RESIDENTIAL AND COMMERCIAL LIGHT OIL BURNERS PART-1 By: William D. Fitzgibbons INTRODUCTION

Size: px
Start display at page:

Download "RESIDENTIAL AND COMMERCIAL LIGHT OIL BURNERS PART-1 By: William D. Fitzgibbons INTRODUCTION"

Transcription

1 Service Application Manual SAM Chapter A Section 12 RESIDENTIAL AND COMMERCIAL LIGHT OIL BURNERS PART-1 By: William D. Fitzgibbons INTRODUCTION The primary objective of this section is to provide the Refrigeration Service Engineer with a working knowledge of the oil fired heat source in Total Comfort... Installation, Service Techniques, and Preventive Maintenance Procedures. While generally applicable, information provided will always be superseded by the burner manufacturer s specifications. All data will be confined to burners of the pressure atomizing type designed to burn #2 Fuel Oil. Although commonly known as residential type burners, advances in both burner design and control components have resulted in manufacture of equipment with rated capacities of in excess of twenty (20) gallons of fuel per hour for commercial and industrial applications. burner components A pressure atomizing burner is usually comprised of the following components as shown in Figure 1. Blast Tube Blower Housing Motor Fuel Pump Blower Wheel Pedestal or Flange Mount End Cone or Choke Ring High Voltage Ignition Transformer Ignition Electrodes Electrode Mount Nozzle Pipe Figure 1 Copyright 1978, 2009, By Refrigeration Service Engineers Society. -1-

2 Delayed Oil Valve (Some Models) Nozzle(s) Air Diffuser Ignition Wires or Bars Pump Drive Couplings Nozzle Adapter Air Volume Controller component location and function Burner Blower Housings are designed for Blower Wheel location above or below center line of Blast Tube, and left or right side motor location resulting in clockwise or counter clockwise rotation of motor, blower, and fuel pump, according to burner manufacturer s design. The blast tube, either an integral part of, or attached to blower housing, houses the firing assembly consisting of nozzle pipe, nozzle(s), electrode mount and electrodes, nozzle adapter, and air diffuser. Burners are available with blast tubes of varying lengths to facilitate proper installation in boilers and furnaces with enclosing panels. The end cone or choke ring is attached to open end of blast tube. According to burner design, the high voltage transformer may be mounted on either side of blower housing or fastened to top of inboard end of housing by a hinge, serving as a cover for the opening providing access to firing assembly. When attached to side of housing, transformer high voltage terminals are accessible from inside housing and are connected to ignition electrodes with cables or preformed bars provided. When transformer is mounted on top of housing, terminals are connected to electrodes with a variety of spring or wiper contactors. High Voltage current is generally 6,000 to 12,000 volts. Extreme caution should be used when checking operation of this component. Figure 2 Typical Nozzle and Electrode Assembly Copyright 1978, 2009, By Refrigeration Service Engineers Society. -2-

