The. Steam ONE-PIPE STEAM SYSTEMS

Size: px
Start display at page:

Download "The. Steam ONE-PIPE STEAM SYSTEMS"

Transcription

1 FULL-COLOR TRAINING GUIDE SERIES The of Steam ONE-PIPE STEAM SYSTEMS

2 ONE-PIPE STEAM SYSTEMS PIPING AND TROUBLESHOOTING

3 ONE-PIPE STEAM SYSTEMS ONE-PIPE STEAM SYSTEMS A. HOW ONE-PIPE SYSTEMS WORK 1. movement in the system and radiators a) vent design and operation b) Main vent and riser vent installation c) must move out through vent for steam to enter. d) Main and riser vents must work first to provide steam to all radiators at the same time. 2. Condensate movement in the radiators a) Radiator supply valves b) The condensate must flow back through the same valve where the steam is entering c) One-pipe radiator valves cannot be throttled 3. vent shut-off a) Float prevents water from escaping b) shuts off when internal element heats up 4. Dimension A condensate movement and return to the boiler in One-Pipe Systems a) The lowest steam carrying pipe must be at least 28 inches above the normal boiler water line. B. SYSTEM CHECKLIST 1. The system piping must provide dry steam wet steam causes water hammer, component damage and water level problems. 2. Make sure air vents are working. a) The most important vents are the main and riser vents. b) Make sure they are working and piped to protect them from water hammer. c) Check the radiator vents. 3. If replacing an old, large boiler, consider the need for a boiler feed system to provide the water storage needed until the condensate returns. 4. One-pipe gravity systems cannot be zoned with zone valves. a) When the zone valve closes, the whole pressure of the boiler pushes back on the returns. b) This requires 30 inches of height over the water level for every PSI at the boiler. c) Most one-pipe systems will have to be equipped with drip traps and feed pumps to allow zoning with zone valves. C. THE NEAR-BOILER PIPING 1. The near boiler piping is the first line of defense for a reliable system. a) Correctly installed, the near boiler piping acts as a moisture separator and boiler water level stabilizer. b) Incorrectly piped or undersized near boiler piping will cause carryover the system components may be damaged and poor heat distribution and noise will occur. D. SIZING THE BOILER 1. The boiler output must be large enough to satisfy all connected radiators. 2. Size the boiler by doing a radiator count, totaling all of the connected Square Feet. 3. Select a boiler with a Steam Net Load Rating (in square feed of EDR) greater than the total connected radiation. 4. If the boiler is undersized, the radiators furthest away will not heat. 5. If the boiler is severely oversized, the steam flow in the mains will cause too much pressure drop. The water in the returns will rise and water hammer can occur. E. COUNTERFLOW SYSTEMS 1. Basic system piping and operation a) Condensate must flow against the flow of steam b) The boiler header must enter the top of the main on counterflow systems. 2. Pipe sizing one pipe counterflow systems a) Mains are sized one size larger than they would be for parallel flow piping. This allows room for the condensate to flow along the bottom of the pipe. F. PARALLEL FLOW SYSTEMS 1. One pipe parallel flow with wet return a) Operation b) Pipe Sizing 2. One pipe parallel flow with dry return a) Operation b) Pipe Sizing 3. One pipe parallel upflow system a) Operation b) Upfeed Riser and Runout piping c) Pipe Sizing 4. One pipe parallel downflow system a) Operation b) Downfeed riser piping c) Pipe Sizing G. TROUBLESHOOTING 1. Water hammer on start-up 2. Water hammer during mid-cycle 3. Water hammer on shut-down 4. Hammering in the boiler 1

4 A. HOW ONE-PIPE SYSTEMS WORK A. HOW ONE-PIPE SYSTEMS WORK Seat AIR VENT TYPICAL Float Float Support Excerpt: Hoffman Steam Heating Systems, ITT Figure 1: Construction The float prevents water from escaping. The float can be damaged by water hammer, preventing the vent from operating correctly. The thermal element expands when heated to close off the vent. 2

5 A. HOW ONE-PIPE SYSTEMS WORK Figure 2: Explanation of Ratings Note that it is important for the boiler cut-out pressure to be lower than the Drop-Out pressure of the vents on the system. Otherwise, they cannot function after the initial cycle. The pressure in the system would keep them closed. 3

6 A. HOW ONE-PIPE SYSTEMS WORK Figure 3: Selection and Application of s Use adjustable vents when you want proportional venting. The larger the radiator, the larger the vent opening. This way each radiator heats in proportion to its size as intended. 4

7 A. HOW ONE-PIPE SYSTEMS WORK Figure 4: Main Installation You will often find the main vent piped as shown on the right. This allows water hammer at the end of the main to slam into the vent. The float will quickly collapse, causing the vent to fail in the closed position. Pipe the Main as shown on the left. This protects the vent from the hammer at the end of the main and provides an air cushion against the shock. If the main vent doesn t work, the radiator vents must remove the air from the system piping. This will cause the closest radiators to heat first and the furthest radiators may not heat at all when the thermostat shuts down the boiler. The Main (and Riser s) is the heart of a one-pipe system. It must work to provide uniform heat in the building by removing the air from the steam distribution piping. When it works, all the radiators receive steam at the same time. 5

8 A. HOW ONE-PIPE SYSTEMS WORK OFF CYCLE s serve as vacuum breakers. When steam condenses, it causes a vacuum. The vents let air back in to fill the void. The system fills with air. The water level in the return finds the same level as the boiler since there is no pressure difference in the piping. Main Water Line Water Hartford Loop Wet Return Burner Off Figure 5: Stand-by Conditions in the System At the end of each heating cycle, the thermostat shuts off the boiler. With no steam being supplied, the steam in the system condenses and creates a vacuum. This vacuum causes air to be pulled in through the vents until the system fills with air. 6

9 A. HOW ONE-PIPE SYSTEMS WORK THERMOSTAT CALLS FOR HEAT Boiler fires. Water boils in boiler, creating steam. Surface level rises slightly because the steam bubbles displace water. Pressure builds in system as steam pushes on the air. Pressure pushes air out through Main and Radiator vents. Water begins to back up in the return riser because flow causes pressure drop in piping. So pressure is lower at end of piping than at boiler. Main Steam Water Line Water Hartford Loop Wet Return Figure 6: Call for Heat The thermostat closes, the boiler fires and the cycle begins. 7

10 A. HOW ONE-PIPE SYSTEMS WORK THE MAIN VENT When the Main works right it exhausts air quickly from the steam piping. So all branch lines receive steam at about the same time. This makes heating uniform throughout the building. If the main vent doesn't work, the first radiators get steam first, causing poor heat distribution. The Main vent closes as steam reaches it. Radiator vents are smaller. They must vent slowly to match the radiation. If they vent too quickly, condensate will back up in the radiator and cause water hammer. The radiator vents continue to vent air as steam pushes up toward the radiators. Water backs up higher in the return as the pressure difference from beginning to end of piping increases with flow and condensate begins to form. Steam Main (Closed) Steam Water Line Water Hartford Loop Wet Return Figure 7: Importance of the Main The Main must quickly evacuate all air from the steam piping. This way all branches receive steam at about the same time. And the building will heat evenly. 8

11 A. HOW ONE-PIPE SYSTEMS WORK HEATING BEGINS IN RADIATORS Steam pushes into the radiators. The radiators cool the steam. Steam begins to condense. The radiators begin to heat up and give off heat to the room as the steam gives off 970 BTU per pound in condensing. Condensate starts to build up in the bottoms of the radiators and flow out through the radiator valves. Condensate runs down the branch piping to the main, flowing against the steam coming up the branches. Steam Steam The heavy start-up condensate load adds to the pressure difference, raising the water level in the return to its highest point during the heating cycle. Boiler water level slightly lower because water has been steamed off and condensate has not returned yet. Steam Condensate Condensate Condensate Main (Closed) Steam Water Line Water Hartford Loop Wet Return Figure 8: Heating Begins in the Radiators When steam pushes into the radiators it starts to condense and heat the radiators. The radiators begin to give off this heat. 9

