PIP RESR001 Packaged, Skid-Mounted Industrial Process Refrigeration Systems Specification

Size: px
Start display at page:

Download "PIP RESR001 Packaged, Skid-Mounted Industrial Process Refrigeration Systems Specification"

Transcription

1 EDITORIAL REVISION October 2010 Process Industry Practices Machinery PIP RESR001 Packaged, Skid-Mounted Industrial Process Refrigeration Systems Specification

2 PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice. This Practice is subject to revision at any time. Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas PIP Member Companies and Subscribers may copy this Practice for their internal use. Changes or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP. Authorized Users may attach addenda or overlays to clearly indicate modifications or exceptions to specific sections of PIP Practices. Authorized Users may provide their clients, suppliers and contractors with copies of the Practice solely for Authorized Users purposes. These purposes include but are not limited to the procurement process (e.g., as attachments to requests for quotation/ purchase orders or requests for proposals/contracts) and preparation and issue of design engineering deliverables for use on a specific project by Authorized User s client. PIP s copyright notices must be clearly indicated and unequivocally incorporated in documents where an Authorized User desires to provide any third party with copies of the Practice. PRINTING HISTORY August 2000 Issued February 2008 Complete Revision January 2002 Editorial & Technical Revision October 2010 Editorial Revision Not printed with State funds

3 EDITORIAL REVISION October 2010 Process Industry Practices Machinery PIP RESR001 Packaged, Skid-Mounted Industrial Process Refrigeration Systems Specification Table of Contents 1. Introduction Purpose Scope References Process Industry Practices Industry Codes and Standards Government Regulations Requirements General Package System Compressors Drivers Heat Exchangers Vessels Lubrication Oil System Purge System System Controls and Instrumentation Electrical Pipe, Valves, and Fittings Pressure-Relieving Devices Insulation Structural Steel Base Noise Compressor Vibration and Critical Speeds Painting Inspection Testing Preparation for Shipment Documentation Appendix A Monitoring System Instrumentation Table Appendix B Purchaser s Quality Surveillance Checklist Data Forms RESR001-R Documentation Requirements Sheet RESR001-D Skid-Mounted Industrial Process Refrigeration Systems Data Sheet Process Industry Practices Page 1 of 20

4 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October Introduction 1.1 Purpose This Practice provides requirements for packaged, skid-mounted industrial process refrigeration systems. 1.2 Scope 2. References This Practice describes the minimum requirements for the performance, design, fabrication, testing, inspection, and preparation for shipment of packaged, skidmounted process refrigeration systems. This Practice is not intended to cover commercial or absorption chiller systems. Applicable parts of the following Practices, industry codes and standards, and references shall be considered an integral part of this Practice. The edition in effect on the date of contract award shall be used, except as otherwise noted. Short titles will be used herein where appropriate. 2.1 Process Industry Practices (PIP) PIP ELSMT01 - AC Squirrel Cage Induction Motors (600 Volts and Below) PIP ELSPS01 - Electrical Requirements for Packaged Equipment PIP ELSPS01D - Data Sheet for Electrical Requirements for Packaged Equipment PIP ELSPS01V - Electrical Requirements for Packaged Equipment Preferred Vendor and Component List PIP PCDPS001 - Packaged Equipment Instrumentation Documentation Requirements Data Sheet and Instructions PIP PCERE001 - Rotating Equipment Monitoring Guidelines PIP PCSPS001 - Packaged Equipment Instrumentation Specification PIP PCSPS010 - Small, General Purpose Packaged Equipment Instrumentation Specification PIP REEE003 - Guidelines for General Purpose Nonlubricated Flexible Couplings PIP STF Fixed Ladders and Cages Details PIP VECV Vessel Design Criteria, ASME Code Section VIII, Divisions 1 and 2 PIP VEDST003 - Shell and Tube Heat Exchanger Specification Sheet PIP VEFV Vessel/S&T Heat Exchanger Standard Details (US Customary Units) PIP VESSM001 - Specification for Small Pressure Vessels and Heat Exchangers with Limited Design Conditions Page 2 of 20 Process Industry Practices

5 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems PIP VESV Vessel Fabrication Specification, ASME Code Section VIII, Divisions 1 and Industry Codes and Standards American Petroleum Institute (API) API Form-Wound Squirrel-Cage Induction Motors Horsepower and Larger API General Purpose Steam Turbines for Petroleum, Chemical, and Gas Industry Services API Special Purpose Steam Turbines for Petroleum, Chemical, and Gas Industry Services API Axial and Centrifugal Compressors and Expander-compressors for Petroleum, Chemical and Gas Industry Services API Reciprocating Compressors for Petroleum, Chemical, and Gas Industry Services API Rotary-Type Positive-Displacement Compressors for Petroleum, Petrochemical, and Natural Gas Industries API Machinery Protection Systems Air Conditioning and Refrigeration Institute (ARI) ARI Positive Displacement Condensing Units American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) ASHRAE 15 - Safety Code for Mechanical Refrigeration American Society of Mechanical Engineers (ASME) ASME Boiler and Pressure Vessel Code Section VIII, Div.1 - Pressure Vessels, (ASME Code) ASME B Chemical Plant and Petroleum Refinery Piping ASME B Refrigeration Piping American Welding Society (AWS) AWS D1.1 - Structural Welding Code National Fire Protection Association (NFPA) NFPA 70 - National Electrical Code (NEC) Rubber Manufacturer s Association (RMA) RMA IP-20 - Classical V-Belts and Sheaves RMA IP-24 - Drives Using Synchronous Belts Process Industry Practices Page 3 of 20