3 The blower wheel is usually mounted directly on motor shaft, and is centered in housing. Fuel pump is mounted on side of blower housing directly opposite motor and connected to motor shaft or blower wheel hub by means of flexible coupling(s) provided. Fuel pump nozzle port is connected to nozzle pipe with soft copper tubing, usually1/4 O.D., where pipe projects through blast tube or blower housing wall. Final connections are made with flared or housing compression fittings. (Figure 2) Fuel pumps commonly used are Webster and Sundstrand. Pump function is to transport fuel oil from tank and discharge it to nozzle(s) at proper atomizing pressure. Pumps are available for both clockwise or counter clockwise rotation, and with left and right hand nozzle ports and left or right hand inlet or suction ports to meet the requirements of various burner manufacturers. Pumps are also designed for use with One or Two Pipe fuel transportation systems. Field changes required will be outlined under Adapting Fuel Pumps to One- and Two-Pipe Systems. Ignition Electrodes are steel rods encased in porcelain insulating tubes. One end terminates in a suitable connector for the high voltage cable or bus bar, and the other end which extends several inches or more beyond its insulating tube, is bent slightly in order to obtain the correct distance between opposing tips when electrodes are assembled in mount, which is part of firing assembly. This distance is known as the spark gap, and is generally specified as 3/16. Distance between center of nozzle(s) and electrode tips vertically, and distance between tips and face of nozzle horizontally governed by angle rating of nozzle used, see Figure 2 for details of electrode setting. It is important that porcelain insulators be dry and clean, as carbon deposits, dust or oil film will permit high voltage current to circumvent spark gap and cause ignition failure and safety shutdown of oil burner. nozzle pipe assemby The nozzle pipe assembly, components of which are covered under a previous heading, is constructed to suit the requirements of a specific burner and no two assemblies will be alike in every detail. A typical assembly is shown in Figure 2. Nozzle pipes may be straight or bent in various ways dependent upon the location at which they project through blast tube or blower housing wall for connection to fuel pump nozzle port. No adjustment of components other than spark gap dimension should be made without first consulting burner manufacturers instructions. Changes in flame pattern are sometimes made by moving nozzle pipe forward or backward in slotted attachment hole, in accordance with burner manufacturers instructions. blower wheel The blower wheel forces what is described as primary air through blast tube where diffuser and choke ring create required turbulence and mix air with the oil spray which is ignited by high voltage spark at electrodes, producing the desired flame pattern and complete combustion. Excess primary air will produce a raw, inefficient flame and insufficient primary air conversely will produce a smudgy, smoky flame resulting in excessive sooting of boiler of furnace and inefficient operation. A primary air volume control is provided on inlet side of blower housing. Correct primary air adjustment is indicated by presence of a slight haze over fire, with no evidence of smoke in combustion chamber or heat exchange areas of boiler or furnace. oil burner installation condition of existing heating equipment Before installing an oil burner in an existing boiler or furnace, it is important to investigate the condition of heating equipment to determine whether the plant can be satisfactorily oil-fired in its present condition or whether repairs are required. Particular care should be taken to determine if there are any leaks in heat exchanger of warm air furnace. Warped or cracked fire, ash-pit, and cleaning doors should be repaired or sealed in order that excess air infiltration may be reduced to a minimum. Copyright 1978, 2009, By Refrigeration Service Engineers Society. -3-

4 Overall dimensions of the ash-pit should be checked to establish whether a suitable combustion chamber can be constructed and to determine the length of burner blast tube required. heating requirements and boiler or furnace capicity If there is any indication that heating requirements are in excess of installed boiler or furnace capacity, it is advisable to check the heating load in accordance with the formula established by the American Society of Heating and Ventilating Engineers, as set forth in the A.S.H.V.E. Guide. If boiler or furnace is undersize for the load, excess fuel consumption will result. In addition, an undersized unit may not provide sufficient heat during unusually cold weather, and sluggish operation and unequal heat distribution will be experienced. Ratings of installed heating boilers may be obtained from a pamphlet published by the Heating, Piping, and Air Conditioning Contractors National Association, Net Load Recommendations for Heating Boilers. The ratings published in this pamphlet list the net steam load in square feet of direct standing radiation. In order to obtain the maximum output of boiler, it is necessary to add a suitable factor, approximately one third, for piping and pickup load. The institute of Boiler and Radiator Manufacturers (IBR) and the Steel Boiler Institute (SBI) have established ratings in gallons per hour (GPH) for boilers. These ratings will be indicated on more recent boiler installations. The National Warm Air Heating and Air Conditioning Association has established similar ratings for forced warm air heating furnaces. These ratings will be noted on furnaces of more recent manufacture and may be found in the fourth edition of Technical Code for the Design and Installation of Mechanical Warm Air Heating Systems. Maximum burner efficiency will be realized when a firing rate is selected that is no larger than actually required to carry the heating load, yet large enough to be responsive to the heat demand. Listed in Table 1 are the approximate furnace or boiler loads that can be satisfactorily carried by nozzles of various capacities. Table 1. Maximum Furnace Or Boiler Loads Corresponding To Various Nozzle Capacities NOZZLE CAPACITY OUTPUT MAXIMUM BOILER CAPACITY Oil Input in Gallons per Hour At Furnace Bonnet or Boiler Output in BTU Per hour Equivalent Direct Radiation [EDR]* Steam Gravity Hot water , , , , , , , , , , , , , , , , , ,000 1,040 1, ,000 1,250 2, ,000 1,460 2, ,000 1,667 2, ,000 1,870 3, ,000 2,083 3, ,000 2,500 4, ,000 2,917 4, ,000 3,333 5, ,000 3,753 6, ,000,000 4,167 6, ,200,000 5,000 8, ,400,000 5,833 9, ,600,000 6,667 10, ,800,000 7,500 12, ,000,000 8,333 13,333 Copyright 1978, 2009, By Refrigeration Service Engineers Society. -4-

