SPECIFICATIONS MODEL EHV X VACUUM OIL PURIFIER
|
|
- Cody Lester
- 5 years ago
- Views:
Transcription
1 SPECIFICATIONS MODEL EHV X VACUUM OIL PURIFIER
2 1 DEGASSING TECHNOLOGY This proposal describes the equipment which shall be supplied by ENERVAC for a system for processing (degassification, dehydration and filtration) transformer insulating fluids. Removing dissolved vapor and gas from a liquid is a physical process. Vapor or gas molecules randomly leave the surface of a liquid into surrounding gas, and also randomly leave the gas and enter the liquid. When the rate of molecules entering the liquid is equal to the rate of molecules leaving an equilibrium is achieved which is called saturation. Henry's Law states that the mass of gas dissolved in a given volume of solvent is proportional to the pressure of the gas with which it is in equilibrium. In a vacuum oil purifier the pressure of the gas is reduced by a vacuum pump and the oil is treated so that equilibrium can be achieved quickly. One approach is to extend the surface between liquid and gas and another is to encourage the formation of bubbles below the surface of the gas. Several approaches can be taken to the removal of dissolved vapors and gases from liquids as shown below. TRAYS extend the surface of the liquid, but no means of encouraging the bubbles to form are included. Trays require a high processing temperature which results in light ends being permanently removed from the oil. RINGS extend the surface of the liquid but no means of encouraging the bubbles to form are included. Rings require a high processing temperature which results in light ends being permanently removed from the oil. GLASS FIBER DEGASSING ELEMENTS both extend the oil surface and present millions of sharp ends to the flow of oil and each creates a "point of release" which encourages the formation of a bubble. This is similar to the stream of bubbles which can often be seen in a glass of Coca Cola or beer, the point from which the bubbles come is a scratch causing a "point of release". ENERVAC degassing accelerator elements are constructed in a way to maximize the "point of release" density. The elements not only stimulate the formation of small bubbles they also help large bubbles to collapse, tests prove that there is much less tendency to foam than with other degassing methods. Using this technique, ENERVAC Vacuum Oil Purifiers provide effective degassing at higher pressures and lower temperatures than other methods. The lower processing temperature assures that light ends, which preserve low viscosity for good cooling properties, are retained in the oil to perform exactly as the oil manufacturer intended. 2
3 2 SCOPE The scope of supply of this specification shall include the design, fabrication and factory testing of one (1) ENERVAC Model Number EHV X Vacuum Oil Purifier, as shown schematically in Bulletin , and shall consist of the equipment and components as subsequently described. The system, when received by the purchaser, shall provide a fully workable unit and shall perform in accordance with this specification. ENERVAC shall supply all necessary physical arrangements, mechanical, electrical connection, piping schematic and all necessary data for use in the operation and maintenance of this system. Prior to delivery of this system, ENERVAC shall provide three (3) copies of the instruction manual. One (1) complete copy of the manual shall be included with the shipment. This manual shall contain: Detailed Operating Instructions Maintenance Information Equipment drawings including Physical Arrangement, Electrical Diagram and Flow Diagram A Recommended Spare Parts List 3 PERFORMANCE Clean oil containing 100 PPM total water content and fully saturated with air at 12% by volume shall be dehydrated and degassified at the full rated capacity of the system, at a minimum oil supply temperature of 2 o C and shall meet the following specifications. Dielectric strength by ASTM Method D-877 shall not be less than 40 KV with new oil. Total soluble water content by ASTM Method D or D (Karl Fisher) shall be less than 10 PPM. Total gas content shall not be greater than 0.25% by ASTM Method D or by Doble Gas Content Analyzer ASTM D CAPACITY The maximum continuous purification capacity shall be 6,000 litres/hour. The ultimate pressure of the vacuum pump shall be less than 0.08 mbar. Capacity of the vacuum system shall be 300 m 3 /hr (50Hz). The system shall be capable of processing at reduced flow if required. 5 POWER REQUIREMENTS 380 Volts, 3 Phase, 50 Hertz - (110 kw Max.) 3
