping system connecting refrigeration and HVAC equipment specified in other sections of these specifications.

More information

1. BEFORE INSTALLATION

1. BEFORE INSTALLATION ENGLISH SPLIT-TYPE AIR CONDITIONERS INSTALLATION MANUAL REFRIGERANT JG79B530H01 Model names are indicated in 1-3. Phillips screwdriver Level Scale Utility knife or scissors 75 mm hole saw Torque wrench

More information

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils Installation, Operation and Maintenance Guide Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

Installation Instructions

Installation Instructions 38MGQ Multi-Zone Ductless System Sizes 18, 27, 36 and 48 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MODEL LV8 COMMERCIAL REFRIGERANT RECOVERY UNIT NATIONAL REFRIGERATION PRODUCTS 985 WHEELER WAY LANGHORNE, PA 19047 (215) 638-8909 FAX (215) 638-9270 A01001 7/11/96 NRP-OM-LV8 7/96

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

INSTALLATION MANUAL. R410A Split Series. Models RXS15LVJU RXS18LVJU. Installation manual R410A Split series. Manuel dinstallation Série split R410A

INSTALLATION MANUAL. R410A Split Series. Models RXS15LVJU RXS18LVJU. Installation manual R410A Split series. Manuel dinstallation Série split R410A INSTALLATION MANUAL R410A Split Series Installation manual R410A Split series English Manuel dinstallation Série split R410A Français Manual de instalación Serie Split R410A Español Models RXS15LVJU RXS18LVJU

More information

[FLARE CONNECTION TYPE] ATTENTION

[FLARE CONNECTION TYPE] ATTENTION SPLIT-TYPE AIR CONDITIONERS Model MXZ-2A20NA [FLARE CONNECTION TYPE] HFC utilized R410A INSTALLATION MANUAL ATTENTION This manual mentions how to install only the outdoor unit, MXZ-2A20NA. As for the way

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

AIR CONDITIONER (MULTI TYPE) Installation Manual. Outdoor Unit. English. Model name:

AIR CONDITIONER (MULTI TYPE) Installation Manual. Outdoor Unit. English. Model name: DB04305801-00 AIR CONDITIONER (MULTI TYPE) Outdoor Unit For commercial use Model name: Heat Pump Model MCY-MHP0404HT-E MCY-MHP0504HT-E MCY-MHP0604HT-E MCY-MHP0404HTJ-E MCY-MHP0504HTJ-E MCY-MHP0604HTJ-E

More information

AC 1 AIR CONDITIONING SYSTEM

AC 1 AIR CONDITIONING SYSTEM AC1 AC2 GENERAL INFORMATION REFRIGERATION SYSTEM Prevention of Release and Excessive quantities (CFCs) for automobile air conditionings is be lieved to cause harm by depleting the ozone layer which helps

More information

INVERTER SPLIT - TYPE

INVERTER SPLIT - TYPE INVERTER SPLIT - TYPE ISSUE No 2 DATE 04/09/08 P/No 2020323A2868 CONTENTS SAFETY PRECAUTIONS Warning 2 Operating temperature 2 BEFORE INSTALLATION Tools needed for installation 3 Items required for installing

More information

OPERATION & MAINTENANCE MANUAL TX600

OPERATION & MAINTENANCE MANUAL TX600 OPERATION & MAINTENANCE MANUAL TX600 RTI TECHNOLOGIES, INC. 4075 East Market Street York, PA 17402 Manual P/N 035-80118-00 (Rev B) ! TABLE OF CONTENTS! TX600 Before Using Page 2 Safety Precautions Page

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Horizontal/Side Discharge Condensing Units

Horizontal/Side Discharge Condensing Units INSTALLATION, OPERATION & MAINTENANCE MANUAL Horizontal/Side Discharge Condensing Units Models CMA12SD-0 CMA18SD-1 CMA24SD-1 CMA30SD-1 CMA36SD-1 CMA48SD-1 517.787.2100 www.marsdelivers.com Horizontal/Side

More information

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump COMFORT...BUILT TO LAST 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump INSTALLATION MANUAL INDOOR UNIT: 1PAMSH09-SZW-14.5 1PAMSH09-SZW-15 1PAMSH12-SZW-15 1PAMSH18-SZW-15