5 * Includes net direct standing radiation, plus one-third allowance for piping and pickup load, plus domestic hot-water load. Equivalent Direct Radiation (EDR) for domestic hot water: Steam Systems 1.5 tank storage capacity in gallons Hot-Water systems 2.0 tank storage capacity in gallons size and location of oil storage tank inside tank If space is available in basement, an inside fuel storage tank is generally used because it is less expensive than an outside tank installation. Customary size is 275 gallon capacity, usually of the vertical-oval type, measuring 26 inches in width, 42 inches in height, and 67 inches in length. A check should be made to determine if a tank this size can be brought into basement through doors and passageways. Oil storage tanks located inside buildings shall not exceed 275 gallon, individual capacity, or 550 gallon, aggregate capacity, unless installed in a specially designed fireproof enclosure in compliance with local regulations. A tank should be located so that it is not less than seven (7) feet in a horizontal direction from any fire or flame. It is necessary also, to place an inside tank in a location permitting compliance with local regulations regarding fill and vent piping. The 275 gallon tank should be supported on 1-1/4 12 pipe legs terminating in 1-1/4 floor flanges. After leveling, flanges should be anchored in cement to prevent movement. outside tank Where available basement space is at a minimum or if storage capacity in excess of 550 gallons is required, the oil tank will usually be placed outside of building and buried below ground. Rules of the National Board of Fire Underwriters (Pamphlet #31) should be followed in locating and installing underground fuel storage tanks. Outside underground tanks should be buried with an earth cover of not less than two (2) feet, or covered by not less than one (1) foot of earth, on top of which has been placed a concrete slab not less than 4 thick. When installing an outside tank it is advisable to first check location of sewer, gas, and water mains entering building. The tank should be located with ample clearance between tank and these pipes in case any of them have to be replaced or serviced in the future. tank piping fill pipe Basement installed tanks require a 2 diameter fill pipe which should terminate outside basement wall at least 5 from any window or building opening. Fill pipe should rise at least 12 above horizontal run outside building and terminate in a tamper proof cap. An indirect fill pipe from outside tank should have double swing joints at both tank and building, and fill pipe emptying directly into tank vertically should terminate not less than 12 above grade to prevent any flood water from seeping into tank. A flush with grade type of fill may be approved if enclosed in water-tight well. When an indirect fill pipe is installed, it is advisable to install a tee fitting at tank and run a combination emergency fill and tank cleaning medium to grade level, capped with watertight fitting. Size of fill pipe for outside tanks will be governed by local regulations based on tank capacity, never less than 2, however. Copyright 1978, 2009, By Refrigeration Service Engineers Society. -5-

6 vent pipe Vent piping for basement or buried oil tanks should not be smaller than 1 1/4 diameter, and shall terminate outside of building at a point not less than 2 feet, measured vertically and horizontally from any window or other building opening. Top of vent pipe must have a return bend or approved vent cap and should extend above grade high enough to prevent being obstructed by either snow or ice. Most communities have specific regulations governing vent pipe height, however, 8 feet above grade is generally accepted. Whether connected to a basement or outside tank the vent pipe should pitch downward toward tank throughout its entire length. A Ventalarm is a must in basement tank installations and is recommended on outside tanks for added safety and convenience in filling. suction and return piping One pipe system function satisfactorily in basement tank installations generally, however, two pipe systems are recommended on all installations, as with this arrangement the fuel pump will purge itself of air automatically and, under emergency conditions, the return line may be used as a suction line. When an outside tank is installed below burner, a two pipe system is mandatory. Changes required in burner pump assembly for One and Two Pipe systems application will be covered in subsequent paragraphs. Most communities permit use of soft copper tubing for suction and return piping between tank and burner using #2 fuel oil, with connections made with flare type fittings. In most basement tank installations, 3/8 OD tubing is satisfactory for both suction and return lines, and 1/2 OD tubing may be used when outside tank is not more than 50 feet from burner. Both suction and return lines should extend to within 3 inches of tank bottom, using slip fittings in tank tappings. A check valve should be installed in suction line at outside tank and tubing should pitch upwards from tank to building wall. Tubing should be formed into loop at tank to allow for minor settling. Some localities require gate valves in suction line both inside and outside of building wall. Installer should familiarize himself with all local regulations before starting installation. Hand valves should never be installed in return line, a return line valve accidentally closed could result in pump breakage and disastrous fire hazard conditions. A variety of fuel oil gauges are available for both basement and outside tank installations and one should be installed, following manufacturer s recommendations. A typical basement tank installation is shown in Figure 3 and an outside tank installation is covered in Figure 4. Figure 3 Typical inside tank installation Copyright 1978, 2009, By Refrigeration Service Engineers Society. -6-