4 6 DIMENSIONS AND WEIGHT The purifying system shall be approximately 1,778 mm Wide x 3,048 mm Long x 1,980 mm High and shall weigh approximately 3,100 kgs. 7 DESCRIPTION OF COMPONENTS The purification system shall be fully assembled on a heavy duty steel base, which shall be sufficiently braced to minimize vibration. A drip lip shall be provided on the base to collect spillage and drippage. The system shall consist of the following components. 7.1 One (1) Oil Inlet Ball Valve 1-1/2 inch NPT. 7.2 One (1) Strainer, complete with a 30 mesh basket. 7.3 One (1) Inlet Flow Sight Indicator. 7.4 One (1) Positive Displacement, Inlet Pump, with mechanical seal. The pump shall be rated at 10% approximate higher flow than discharge pump. It shall be direct driven by a 1.5 kw, 1800 RPM TEFC electric motor. 7.5 One (1) Inlet Pump Relief Valve. 7.6 One (1) 96 kw Electric Inlet Oil Heater. The heater shall contain six, 16 kw heater elements, which shall have a watt density not greater than 1.7 W/cm 2. The heater shall be capable of increasing the oil temperature 30 o C in a single pass. The heater elements shall be controlled in two banks by contactors. Fuses shall be used for over current protection of each bank of heater elements One (1) Flow Switch, which shall be interlocked with the heater and shall require flow prior to energizing heaters One (1) Indicating Temperature Controller, which shall be used to control the electric heating elements to maintain the desired oil temperature. The controller shall be panel mounted. The temperature controllers, on deviation from the set point, activates the heater contactors through a series of time delay relays, which energize the required number of heating elements, raising the oil temperature to the set point. The digital controller set point is adjustable by a single adjusting button, thereby changing the set point on all elements simultaneously. The heater controller is designed to drop out the heating load on loss of power or oil flow. On resumption of power or flow, the controller resumes function and begins to energize banks of heating elements as required through the time delay relays. 4
5 The heater element banks are energized individually at timed intervals to prevent an overload on the power supply to the system. 7.8 One (1) Degassification Chamber. The illuminated chamber shall have a viewing port and a hinged service door. 7.9 One (1) Float Actuated Level Control Valve. The valve is actuated by a float mechanism in the degassification chamber to maintain the desired oil level. The level control valve is fully modulating and will maintain an inlet flow equal to the capacity of the discharge pump One Vacuum Gauge, 0-50 Torr range, to indicate the vacuum in the processing chamber One (1) Pressure Gauge, which is used to monitor pressure drop across the degassification accelerator elements, thus showing the need to replace the elements One (1) Foam Detector, which shall be activated on the appearance of excessive foam One (1) Solenoid Operated Valve to break vacuum on appearance of foam. The valve shall be operated by the Foam Detector. The inlet pump shall be stopped on appearance of, or persistent foaming condition One (1) Degassification Header, which shall contain chemically inert accelerator degassing elements One (1) High Level Detector. This level switch shall stop the inlet pump to prevent flooding and is a back-up for the flow control valve Float Actuated Level Control Valve One (1) Low Level Switch shall be interlocked with the discharge pump to prevent it from operating unless sufficient oil head is present One (1) Positive Displacement Discharge Pump with double mechanical seals. The pump shall have a rating of 6,000 litres/hour and shall be belt driven by a 1.1 kw, 1200 RPM, TEFC electric motor One (1) Discharge Pump Relief Valve Two (2) Sampling Cocks shall be provided, one for the incoming oil and one for processed oil, as shown on the Flow Diagram One (1) Outlet Flow Sight Indicator 7.22 One (1) Discharge Ball Valve 1-1/2 inch NPT One (1) Manual Recirculation Ball Valves One (1) System Relief Valve One (1) Enervac Model E858B-1-EP-718-1/2A2 Oil Filter to be installed after the outlet pump. The Afterfilter is furnished with replaceable pleated paper elements with a micron selectivity of 0.5 microns and a filtration efficiency of 98%. Standard filter units are of steel construction and complete with manual drain valve and pressure gauges to monitor differential pressure. 5