6 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October Government Regulations 3. Requirements U.S. Department of Labor, Occupational Safety and Health Administration (OSHA) 3.1 General OSHA 29 CFR Occupational Safety and Health Standards The supplier shall assume full responsibility for the complete, as shipped, unit Subsuppliers and subcontractors used by the supplier shall be subject to written approval by the purchaser before placement of suborders Any proposed exceptions to this Practice or any referenced PIP Practices, purchaser s data sheets, and referenced codes and standards shall be provided with the proposal Unless otherwise specified in writing by the purchaser, no substitution for material, equipment, or components shall be permitted A qualified project engineer shall be named and assigned. The project engineer shall coordinate the project and serve as sole contact with the purchaser from issuance of purchase order through completion of startup and commissioning. 3.2 Package System The refrigeration package shall provide liquid refrigerant to its chiller(s) (evaporator[s]) in the quantity and at the temperature necessary to produce the specified process temperature and refrigeration duty The purchaser shall specify the period of continuous operation required on the data sheet, RESR001-D Performance, capacity, and operating conditions shall be in accordance with the purchaser s data sheet, PIP RESR001-D The refrigeration system shall consist of a complete package with all components (compressor, evaporator, condenser, driver, instrumentation, etc.) factory mounted, piped, and wired Unless written approval is received from purchaser, multiple baseplates designed to facilitate shipping shall not be permitted The system shall be capable of stable operation at specified minimum load Rating condition used to establish the capacity of the refrigeration package system shall be provided with the proposal Storage capacity for refrigerant receiver shall be sufficient to retain the entire system refrigerant inventory if 90% full, including the volume of purchaserfurnished heat exchangers and piping if applicable. Purchaser shall provide piping and exchanger refrigerant volumes if they impact receiver sizing. Page 4 of 20 Process Industry Practices

7 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems Fluorocarbon systems shall have a replaceable-element desiccant filter dryer with visual moisture indication. The element shall be replaceable while system is in operation Unless otherwise specified, the system refrigerant shall be supplied by purchaser The refrigeration system high-pressure side maximum allowable working pressure (MAWP) shall be greater than the condensing pressure by a minimum of 170 kpa (25 PSI) or 10%, whichever is greater The refrigeration system low-pressure and high-pressure MAWPs shall be a minimum of 340 kpa (50 PSI) greater than the refrigerant vapor pressure at the maximum specified ambient temperature Unless otherwise specified on the purchaser s data sheet, PIP RESR001-D, the system and all auxiliaries shall be designed for unprotected outdoor installation The refrigeration system shall be designed for the area electrical classification specified on the purchaser s data sheet, PIP RESR001-D Any special tools required for operation and/or maintenance shall be provided with the package The complete package shall meet the noise limits in accordance with the purchaser s data sheet, PIP RESR001-D. 3.3 Compressors General The compressor shall be designed and manufactured for the refrigerant being compressed The system shall be provided with proper equipment to ensure that liquid cannot enter the compressor suction. Equipment provided for this purpose shall be detailed in the proposal Unless purchaser has specified a desired compressor type on the data sheet, vendor shall provide the type of compressor that is most suited for this specific application The compressor shall be provided with seals to prevent the loss of refrigerant or the contamination of refrigerant over the range of operating conditions and during periods of idleness. 1. Seal operation shall be suitable for variations in suction conditions that may prevail during startup and shutdown. 2. A description of the seal system and the guaranteed maximum refrigerant leakage rate shall be provided with the proposal Unless otherwise approved by purchaser, complete compressor casing, including all welded connections, shall be hydrostatically tested to 1.5 times the maximum case design pressure or pneumatically tested at 1.1 times the maximum case design pressure. 1. The test shall be maintained for 30 minutes or more to permit complete examination of parts under pressure. Process Industry Practices Page 5 of 20

8 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October The certified test results shall be submitted to purchaser within five business days of the test being performed Cast iron and ductile iron pressure-containing parts shall not be permitted for compressors that handle flammable or hazardous refrigerants Compressor inlet pressure shall be greater than atmospheric pressure if flammable refrigerants are used Compressors shall be in accordance with ASHRAE If multiple compressors are provided, isolation valves and controls shall be provided that permit the operation of the system with the remaining compressors if one or more is out of service Reciprocating Compressors The compressor may be open, semi-hermetic, or hermetic in accordance with the purchaser s data sheet, PIP RESR001-D Compressors shall have a method to prevent liquid refrigerant accumulation in the crankcase if compressor is unloaded or idle with the system under pressure. The method and equipment provided for this purpose shall be detailed in the proposal If a flooded evaporator is used in the refrigeration cycle, the compressor shall have the following features: a. Automatic control from temperature- or pressure-sensing elements b. Crankcase heater energized during off cycles c. An automatic solenoid to close liquid line when the compressor is stopped d. A solenoid valve to shut off cooling water to water-cooled compressors when the compressor is stopped Layout shall provide sufficient room around and above the compressor to permit removal of cylinders and valves from the compressor frame and to permit removal of the flywheel and crankshaft Compressors less than 20 kw (25 hp) shall be provided with feet with vibration isolation pads A detailed description of the compressor-unloading system shall be provided in the proposal Open compressors shall be directly connected through a coupling. The drive coupling shall be in accordance with PIP REEE Hermetic and semi-hermetic compressors shall be in accordance with ARI 520 and have the following features: a. Cooled by suction gas b. Accessible for maintenance c. Drivers shall not require motor heaters Page 6 of 20 Process Industry Practices

9 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems Rotary Compressors The compressor shall be helical rotor, screw compressor type If the compressor is an oil flooded design, the oil shall be compatible with the refrigerant. Comment: Oil flooded designs may be preferred because they require fewer seals The seal system shall be designed to contain the refrigerant during all modes of operation such as startup, shutdown, and periods of idleness If specified, the seal system shall be designed for zero leakage Capacity control from full load down to specified minimum load shall be provided by internal slide valves and, if required, by hot gas bypass that provides automatic unloading Oil separation in compressor discharge shall be the supplier s recommended design for refrigeration systems Drive coupling shall be in accordance with PIP REEE Centrifugal Compressors 3.4 Drivers Unless otherwise specified, the compressor may be open or hermetic Compressor capacity control may be variable speed drive, inlet guide vanes, suction dampers, or a combination subject to purchaser approval. The control system proposed shall be explained and detailed in the proposal The purchaser shall provide applicable gear specification for gear boxes, if required Drive coupling shall be in accordance with PIP REEE Electric Motors (Open Drive Systems) Electric motors shall be in accordance with PIP ELSMT01 or API 541, as applicable Steam Turbines Steam turbines shall be in accordance with API 611 or API 612, as specified by purchaser Belt Drives V-belts shall be in accordance with RMA IP Synchronous belts shall be in accordance with RMA IP-24. Comment: Synchronous belts provide a more positive drive mechanism. Process Industry Practices Page 7 of 20