12 A. HOW ONE-PIPE SYSTEMS WORK STEADY STATE HEATING Steam fills radiators until it reaches the radiator vents. The radiator vents close when exposed to the steam temperature. The boiler continues to fire, providing steam to the system, until the thermosat is satisfied. The riser level drops as the start-up condensate load passes back to the boiler. The steady level is just enough to overcome the pressure loss through the steam piping and return piping. Boiler water level is lower because of condensate out in the system. In some cases the water level may go out of the gauge glass when the boiler shuts down. This is because the steam bubbles in the boiler collapse, so the surface level drops. And the condensate has not returned from the system. Steam Steam Condensate Closed Condensate Steam Condensate Closed Main (Closed) Steam Water Line Water Hartford Loop Wet Return Figure 9: Steady State Heating Conditions The steam has pushed into the radiators and reached the radiator vents. They shut off when exposed to the steam temperature. The heating cycle continues until the thermostat shuts off the boiler. 10

13 A. HOW ONE-PIPE SYSTEMS WORK STEAM SYSTEM OPERATION CYCLE START AIR IN RADIATOR STEAM AT RADIATOR INLET Figure 10: Radiator at Start of Cycle Radiator is full of air. If Main works, all radiators receive steam at the same time. 11

14 A. HOW ONE-PIPE SYSTEMS WORK STEAM SYSTEM OPERATION AIR VENT ALLOWS AIR TO BE PUSHED OUT BY THE STEAM CONDENSATE STARTS TO FORM RADIATOR BEGINS TO BE WARMED BY CONDENSING STEAM Figure 11: Radiator Begins to Receive Steam If Radiator works, the steam pressure pushes air out through the vent, allowing steam to enter. Condensate begins to form and roll back through the radiator valve. 12

15 A. HOW ONE-PIPE SYSTEMS WORK STEAM SYSTEM OPERATION AIR VENT CLOSES AS STEAM REACHES VENT CONDENSATE LOAD INCREASED Figure 12: Steam Reaches the The vent closes as its element is heated and expanded by the steam temperature. 13

16 A. HOW ONE-PIPE SYSTEMS WORK RADIATOR SUPPLY VALVE CANNOT BE USED TO CONTROL FLOW Valve must be kept fully open when in use Partially closed valve restricts condensate Excerpt: Hoffman Steam Heating Systems, ITT Figure 13: Radiator Supply Valve One-Pipe Radiators Do not throttle the valve. This will restrict condensate flow and cause hammer in the radiator. 14

17 A. HOW ONE-PIPE SYSTEMS WORK DIMENSION "A" GRAVITY RETURN SYSTEMS 28" A Note: Return line loss includes safety factor Figure 14: Gravity Return Systems Dimension A The only way water can be pushed back into the boiler is for the return water to raise to a height high enough to overcome the line losses and the difference in pressure between the boiler and the end of the main. Allow 28 inches as shown for most existing gravity systems. 15

18 A. HOW ONE-PIPE SYSTEMS WORK DIMENSION "A" GRAVITY RETURN SYSTEMS System Size Over 100 MBH Under 100 MBH Steam Piping Pressure Drop Wet Return Pressure Drop Wet Return Pressure Drop Safety Factor Overall Safety Factor Start-up Condensate Allowance TOTALS 14" 4" 2" 8" 28" 3.5" 3.5" 7" 14" Figure 15: Dimension A Adding Up the Drops Most gravity systems were piped for a 1/2 psig (14 inches) drop through the main. If the drop is higher, increase the 28" minimum. If the pipe insulation has been removed and not replaced, increase the 8" start-up condensate allowance. 16

19 B. SYSTEM CHECKLIST B. SYSTEM CHECKLIST THE SYSTEM 1. The system must provide dry steam for performance and system component life. 2. Wet steam will cause water hammer, resulting in damage to vent valves or anything else in the way. 3. Water carryover to the system will cause the boiler water level to drop too quickly. This will cause overfilling and flooding. CHECK DIMENSION A 4. Make sure the lowest steam carrying pipe (or dry return) is at least 28 inches above the normal boiler water line. If the piping pressure drop is more than 1/2 psig, increase this minimum as needed. 5. Dimension A may have been correct at one time, but it could have changed if the piping was modified over the years. 6. The new boiler water line may not be the same as the old boiler. If the new water line is higher, be very careful that you still have the 28 inches minimum to any steam carrying pipe or dry return. CHECK ALL AIR VENTS 7. Make sure all main and riser vents and all radiator vents are working. 8. Make sure the main vent is piped correctly. COMPARE NEW BOILER TO OLD 9. If you are replacing an old, large boiler, you may need to install a boiler feed system to provide the storage needed. a) The old, large boilers had more water content. So they could steam longer before they needed water added. b) New, high efficiency boilers don t have as much water content. So they can usually only steam for about 15 minutes before they drop to the low water point. c) A boiler feed system tank holds enough water to allow a long time for condensate to come back. It can supply water to the boiler when needed while the condensate makes its rounds in the system. BE CAREFUL WHEN ZONING 10. Gravity return systems usually don t have enough height from the boiler to the lowest steam carrying pipe to provide 30 inches for every psi pressure at the boiler. a) One-pipe systems should operate around 2 psig at the boiler. This would be 60 inches (5 feet) of pressure applied on the returns when a zone valve is closed. 11. If you are installing zone valves, you will probably have to also install a boiler feed system or condensate receiver system and install drip traps on the main and return risers. The system will no longer be gravity return. CHECK THE SYSTEM HISTORY 12. Ask the owner and maintenance personnel about any problems the system had before. This will give you a good lead on repairs or replacements that may be needed. CHECK ALL THE PIPING 13. Make sure the wet returns are not plugged or leaking. If there are signs that the old boiler used a lot of make-up water it could be that the wet return is leaking. Replace the wet returns. 14. Make sure all pipes are sloped in the right direction. If they are pitched the wrong way or sagging, hammer will occur. 15. If additional heated space has been added to the building, make sure the pipes are large enough for the connected radiation. 17

20 B. SYSTEM CHECKLIST DIMENSION "B" GRAVITY RETURN SYSTEMS Steam Supplies Zone Valve Pressure = 0 when valve closes Water Line 30" per PSI at Boiler B Returns Boiler pressure acts on water in returns Figure 16: Dimension B Result of Zone Valve or Trap on Gravity System When the zone valve closes, all of the boiler pressure pushes back on the returns. This raises the water level in the returns above the boiler water level 30 inches for every psi pressure at the boiler. This will usually require the addition of drip traps and a feed system. 18

21 C. THE NEAR-BOILER PIPING C. THE NEAR-BOILER PIPING NEAR-BOILER PIPING Steam Supply 2" Skim Connection Offset Header Required to Prevent Damage to Boiler From Expansion of Header Figure 17: Return Typical Near-Boiler Piping 19

22 C. THE NEAR-BOILER PIPING 1. Follow the boiler manufacturer s guidelines on nearboiler piping and pipe sizing. 2. Pay special attention to the number and location of risers off of the boiler. 3. Too few risers or risers in the wrong locations can cause a sloped water line in the boiler and/or heavy carryover to the system. a) Sloped water line can actually result in dry firing some sections of the boiler and result in severe damage. RIGHT Water separates from the steam when it turns up into the take-off. EQUALIZER HEADER CONNECTIONS FOR MULTIPLE BOILER RISERS WRONG Water pools under the take-off, causing heavy carryover to the system. EQUALIZER Figure 18: Correct Piping of Steam Take-Off from Boiler Header 20