More information

Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel:

Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel: Ocean Breeze Split System General Installation Manual Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida 34997 Tel: 772 220 0038 Warning: The Air Conditioning Unit is a pressurized system; potential

More information

SECTION (15530) - REFRIGERANT PIPING

SECTION (15530) - REFRIGERANT PIPING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Tubes. 2. Fittings. SECTION 23 23 00 (15530) - REFRIGERANT PIPING 3. Joining Materials. 4. Specialties. B. Related Sections: 1.02 REFERENCES 1. Section

More information

DLCMRA. INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

DLCMRA. INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... DLCMRA INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 GENERAL... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4

More information

Indoor Unit Operation & Installation Manual

Indoor Unit Operation & Installation Manual Indoor Unit Operation & Installation Manual MVAH009MV2AA MVAH012MV2AA MVAH018MV2AA MVAH024MV2AA MVAH030MV2AA MVAH036MV2AA MVAH042MV2AA MVAH048MV2AA Please read this manual carefully before using Keep this

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

CC Series VACUUM PUMPS

CC Series VACUUM PUMPS CC Series VACUUM PUMPS OPERATING MANUAL Thank you for selecting a Javac select product! Please read this operation manual carefully before use. Only suitably qualified personnel should operate this equipment.

More information

NO. F ISSUED: JUN. 15, 2009 REVISED: HOSHIZAKI MODULAR CRESCENT CUBER KMD-201AA KMD-201AWA MODEL SERVICE MANUAL

NO. F ISSUED: JUN. 15, 2009 REVISED: HOSHIZAKI MODULAR CRESCENT CUBER KMD-201AA KMD-201AWA MODEL SERVICE MANUAL NO. F037-775 ISSUED: JUN. 15, 2009 REVISED: HOSHIZAKI MODULAR CRESCENT CUBER MODEL KMD-201AA KMD-201AWA SERVICE MANUAL CONTENTS PAGE I. SPECIFICATIONS ---------------------------------------------------------------------------------------

More information

REFRIGERANT PIPING

REFRIGERANT PIPING SECTION 232300 - REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

WELDING, CUTTING, AND BRAZING SAFETY PROGRAM

WELDING, CUTTING, AND BRAZING SAFETY PROGRAM WELDING, CUTTING, AND BRAZING SAFETY PROGRAM HOT WORK TABLE OF CONTENTS 1.0 Introduction 1.1 Purpose 1.2 Scope 2.0 Responsibilities 2.1 Building Office 2.2 Building Personnel 2.3 Individuals Performing

More information

R32. Installation Manual Split Type Wall Mounted Air Conditioner. This appliance shall be installed in accordance with: REFRIGERANT

R32. Installation Manual Split Type Wall Mounted Air Conditioner. This appliance shall be installed in accordance with: REFRIGERANT SWING LRSWING Installation Manual Split Type Wall Mounted Air Conditioner COOL RUN C SPEED TURBO ON/OFF FAN COOL HEAT SWING SWING Rinnai Systems Models System Indoor Outdoor HSNRQ25B HINRQ25B HONRQ25B

More information

Installation Instructions

Installation Instructions 38MGR Multi-zone Outdoor Unit Ductless System Sizes 18, 24, 30, 36 and 48 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 GENERAL... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS...

More information

AUTOMOTIVE AIR CONDITIONER REFRIGERANT HANDLING SYSTEM

AUTOMOTIVE AIR CONDITIONER REFRIGERANT HANDLING SYSTEM AUTOMOTIVE AIR CONDITIONER REFRIGERANT HANDLING SYSTEM OPERATION MANUAL Index I Caution.... 2 II Notation.. 2 III Technical parameter...3 IV Functions... 3 V Device Description. 3 (I) Control panel. 4

More information

50TM TFF COMBINATION HEATING/COOLING UNITS

50TM TFF COMBINATION HEATING/COOLING UNITS 50T-1SB 50TM007-012 50TFF004-014 COMBINATION HEATING/COOLING UNITS PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS Copyright 2002 Carrier Corporation Syracuse, New York

More information