10 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October Heat Exchangers General System heat exchangers shall be in accordance with PIP VECV1001 and PIP VESV1002 or PIP VESSM001, as applicable Exchangers shall be arranged such that maintenance space for tube pulling or cleaning shall be to the outside of the skid. Space required shall be shown on proposal drawings The condenser and evaporator shall be independent vessels Unless otherwise specified, the condenser and evaporator shall have a DN 20 (NPS ¾) drain and vent connection(s) on both the shell and tube sides, complete with valve and plug. Drains shall be at the low point to allow for complete drainage Shell and Tube Unless otherwise specified on purchaser s exchanger specification sheet, PIP VEDST003, exchangers shall be, as a minimum, TEMA C The purchaser shall furnish exchanger design requirements on specification sheet PIP VEDST A completed exchanger specification sheet, PIP VEDST003, shall be provided with the proposal For systems using water as the condensing media, the following design requirements shall apply: a. The condensing system shall be sized for full capacity and maximum inlet water supply temperature. b. The water side of the condensing system shall be designed to not require throttling. Comment: Throttling the cooling water accelerates fouling of the exchanger If a flooded type evaporator is provided, it shall be provided with a full-length, level gauge Direct Expansion If approved by the purchaser, a direct expansion type evaporator up to 350 kw. (100 tons) of refrigeration may be provided Direct expansion evaporators shall include thermal expansion valve(s), equalizing line, and a back-pressure regulator Subcooler If approved by the purchaser, a subcooler may be provided Design details of the subcooler shall be provided with the proposal. Page 8 of 20 Process Industry Practices

11 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems 3.6 Vessels General System vessels shall be in accordance with PIP VECV1001 and PIP VESV1002 or PIP VESSM001, as applicable Receiver The receiver shall have a dip tube with vortex breaker and/or adequate submergence to prevent vortexing in the liquid outlet line The receiver shall be provided with a full-length sight level gauge Unless otherwise specified, the receiver shall have a DN 20 (NPS ¾) minimum vent and drain complete with valve and plug. Drains shall be at the low point to allow for complete drainage The receiver shall have a DN 25 (NPS 1) minimum refrigerant charging/evacuation connection complete with valve and plug Oil Separator (Rotary Compressor Systems) Unless otherwise approved by purchaser, mounting the motor/compressor drive train on a horizontal oil separator shall be limited to 600 kw (800 hp) driver. If the driver is greater than 600 kw (800 hp), the system shall be provided with an independently supported drive train The separator design shall incorporate a method for removing oil from the dry side of the separator Adequate access for changing and maintaining the coalescing elements shall be provided. The coalescing elements shall be replaceable The oil carryover rate shall be provided in the proposal The oil separator shall have a heater(s) that is capable of raising the oil temperature from minimum ambient temperature to minimum allowable starting temperature within 12 hours maximum. Any requirements for insulating the separator to meet this requirement shall be detailed on review drawings provided with the proposal The oil separator shall have a replaceable heater(s) If multiple compressors are used, each compressor shall have an individual discharge line into the separator The separator shall have a low-oil-level switch interlocked to turn the heater(s) off if oil level is low The oil separator shall have level gauges Oil Recovery Pots (Reciprocating or Rotary Compressor) Oil recovery systems shall be provided with the following features as a minimum: a. A direct level indicator Process Industry Practices Page 9 of 20

12 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October 2010 b. An oil still/receiver with a thermostatically controlled electric heater for flashing liquid refrigerant. Minimum liquid level shall be maintained above heating elements while energized c. A solenoid-operated feed valve to automatically charge oil to the recovery system if the heater is energized d. Oil recovery piping from recovery pot to the oil reservoir Recovery pots shall be in accordance with PIP VECV1001 and PIP VESV1002 or PIP VESSM001, as applicable Suction Knockout Drum A suction knockout drum shall be provided On direct expansion units, the system shall be provided with a suction trap to prevent liquid from entering the compressor. The trap shall be arranged for automatic draining On flooded or thermosyphon evaporator units, the evaporator shall be provided with an integral surge drum to provide for complete separation of liquid and gas Design details of the suction knockout drum shall be provided prior to fabrication. If applicable details shall include mesh pad sizing and boil-out coil Sizing criteria shall be provided with the proposal A high-liquid-level shutdown switch shall be provided, as a minimum A liquid-level indicator shall be provided Suction knockout drums shall be in accordance with PIP VECV1001 and PIP VESV1002 or PIP VESSM001, as applicable Economizer (If Provided) A description of the system, system efficiencies, and any additional costs associated with the economizer shall be provided with the proposal Design details shall be provided with the proposal If used for a screw compressor application, a pressure-regulating device shall be provided to prevent exceeding the vessel minimum design temperature during low-load operation A high-liquid-level shutdown switch shall be provided on the economizer A level indicator shall be provided on the economizer Economizers shall be in accordance with PIP VECV1001 and PIP VESV1002 or PIP VESSM001, as applicable. Page 10 of 20 Process Industry Practices

13 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems 3.7 Lubrication Oil System General A pressurized lubrication system(s) shall be provided that will supply oil to meet the requirements of the bearings, seals, and controls Unless otherwise specified on purchaser s data sheet, PIP RESR001-D, the system shall be in accordance with supplier s standard If a water-cooled oil cooler(s) is required, it shall be in accordance with PIP VESSM001 and TEMA C, and the materials of construction shall be as specified for the refrigerant. The oil cooler(s) shall be piped and in place within the packaged unit Provisions for monitoring the oil system shall be, as a minimum, in accordance with the Monitoring System Instrumentation Table in Appendix A When specified by the purchaser, the system refrigerant may be used as the cooling medium for the oil cooler Pumps Main and auxiliary oil pumps shall be positive displacement and shall be rated to sustain continuous operation of the compressor Main (if required and not shaft driven) and auxiliary lube oil pumps shall be provided with maintenance block valves and discharge check valves The proposal shall state whether a main oil pump shall be provided Auxiliary oil pump shall be electric motor driven. Requirements for the motor shall be specified on the purchaser s data sheet, PIP RESR001-D Pump casings shall be steel or ductile iron System low-oil-pressure switch shall start auxiliary oil pump and alarm on the local control panel Reservoir Oil reservoirs that are not pressurized shall be stainless steel If a pressurized carbon steel oil reservoir is specified, the reservoir shall be provided with the supplier s standard internal coating. Note: The oil reservoir may be part of the oil separator The reservoir shall have an oil heater and temperature control capable of increasing the oil temperature from minimum ambient temperature to minimum starting temperature within 12 hours maximum Lube oil heaters shall be thermostatically controlled, stainless steel, sheathed, and shall have a maximum watt density of 2.0 watts/cm 2 (13 watt/inch 2 ). Process Industry Practices Page 11 of 20