6 7.27 Free displacement of vacuum package 300 m 3 /hr (50Hz). Ultimate vacuum level: 0.08 mbar All necessary pressure gauges and valves as shown on the Flow Diagram shall be provided to complete system. Suitable flexible connections shall also be provided in the piping to minimize vibration A NEMA 12 Control Cabinet shall be provided, which shall contain all necessary control items required for the system. All motors shall be provided with magnetic starters for full voltage, across-the-line starting. Each motor shall have sufficient overload protection. Fuses shall be provided with each motor starter The following instruments shall be mounted on the control box: Temperature Controller All other gauges shall be locally mounted The following conditions shall have audible and visual alarms: High Foam/High Level Low Oil Level 7.33 Electrical System 7.34 Piping All components shall be suitable for 380 Volt, 3 Phase, 50 Hertz power supply. One (1) dry-type 500 VA transformer shall be supplied for control circuits. All piping shall be carbon steel, sized for the designed flow, braced and supported to prevent vibration. Piping will be welded construction when possible, to minimize leaks. Special vacuum tight welded 'O' ring unions and pipe flanges shall be provided to allow removal of components for maintenance, when necessary. 8 OPTIONAL VOLTAGE - (INCLUDED) Option 38 is included, 380 Volt, 3 Phase, 50 Hertz power supply. 9 PRE-FILTER OPTION OPTION P - (SEE QUOTATION) The Pre-filter is furnished with replaceable pleated paper elements with a micron selectivity of 5 microns and a filtration efficiency of 98%. Standard filter units are of steel construction and complete with manual drain valve and pressure gauges to monitor differential pressure. 10 FLOW METER OPTION OPTION M - (SEE QUOTATION) One (1) electronic in-line flow totaliser to provide a dependable and accurate totaling. The meter is furnished with digital menu display, for multi-choice flow units (lpm, Usgpm, IMPgpm), resettable main totaliser and daily totaliser. This display is registered in a choice of litres in 7 digits, and US Gallons, Imperial Gallons or cubic meters, all in 6 digits. 6
7 11 VACUUM BOOSTER OPTION VB - (NOT INCLUDED) One (1) Roots type vacuum blower, Kinney model KMBD-1600 or equivalent to improve the vacuum pump down time when vacuuming a transformer. The vacuum booster will have a free air displacement of 2,700 m 3 /hr. 12 HYGROMETER OPTION H - (SEE QUOTATION) One (1) Doble Domino Hygrometer can be supplied, digital readout for monitoring water content in the transformer oil, complete with probe, cable, sampling cell. Probe locations are as follows: H1 H2 Discharge or Inlet of Vacuum Oil Purifier Discharge or Inlet to Vacuum Oil Purifier in addition to H1 above. 13 ELECTRONIC VACUUM CONTROLLER OPTION - OPTION C1 - (NOT INCLUDED) C1 C2 C3 Electronic Vacuum Controller with one probe Electronic Vacuum Controller with two probes Electronic Vacuum Controller with three probes 14 CASTERS OPTION W - (NOT INCLUDED) Unit can be mounted on casters for in-plant mobility. Wheels would be 6" diameter polyolefin, 2 swivel, 2 stationary. 15 CIRCUIT BREAKERS OPTION B - (NOT INCLUDED) Circuit breakers can replace fuses for over current protection. 16 VITON GASKETS - OPTION V - (NOT INCLUDED) Viton gaskets and seals can be incorporated in the vacuum oil purifier replacing Buna-N material. 17 SPECIAL OPTIONS - OPTION X - (INCLUDED) Vacuum Oil Purifier will be mounted in a tag-a-long aluminum enclosed trailer with double open rear doors, side access doors, interior fluorescent lights, convenience receptacles, pintle hook type hitch. 7
SPECIFICATIONS MODEL E859C MINI DEHYDRATOR
SPECIFICATIONS MODEL E859C MINI DEHYDRATOR 1 DEHYDRATION TECHNOLOGY This proposal describes the equipment which shall be supplied by ENERVAC for a system for processing (dehydrating, de-aerating, purifying
More informationMobile Transformer Oil Purification Plant
Mobile Transformer Oil Purification Plant Mobile Transformer Oil Purification Plant 1. GENERAL The necessity for regular purification of electrical insulating fluids in electrical apparatus has been recognized
More informationTel: Fax: Website:
Vacuum Dehydration Oil Purification System(Oil Purifier) The water and particles contamination in lubrication, hydraulic and dielectric oils badly affect the oils performance and threaten system reliability.