7 Copyright 1978, 2009, By Refrigeration Service Engineers Society. -7-

8 Figure 4 Typical outside tank installation figure 8- One And Two Pipe Changeover-Witout extra parts adapting pumps to one or two pipe fuel supply systems Two most widely used Fuel Units (pumps) are... Sundstrand and Webster. Field changes to adapt these Fuel Units to One or Two Pipe systems are as follows: Sundstrand, Model J and H, Two Pipe System, remove 3/8 pipe plug from return line port. Insert 1/8 socket head pipe plug (provided with unit) into tapping in return port opening, using 3/16 Allen Wrench, and draw up tight. Connect return line to tank to return port. For One Pipe System the 1/8 pipe plug must be removed and return port plugged. Figure 5 shows details. Webster all 6000 and 8000 Series units as Figure 6 indicates Letter P is stamped on pump body adjacent to suction strainer housing cover. Suction strainer housing cover has symbols S1 and S2 stamped on top at opposite sides. When S1 symbol is over P stamped on pump body, unit is adapted for One Pipe System. To reverse as required, remove four screws holding suction strainer housing cover, making sure not to damage gasket. Remove small guide stud from underside of cover with small screwdriver and replace on opposite edge of cover. Replace cover with required symbol (S1 or S2) over P stamping. Return port is plugged for One Pipe System. Webster, type 1R and 2R units illustrated in Figure 7. No special tools are required to change these units from One to Two Pipe Systems. Simply insert a small screwdriver into inlet opening on side marked RET and draw 1/4 by-pass screw tight for Two Pipe System. For One Pipe System, unscrew by-pass screw three (3) complete turns and plug return port, reference Figure 8. Copyright 1978, 2009, By Refrigeration Service Engineers Society. -8-

9 Figure 7 Copyright 1978, 2009, By Refrigeration Service Engineers Society. -9-

10 . No special tools or extra parts are needed to change Webster Service-Saver Fuel-units from a one to two-pipe system. Simply insert a screw driver into the inlet opening on the side marked RET, tighten the 1/4 screw and attach the return line for a two-pipe system. When one pipe system is used, plug is inserted in bottom chamber and 1/4 screw is unscrewed three complete turns. fuel units, ajusting nozzle pressure Sundstrand Fuel Units Pressure adjusting screw is located under cap opposite nozzle port. To adjust pressure, stop burner and remove 1/8 plug adjacent to return port. Insert 150# gauge in tapping and restart burner. Remove cap from pressure regulator screw and turn in or out with small screwdriver to obtain standard 100# pressure. Stop burner and replace 1/8 plug and cap. A small container should be kept handy to collect residual oil discharged during disassembly and assembly operations. Webster Series 6000 and 8000 Fuel Units Nozzle pressure adjustment medium is an Allen Screw located under small slotted head screw centered in top of pressure regulator cover. To adjust, stop burner, remove slotted head screw and 1/4 plug in side of regulator body and insert 150# pressure gauge in 1/4 tapping. Restart burner and turn Allen Screw in or out until nominal nozzle pressure of 100# is obtained. Stop burner and replace 1/4 plug and slotted head screw, making sure that small gasket under screw head is intact. Webster Series 1R and 2R Fuel Units Nozzle pressure adjustment medium is screw under cap opposite nozzle port. To adjust, stop burner and remove adjusting screw cap and pipe plug nearest nozzle port. Insert 150# pressure gauge in pipe tapping. Restart burner and turn pressure adjusting screw in or out to obtain nominal 100# nozzle pressure. Stop burner and replace pipe plug and adjusting screw cap. combustion chamber or firebox The Combustion Chamber or Firebox is a most important requisite to efficient Oil Fired System operation. It is, as the name implies, a chamber or box in which combustion takes place. The burner blast tube is inserted in opening left in front wall of chamber to Copyright 1978, 2009, By Refrigeration Service Engineers Society. -10-