14 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October A reservoir shall have the following features: a. Oil-level indication device b. Low-point drain valve c. Temperature indicator d. A nonpressurized reservoir shall have an air eductor or motorized oil mist demister (Any requirements for the motor shall be specified on the data sheets.) e. Removable cover plate for inspection and cleanout Stand alone (non-oil separator) reservoir retention time shall be 10 minutes minimum Piping/Valves Piping vibration levels shall be limited to 12 mm/sec (0.5 inches/sec) Stainless steel tubing may be provided for lines up to 25 mm (1 inch) Lubrication oil system piping shall be welded and shall be in accordance with ASME B Slip-on flanges are permitted Piping and tubing downstream of the oil filter shall be stainless steel Carbon steel piping upstream of the filter is permitted Piping and tubing shall have a leak-free design that uses flanges and/or tubing fittings. 1. Use of threaded connections shall be minimized. 2. Piping, tubing, and flanges shall be proven leak-free in accordance with Section 3.20 of this Practice As a minimum, pressure relief valves shall be made of cast steel Oil pump discharge lines shall have check valves Each oil pump discharge line shall have a separate pressure relief valve Oil drain lines shall operate no more than half full Filters and Cooler The lubrication oil system shall have the following features: a. Dual oil filters (1) The filter arrangement shall include valves that allow element changeout while the refrigeration system is in operation. (2) Filter-housings shall include vents and drains. Page 12 of 20 Process Industry Practices

15 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems 3.8 Purge System b. Unless otherwise specified on data sheet RESR001-D, dual oil coolers shall be provided. c. A self-contained, thermostatically controlled oil temperature control valve that bypasses oil for temperature control Unless otherwise specified, materials of construction for filters and valve bodies shall be carbon steel Filters shall have a removal efficiency of 90% at 10-micron nominal and 15 micron absolute capability Lube oil cooler shall have the following features: a. A fixed tubesheet bundle with water in the tube side b. An average wall thickness of 1.2 mm (18 BWG) minimum c. Materials of construction as specified for the condenser. d. Fouling factor as specified for the condenser Filter housings and coolers shall be in accordance with PIP VESSM Systems shall have a high-efficiency automatic purge system The purge system shall continuously remove non-condensable gas from the refrigerant Refrigerant shall be returned to the system Non-condensables shall be provided with a connection for venting to purchaser s vent system The purge system shall be detailed, including a description of all associated instrumentation, controls, and valves in the proposal. 3.9 System Controls and Instrumentation General Controls and Instrumentation 3.10 Electrical PIP PCDPS001 Packaged Equipment Instrumentation Documentation Requirements Data Sheet and Instructions PIP PCSPS001 Packaged Equipment Instrumentation Specification PIP PCSPS010 Small, General Purpose Packaged Equipment Instrumentation Specification PIP PCERE001 Rotating Equipment Monitoring Guidelines General PIP ELSPS01 Electrical Requirements for Packaged Equipment Process Industry Practices Page 13 of 20

16 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October PIP ELSPS01D Data Sheet for Electrical Requirements for Packaged Equipment PIP ELSPS01V Electrical Requirements for Packaged Equipment - Preferred Vendor and Component List 3.11 Pipe, Valves, and Fittings Fluorocarbon-based refrigerant system piping and valves shall be in accordance with ASME B31.5 and ASHRAE Hydrocarbon and ammonia-based refrigerant systems shall be in accordance with ASME B Unless otherwise approved in writing by the purchaser, the use of copper pipe and tubing shall not be permitted Threaded connections in refrigerant service shall not be greater than DN 20 (NPS ¾) Vent and drain connections or valves shall be socket-weld by threaded and have plugs or blinds of the same material as the connection or valve Individual system components shall have isolation and vent valves to permit maintenance with minimum depressuring of the system and/or piping All valves shall have a stainless steel identification tag. The purchaser shall provide tag numbers All refrigerant isolation valves shall be back seat design with seal caps and socket-weld or flanged connections All fasteners in pressure/process containment applications shall be in accordance with DIN or ASTM/ANSI standards for chemical and physical properties. In accordance with ASTM/ANSI, the fasteners shall bear the manufacturer s symbol (stamp) and the applicable specification grade. Fasteners without these features shall not be permitted The allowable forces and moments for battery limit connections shall be provided by the supplier If flexible expansion joints are required to avoid excessive loads on the compressor, they must be approved by the purchaser Unless otherwise specified, interconnecting piping between skids shall be provided by purchaser If supplier is providing interconnecting piping, the piping shall be matchmarked and numbered for easy installation If piping and/or equipment shall be assembled and disassembled in supplier s shop, purchaser retains the right to inspect and approve shop fit-up Pressure-Relieving Devices Pressure-relieving devices shall be provided in accordance with ASME Code, ASHRAE 15, and as specified by purchaser. Page 14 of 20 Process Industry Practices

17 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems The sizing basis and inlet pressure-drop calculations shall be provided for purchaser s approval The inlet pressure drop to the relief valve shall be calculated and shall be in accordance with paragraph M-7 of ASME Code, (i.e., shall be less than 3%) For compressible fluid systems, the irreversible pressure losses in the relief valve inlet piping shall not exceed 3% of set pressure based on a flow rate equal to the relief valve ASME-rated capacity (nameplate capacity) Relief valve mounting locations and inlet and outlet piping requirements for refrigerants that are toxic or hazardous may require special design considerations to avoid liquid accumulation or undesirable discharges to the atmosphere. In such applications, the purchaser shall advise relief valve mounting locations, piping layout, pressure drop, and maximum back pressure for relief valves piped to a closed system Insulation Unless otherwise specified, insulation shall be provided by purchaser Space shall be provided for purchaser-supplied and -installed insulation system. Adequate spacing for valve actuation, equipment maintenance, and other component functionality shall be maintained Insulation and insulation thickness shall be indicated on the P&ID Structural Steel Base General A structural steel base shall be provided upon which all system equipment shall be mounted Equipment, piping, and conduit shall not extend below the top of the structural steel base beams. Piping and conduit shall not protrude beyond the outer perimeter of the base beams Equipment shall be arranged on the base for accessibility and ease of maintenance The common structural steel base shall be sufficiently rigid to prevent flexing or distortion of skid equipment during lifting, transportation and installation Skid shall conform to local environmental requirements Fabrication Structural steel shall be seal welded in accordance with AWS D Maintainability must be considered when attaching equipment supports to the skid. Note: Welding supports may cause difficulty when performing maintenance on the skid. Cutting the members may lead to corrosion issues Ends of tubular steel members shall be capped and seal welded. Process Industry Practices Page 15 of 20