More informationACORE Filtration Co.,Ltd provides engineering,
Oil Filtration Systems For Every Demanding Application VLF Lube Oil Purifier ACORE Filtration Co.,Ltd provides engineering, manufacturing, sales of industrial oil filtration systems, we have been striving
More informationVAC-U-DRY VACUUM DEHYDRATOR
VAC-U-DRY VACUUM DEHYDRATOR Remove Free & Dissolved Water down to 20 PPM (0.002%) Flow range 5~60 gpm,19~225 lpm Visually Monitor Fluid and Process through Clear Chamber Covers High Operating Vacuum and
More informationOIL TREATMENT ARRAS MAXEI
I BETH4GB_A page 1/5 TECHNICAL DESCRIPTION OF THE STANDARD PLANTS PREAMBLE SUMMARY: Principle of operation Main characteristics Components of the plant Description of the plant 3 Operating diagram 4 Optional
More informationOIL TREATMENT ARRAS MAXEI
I BETH8GB_A page 1/5 TECHNICAL DESCRIPTION OF THE STANDARD PLANTS PREAMBLE SUMMARY: Principle of operation Main characteristics Components of the plant Description of the plant 3 Operating diagram 4 Optional
More informationDirect Fired Heater Model AD Specification
Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI
More informationSECTION STEAM CONDENSATE PUMPS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationCONTENTS AUTOMATIC TRANSFER SWITCHES
CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training
More informationLaboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls
Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Scroll Enclosed Air Compressor System is designed to provide clean, dry air for
More informationLABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS
SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards
Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product
More informationVAC-U-DRY VACUUM DEHYDRATION SKIDS
VAC-U-DRY VAC-U-DRY VACUUM DEHYDRATION SKIDS Remove Free & Dissolved Water down to 20 PPM (0.002%) Remove Free & Dissolved gasses Standard Flow range 5~60 gpm,19~225 lpm (larger units available) Visually
More informationInternal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.
A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall
More informationVUD. Vac-U-Dry Vacuum Dehydrators. hyprofiltration.com/vud
VUD Vac-U-Dry Vacuum Dehydrators The optimized balance between heat, vacuum, process design and an easy, user friendly operating system for removal of water and particulate from hydraulic and high viscosity
More informationParagon. Induced Draft, Counter Flow Optional Accessories
ANTIFREEZE PACKAGE / RESISTANCE HEATING OPTION The antifreeze package is supplied to provide protection against freezing of standing water in the cooling tower sump due to shutdown during winter operation.
More informationTM Series. Induced Draft, Counter Flow Optional Accessories
ANTIFREEZE PACKAGE / RESISTANCE HEATING OPTION The antifreeze package is supplied to provide protection against freezing of standing water in the cooling tower sump due to shutdown during winter operation.
More informationEnclosed Scroll Air Compressor System SES 3-5 HP
Enclosed Scroll Air Compressor SES 3-5 HP Specification General The Powerex Enclosed Scroll Air Compressor unit is designed to provide clean, dry air for industrial applications where the quality of the
More informationHR Heated HB Blower. Smart Solutions for Drying Compressed Air. Dual Tower Heat Reactivated Desiccant Air Dryer
Smart Solutions for Drying Compressed Air Dual Tower Heat Reactivated Desiccant Air Dryer HR Heated HB Blower 800.943.794 www.engineeredairproducts.com Engineered Air Products Moisture in compressed air
More informationSECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.
SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.
More information重庆阳江机械制造有限公司. Electricity factory Transformer station Oil connection stations Transformer repair shop
重庆阳江机械制造有限公司 Chongqing Yangjiang Machine Manufacturing Co., LTD NO 75,Tianma Road, Shapingba district, Chongqing, China Tel:0086-23- 65770714cell:0086-18602394469 E-mail:cnoilrecycling@gmail.com ZLA Two-Stage
More informationDTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5
Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3
More informationYOUR PROCESS DEMANDS THE MOST DEPENDABLE TEMPERATURE CONTROL UNIT AVAILABLE.
Temperature Control Units Water & Oil 0-00 F Portable Chillers 0 - F Central Chillers Packages & Modules 0 - F Pump Tank Stations Chilled or Tower Water 00-0 gallons Cooling Tower Cells 4-40 tons Filters
More informationMission Critical. Fuel Supply Systems
Fuel Supply Systems Insight Onsite Fuel Supply Systems Page 2 Simplex Mission Critical Fuel Supply Systems are comprehensive, integrated, project-matched fuel management systems for diesel and turbine
More informationDual Tower Heat Reactivated Desiccant Air Dryer
Dual Tower Heat Reactivated Desiccant Air Dryer idhpe Dryer idbpe Dryer Eliminate Water from Your Compressed Air System Moisture in compressed air is damaging. Without proper treatment, this vital energy
More informationA. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.