23 D. SIZING THE BOILER D. SIZING THE BOILER TUBULAR RADIATION RATING Square Feet per Section Height 3 Tube 4 Tube 5 Tube 6 Tube 7 Tube 14" " " " " " " COLUMN RADIATION RATING Square Feet per Section Height 1 Column 2 Column 3 Column 4 Column 5 Column 14" " " " " " " " " " " RADIANT CONVECTOR Width Height Square Feet Per Section 5" 20" /2" 20" 3.40 CAST IRON BASEBOARD Width Height Square Feet Per Linear Foot 2 1/2" 10" 3.40 SIZE THE BOILER TO HANDLE THE RADIATION Figure 19: Select a Boiler with a Net Load Rating Greater Than the Total Connected Radiation 21

24 E. COUNTERFLOW SYSTEMS E. COUNTERFLOW SYSTEMS ONE-PIPE COUNTERFLOW SYSTEM Steam main feeds steam to system and condensate back to boiler. Condensate flows against the steam in the main. The main pitches upward away from the boiler twice as much as a parallel flow system. No return riser is used since the condensate feeds back to the equalizer pipe. No Hartford Loop is needed since the return is above the water line. The boiler header must enter the top of the main, unlike parallel flow systems, where the main feeds off the top of the boiler header. Note that Dimension A is at the lowest point of the steam main as shown. But Dimension A doesn't have to be 28 inches for counterflow systems. There is almost no pressure drop from the boiler to the point of condensate return. The only loss is the piping loss for the condensate. Main Steam A Condensate Water Line Pitch up 1" per 10 ft Maximum Header Length 100 ft Figure 20: Schematic Piping Typical Counterflow System in Operation 22

25 E. COUNTERFLOW SYSTEMS PIPE SIZING ONE-PIPE COUNTERFLOW SYSTEMS STEAM SUPPLY SIZING - ONE PIPE COUNTERFLOW MAIN PITCHED MINIMUM 1 INCH PER 10 FEET 2 1/2" , " , " 1, , " 2, , " 4,546 1,091,040 1,137 Note: Pipe capacities based on recommended increase one pipe size for counterflow one-pipe mains RUNOUT SIZING FOR RUNOUTS UNDER 8 FEET (ADD ONE PIPE SIZE FOR LONGER RUNOUTS) 1" 28 6, /4" 64 15, /2" 64 15, " 92 22, /2" , " , RADIATOR SUPPLY VALVES AND VERTICAL CONNECTORS 1" 28 6, /4" 64 15, /2" 92 22, " , BOILER EQUALIZER CONNECTION 1 1/2" , /2" 6,400 1,536,000 1,600 Figure 21: Minimum Pipe Sizes One-Pipe Counterflow Systems Use this chart to compare the size of existing piping and to determine sizing of lines for added zones and branches. 23

26 F. PARALLEL FLOW SYSTEMS F. PARALLEL FLOW SYSTEMS ONE-PIPE PARALLEL SYSTEM with WET RETURN Steam main feeds steam to system and condensate to Return. Condensate flows with the steam in the main. The main pitches downward away from the boiler at least 1 inch per 20 feet. The return riser feeds condensate to the wet return. Steam Radiator Radiator Dimension A must be 28 inches for most systems. Check the main and return sizes against the chart to be sure this is enough. Condensate Condensate Main Steam Steam Water Line Condensate Pitch down 1" per 20 ft A Water Hartford Loop Wet Return Figure 22: Schematic Piping One-Pipe Parallel Flow System with Wet Return 24

27 F. PARALLEL FLOW SYSTEMS PIPE SIZING ONE-PIPE PARALLEL FLOW SYSTEM WITH WET RETURN STEAM SUPPLY SIZING - ONE PIPE PARALLEL FLOW MAIN PITCHED MINIMUM 1/2 INCH PER 10 FEET 2" , /2" , " 1, , " 2, , " 4,546 1,091,040 1,137 6" 7,642 1,834,080 1,911 RADIATOR RUNOUT SIZING FOR RUNOUTS UNDER 8 FEET (ADDONEPIPESIZEFORLONGERRUNOUTS) 1" 28 6, /4" 64 15, /2" 64 15, " 92 22, /2" , " , RADIATOR SUPPLY VALVES AND VERTICAL CONNECTORS 1" 28 6, /4" 64 15, /2" 92 22, " , WET RETURN SIZING 1" , /4" 1, , /2" 1, , " 4, ,000 1,000 BOILER EQUALIZER CONNECTION 1 1/2" , /2" 6,400 1,536,000 1,600 Figure 23: Minimum Pipe Sizes One-Pipe Parallel Flow System with Wet Return Use this chart to compare the size of existing piping and to determine sizing of lines for added zones and branches. 25

28 F. PARALLEL FLOW SYSTEMS ONE-PIPE PARALLEL SYSTEM with DRY RETURN Steam main feeds steam to system and condensate to Return. Condensate flows with the steam in the main. The main and dry return pitch downward away from the boiler at least 1 inch per 20 feet. The dry return feeds condensate to the return riser. Locate the Main near the end of the dry return. Steam Radiator Radiator Dimension A must be 28 inches for most systems. Check the main and return sizes against the chart to be sure this is enough. Condensate Condensate Pitch down 1" per 20 ft Steam Main Condensate Steam A Dry Return Water Line Water Hartford Loop Wet Return Figure 24: Schematic Piping One-Pipe Parallel Flow System with Dry Return 26

29 F. PARALLEL FLOW SYSTEMS PIPE SIZING ONE-PIPE PARALLEL FLOW SYSTEM WITH DRY RETURN STEAM SUPPLY SIZING - ONE PIPE PARALLEL FLOW M AIN PITCHED MINIMUM 1/2 INCH PER 10 FEET 2" , /2" , " 1, , " 2, , " 4,546 1,091,040 1,137 6" 7,642 1,834,080 1,911 RADIATOR RUNOUT SIZING FOR RUNOUTS UNDER 8 FEET (AD D O N E PIPE SIZE FO R LO N G ER RU N O U TS) 1" 28 6, /4" 64 15, /2" 64 15, " 92 22, /2" , " , RADIATOR SUPPLY VALVES AND VERTICAL CONNECTORS 1" 28 6, /4" 64 15, /2" 92 22, " , D R Y R ETU R N S IZIN G 1" , /4" , /2" 1, , " 2, , W ET R ETU R N S IZIN G 1" , /4" 1, , /2" 1, , " 4, ,000 1,000 BOILER EQUALIZER CONNECTION 1 1/2" , /2" 6,400 1,536,000 1,600 Figure 25: Minimum Pipe Sizes One-Pipe Parallel Flow System with Dry Return Use this chart to compare the size of existing piping and to determine sizing of lines for added zones and branches. 27

30 F. PARALLEL FLOW SYSTEMS ONE-PIPE PARALLEL UPFEED SYSTEM Steam main feeds steam to Upfeed Risers and Branches. Main and dripped risers feed condensate to returns. The main pitches downward away from the boiler at least 1 inch per 20 feet. Note that dripped riser connections pitch down from the main. Undripped riser connections pitch upward from the main. Dimension A must be 28 inches for most systems. Check the main and return sizes against the chart to be sure this is enough. The lowest steam carrying pipe, either a main or a riser or branch line, determines the smallest Dimension A. Provide a Main at the top of each riser and at the end of the steam main. Radiator Main Radiator Main Radiator Give good pitch to long feeds Supply Main Riser Not Dripped Main Riser Dripped A Hartford Loop Boiler Water Line Wet Return A Riser Drip Dirt Pocket Figure 26: Schematic Piping One-Pipe Parallel Upfeed System Steam feeds up the risers to the radiation. Condensate flows down the risers to the main or to drip legs as shown. 28