18 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October Noise Installation Lifting Note: The purpose of seal welding is to minimize or prevent hidden corrosion which shortens the life of the base Skids shall be designed for mounting on a concrete foundation Anchor points and foundation requirements shall be specified Vertical jack bolts located next to anchor bolt holes shall be provided for positioning the structural baseplate(s) prior to grouting. Stainless steel shims shall be used for supporting the skid. The shims shall straddle the anchor bolts Machined mounting blocks for compressor and driver shall be provided Stainless steel shim packs shall be provided for aligning the compressors and main drives mounted on the structural steel skid. Shims shall be a minimum of 3 mm. (1/8 inch) and shall straddle bolt holes Axial and transverse alignment bolts shall be provided for driver System shall be provided with lifting lugs for a minimum four-point lift If required, spreader bars shall be provided Individual system components shall have eyebolts or lifting lugs to facilitate lifting Weights of individual components shall be provided A drawing that indicates system lifting points, center of gravity of each skid, and the weight at each point shall be provided by the supplier Ladders and Platforms Refer to PIP STF05501, Fixed Ladders and Cages The noise level at a distance of 1 meter (3 feet) from each skid shall be provided If the sound pressure level exceeds the level specified on the purchaser s data sheet, PIP RESR001-D, information indicating additional sound treatment required to obtain the conditions specified shall be included Compressor Vibration and Critical Speeds The supplier shall be responsible for performing necessary torsional studies and eliminating any lateral or torsional vibrations that can affect the operation of the system Operating speed(s) shall have at least a 20% separation margin from the torsional and lateral critical speeds or system resonances. Page 16 of 20 Process Industry Practices

19 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems Peak unfiltered velocity (with compressor installed on the supplier s baseplate and within the specified operating range) in any plane measured on the bearing housing relative to a radial bearing shall not exceed the following: 3.17 Painting a. For reciprocating compressors, 10 mm./sec. (0.4 inch per second) b. For screw compressors, 6 mm./sec. (0.25 inch per second) c. For centrifugal compressors and drive motors, 2.5 mm./sec. (0.1 inch per second) Unless otherwise specified, the painting shall be the supplier s standard. The proposed paint system shall be detailed in the proposal Paints and coatings shall be stored, mixed, catalyzed, thinned, and applied according to paint manufacturer s instructions Paint systems shall be shop-applied Components that are inaccessible after fabrication shall be primed and coated before installation with paint acceptable for service conditions for the component Surfaces that cannot be accessed for painting after assembly shall be prepared and primed before final assembly Top or final coat shall not be applied until all fabrication and assembly is complete and all surfaces are primed in areas to be coated Primer(s) shall be applied the same day as surface preparation and before oxidation Exposed alloy equipment shall not be painted. However, alloy equipment shall be painted before being insulated Inspection General Supplier and subsuppliers shall perform the inspections that are necessary to ensure conformance to the purchase order specification and referenced documents Additional inspections of the equipment by the purchaser s representative shall not relieve supplier or subsuppliers of responsibility for meeting purchase order requirements If specified on the purchaser s data sheet, PIP RESR001-D, a prefabrication meeting of the responsible purchaser and supplier personnel shall be arranged to review all purchase order requirements. Comment: Site and design personnel are encouraged to attend. Process Industry Practices Page 17 of 20

20 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October Quality Surveillance by Purchaser Quality surveillance shall be performed by purchaser s representative of items provided on this purchase order The intent of purchaser s quality surveillance shall be to monitor and audit supplier s quality control (QC) effort to assure compliance with purchase order specification and drawings so that quality requirements are attained and verifiable The purchaser s representative shall participate in and witness surveillance activities as deemed necessary. The following surveillance activities shall be conducted by purchaser as a minimum: a. Preliminary - Inspect shop before start of fabrication b. Intermediate - Witness hydrostatic/pneumatic tests of all pressure vessels c. Intermediate - Inspect motor at motor manufacturer s facility d. Intermediate - After blast cleaning but before painting, perform electrical check-out and witness functional test of all controls e. Final - Witness mechanical run (if specified) and leak test Comment: See Appendix B Purchaser s Quality Surveillance Checklist for activities that may be performed by the purchaser s representative The purchaser s representative shall contact supplier to schedule surveillance visits A complete set of approved drawings for use at the time of the surveillance activities shall be made available to the purchaser s representative The following documents/records shall be made available for review by the purchaser s representative: a. Vessel manufacturer s pressure vessel data reports b. Certified mill test reports c. Certification of hydrostatic/pneumatic testing, including pressures, time held, type and location of any leaks and methods of repair; microprocessor shop logs; and certification of compressor run test d. Compressor assembly records A safe work area and testing equipment shall be provided for purchaser s representative If major components or services are obtained from subsuppliers, purchaser surveillance and notification requirements shall be included in suborders. Page 18 of 20 Process Industry Practices

21 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems 3.19 Testing 1. Purchaser s representative shall be notified and given the option of inspecting items provided by subsuppliers at the point of manufacture. 2. The supplier shall arrange for approved drawings to be used by the purchaser s representative at the subsupplier s location Purchaser shall be notified a minimum of 10 working days before any testing, including testing of parts or assemblies in subsupplier s facilities, so that purchaser s representative may witness the system tests Purchaser reserves the right to conduct a field performance test with the participation of the supplier s representative. If this test is to be conducted, purchaser and supplier shall agree beforehand on the acceptance criteria Before assembly on system skid, pressure vessels and/or heat exchangers shall be pneumatic-tested or hydro-tested at fabrication facilities Water for hydro-testing shall have a maximum Chloride content of 50 PPM. Hydro-tested components shall be thoroughly drained Compressors shall be given manufacturer s standard pressure and running tests. Test procedure shall be provided to purchaser for review a minimum of 2 weeks before test Controls shall be functionally tested Lubrication System Tests Functional Test 1. The supplier s standard oil system functional test shall be described in the proposal. 2. The supplier s test shall be reviewed, modified and approved by the purchaser. 3. The functional test shall include the control panel and all electrical circuits Cleanliness Test 1. As a minimum, after the lubrication oil system is clean, it shall be given a cleanliness test consisting of circulating the lubrication oil for a minimum of 1 hour through test screens or filters. 2. Compressor and bearings shall be bypassed during oil system run test. 3. There shall be no surface evidence (either visible or tactile) of scale, rust, metal shavings, or sand in the lubrication oil filters. 4. The supplier s standard oil system cleanliness test shall be described in the proposal A continuity test shall be performed on all electrical circuits before final inspection. Process Industry Practices Page 19 of 20