11 a minimum of 1/4 from inside face of wall. Many furnaces and boilers of recent manufacture incorporate factory installed combustion chambers with provision for either specific or universal oil burner installation. Older heating plants require on the job combustion chamber construction. Combustion chambers may be constructed of hard fire brick or soft insulating brick capable of withstanding temperatures of from 2,600 F to 3,000 F. More recently, however, combustion chambers are being prefabricated of stainless steel or in sectional units of preformed refractory material in an assortment of shapes and sizes. Sections are assembled in furnace or boiler and joints sealed with suitable high temperature cement. Space Age Technology has also made available several forms of blanket type high temperature insulating material in sheets or preformed, which may be used to reline an inefficient existing combustion chamber or construct a new one. This material, produced under a variety of trade names, may be cut with a scissors and formed like fiberglass. When subjected to high temperatures it hardens and becomes self supporting. Joints in all combustion chambers (bottom, sides, and around blast tube of burner) must be sealed to prevent infiltration of air other than that supplied by burner blower. Figure 9 shows cutaway view of typical field constructed combustion chamber. Combustion chamber top is open to allow hot gasses to circulate through passages of boiler or furnace and effect required heat exchange. Any space between outer surfaces of chamber and boiler or furnace must be filled with loose insulating wool or pellets. If floor of chamber is laid on concrete floor at least 1 of dry asbestos, block insulation, or hollow tile should first be laid on floor to guard against buckling of concrete floor due to excessive heat transfer. Combustion chambers are sized for input of boiler or furnace in Btu s, as converted to gallons of fuel oil burned per hour, and shaped to fit the physical dimensions of the boiler or furnace. Shape of combustion chamber also dictates angle of nozzle to be used in burner. See Table 2 for chamber size and nozzle data. 80 Sq. In. Per Gal. 90 Sq. In. Per Gal. 100 Sq. In. Per Gal. Nozzle Size GHP Sq. Inch Area Combustion Chamber Table II Combustion Chamber Data Dia. Round Combustion Chamber Inches Square Combustion Chamber Inches Rectangular Combustion Chamber Inches Wth. Lgth. Height From Nozzle to Floor Inches / / /2 10-1/2 11-3/ / /2 11-1/ /8 12-5/8 14-1/ / /4 14-1/ / /2 15-1/2 17-1/ / /4 17-1/ / / / /4 21-1/ /2 23-1/ / /2 24-1/ / /2 25-1/ / /2 26-1/ / /4 27-1/ /4 28-1/ /4 29-1/ / /4 31-3/ / /4 33-1/ / /2 34-1/ /2 37-1/ /4 38-3/4 Round Combustion Chambers usually / /4 41-1/4 42-1/2 42-1/2 not used in these sizes / Sq. Ft. of Steam Rad. (Approx.) The above data applies to the majority of conventional pressure atomizing burners. There are some models of burners that will require a different height from floor to nozzle. Consult your burner manufacturer. You will note the absence, in Table II, of a dimension from center of nozzle to top of combustion chamber. This dimension should always be twice that of nozzle center to floor of chamber. The reason for twice as much refractory above the nozzle as below is that all combustion should take place in the presence of red hot refractory. Above the combustion chamber there should be no flame, only completely burned gases. In no case should combustion chamber walls extend more than three or four inches higher than boiler water leg (bottom of water filled section). To do so reduces effective heating surface of boiler. When dimension from center of nozzle to top of chamber requires chamber walls to be extended beyond this height, the use of twin nozzles is recommended, for example, Copyright 1978, 2009, By Refrigeration Service Engineers Society. -11-

12 two seven gallon nozzles mounted in horizontal adapter instead of fourteen gallon nozzle. When this is done chamber height need only be that required for a seven gallon nozzle. It should be noted however that all chamber walls should protect a minimum of three inches of the boiler water leg from direct flame. Whether a boiler is round or square it is recommended that a round combustion chamber be used whenever possible. Figure 10 shows how, in a round chamber, gases can sweep back and continue mixing with atomized oil for more complete combustion. Figure 11 shows how, in a square cornered firebox, air strikes back wall, goes right and left and strikes other walls. This air travels up each corner of firebox, reduces gas temperatures and results in lower CO 2 readings, indicating low efficiency. From these illustrations it can be seen that when a square or rectangular chamber must be used, square corners must be eliminated, as shown in Figure 12. When combustion gas travel is up through the back sections of boiler, the rear wall of combustion chamber should be of corbel or throwback construction to cause gases to sweep back towards the boiler door, effecting greater heat exchange in forward sections before leaving boiler. Figure 12 also shows a side view of corbel construction. It cannot be overemphasized that whether the combustion chamber be round, square, or rectangular, all space between its walls and boiler or furnace must be filled with loose insulation fill and a sealing cap of refractory cement placed over top of walls and trowelled into all crevices and section configurations. Space between burner blast tube and opening in front wall of chamber must be sealed with asbestos rope or refractory cement. mounting burner If heating plant is prepackaged, burner will either be mounted at factory or provision made for flange mounting with mounting holes pre-drilled and tapped for easy assembly. When installation is made in previously coal fired boiler or furnace, burner is usually floor mounted. Copyright 1978, 2009, By Refrigeration Service Engineers Society. -12-