31 F. PARALLEL FLOW SYSTEMS PIPE SIZING ONE-PIPE PARALLEL UP-FLOW SYSTEM STEAM SUPPLY SIZING - ONE PIPE PARALLEL FLOW MAIN PITCHED MINIMUM 1/2 INCH PER 10 FEET 2" , /2" , " 1, , " 2, , " 4,546 1,091,040 1,137 6" 7,642 1,834,080 1,911 UPFEED RISER RUNOUT SIZING WHEN RISER IS DRIPPED RUNOUT SLOPED DOWN 1/2" PER 10 FT 1" 68 16, /4" , /2" , " , /2" , UPFEED RISER RUNOUT SIZING WHEN RISER IS NOT DRIPPED RUNOUT SLOPED UP 1/2" PER 10 FT 1" 28 6, /4" 55 13, /2" 81 19, " , /2" , RADIATOR RUNOUT SIZING FOR RUNOUTS UNDER 8 FEET (ADD ONE PIPE SIZE FOR LONGER RUNOUTS) 1" 28 6, /4" 64 15, /2" 64 15, " 92 22, /2" , " , UP-FEED RISER SIZING 1" 45 10, /4" 98 23, /2" , " , /2" , " , " 1, , UP-FEED RISER DRIP SIZING Riser Size Drip to Wet Return Drip to Dry Return (With Loop Seal) 1" 3/4" 3/4" 1 1/4" 3/4" 3/4" 1 1/2" 3/4" 1" 2" 1" 1" 2 1/2" 1" 1" 3" 1" 1" WET RETURN SIZING 1" , /4" 1, , /2" 1, , " 4, ,000 1,000 DRY RETURN SIZING 1" , /4" , /2" 1, , " 2, , RADIATOR SUPPLY VALVES AND VERTICAL CONNECTORS 1" 28 6, /4" 64 15, /2" 92 22, " , BOILER EQUALIZER CONNECTION Pipe Size Square Ft EDR Btu/Hr Net 672Pounds/Hr 1 1/2" , /2" 6,400 1,536,000 1,600 Figure 27: Minimum Pipe Sizes One-Pipe Parallel Upfeed System Use this chart to compare the size of existing piping and to determine sizing of lines for added zones and branches. 29

32 F. PARALLEL FLOW SYSTEMS UP-FEED RUNOUT WHEN NOT DRIPPED Up-Feed Riser Pitch 1/2" per Foot & Increase Pipe One Size One size larger than riser Steam Main 3 Ft Approximately Figure 28: Upfeed Riser and Runout When Not Dripped 30

33 F. PARALLEL FLOW SYSTEMS UP-FEED RISER WITH DRIP LINE Up-Feed Riser Steam Main Pitch 1/2" per 10 ft Wet Return Elevation End View Figure 29: Upfeed Riser Connection When Dripped to Wet Return 31

34 F. PARALLEL FLOW SYSTEMS UP-FEED BRANCH CONNECTION (NOT DRIPPED) Up-Feed Riser Steam Main Pitch 1/2" per 10 ft Elevation End View Figure 30: Upfeed Branch Connection When Not Dripped 32

35 F. PARALLEL FLOW SYSTEMS RUNOUT TO DOWN-FEED RISER Steam Main Pitch 1/2" per 10 ft Down-Feed Riser Elevation End View Figure 31: Downfeed Riser Connection to Steam Main 33

36 F. PARALLEL FLOW SYSTEMS ONE-PIPE PARALLEL DOWNFEED SYSTEM Express Steam Riser feeds top floor steam main. Steam main feeds steam to Downfeed Risers and Branches. Main and dripped risers feed condensate to returns. The main pitches downward away from the boiler at least 1 inch per 20 feet. Note that dripped riser connections pitch down from the main. Undripped riser connections pitch upward from the main. Dimension A must be 28 inches for most systems. Check the main and return sizes against the chart to be sure this is enough. The lowest steam carrying pipe, either a main or a riser or branch line, determines the smallest Dimension A. Provide a Main at the top of each riser and just above the lowest branch on each of the Downfeed Risers. Main Radiator Radiator Radiator Give good pitch to long feeds Main Express Steam Supply Riser Main A A Main Riser Dripped A Hartford Loop Boiler Water Line Wet Return Riser Drip Dirt Pocket Figure 32: Schematic Piping One-Pipe Parallel Downfeed System The main advantage of this system is that the condensate flows in the same direction as the steam in all of the downfeed risers. 34

37 F. PARALLEL FLOW SYSTEMS PIPE SIZING ONE-PIPE PARALLEL FLOW DOWN FEED SYSTEM S T E A M S U P P L Y S IZ IN G - O N E P IP E P A R A L L E L F L O W M A IN P I T C H E D M I N I M U M 1 / 2 I N C H P E R 1 0 F E E T P i p e S i z e S q u a r e F t E D R B t u /H r N e t P o u n d s / H r 2 " , / 2 " , " 1, , " 2, , " 4, , 0 9 1, , " 7, , 8 3 4, , E X P R E S S R I S E R S I Z I N G - P A R A L L E L D O W N F E E D S Y S T E M P i p e S i z e S q u a r e F t E D R B t u /H r N e t P o u n d s / H r 2 1 / 2 " , " 1, , / 2 " 1, , " 2, , " 4, , 0 0 8, , " 7, , 7 2 8, , " 1 5, , 6 0 0, , D O W N - F E E D R I S E R S & B R A N C H E S T O D O W N F E E D R I S E R S P i p e S i z e S q u a r e F t E D R B t u /H r N e t P o u n d s / H r 1 " , / 4 " , / 2 " , " , / 2 " , " 1, , / 2 " 1, , " 2, , R A D I A T O R R U N O U T S I Z I N G F O R R U N O U T S U N D E R 8 F E E T ( A D D O N E P I P E S I Z E F O R L O N G E R R U N O U T S ) P i p e S i z e S q u a r e F t E D R B t u /H r N e t P o u n d s / H r 1 " 2 8 6, / 4 " , / 2 " , " , / 2 " , " , W E T R E T U R N S IZ IN G P i p e S i z e S q u a r e F t E D R B t u /H r N e t P o u n d s / H r 1 " , / 4 " 1, , / 2 " 1, , " 4, , , R A D I A T O R S U P P L Y V A L V E S A N D V E R T I C A L C O N N E C T O R S P i p e S i z e S q u a r e F t E D R B t u /H r N e t P o u n d s / H r 1 " 2 8 6, / 4 " , / 2 " , " , B O I L E R E Q U A L I Z E R C O N N E C T I O N P i p e S i z e S q u a r e F t E D R B t u /H r N e t P o u n d s / H r 1 1 / 2 " , / 2 " 6, , 5 3 6, , Figure 33: Minimum Pipe Sizes One-Pipe Parallel Downfeed System Use this chart to compare the size of existing piping and to determine sizing of lines for added zones and branches. 35

38 G. TROUBLESHOOTING G. TROUBLESHOOTING Figure 34: How Water Hammer Occurs 36

39 G. TROUBLESHOOTING TROUBLESHOOTING WATER HAMMER ON START-UP LOOK FOR SAGS IN STEAM MAIN AND DRY RETURN PIPING, WHERE WATER CAN POCKET. LOOK FOR CONCENTRIC REDUCER WHICH WOULD CAUSE WATER TO POCKET. CHECK FOR LONG STEAM MAINS WITH NO DRIP LINES. CHECK DIMENSION "A". IF THE BOILER WATER LEVEL IS TOO HIGH, DRY RETURNS MAY NOW BE WET. Figure 35: Troubleshooting Water Hammer Which Occurs Shortly After Start-up 37

40 G. TROUBLESHOOTING TROUBLESHOOTING WATER HAMMER IN MID-CYCLE WET RETURN LINES MAY BE CLOGGED, CAUSING CONDENSATE TO BACK UP INTO STEAM PIPING. DIRTY BOILER WATER OR WRONG NEAR-BOILER PIPING COULD BE CAUSING WET STEAM. THE BOILER MAY BE OVERSIZED OR OVERFIRED. THIS CAUSES TOO MUCH PRESSURE DROP IN MAIN, SO CONDENSATE BACKS UP IN RISER. Figure 36: Troubleshooting Water Hammer Which Occurs During Mid-Cycle 38