22 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October All shutdown and safety devices, except relief valves and rupture disks, shall be functionally tested by simulating the conditions required for actuation Vacuum Test Assembled refrigeration system shall be evacuated to 20-mm Hg absolute for a minimum of 2 hours System shall then be sealed with the vacuum pump off, and vacuum shall hold for a minimum of 6 hours with less than 2-mm Hg rise If refrigeration system fails to hold vacuum, leaks shall be identified and repaired and the vacuum test shall be repeated Upon successful completion of the vacuum test, vacuum shall be broken with dry nitrogen, and system shall be pressurized to 1 bar (15 psi) for shipment If system consists of more than one skid, each skid shall hold vacuum on the refrigerant side in accordance with Section Preparation for Shipment Refrigeration packages shall be completely assembled at the factory before shipment Items to be disassembled for shipment shall be detailed in the proposal System shall be pressurized to 1 barg (15 psig) with dry Nitrogen for shipment Pressure gauges shall be provided to monitor pressure during shipment and placement of unit All instrument panel openings shall be plugged for shipment to prevent water or dirt from entering during shipment and storage before installation The purchaser s representative shall have the right to perform a final inspection before shipment Final release by the purchaser s representative shall be obtained before shipment of material or equipment Documentation Documentation shall be provided in accordance with purchaser s documentation requirements sheet, PIP RESR001-R, and this Practice. Page 20 of 20 Process Industry Practices

23 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems Appendix A Monitoring System Instrumentation Table Evaporator Unit System Instrumentation Alarm Shutdown Process Inlet Temperature Local Panel Process Outlet Temperature 1 High/Low Process Inlet Pressure 2 Process Outlet Pressure 2 Level Indication Condenser Cooling Water Outlet Temperature 2 High High Cooling Water Outlet Pressure 2 Cooling Water Inlet Temperature 2 Cooling Water Inlet Pressure 2 Low Low Refrigerant Outlet Pressure Refrigerant System Receiver Liquid Level Dryer Moisture Content Compressor Suction Pressure Low Low Discharge Pressure Low Suction Temperature Low Low Discharge Temperature High High Vibration High Bearing Temperature High High Oil System Reservoir Level Low Reservoir Temperature Pump Discharge Temperature Low Low Return Oil Temperature High High Cooling Water Return High Filter Differential Pressure High Low-Pressure Switch Low Low Oil Separator Level Indication Receiver Level Indication Motor (if appl.) Bearing Temperature High Vibration Probes High Gear Box (if appl.) Winding Temperature NOTES: 1) Low-process-outlet-temperature alarm and shutdown may be required to prevent freeze damage. 2) By Purchaser. Process Industry Practices Page A-1

24 This page is intentionally blank.

25 EDITORIAL REVISION October 2010 PIP RESR001 Packaged, Skid-Mounted Process Industrial Refrigeration Systems Appendix B Purchaser s Quality Surveillance Checklist B.1 In-Process B.1.1 B.1.2 B.1.3 B.1.4 B.1.5 B.1.6 B.1.7 B.1.8 B.1.9 Witness hydrostatic/pneumatic test of all pressure vessels. Verify material and thickness of tubesheets. Witness/verify tube expansion procedures on all heat exchangers. Review the following documents: a. Mill test reports b. Certificates of compliance c. ASME Code data reports d. Microprocessor shop logs e. Pressure test results for vessels f. Compressor assembly records g. Certification of compressor run test Visually inspect all welding before painting, including baseplate, piping, vessels, and peripherals. Spot-check piping internal diameter, where possible, for burn through, excessive protrusion, or unremoved slag. Review dimensional records for the package. If determined to be necessary, perform a check of critical dimensions, including location and elevation of field connections, runout, and alignment with compressor and drive motor. Check for satisfactory results of blast cleaning in accordance with supplier s standard procedure. B.1.10 Ensure proper application of all pipe dope and/or joint compound on all threaded connections and conduit before paint application. B.1.11 Verify that all thermocouples, probes, and other instrument appurtenances are adequately taped and protected from spray painting. B.1.12 Verify that small gages and panel devices are removed before painting if they cannot be adequately protected from paint. B.1.13 Check all bolting for proper identification and markings in accordance with Section Request and verify replacement of any fasteners not in accordance with Section B.1.14 Witness compressor mechanical run test and leak testing of the complete system before painting. Process Industry Practices Page B-1

26 PIP RESR001 EDITORIAL REVISION Packaged, Skid-Mounted Process Industrial Refrigeration Systems October 2010 B.2 Electrical Check-out B.2.1 Verify the following local panel requirements: a. Meet electrical area classification b. Material c. Type d. Configuration e. Dimensions f. Welds g. Cutting h. Bolting i. Shaping j. Type of cable entry k. Exit door pad-locking and hinge l. Access openings for field use m. Lifting means n. Workmanship o. Painting B.2.2 Verify type and arrangement of the following components: a. Pushbuttons b. Selector switches c. Pilot lights d. Terminal blocks e. Raceways f. Color-coding. B.2.3 Verify the following instrument requirements: a. Model number b. Chart or dial range c. Calibration d. Specified identification tag B.2.4 Verify the following alarm system requirements: a. Alarm operation sequence b. Alarm acknowledge c. Test d. Reset Page B-2 Process Industry Practices

PIP ELIMTD00 Motor Installation Details for Class I, Division 1 Areas (Motors 600 Volts and Below, 60 hp Maximum)

PIP ELIMTD00 Motor Installation Details for Class I, Division 1 Areas (Motors 600 Volts and Below, 60 hp Maximum) COMPLETE REVISION September 2014 Process Industry Practices Electrical PIP ELIMTD00 Motor Installation Details for Class I, Division 1 Areas (Motors 600 Volts and Below, 60 hp Maximum) PURPOSE AND USE

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

PIP PCTPA001 Testing of Process Analyzer Systems

PIP PCTPA001 Testing of Process Analyzer Systems January 2016 Process Control PIP PCTPA001 Testing of Process Analyzer Systems PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice

More information

PIP PNE00004 Steam Trap Guidelines

PIP PNE00004 Steam Trap Guidelines July 2016 Piping PIP PNE00004 Steam Trap Guidelines PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from

More information

SECTION CHILLERS

SECTION CHILLERS SECTION 15650 PART I - GENERAL 1.01 WORK INCLUDED A. Extent of work shall be as indicated on Drawings and provisions of this section, including schedules and equipment lists associated with either Drawings

More information

SECTION AIR COMPRESSORS AND ACCESSORIES

SECTION AIR COMPRESSORS AND ACCESSORIES PART 1 GENERAL 1.01 WORK INCLUDED SECTION 11370 AIR COMPRESSORS AND ACCESSORIES A. This specification includes air compressors with air dryers. B. Furnish, install, start-up, and test air compressors and

More information

SECTION AIR COMPRESSORS AND ACCESSORIES

SECTION AIR COMPRESSORS AND ACCESSORIES PART 1 GENERAL 1.01 WORK INCLUDED SECTION 11370 AIR COMPRESSORS AND ACCESSORIES A. This specification includes air compressors with air dryers. B. Furnish, install, start-up, and test air compressors and

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Process Control PIP PCEA001 Fixed Gas Detection Guidelines

Process Control PIP PCEA001 Fixed Gas Detection Guidelines November 2015 Process Control PIP PCEA001 PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical

More information

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification Electrical Engineering Guide for Determining Electrical Area Classification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-42 22 16.00 40 (August 2017) --------------------------------- Preparing Activity: NASA Superseding UFGS-42 22 16.00 40 (August 2014) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. Design and specify refrigeration systems and equipment in accordance with "Energy Conservation Standards" stipulated in Section 15010, Basic

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES Page 226119-1 SECTION 226119 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This section outlines the requirements for the nitrogen-generating sprinkler corrosion inhibiting system. The work

More information

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 236426.11 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B.

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15684 ROTARY SCREW WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 An optional

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

Liebert CSU3000 Chiller

Liebert CSU3000 Chiller CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,

More information

REFRIGERANT PIPING SYSTEM

REFRIGERANT PIPING SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The requirements of this section apply to the refrigerant piping system connecting refrigeration and HVAC equipment specified in other sections of these specifications.

More information

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers. SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

(2) 325 tpd York Chlorine Liquefier Systems

(2) 325 tpd York Chlorine Liquefier Systems (2) 325 tpd York Chlorine Liquefier Systems The liquefier is a split bundle and serves as both the primary liquefier and the secondary liquefier. The total for each York system is 325 tons liquid Cl2,

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days Proposal Trane A Division of American Standard Inc. Prepared For: John Weston Desmet Ballestra Job Name: LAUER1 Biodiesel Chiller Pennsylvania Date: August 21, 2006 Proposal Number: G1-95502-1 Engineer:

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

JCseries EVAPORATIVE CONDENSER. engineering data

JCseries EVAPORATIVE CONDENSER. engineering data JCseries EVAPORATIVE CONDENSER engineering data Recold JC Series Evaporative Condenser Contents 2 Construction... 3 Schematic... 4 Engineering Data... 5 Selection Procedure... 6-9 Multi-Circuited Selection

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 WATER-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SECTION INCLUDES A. Water heaters. B. Packaged water heating systems. C. Domestic water heat exchangers. D. Water storage tanks. E. Water softeners. F. Reverse osmosis equipment. G.

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

SECTION CENTRIFUGAL WATER CHILLERS

SECTION CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Chiller package. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Condenser water connections. F. Variable

More information

IIAR Minimum Safety Criteria for a Safe Ammonia Refrigeration System

IIAR Minimum Safety Criteria for a Safe Ammonia Refrigeration System Bulletin No. 109 10/97 Guidelines for: IIAR Minimum Safety Criteria for a Safe Ammonia Refrigeration System International Institute of Ammonia Refrigeration NOTICE The information contained in these guidelines

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

SECTION HEATING BOILER FEEDWATER EQUIPMENT

SECTION HEATING BOILER FEEDWATER EQUIPMENT SECTION 23 53 00 HEATING BOILER FEEDWATER EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes boiler feedwater pumps, de-aerators, accessories, controls and tanks. 1.2 REFERENCES A. ASME (American

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS SECTION 23 22 23 STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable in the

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information

SECTION DOMESTIC WATER HEATERS

SECTION DOMESTIC WATER HEATERS SECTION 223500 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS SECTION 22 36 01 ELECTRIC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

DESIGN STANDARDS SECTION 15600

DESIGN STANDARDS SECTION 15600 PART 1 - GENERAL 1.1 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.2 General requirements: A. Reciprocating

More information

SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller:

SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller: SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC). 3. 15711 - Induced Draft Cooling Tower. B.

More information

Guide Specifications

Guide Specifications Guide Specifications Hot Water fired Adsorption Liquid Chillers Bry-Air Adsorption Chiller Overview The chiller shall be a Bry-Air ADC series. The chiller shall consist of a robust, compact, packaged chiller

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION COOLING TOWERS

SECTION COOLING TOWERS SECTION 23 65 00 COOLING TOWERS PART 1 - GENERAL 1.1 DESCRIPTION A. Packaged, induced draft open circuit cooling tower complete with fill, fan, inlet louvers and associated accessories and equipment. 1.2

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM SECTION 23 81 06 - PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. This Section includes equipment types that contain all the components of the refrigeration process within

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

ISO INTERNATIONAL STANDARD. Petroleum, petrochemical and natural gas industries Rotary-type positivedisplacement. Part 1: Process compressors

ISO INTERNATIONAL STANDARD. Petroleum, petrochemical and natural gas industries Rotary-type positivedisplacement. Part 1: Process compressors INTERNATIONAL STANDARD ISO 10440-1 Second edition 2007-08-01 Petroleum, petrochemical and natural gas industries Rotary-type positivedisplacement compressors Part 1: Process compressors Industries du pétrole,

More information

Landfill & Digester Gas Dryers. Features and Benefits

Landfill & Digester Gas Dryers. Features and Benefits Landfill & Digester Gas Dryers Landfill gas is generated by the anaerobic decomposition of organic matter deposited in landfills. Digester gas is produced as a by-product of the digestion of sewage sludge.