13 Pedestal mounts generally permit height adjustment adequate for centering of burner blast tube in opening left in front wall of combustion chamber. When this is possible, burner base may be anchored directly to concrete floor. When additional height from floor is required, burner base should be supported at the correct height by pieces of unused firebrick or other non-inflammable material and short lengths of 3/8 threaded rod with lower end bent at 90 x 1 suspended from base anchoring holes with nut and washer above base. A simple wooden form with inside measurement several inches larger than burner base is then placed in position and filled with Portland cement or Sakrete mix to the level of burner base. When concrete base has set, anchor nuts may be tightened securely. Burner should be centered with relation to side walls of chamber and centerline of nozzle should be correct height from chamber floor. Burner blast tube should pitch slightly (max. 1/16 over its length) towards combustion chamber to prevent oil leaking from any firing assembly malfunction from flowing back to blower housing and on basement floor. Copyright 1978, 2009, By Refrigeration Service Engineers Society. -13-

Model 601CRD Oil Burner

Model 601CRD Oil Burner Model 601CRD Oil Burner Installation and Operating Instructions For Use By Qualified Service Technicians Only CRD burners feature a combustion head incorporating a new design concept which provides a means

More information

INSTALLATION AND OPERATION MANUAL FOR 2 STAGE RIELLO BURNER ADDENDUM TO ( Mo 437 manual )

INSTALLATION AND OPERATION MANUAL FOR 2 STAGE RIELLO BURNER ADDENDUM TO ( Mo 437 manual ) INSTALLATION AND OPERATION MANUAL FOR 2 STAGE RIELLO BURNER ADDENDUM TO ( Mo 437 manual ) FOR USE WITH MODEL: OH6FX072DV4 PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION, INITIAL FIRING, AND BEFORE

More information

DOMESTIC WATER HEATER OIL FIRED

DOMESTIC WATER HEATER OIL FIRED DOMESTIC WATER HEATER OIL FIRED Models : CMO32-II CMO32-II-R CMO50-II CMO32-II & CMO32-II-R INSTALLER / SERVICE TECHNICIAN: USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE

More information

CMO32 CMO50 DOMESTIC WATER HEATER OIL-FIRED. Models: CMO32 CMO50

CMO32 CMO50 DOMESTIC WATER HEATER OIL-FIRED. Models: CMO32 CMO50 DOMESTIC WATER HEATER OIL-FIRED Models: CMO32 CMO50 DNS-1102 Rev. A DNS-0413 Rev. A CMO32 CMO50 INSTALLER / SERVICE TECHNICIAN: USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF

More information

BC Series II OIL-FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR US AND CANADIAN SALES

BC Series II OIL-FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR US AND CANADIAN SALES Models BC3095 BC4100 BC4115 BC Series II OIL-FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR US AND CANADIAN SALES Maximum Allowable Working Pressure 30 psi. Manufactured by: ECR

More information

NOZZLE MIX COMBINATION BURNER NMC200 SERIES

NOZZLE MIX COMBINATION BURNER NMC200 SERIES NOZZLE MIX COMBINATION BURNER NMC200 SERIES INSTRUCTIONS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

CHIMNEYS AND VENTS CHAPTER 8

CHIMNEYS AND VENTS CHAPTER 8 CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

HVAC Equipment Access Equipment Location

HVAC Equipment Access Equipment Location City of Lancaster- Building Department 121 East Chestnut Street, Suite 102, Lancaster, Ohio 43130-3825 (740) 687-6649, Fax (740) 681-5030 Web site: www.ci.lancaster.oh.us/dept/building HVAC Heating, Ventilating,

More information

VSA SEWAGE PUMP. Capacities to 1600 gpm, Heads to 120, Horsepower range 3/4 thru 40, 3 thru 6 discharge, 1750 and 1150 operation.