Section 15 _ Energy Recovery Air Handling System Part 1: GENERAL 1.1 Section Includes: A. Energy Recovery Air Handler B. Controls (most by Others) C. Equipment Schedule 1.2 Related Sections: A. Section
More informationPortable Purification zf04 Systems Models PVS 185, 600, 1200, 1800, 2700
Portable Purification zf04 Systems Models PVS 185, 600, 1200, 1800, 2700 185 Principles of Operation Contaminated oil is drawn into the Parker Portable Purification System by a vacuum of 25 In/Hg. The
More informationModels. Options. Standard Features. LoH 2 O
LoH O Models LoH O Standard Features Uses 8 gallons (9. liters) of water per hour with sanitizing hot water rinse All tanks and hoods constructed from durable stainless steel with a No. finish and heliarced
More informationC. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.
SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.
More informationPOWER TRANSFORMER OIL PROCESSING SPX TRANSFORMER SOLUTIONS, INC.
Regional Technical Seminar POWER TRANSFORMER OIL PROCESSING SPX TRANSFORMER SOLUTIONS, INC. June 20, 2018 Agenda 1. Oil Processing Theoretical Information Transformer Drying Theory Insulation Media 2.
More informationSENTRA Series Water Unit
SENTRA Series Water Unit Standard Unit: F to 0 F Process Fluid Temperatures* Optional High Temperature Configuration to 0 F Direct Injection Cooling 0 to kw Heaters to 7. HP Centrifugal Pumps (0-00 GPM)
More informationAFD Industrial Dehumidifier Series
Dryomatic HUMIDITY CONTROL A MEMBER OF MARDUK HOLDING COMPANY LLC AFD Industrial Dehumidifier Series DRYOMATIC is a Leader in the Dehumidification Industry with Over 5 Years Experience and Thousands of
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-42 22 16.00 40 (August 2017) --------------------------------- Preparing Activity: NASA Superseding UFGS-42 22 16.00 40 (August 2014) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationTITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F
Temperature Control Units Water & Oil - F Portable Chillers Air & Water-Cooled - 7 F Central Chillers Air & Water-Cooled Packages & Modules - 7 F Pump Tank Stations Chilled or Tower Water - gallons Cooling
More informationINSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS
INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS GENERAL INDEECO Industrial Control Panels are designed to provide years of trouble free operation if properly
More informationModular Supply Make-Up Air Unit
Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features
More informationFUEL OIL DAY TANKS. SST Level Controller: UL 508 LISTED
FUEL OIL DAY TANKS SST Series - Engineering Submittal SST Series - Advanced Line Day Tanks Construction: UL 142 aboveground steel tank all seam welded, square, atmospheric tank of heavy gauge steel with
More informationGIRTON CABINET WASHER MODEL 794A
DESCRIPTION GIRTON CABINET WASHER MODEL 794A The washer shall be a Girton Model 794A Cabinet Type Pressure Washer constructed of type-304 stainless steel, utilizing a reciprocating header spray system.
More information30 F to 300 F Process Temperatures* 1/2 to 7.5 HP Centrifugal Pumps ( GPM) 3/8-1 Solenoid Cooling Valves (VE & 300 F models)
Temperature Control Units Water & Oil - 00 F Portable Chillers Air & Water-Cooled 0-70 F Central Chillers Air & Water-Cooled Packages & Modules 0-70 F Pump Tank Stations Chilled or Tower Water 00-00 gallons
More informationBHARAT HEAVY ELECTRICAL LIMITED, JHANSI
BHARAT HEAVY ELECTRICAL LIMITED, JHANSI Specification No. 7182/R2 Item No. ME-1/5/2639 Location BAY-6 Quantity ONE NO. NOTE : 1 VENDOR must submit complete information against clause No. 10.0 ( Qualifying
More informationChilled Water DOAS Fan Powered Terminal Units
Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner
More informationTYPICAL CPA SPECIFICATIONS
TYPICAL CPA SPECIFICATIONS 4/10/2017 UNIT CONSTRUCTION: Casing: The exterior casing of the unit shall be constructed of 18-gauge, G235 galvanized steel (optional stainless steel or aluminum), unpainted.
More informationTECHNICAL. Series 18. Pump Packages
TECHNICAL S Y S T E M S Series 18 Pump Packages Series 18 Pump Packages Standard Features Close-coupled, end-suction, centrifugal pumps Mounted and wired pump starters Hand-Off-Auto switch for each pump
More informationJFT Flight Machine. JFT Flight Machine. Models. Options. Standard Features. JFT Flight Machine
JFT Flight Machine Models JFT Flight Machine Options Project Item Quantity CSI Section 00 Approval Date Blower dryer Additional wash section Additional load module Additional unload module (8m) wash down
More informationC. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.
SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers
More informationProcess Water Heater For Industrial Applications All Voltages, Single or Three Phase Up To 88 KW
MODEL V Process Water Heater For Industrial Applications All Voltages, Single or Three Phase Up To 88 KW Features Industrial Grade Construction Stainless steel pressure vessel provides maximum service
More informationElectric Pumps. Introduction. W4100, W4200 & W4300 Condensate Pumps. Typical Condensate Pump Features
Electric Pumps Introduction W4100, W4200 & W4300 Condensate Pumps Watson McDaniel s Condensate Return and Boiler Feed Pumps are equipped with Cast Iron bodies and Bronze Impellers. The pump receiver tanks
More informationGuide Specifications PART 1 GENERAL 1.01 SUMMARY
Guide Specifications PART 1 GENERAL 1.01 SUMMARY A The environmental control system shall be designed specifically for precision temperature control applications. It will automatically monitor and control
More informationDirect Gas-Fired Make-Up Air
Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The
More information.2 Section Waste Management and Disposal.
Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3
More informationKINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION
SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationIndirect Gas-Fired Make-Up Air
Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up
More informationVENTLESS DOOR-TYPE DISHWASHER
Item # Quantity C.S.I. Section 11400 VENTLESS STANDARD FEATURES Internal condensing system minimizes water vapor Does not require a vent hood Energy recovery Sense-A-Temp 70 F rise electric booster heater.74
More informationPURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN
VALVES VESSELS SYSTEMS CONTROLS PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN System drawings shown in this bulletin are for illustration purposes only. Refrigeration systems
More informationSECTION AIR COMPRESSORS AND ACCESSORIES
PART 1 GENERAL 1.01 WORK INCLUDED SECTION 11370 AIR COMPRESSORS AND ACCESSORIES A. This specification includes air compressors with air dryers. B. Furnish, install, start-up, and test air compressors and
More informationZLA Series Double-stages Vacuum Transformer Oil Purifier Transformer Oil Purification
1 ZLA Series Double-stages Vacuum Transformer Oil Purifier Transformer Oil Purification ZLA series double-stage vacuum transformer oil purifier is particularly suitable for dehydration, degasification
More informationA. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:
SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL
More informationVUD. Vac-U-Dry Vacuum Dehydrators. hyprofiltration.com/vud
VUD Vac-U-Dry Vacuum Dehydrators The optimized balance between heat, vacuum, process design and an easy, user friendly operating system for removal of water and particulate from hydraulic and high viscosity
More informationPhillips. HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants
Phillips REFRIGERATION MECHANICAL PUMP RECIRCULATORS BULLETIN MPR-03E Engineering Data VALVES VESSELS SYSTEMS CONTROLS HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants
More informationCL64T INDUSTRIAL TOTE WASHER
Item # Quantity C.S.I. Section 11400 STANDARD FEATURES Selectable Speed 4, 5, 6 feet/minute Opti-RinSe system Rapid return conveyor drive mechanism Insulated hinged double doors with door interlock switches
More informationAnnexe: Width 9 mtrs (4+2), length 130 mtrs divided into following sections: Impulse Test Lab. Routine Test Lab. Stores. Works offices.
(Note: List of routine and General Machines and Equipments,Tools,Tackles, Small Testing Equipments etc. are not included).recent Expansion at our Yewat Work Land: Additional 50000 sq mts of land. Shed:
More informationAFD DEHUMIDIFIER SERIES
The DRYOMATlC AFD Series is a complete factory engineered and fabricated desiccant dehumidification system with performance capabilities as shown on AFD data sheets~ The desiccant dehumidifier is a complete
More informationSECTION ROTARY-SCREW WATER CHILLERS
PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.