More information

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories. SECTION 15650 REFRIGERATION EQUIPMENT PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories. B. Related Section: 1. 11400

More information

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 10438-1 Second edition 2007-12-15 Petroleum, petrochemical and natural gas industries Lubrication, shaft-sealing and control-oil systems and auxiliaries Part 1: General requirements

More information

Ammonia Refrigeration RAGAGEP

Ammonia Refrigeration RAGAGEP Ammonia Refrigeration RAGAGEP Recognized and Generally Accepted Good Engineering Practice Peter Thomas, P.E., CSP Resource Compliance, Inc. Introduction Where does the term RAGAGEP come from? CalARP RAGAGEP

More information

Refrigeration Technology in Building Services Engineering

Refrigeration Technology in Building Services Engineering Unit 70: Unit code: T/600/0459 QCF Level: 3 Credit value: 10 Guided learning hours: 60 Unit aim Refrigeration Technology in Building Services Engineering This unit develops an understanding of the principles,

More information

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers Bulletin 1200/4 (Revised 5/12) Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers INNOVATORS IN HEAT TRANSFER I. INSTALLATION OF HEAT EXCHANGERS A. HEAT EXCHANGER SETTINGS 1)

More information

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016 SECTION 23 21 23 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section.

More information

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES SECTION 23 23 00 REFRIGERANT PIPING AND SPECIALITIES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Refrigerant piping. 2. Unions, flanges, and couplings. 3. Pipe hangers and supports. 4. Refrigerant

More information

CPF PRODUCT DESCRIPTION

CPF PRODUCT DESCRIPTION CPF 175 340 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPF 175-340 compressor is a quiet, complete and ready-for-use unit for the production of compressed air in industrial applications. OVERVIEW The CHICAGO

More information

TM Series. Induced Draft, Counter Flow Optional Accessories

TM Series. Induced Draft, Counter Flow Optional Accessories ANTIFREEZE PACKAGE / RESISTANCE HEATING OPTION The antifreeze package is supplied to provide protection against freezing of standing water in the cooling tower sump due to shutdown during winter operation.

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

Module 7: Air Supply System

Module 7: Air Supply System Terms and Definitions Components of the Air Supply System Basic Functions of the Air Supply System Parts of a Compressor Characteristics of Compressors Loading and Unloading Process Characteristics of

More information

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units. SECTION 15650 REFRIGERATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units. 4. Air

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

THE FOLLOWING CHANGES/ADDITIONS TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED:

THE FOLLOWING CHANGES/ADDITIONS TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED: Business Services Procurement and Contracting 16550 SW Merlo Road Beaverton, OR 97003 (503) 356-4324 February 20, 2018 SOLICITATION ADDENDUM NO. 2 ITB 18-0003 Kinnaman-Hiteon Chiller Replacement THE FOLLOWING

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL Section 23 20 00 FLUID SYSTEMS EQUIPMENT PART 1 GENERAL 1. CHILLERS Page 23 20 00-1 A. Provide chiller packages with centrifugal compressors, or screw compressors, and water cooled condensers. B. Design

More information

HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL

HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL H-Series & 203 THRU 223 SERIES ARROW PNEUMATICS, INC. REGENERATIVE DRYER DIVISION 2111 WEST 21ST STREET BROADVIEW, IL 60155 708-343-9595 708-343-1907

More information

1. Know your process. The following guidelines will help you navigate what can be a challenging and time consuming task.

1. Know your process. The following guidelines will help you navigate what can be a challenging and time consuming task. Many processes today require an indirect method of heating, which implies the use of a heat transfer medium, instead of circulating the process directly into a heater. Thermal oil, water, glycol mixtures,

More information

4 route 147, C.P.33 Coaticook, Qc J1A 2S8

4 route 147, C.P.33 Coaticook, Qc J1A 2S8 4 route 147, C.P.33 Coaticook, Qc J1A 2S8 TABLE OF CONTENTS INSTALLATION Nozzles p.3 Clearance for dismantling p.4 Foundations p.4 Foundation bolts p.5 Leveling p.5 Bolted joints p.5 Recommended bolt tightening

More information

Page 1 of Relevant Provincial Jurisdictional legislation.

Page 1 of Relevant Provincial Jurisdictional legislation. Page 1 of 15 1. Act, Regulations and Codes (6.7%): To locate information relating to the staffing, operation, maintenance, inspection, and testing of the refrigeration plant and its equipment using reference

More information

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00 I&M NUMBER: 316-42-5-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Watlow heaters are built to comply with UL and CSA dielectric requirements, it may be

More information

SECTION COOLING TOWERS

SECTION COOLING TOWERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 65 00 COOLING TOWERS SPEC WRITER NOTES: 1. DELETE BETWEEN //---// if not applicable to project. Also delete any other item or paragraph not applicable in the

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

Goulds 3600 Between-Bearing, Axially-Split, Multi-Stage Pumps. Goulds Pumps

Goulds 3600 Between-Bearing, Axially-Split, Multi-Stage Pumps. Goulds Pumps Between-Bearing, Axially-Split, Multi-Stage Pumps Goulds Pumps A Leader in API Engineered Pump Package Solutions Proven API Leadership ITT Goulds Pumps is a proven leader in API Pumps Over 18,000 units

More information

ENGINEERING SPECIFICATION ASU TYPE NITROGEN GENERATION UNIT FOR DIESEL HYDROTREATER UNIT FOR HINDUSTAN PETROLEUM CORPORATION LTD.

ENGINEERING SPECIFICATION ASU TYPE NITROGEN GENERATION UNIT FOR DIESEL HYDROTREATER UNIT FOR HINDUSTAN PETROLEUM CORPORATION LTD. ENGINEERING SPECIFICATION FOR DIESEL HYDROTREATER UNIT FOR HINDUSTAN PETROLEUM CORPORATION LTD. VISAKH REFINERY DHT PROJECT TEIL JOB NO. : 6261 DOCUMENT NO: 6261- A - 95-48 -051 A 16-March-09 For Client

More information

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

CPVS PRODUCT DESCRIPTION

CPVS PRODUCT DESCRIPTION CPVS 20 30 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPVS 20-30 compressor is a quiet, complete and ready-for-use unit for the production of compressed air for light and medium industrial applications.

More information

PROJ. NO SECTION REFRIGERANT PIPING

PROJ. NO SECTION REFRIGERANT PIPING SECTION 23 23 00 REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information