41 G. TROUBLESHOOTING TROUBLESHOOTING WATER HAMMER IN MID-CYCLE Use close nipple only Hartford Loop CHECK THE HARTFORD LOOP. THE NIPPLE MAY BE TOO LONG. ONLY USE A CLOSE NIPPLE. MAKE SURE THE STEAM PIPING IS INSULATED. IF INSULATION HAS BEEN REMOVED, TOO MUCH PIPING CONDENSATE WILL RESULT AND CAUSE CONDENSATE TO BUILD UP IN THE PIPING. RADIATOR VENTS MAY BE TOO QUICK. THIS CAUSES CONDENSATE TO POOL AND BLOCK SUPPLY. Figure 37: Troubleshooting Water Hammer Which Occurs During Mid-Cycle 39

42 G. TROUBLESHOOTING TROUBLESHOOTING WATER HAMMER ON SHUTDOWN Top of Nipple 2 to 4" Below Boiler Water Line Hartford Loop CHECK THE HARTFORD LOOP. THE NIPPLE MAY BE TOO CLOSE TO THE BOILER WATER LEVEL. IT MUST BE 2 TO 4 INCHES BELOW. MAKE SURE THE STEAM PIPING IS INSULATED. IF BOILER ROOM PIPING INSULATION HAS BEEN REMOVED, BUT SYSTEM PIPING INSULATION REMAINS, A VACUUM WILL OCCUR IN THE BOILER ROOM PIPING ON SHUTDOWN, CAUSING WATER LEVEL TO BOUNCE. Figure 38: Troubleshooting Water Hammer Which Occurs On Shut-Down 40

43 G. TROUBLESHOOTING TROUBLESHOOTING HAMMERING IN THE BOILER Steam Pocket CHECK FOR FLAME IMPINGEMENT ON THE LEGS OF WET BASE BOILERS. THIS CAUSES STEAM POCKETS TO FORM. THE STEAM COLLAPSES AND CAUSES HAMMER. CHECK THE BOILER FOR SEDIMENT ACCUMULATION. SEDIMENT IN THE LEGS OR BOTTOM OF THE BOILER CAN SLOW CIRCULATION AND CAUSE HAMMER. OVERSIZED TANKLESS COILS CAN CAUSE THE BOILER WATER LEVEL TO COLLAPSE DURING HIGH POTABLE WATER FLOW. THIS CAN CAUSE HAMMERING. Figure 39: Troubleshooting Hammering in the Boiler 41

44 FULL-COLOR TRAINING GUIDE SERIES ONE-PIPE STEAM SYSTEMS Price $ CHOS396 R2 (12/10-1M)

The. Steam TWO-PIPE STEAM & PUMPED RETURN

The. Steam TWO-PIPE STEAM & PUMPED RETURN FULL-COLOR TRAINING GUIDE SERIES The of Steam TWO-PIPE STEAM & PUMPED RETURN The Color of Steam The Color of Steam A. PUMPED RETURN SYSTEMS 1. When Is a Pump Needed? 2. Pumped Return Systems 3. Boiler

More information

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Introduction to Hydronics A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Hydronic heating systems use hot water or steam to deliver the

More information

VENTS. Main Steam Vents. How to Select Steam Vents. For Steam Vent selection information, please refer to Selection Guidelines on page 133.

VENTS. Main Steam Vents. How to Select Steam Vents. For Steam Vent selection information, please refer to Selection Guidelines on page 133. Main Steam How to Select Steam For Steam Vent selection information, please refer to Selection Guidelines on page 133. Model Radiator Convector Unit Thermostatlic Number (Angle Type) (Bottom Inlet) Heater

More information

Steam System Best Practices Document No. 11

Steam System Best Practices Document No. 11 Plant Support & Evaluations, Inc 400 Lombardi Ave. Green Bay, WI 54304 888-615-3559 www.plantsupport.com Fax: 888-615-8664 Steam System Best Practices Document No. 11 The Number One Problem in a Steam

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-214(C) Series 61 Low Water Cut-Off OPERATION

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-214(C) Series 61 Low Water Cut-Off OPERATION Series 61 Low Water Cut-Off Typical Applications: - Primary or secondary low water cut-off for hot water and steam boilers. - Low water cut-off - High water cut-off - Alarm actuator OPERATION Maximum Boiler

More information

Main Steam Vents. Hoffman Specialty Regulators. How to Select Steam Vents

Main Steam Vents. Hoffman Specialty Regulators. How to Select Steam Vents Hoffman Specialty Regulators Main Steam How to Select Steam Model Radiator Convector Unit Thermostatlic Number (Angle Type) (Bottom Inlet) Heater Mains Vent (only) Remarks 1A X Adjustable Orifice 70A X

More information

INSTRUCTION MANUAL HS-229G

INSTRUCTION MANUAL HS-229G INSTRUCTION MANUAL HS-229G 510977 STEP 1 - Where to Install the Thermostatic Steam Trap Determine where to install the thermostatic steam trap based on the following information. a. The trap should be

More information

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job SERIES Commercial, Forced Draft, Hot Water or Steam Boiler Sizes from to,8 MBH output The right fit for any commercial job The Series is built to handle any installation - businesses, institutions, apartments,

More information

Air Vents for Hot and Chilled Water Systems

Air Vents for Hot and Chilled Water Systems Air Vents for Hot and Chilled Water Systems Sparco Automatic Vent for Hot Water or Steam Heating The Sparco brand HV190 is a tiny-sized automatic air vent for hot water and steam systems. Installs in baseboards,

More information

Information Job Sheet 4. Closed-Loop Drainback Systems. Drainback tanks

Information Job Sheet 4. Closed-Loop Drainback Systems. Drainback tanks Information Job Sheet 4 Closed-Loop Drainback Systems Drainback systems can consist of two closed-loop circuits. Each loop contains an active pump to circulate the solar and storage fluids independently.

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

WATER HAMMER something that never should occur in a steam system

WATER HAMMER something that never should occur in a steam system BEST PRACTICE NO. 11 WATER HAMMER something that never should occur in a steam system 1. STEAM AND CONDENSATE WATER HAMMER Water hammer is never normal in a steam and condensate system, and it is totally

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C) Models 51, 51-S and 53 Boiler Water Feeders Models 51-2, 51-S-2 and 53-2 Feeder Cut-Off Combinations McDonnell & Miller Installation & Maintenance Instructions MM-315(C) OPERATION Maximum Water Supply

More information

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM BEST PRACTICE NO. 30 WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM Air and noncondensable gases are one of the major problems in a steam system that can cause production

More information

APPLICATION GUIDELINES STEAM MAIN DRAINAGE

APPLICATION GUIDELINES STEAM MAIN DRAINAGE APPLICATION GUIDELINES STEAM MAIN DRAINAGE 1) Steam Main Drip Leg Dimensions 2) Types of Warm-Up a) Supervised b) Automatic 3) Spacing of Drip Legs 4) Low Pressure Drainage-- Sizing Traps for Automatic

More information

Methods for controlling one and two pipe systems for comfort, even temperature distribution and energy savings.