VSA SEWAGE PUMP. Capacities to 1600 gpm, Heads to 120, Horsepower range 3/4 thru 40, 3 thru 6 discharge, 1750 and 1150 operation. Brochure# 228E 122011 TYPE VSA SEWAGE PUMP Capacities to 100 gpm, Heads to 120, Horsepower range 3/ thru 0, 3 thru discharge, 1750 and 1150 operation. HIGHLIGHTS Wet-Pit Installations Pumps Suspend From

More information

POWER VENTER. Model: PVE Series

POWER VENTER. Model: PVE Series POWER VENTER Model: PVE Series CONTENTS Typical Venting System Components... System Operation... Power Venter Sizing... Installation Safety Instructions... Installation of Power Venter... Connecting Power

More information

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

POWER VENTER SYSTEM. Model: PVO-300, PVO-600 POWER VENTER SYSTEM Model: PVO-300, PVO-600 Included is one ETL and cetl listed Power Venter to be used primarily with a single 120VAC controlled oil fired furnace, boiler, or water heater. The PVO may

More information

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh WATER HEATERS / BOILERS COWB3 Oil-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 0654 March 08 Supersedes September 05 AFUE up to 85.% Heating Input 05,000 to 45,000 Btuh MODEL NUMBER IDENTIFICATION

More information

PVE SERIES POWER VENTER SYSTEM MANUAL

PVE SERIES POWER VENTER SYSTEM MANUAL PVE SERIES POWER VENTER SYSTEM MANUAL Contents Page I. Typical Venting System Components 2 II. System Operation 3 III. Power Venter Sizing 3,4 IV. Installation Safety Instructions 5,6 V. Installation of

More information

STARFIRE IV SERIES 4 WATER OIL FIRED CAST IRON BOILER

STARFIRE IV SERIES 4 WATER OIL FIRED CAST IRON BOILER Models SFH-3085 SFH-3100 SFH-4100 SFH-4125 SFH-4145 SFH-5160 SFH-5185 SFH-6175 SFH-6210 STARFIRE IV SERIES 4 WATER OIL FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL Tested For 75

More information

Installation Instructions

Installation Instructions Dear customer! Thank you for choosing this quality product from ASKO. We hope it will meet your expectations and fulfil your needs for many years to come. Scandinavian design combines clean lines, everyday

More information

Oil burners fuel unit with solenoid valve

Oil burners fuel unit with solenoid valve Oil burners fuel unit with solenoid valve Type VM www.deltapumps.com VM1 - VM4U flanged Certified Quality System Printed in Italy - DE112/0404 Oil burners fuel unit with solenoid valve Type VM The DELTA

More information

MODEL CF CEILING SUPPORTED CHIMNEY

MODEL CF CEILING SUPPORTED CHIMNEY Manufactured by Selkirk Canada Corp. - Hamilton, Ontario Installation Instructions for MODEL CF CEILING SUPPORTED CHIMNEY Round Top Storm Collar Flashing Attic Insulation Shield/Firestop Spacer Intermediate

More information

Oil burners fuel unit with solenoid valve

Oil burners fuel unit with solenoid valve Oil burners fuel unit with solenoid valve Type VM www.deltapumps.com VM1 - VM4U flanged Certified Quality System Printed in Germany VM_e.pdf - 18.05.08 Page 1/6 Oil burners fuel unit with solenoid valve

More information

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1 A AD Oil burners fuel unit deltapumps.com DE116-0709 A-AD_en_0709.pdf - 16.11.09 Page 1/1 Oil burners fuel unit Type A, AD 1- Applications The DELTA aluminium fuel unit type A is an efficient and modern

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury.

The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury. The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury. The Warning signal alerts you to potential hazards or unsafe practices which,

More information

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION INSTALLATION AND OPERATING INSTRUCTIONS FOR THE HARDY Fuel Oil Furnace Models D-140 & D-350 HARDY MANUFACTURING COMPANY, INC. 12345 ROAD 505 PHILADELPHIA, MS 39350 PHONE: (601) 656-5866 FAX: (601) 656-4559

More information

STARFIRE IV SERIES 4 WATER OIL FIRED CAST IRON BOILER

STARFIRE IV SERIES 4 WATER OIL FIRED CAST IRON BOILER Models SFH-3085 SFH-3100 SFH-4100 SFH-4125 SFH-4145 SFH-5160 SFH-5185 SFH-6175 SFH-6210 STARFIRE IV SERIES 4 WATER OIL FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL Tested For 75

More information

CLM FORCED DRAFT WATER BOILER

CLM FORCED DRAFT WATER BOILER FORM 1728 3/25/2004 CLM FORCED DRAFT WATER BOILER TABLE OF CONTENTS 1. KNOCK-DOWN TYPES AND DEFINITIONS 1 2. BOILER FOUNDATION 1 3. BOILER FRAME & TUBE INSTALLATION 2 REFRACTORY TILE INSTALLATION 3 4.