More informationMACH N-407 Heat Pump Air-Cooled Chiller
MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type
More informationVent-Rite. Cast Iron And Steel Receivers. Simplex, Duplex, Triplex And Quadruplex Units. Pump Capacities To 150 GPM. Discharge Pressure To 75 PSI
Vent-Rite BULLETIN VCRV AUGUST 0 GUARDIAN Plus Cast Iron And Steel Receivers Simplex, Duplex, Triplex And Quadruplex Units Pump Capacities To 0 GPM Discharge Pressure To 7 PSI 87 Dewey Avenue Benton Harbor,
More informationSECTION DOMESTIC WATER HEATERS
SECTION 223500 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationOur Purifier systems
Our Purifier systems are the best line of industrial jet washers in the world! Using water based solutions, these heavy duty spray washing systems clean the dirtiest parts in just minutes. Rinse and dry
More informationCMM-R. CMM-R transformer oil regeneration plant. Oil regeneration CMM-6R
Contents 1. Oil regeneration... 2 2. Degassing, thermal vacuum drying of oil... 8 3. Vacuumizing of equipment... 20 4. Zeolite Regeneration Units... 21 5. Zeolite Oil Drying Unit... 22 6. Oil filtration
More informationCirculating Oil Temperature Control System
Installation & Operation Manual Circulating Oil Temperature Control System i PQ451 161-123417-037 February 2019 Table of Contents Contents Page Number Section 1 Getting Started... 1 Section 2 Installation...
More informationSECTION HEATING BOILER FEEDWATER EQUIPMENT
SECTION 23 53 00 HEATING BOILER FEEDWATER EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes boiler feedwater pumps, de-aerators, accessories, controls and tanks. 1.2 REFERENCES A. ASME (American
More informationVacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager
INTRODUCTION The science of creating vacuum is often misunderstood and when the desired vacuum condition is not being achieved in a manufacturing setting this usually means production comes to a halt and
More informationULTRA-SAFE Explosion-proof Duct Heaters
Standard Construction Heat Exchanger has copper tubes with integral aluminum fins. Each unit undergoes hydrostatic testing at 350 psig, five times the pressure relief valve setting of 70 psig. Heat Transfer
More informationIndustrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation
Industrial Space Heating Direct Gas-Fired Heating Greenheat 00% Outdoor Air Greenheat 50/50 Recirculation 80/0 Recirculation March 008 Product Overview Industrial Space Heating Greenheck s space heating
More informationPACKAGE AIR CONDITIONER
PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior
More informationLiebert CSU3000 Chiller
CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,
More informationWallace & Tiernan Gas Feed Systems V2000 Chlorinator
Wallace & Tiernan Gas Feed Systems V2000 Chlorinator Introduction Siemens Water Technologies chlorination equipment has the benefit of 100 years of experience in gas feed technology. V2000 chlorinators
More informationINSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS
INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.
More informationCall us today! (800)
500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,
More informationFT900SDBD DUAL RINSE FLIGHT-TYPE DISHWASHER
Item # Quantity C.S.I. Section 11400 FT900SDBD DUAL RINSE FLIGHT-TYPE DISHWASHER STANDARD FEATURES Opti-RinSe system with dual rinse Water usage 72 gph @ 20 psi Microprocessor controls Low temperature
More informationCL44eR DISHWASHER STANDARD FEATURES MODEL OPTIONS AT EXTRA COST ACCESSORIES DIRECTION OF OPERATION VOLTAGE. Item # Quantity C.S.I.
Item # Quantity C.S.I. Section 11400 DISHWASHER STANDARD FEATURES Energy recovery 202 racks per hour Opti-RinSe system 30 KW electric booster heater Rapid return conveyor drive mechanism Insulated hinged
More informationAM-14/AM-14C DISHWASHERS
AM-14/AM-14C DISHWASHERS Item # Quantity C.S.I. Section 11400 AM-14/AM-14C DISHWASHERS STANDARD FEATURES 53 racks per hour hot water sanitizing 16 gauge stainless steel tank, chamber, doors, frame and
More informationTemptek Auxiliary Equipment
Temptek Auxiliary Equipment Mold Temperature Controllers - Water Units VT-275-LX VT Series Mold Temperature Controllers are used to process temperature control to 250 F. These units use an incoloy heater
More informationSioux EN-Series. All-Electric Extra Heavy Duty Industrial Steam Cleaners and Pressure Washers
Sioux EN-Series All-Electric Steam Cleaners and Pressure Washers Sioux EN-Series All-Electric Extra Heavy Duty Industrial Steam Cleaners and Pressure Washers Model EN-270-H4-3000-XP When Performance and
More informationSECTION AIR COMPRESSORS AND ACCESSORIES
PART 1 GENERAL 1.01 WORK INCLUDED SECTION 11370 AIR COMPRESSORS AND ACCESSORIES A. This specification includes air compressors with air dryers. B. Furnish, install, start-up, and test air compressors and
More informationB. Section Transfer Switches: Automatic transfer switch.