Methods for controlling one and two pipe systems for comfort, even temperature distribution and energy savings. Methods for controlling one and two pipe systems for comfort, even temperature distribution and energy savings. or Living with a Steam Heating System, a Guide for New Yorkers (but not engineers) Authors:

More information

Steam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle

Steam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle Steam Trap Presentation for IDEA Distribution Workshop Presenter: Joe Radle Proper Piping when Reducing Pipe Size Concentric reducer Eccentric reducer Correct Wrong Typical Steam Main Drip Station D Size

More information

Efficient Steam System Design

Efficient Steam System Design Efficient Steam System Design The word Efficient is often used to describe the general performance of a system. However it is important to distinguish between efficiency and effectiveness. Efficiency is

More information

STEAM / GAS APPLICATION GUIDE

STEAM / GAS APPLICATION GUIDE WET-BASE CAST-IRON MODULAR BOILERS Guidelines for the design, purchase and installation of Slant/Fin gas-fired steam modular boiler systems. STEAM / GAS APPLICATION GUIDE CONTENTS Introduction...1 Ratings

More information

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING Series 47 and 247 Mechanical Water Feeders McDonnell & Miller Installation & Maintenance Instructions MM-316(C) Series 47-2 and 247-2 Combination Mechanical Water Feeder/Low Water Cut-Off Series 47 Water

More information

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107 TABLE OF CONTENTS FLOAT AND THERMOSTATIC SERIES PAGE How to Select All 107 C 14 H 8 I 12 X 14 Competitive Changeover 18 THERMOSTATIC 8C 22 9C 2 17C 20 Competitive Changeover 17C 24 Replacement Modules

More information

How to Trap: Installation and Testing

How to Trap: Installation and Testing How to Trap: Installation and Testing 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing Energy Down

More information

Silhouette. Feedwater Heater. Boiler Feedwater

Silhouette. Feedwater Heater. Boiler Feedwater Roth Roth Low Low Silhouette Silhouette TRAY DEAERATORS Boiler Boiler Feedwater Feedwater Heater Heater Capacities Capacities to to 50,000 50,000 lb/hr lb/hr Model RDTV-150-5-1-2 vertical tray type deaerator

More information

Boiler Steam Supply Piping Basics November 18, ) Q: What kind of condensate traps should be used on vacuum condensate return systems?

Boiler Steam Supply Piping Basics November 18, ) Q: What kind of condensate traps should be used on vacuum condensate return systems? Boiler Steam Supply Piping Basics November 18, 2015 1) Q: What kind of condensate traps should be used on vacuum condensate return systems? A: What is often used in a vacuum system is a thermodynamic disc

More information

CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES

CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES Where to Install Pipe Temperature Sensors for Freeze Protection 1 WHICH PIPES SHOULD I MONITOR FOR FREEZE

More information

STEAM SYSTEMS TOP SAFETY ITEMS FOR STEAM OPERATIONS. July, 2018

STEAM SYSTEMS TOP SAFETY ITEMS FOR STEAM OPERATIONS. July, 2018 STEAM SYSTEMS TOP SAFETY ITEMS FOR STEAM OPERATIONS July, 2018 Inveno Engineering LLC Tampa, Florida www.invenoeng.com kelly.paffel@invenoeng.com 239-289-3667 graham.thorsteinson@invenoeng.com 404-375-0785

More information

COMMERCIAL HYDRONIC PRODUCTS A MESTEK COMPANY. Convectors STEAM AND HOT WATER RADIATION CC-13

COMMERCIAL HYDRONIC PRODUCTS A MESTEK COMPANY. Convectors STEAM AND HOT WATER RADIATION CC-13 COMMERCIAL HYDRONIC PRODUCTS A MESTEK COMPANY Convectors STEAM AND HOT WATER RADIATION CC-13 Sterling Convectors are engineered for both forced hot water and two-pipe steam heating system installation

More information

Hoffman Specialty General Catalog

Hoffman Specialty General Catalog Hoffman Specialty General Catalog HS-900E ESP-PLUSTM For computer aided selection of Steam Trap and Regulators, please refer to the Steam Specialty Component Selectors in the Hoffman Specialty website

More information

Installation and Testing of Inverted Bucket Steam Traps Manual

Installation and Testing of Inverted Bucket Steam Traps Manual Installation and Testing of Inverted Bucket Steam Traps Manual 307-EN Please read and save these instructions Armstrong IB Traps Installation Before Installing Run pipe to trap. Before installing the trap,

More information

Series 300 VTB. Installation Instructions

Series 300 VTB. Installation Instructions Series 300 VTB Installation Instructions Sizes 7 12 16 20 30 HP #2 Fuel Oil Gas (500 to 2500 BTU) Gas Light Oil Combination High Pressure Steam Sizes 7 thru 16 HP (125 PSI) Sizes 20 and 30 HP (150 PSI)

More information

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT

More information

MODERNIZATION OF HYDRONIC SYSTEMS

MODERNIZATION OF HYDRONIC SYSTEMS TECHNCAL NOTE Small Homes Council-Building Research Council, University of llinois at Urbana-Champaign MODERNZATON OF HYDRONC SYSTEMS Warren S. Harris, Professor Emeritus of Mechanical Engineering, University

More information

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions ! Condensate Return Systems General Installation, Operation, & Service Instructions INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. SAFETY INSTRUCTIONS This safety alert symbol will be used in this

More information

Basic System Operation

Basic System Operation Steam s T hey ve been with us for over two hundred years, and most of the time, they re so reliable most folks don t give them much thought. They sit in buildings all over the world, transferring heat

More information

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND Aqua Balance AquaBalance TM CONTROL MODULE QUICK START GUIDE 10 1 Domestic Hot Water temperature setpoint decreasing button 2 Domestic Hot Water temperature setpoint increasing button 3 Central Heating

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY. Information Reviewed and Reaffirmed. August No.

STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY. Information Reviewed and Reaffirmed. August No. STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY Information Reviewed and Reaffirmed August 196 No. 1664 11111111111134 areillin1111111 1 11111111 1 1[1 11 nin FOREST

More information

COOLING / HEATING COILS

COOLING / HEATING COILS COOLING / HEATING COILS GENERAL INSTALLATION OPERATION AND MAINTENANCE COIL TYPES CHILLED WATER / GLYCOL HOT WATER / GLYCOL DIRECT EXPANSION (EVAPORATIVE COOLING) STEAM DISTRIBUTING STANDARD STEAM Type

More information

TABLE OF CONTENTS INTRODUCTION CHAPTER 7 HEAT LOSS CALCULATION. Short Form Survey Sample Calculation...74

TABLE OF CONTENTS INTRODUCTION CHAPTER 7 HEAT LOSS CALCULATION. Short Form Survey Sample Calculation...74 The Heating Helper TABLE OF CONTENTS INTRODUCTION... 2 CHAPTER 1 STEAM. Two Pipe Steam (Sizing)... 15. One Pipe Steam (Sizing)... 16. Relevant Information. to Steam Piping... 17. Steam Boiler Piping Schematics...

More information

Universal Fire Tube Boiler Wall Mount Models

Universal Fire Tube Boiler Wall Mount Models Universal Fire Tube Boiler Wall Mount Models USER S INFORMATION MANUAL Models WBRU**80W / 100W / 120W / 140W / 175W / 199W **NG denotes Natural Gas Model, LP Denotes Propane Model Heat Exchanger Bears

More information

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners 1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):

More information

Removal of Non-condensable Gases and Air Is Critical In A Steam System

Removal of Non-condensable Gases and Air Is Critical In A Steam System Removal of Non-condensable Gases and Air Is Critical In A Steam System Air and non-condensable gases are one of the major problems in a steam system. Both can cause production problems for a steam system

More information

HOME OWNER S INFORMATION Induced Combustion Gas Furnace

HOME OWNER S INFORMATION Induced Combustion Gas Furnace HOME OWNER S INFORMATION Induced Combustion Gas Furnace NOTE TO INSTALLER: This manual must be left with the equipment user. USER: Please read all instructions in the manual and retain all manuals for

More information

Steam and Gas Power Systems Prof Ravi Kumar Department of Mechanical and Industrial Engineering Indian Institute of Technology - Roorkee

Steam and Gas Power Systems Prof Ravi Kumar Department of Mechanical and Industrial Engineering Indian Institute of Technology - Roorkee Steam and Gas Power Systems Prof Ravi Kumar Department of Mechanical and Industrial Engineering Indian Institute of Technology - Roorkee Module No # 02 Lecture No # 09 Boilers Mountings and Accessories

More information

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

Bringing a Steam Boiler On-Line from Cold.

Bringing a Steam Boiler On-Line from Cold. Bringing a Steam Boiler On-Line from Cold. To help understand what needs to be done and why things need to be done in a certain way, the following procedure presumes that the boiler is completely cold

More information

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh WATER HEATERS / BOILERS COWB3 Oil-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 0654 March 08 Supersedes September 05 AFUE up to 85.% Heating Input 05,000 to 45,000 Btuh MODEL NUMBER IDENTIFICATION

More information

Boiler Manual. Series 3 Water & steam boilers for use with Gas, Light Oil, & Gas/Light Oil Fired Burners. Maintenance Parts. Installation Startup

Boiler Manual. Series 3 Water & steam boilers for use with Gas, Light Oil, & Gas/Light Oil Fired Burners. Maintenance Parts. Installation Startup 94 Series 3 Water & steam boilers for use with Gas, Light Oil, & Gas/Light Oil Fired Burners Boiler Manual Installation Startup Maintenance Parts For additional information, refer to.. Burner specification

More information

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw SEMI-INSTANTANEOUS ENERGY: STEAM TO WATER U-TUBE SINGLE-WALL & DOUBLE-WALL HEAT EXCHANGERS FLOOR DRAIN Typical Construction Figure 34-1 FLOOR DRAIN 1. U-tube

More information

How to Trap: Steam Tracer Lines

How to Trap: Steam Tracer Lines How to Trap: Steam Tracer Lines 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing Energy Down to Earth

More information

JD Series Cast Iron Commercial Hot Water or Steam Boiler

JD Series Cast Iron Commercial Hot Water or Steam Boiler JD Series Cast Iron Commercial Hot Water or Steam Boiler INSTALLATION, OPERATION & MAINTENANCE MANUAL An ISO 9001-2008 Certified Company Utica Boilers 2201 Dwyer Ave. Utica, NY 13501 Phone: (315) 797-1310

More information

Mini Pump Trap. Features: n Low maintenance - No leaking seals, impeller or motor problems reducing maintenance and downtime.

Mini Pump Trap. Features: n Low maintenance - No leaking seals, impeller or motor problems reducing maintenance and downtime. Armstrong Mini Pump Bulletin AFH-223 The Armstrong mini pump trap is the smallest non-electric solution that can move condensate or other liuids from lower to higher points and from lower to higher pressures.

More information

Inverted Bucket Float & Thermostatic Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS

Inverted Bucket Float & Thermostatic Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS Inverted Float & Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS ABOUT US In 1916, the company, then known as the Sterling Engineering Company, began designing and manufacturing valves, traps, strainers

More information

TCV-1. Convector Steam and Hot Water Unit Heaters

TCV-1. Convector Steam and Hot Water Unit Heaters TCV-1 Convector Steam and Hot Water Unit Heaters Convector Radiation Turbonics Convectors are engineered for both forced hot water and two-pipe steam heating system installation with heating elements of

More information

FLO-RITE-TEMP INSTANTANEOUS WATER HEATER INSTALLATION AND ADJUSTMENT INSTRUCTIONS FOR SINGLE AND DOUBLE WALL UNITS

FLO-RITE-TEMP INSTANTANEOUS WATER HEATER INSTALLATION AND ADJUSTMENT INSTRUCTIONS FOR SINGLE AND DOUBLE WALL UNITS FLO-RITE-TEMP INSTANTANEOUS WATER HEATER INSTALLATION AND ADJUSTMENT INSTRUCTIONS FOR SINGLE AND DOUBLE WALL UNITS Bulletin No. AY-780-L This bulletin should be used by experienced personnel as a guide

More information

Niles Steel Tank Hot Water Generator Installation and Operation Manual

Niles Steel Tank Hot Water Generator Installation and Operation Manual Niles Steel Tank Hot Water Generator Installation and Operation Manual Contents: Contents 1 Hazard definitions 1 1. General Information.... 2 Availability... 3 Optional Control Packages... 5 2. Installation....

More information

WHISPA III 5000 WM & 9000 WM. heatingthroughinnovation. Installation, Operating, Maintenance and After Sales Manual. Part Number: Issue 1

WHISPA III 5000 WM & 9000 WM. heatingthroughinnovation. Installation, Operating, Maintenance and After Sales Manual. Part Number: Issue 1 Installation, Operating, Maintenance and After Sales Manual. WHISPA III 5000 WM & 9000 WM heatingthroughinnovation. Product Serial Number: Installation Date: Part Number: 1371054 Issue 1 Tested to UL &

More information

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils Installation, Operation and Maintenance Guide Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils

More information

Things To Know About Tankless Water Heaters II

Things To Know About Tankless Water Heaters II Fall 2012 Things To Know About Tankless Water Heaters II Inside... Sizing Tables... Page 2 Two-pound Systems... Page 3 Two-pound Line Table... Page 3 Venting Specifications... Page 3 In the last Think

More information

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods 230520 HEAT GENERATION Cornell s Design and Construction Standards provide mandatory design constraints and acceptable or required products for all construction at Cornell University. These standards are

More information

STEAM AND TRAP FUNDAMENTALS

STEAM AND TRAP FUNDAMENTALS STEAM AND TRAP FUNDAMENTALS Nick Westerberg Westerberg and Associates Newman Lake, WA Steam is an invisible gas that is generated by adding heat energy to water, usually from burning fuel in a boiler.

More information

Steam Site Guide. Steam Site Guide. Heat Exchange Applications - SI Units

Steam Site Guide. Steam Site Guide. Heat Exchange Applications - SI Units Steam Site Guide Steam Site Guide Heat Exchange Applications - SI Units Steam Site Guide Content Introduction... 03 01. Estimating Steam Loads... 04 02. Steam Table SI... 07 03. Sizing a Steam Pipe...

More information

S AGE E NGINEERING A SSOCIATES, LLP

S AGE E NGINEERING A SSOCIATES, LLP S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September

More information

Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment

Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment Float & Thermostatic Steam Traps from Spirax Sarco About float & thermostatic steam traps Most

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

STARFIRE V STEAM Series 5 OIL-FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL. Models

STARFIRE V STEAM Series 5 OIL-FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL. Models STARFIRE V STEAM Series 5 OIL-FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL Models SFE-3090S SFE-3090ST SFE-4125S SFE-4125ST SFE-5185S SFE-5185ST SFE-6210S SFE-6210ST PATENT 7,823,544

More information

16 Series GAS-FIRED STEAM BOILERS MODELS

16 Series GAS-FIRED STEAM BOILERS MODELS 16 Series GAS-FIRED STEAM BOILERS MODELS 1603HSID 1604HSID 1605HSID 1606HSID 1607HSID 1608HSID 1609HSID INSTALLATION, OPERATION & MAINTENANCE MANUAL MODEL HSID Electronic Intermittent Ignition PENNCO BOILERS

More information

Partner. Peerless. Indirect-Fired. Water Heater. Installation, Operation & Maintenance Manual

Partner. Peerless. Indirect-Fired. Water Heater. Installation, Operation & Maintenance Manual Peerless Indirect-Fired Partner Water Heater Installation, Operation & Maintenance Manual Product Selection 1. The following guidelines apply to residential systems only. For commercial or institutional

More information

GOLD Plus 30/40/60/80

GOLD Plus 30/40/60/80 PLUS Line Indirect-Fired Water Heaters Series 3 Manual Installation Startup Maintenance Parts PLUS 100/110/119 GOLD Plus 30/40/60/80 Plus 40/60/80 This manual must only be used by a qualified heating installer/service

More information

PRESSURE MOTIVE PUMP (PMP) APPLICATIONS

PRESSURE MOTIVE PUMP (PMP) APPLICATIONS DRAINAGE of a SINGLE SOURCE of for a CLOSED LOOP SYSTEM PURPOSE: For removing condensate from below steam heat transfer equipment when a modulating valve is used for control and stall conditions will exist.