SECTION 263213 - ENGINE GENERATORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Packaged engine generator set. B. Exhaust silencer and fittings. C. Remote control panel. D. Battery and charger. E. Weatherproof
More informationSECTION COOLING TOWERS
SECTION 23 65 00 COOLING TOWERS PART 1 - GENERAL 1.1 DESCRIPTION A. Packaged, induced draft open circuit cooling tower complete with fill, fan, inlet louvers and associated accessories and equipment. 1.2
More informationMODEL MW200 MODEL MW600 AIR DRYER
OPERATING MANUAL MODEL MW200 MODEL MW600 AIR DRYER Mail Address: 226A Commerce St. Tel: 303-465-3063 Broomfield, CO 80020 Fax: 303-465-9294 TABLE OF CONTENTS 1.0 GENERAL...3 2.0 SPECIFICATIONS...3 3.0
More information"ESDDR" Series Electric Humidifier
ESDDR-1 Deionized, Demineralized, or Reverse Osmosis Water "ESDDR" Series Electric Humidifier The Electric Humidifier from PURE Humidifier Co. is loaded with features and options. All you need is deionized,
More informationDomestic. Pump Series CB and CBE Condensate Units SINGLE OR DUPLEX 1,000 THRU 140,000 SQ. FT. EDR-250 THRU 34,748 LB./HR.
Cast Iron Receivers: For years of dependable service; warranted for 20 years from date of shipment against failure due to corrosion. Each Receiver comes standard with Inlet connection, an overflow and
More informationClean-Out-of-Place (COP) Parts Washer
Food & Beverage Clean-Out-of-Place (COP) Parts Washer Technical Datasheet Cleaning Confidence 1915 S. Stoughton Rd., Madison, WI 53716 (o) 800-356-3300 (f ) 608-222-5348 sanimatic.com Model Number Key
More informationR- 410A Series Zero Ozone Depletion
Form: WR-GS-0705 GENERAL SPECIFICATION Compact Connectable Reversing 10-30HP Water to Water Geothermal Heat Pump R- 410A Series Zero Ozone Depletion Chiller Solutions LLC, 2008 General Description The
More informationFAN SEPARATOR. Fan / Separator H2SO4 (Sulfuric Acid) is Designed to Remove Fume and Other Contaminants from the Air Stream.
FAN SEPARATOR Fan / Separator H2SO4 (Sulfuric Acid) is Designed to Remove Fume and Other Contaminants from the Air Stream. FAN / SEPARATOR SPECIFICATIONS Various materials of construction may be used to
More informationFT900BD FLIGHT-TYPE DISHWASHER
Item # Quantity C.S.I. Section 11400 FT900BD FLIGHT-TYPE DISHWASHER STANDARD FEATURES Opti-RinSe system Water usage 120 gph @ 20 psi Microprocessor controls Low temperature alert Blower dryer with 2 H.P.
More informationAdvance Release September 2009
Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*
More informationOIL FILTRATION SYSTEMS, INC. 111 Parkway Drive, Boerne, Texas Phone: Web: oilfiltrationsystems.com.
Success Story Repair & Modification i of Competitors Oil Purification Systems 1. Repair & Enhancement of Pall HVP-900 (15 GPM) Oil Purifier 1 system. Page 2 2. Repair & Enhancement of FilterDyne (5 GPM)
More informationDry Bulk Truck Blowers
Dry Bulk Truck Blowers M-D Pneumatics Blowers & Vacuum Boosters Quality, dependability, and outstanding performance. Excellence at work. Excellence in life. Tuthill Vacuum & Blower Systems tuthillvacuumblower.com
More informationARRAS MAXEI OIL TREATMENT
I BETH09GB_E page 1/6 SUMMARY: Principle of operation 2 Main characteristics 2 Components of the plant 2 Description of the plant 3 Flow diagram 4 Options 5 TECHNICAL DESCRIPTION OF THE OIL TREATMENT PLANT
More informationLandfill & Digester Gas Dryers. Features and Benefits
Landfill & Digester Gas Dryers Landfill gas is generated by the anaerobic decomposition of organic matter deposited in landfills. Digester gas is produced as a by-product of the digestion of sewage sludge.
More informationDatasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description
FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components
More information