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW/HORIZONTAL & DOWNFLOW TWO STAGE INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this manual is not

More information

THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY

THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY 1 Boiler Room Hazards A Risk Of Explosion Exists High Pressure steam Combustion Gases Chemicals Moving Machinery Hot Surfaces www.bangladeshworkersafety.org

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

Heat Transfer Packages

Heat Transfer Packages Heat Transfer Packages Heat Transfer Package (HTP Series) Building Heat, Process Heat, Swimming Pool Heater, Cooling Applications and Snow Melt Package (SMP Series) Steam,, High Temperature Hot Water,

More information

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual Armstrong J Series, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual This bulletin should be used by experienced personnel as a guide to the installation

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR POINT OF USE STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL PS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR POINT OF USE STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL PS INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR POINT OF USE STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL PS Edition 2011 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615

More information

How to Trap: Trap Selection and Safety Factors

How to Trap: Trap Selection and Safety Factors How to Trap: Trap Selection and Safety Factors Bringing Energy Down to Earth Say energy. Think environment. And vice versa. Any company that is energy conscious is also environmentally conscious. Less

More information

Trade of Plumbing. Module 2: Domestic Hot and Cold Water Service Unit 10: Hot Water Supply Phase 2

Trade of Plumbing. Module 2: Domestic Hot and Cold Water Service Unit 10: Hot Water Supply Phase 2 Trade of Plumbing Module 2: Domestic Hot and Cold Water Service Unit 10: Hot Water Supply Phase 2 Table of Contents List of Figures... 4 List of Tables... 5 Document Release History... 6 Module 2 Domestic

More information

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS INSTALLATION AND OPERATING INSTRUCTIONS File No: 10.895 Date: march 8, 014 Supersedes: 10.895 Date: december 10, 013 1.0 Symbols used in this document 1.0

More information

BASE-RAY CAST IRON BASEBOARD RADIATION

BASE-RAY CAST IRON BASEBOARD RADIATION INSTALLATION MANUAL FOR BASE-RAY CAST IRON BASEBOARD RADIATION TABLE OF CONTENTS PAGE 2 RATINGS 4 ASSEMBLY CHART 5 SYSTEM TYPES 6 SERIES LOOP SYSTEMS 7 SERIES LOOP DESIGN 8 INSTALLATION DETAILS 9 INSTALLATION

More information

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers. SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

Akva Lux VX District heating substation for indirect heating and domestic hot water systems

Akva Lux VX District heating substation for indirect heating and domestic hot water systems Akva Lux VX District heating substation for indirect heating and domestic hot water systems Akva Lux VX Table of Contents Akva Lux VX... 1 Table of Contents... 1 Safety notes... 2 Delivery... 2 Transport

More information

Bosch 80% AFUE Gas Furnace BGS80 Model

Bosch 80% AFUE Gas Furnace BGS80 Model Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace User's Information Manual 3124627 2 Bosch 80% AFUE Gas Furnace User's Information Manual Data subject to change 06.2018

More information

Checklists LAUNDRY GREENKEYGLOBAL.COM

Checklists LAUNDRY GREENKEYGLOBAL.COM Checklists INFO@GREENKEYGLOBAL.COM GREENKEYGLOBAL.COM Laundry In-house laundry is one of the most energy-intensive areas of a hotel's operation. Its use of energy per square foot may even surpass the kitchen.

More information

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE ACHP 254 Domestic & Commercial Heating II Prepared By: CHARLES STEAD Updated By: Michael J. Newtown, P.E. CANINO SCHOOL

More information

PT15 MATERIAL : DIMENSIONS - Nominal in inches. AVAILABLE SPARES: Disc (Packet of 5) ORDERING INFORMATION: Refer to "HOW TO ORDER" page.

PT15 MATERIAL : DIMENSIONS - Nominal in inches. AVAILABLE SPARES: Disc (Packet of 5) ORDERING INFORMATION: Refer to HOW TO ORDER page. PT5 Thermodynamic Steam Traps MATERIAL : No. PART MATERIAL QTY. (Nos.). BODY ASTM A743 Gr. CA 40 0 (Seat Hardened) (Cast Equiv. AISI 420) 2. DISC CAP ASTM A743 Gr. CA 40 0 (Cast Equiv. AISI 420) 3. DISC

More information

UH16 Series Gas Fired Steam Boilers

UH16 Series Gas Fired Steam Boilers UH16 Series Gas Fired Steam Boilers Models UH1603HSID UH1604HSID UH1605HSID UH1606HSID UH1607HSID UH1608HSID UH1609HSID INSTALLATION, OPERATION & MAINTENANCE MANUAL MODEL HSID Electronic Intermittent Ignition

More information

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER Room Air Conditioner Installation and Operation Manual UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER (VOLTS) MIN. MAX. MIN. F ( C) MAX. F ( C) WAC060K7A 127-1-60 114.3 139.7 70(20.1)

More information

Pamphlet A2404. Mechanical Pump & Pump/ Trap. GP Series GT Series

Pamphlet A2404. Mechanical Pump & Pump/ Trap. GP Series GT Series Pamphlet A2404 Mechanical Pump & Pump/ Trap GP Series GT Series Effective Processing Improves Plant Efficiency Increased productivity and product quality, plus reduced energy consumption and water treatment

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW & DOWNFLOW/HORIZONTAL CONDENSING GAS FURNACES SAFETY Recognize this symbol as an indication of Important Safety Information If not installed, operated and maintained in

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016 Boiler Condensate Return Basics Presented by Steve Connor February 24, 2016 What We Are Covering Today? Brief review of the total steam system Why a proper condensate return system is so important Condensate

More information

STS Steam-to-Steam Humidifier

STS Steam-to-Steam Humidifier IMPORTANT: Read and save these instructions. STS Steam-to-Steam Humidifier Installation, Operation, and Maintenance Manual Warnings and cautions WARNING Indicates a hazardous situation that could result

More information

PLYMOUTH STEAM SERIES 2 GAS-FIRED STEAM BOILERS

PLYMOUTH STEAM SERIES 2 GAS-FIRED STEAM BOILERS PLYMOUTH STEAM SERIES 2 GAS-FIRED STEAM BOILERS INSTALLATION, OPERATION & MAINTENANCE MANUAL MODEL PVSB Continuous Pilot MODEL PSB Electronic Intermittent Ignition H ECR International, Inc. 2201 Dwyer

More information

Gas Fired Residential Combi Boiler Floor and Wall Mount Models

Gas Fired Residential Combi Boiler Floor and Wall Mount Models Gas Fired Residential Combi Boiler Floor and Wall Mount Models USER S INFORMATION MANUAL Models WBRC**140W WBRC**199W WBRC**140F WBRC**199F ** NG Refers to Natural Gas Operation LP Refers to Propane Gas

More information

Solar Water Heaters. Bastián Acevedo Bustos. Electronic Engineering Student, Tarapacá University. Environmental Studies Student, York University

Solar Water Heaters. Bastián Acevedo Bustos. Electronic Engineering Student, Tarapacá University. Environmental Studies Student, York University Solar Water Heaters Bastián Acevedo Bustos Electronic Engineering Student, Tarapacá University Environmental Studies Student, York University Systems Active System Active systems use one or more pumps

More information

S. P. THERMAL SYSTEMS INC.

S. P. THERMAL SYSTEMS INC. S. P. THERMAL SYSTEMS INC. 4504 Green Meadow Blvd. Beamsville Ontario L0R1B5 Canada Phone: 905 563 8651 Fax: 905 563 6234 BOILER & WATER TREATMENT REVIEW NOTE: This article is provided as a Guide Only.

More information

2007 ASME Boiler & Pressure Vessel Code 2007 Edition July 1, 2007

2007 ASME Boiler & Pressure Vessel Code 2007 Edition July 1, 2007 AN INTERNATIONAL CODE 2007 ASME Boiler & Pressure Vessel Code 2007 Edition July 1, 2007 VI RECOMMENDED RULES FOR THE CARE AND OPERATION OF HEATING BOILERS ASME Boiler and Pressure Vessel Committee Subcommittee

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this

More information

KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT

KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT Jerry Wright Paramount Supply Company Eugene, OR Introduction Keep your trap shut or get the condensate out. Which way is it? Can you have it both ways? Which

More information