More information

INSTALLATION GUIDE Dual Fuel Ranges

INSTALLATION GUIDE Dual Fuel Ranges INSTALLATION GUIDE Dual Fuel Ranges Contents Wolf Dual Fuel Ranges......................... 3 Safety Instructions............................ 4 Dual Fuel Range Specifications.................. 5 Dual Fuel

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

Installation & Maintenance Manual

Installation & Maintenance Manual Installation & Maintenance Manual MOL 200 S1L (B30A) Oil Burner 11/12 Tel: +44 (0) 1905 794331 Fax: +44 (0) 1905 794017 Email: info@nu-way.co.uk Web: www.nu-way.co.uk DESCRIPTION COMPONENTS 1. Shrouded

More information

Single stage operation oil burner

Single stage operation oil burner Installation & Operating Manual Single stage operation oil burner WARNING NON-RETROFIT APPLICATIONS If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow

More information

MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS

MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS 1. FEATURES The Type N Trap range is particularly suitable for high pressure/high temperature trapping applications

More information

EUTECTIC EC-10DV Series

EUTECTIC EC-10DV Series EUTECTIC EC-10DV Series DIRECT VENT OIL-FIRED WATER BOILER/NO. 2 OIL VENTING INSTALLATION INSTRUCTIONS CONTENTS..........................................PAGE Basic Guidelines..........................................1

More information

Installation Instructions

Installation Instructions Installation Instructions For Free Standing NoFrost Combined Refrigerator-Freezers CS 1660 7084 203-00 Important Please Read and Follow these Instructions These instructions contain Danger, Warning and

More information

Burn Easy Installation Instructions LP or Natural Gas Fired Units. Cremator Setup:

Burn Easy Installation Instructions LP or Natural Gas Fired Units. Cremator Setup: Burn Easy Installation Instructions LP or Natural Gas Fired Units Cremator Setup: 1. Place cremator, outdoor on a solid base consisting of concrete or gravel. Keep this site free of all vegetation. Combustibles

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-200 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per CSA B140.8 Portable Oil Fired Heaters / CSA B140.02003

More information

MULTIPLEX SELF RECUPERATIVE gas burner

MULTIPLEX SELF RECUPERATIVE gas burner Installation - Maintenance MULTIPLEX SELF RECUPERATIVE gas burner SERIES MPSR The Nu-way Multiplex Recuperative System offers the alternative of a self-recuperative burner or a separate recuperator and

More information

US Filtermaxx. 200,000 BTU Waste Oil Burner

US Filtermaxx. 200,000 BTU Waste Oil Burner US Filtermaxx 200,000 BTU Waste Oil Burner Assemble the Burner: Remove all the parts from the box. Locate the burner flange coupling and attach it to the front of the burner as seen in the photo below

More information

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2 3002239 RSIF 2014-04-04 Installation and operation manual RSIF power venter READ AND SAVE THESE INSTRUCTIONS! Product information Chapters 1 + 2 Mechanical installation Chapter 3 Electrical installation

More information

21 20 LITER GAS FRYER FFA3200 INSTALLATION AND SERVICING.

21 20 LITER GAS FRYER FFA3200 INSTALLATION AND SERVICING. 21 20 LITER GAS FRYER FFA3200 INSTALLATION AND SERVICING www.anvilworld.com 20 ALL ANVIL EQUIPMENT COMES WITH A ONE YEAR WARRANTY ON COMPONENTS AND DEFECTIVE WORKMANSHIP. www.anvilworld.com 19 20 LITER

More information

Corn Flame Energy Corn Stove Model 3000

Corn Flame Energy Corn Stove Model 3000 Corn Flame Energy Corn Stove Model 3000 Installation and Operation Guide Read thoroughly before starting installation Save this manual for future reference SAFETY NOTICE If this stove is not properly installed,

More information

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels Installation Instructions For the 18 Built-In Dishwasher and Front Color Panels Printed in USA 154232102 Before You Begin DO NOT INSTALL DISHWASHER UNTIL YOU HAVE READ ALL INSTRUCTIONS. FOR YOUR SAFETY,

More information

mith Mills 4500A Smith Mills 4500A 4500A-3R OIL, GAS OR COMBINATION GAS/OIL COMMERCIAL BOILER/BURNER CAST IRON

mith Mills 4500A Smith Mills 4500A 4500A-3R OIL, GAS OR COMBINATION GAS/OIL COMMERCIAL BOILER/BURNER CAST IRON Mills 00A mith Mills 00A Smith CAST IRON OIL, GAS OR COMBITION GAS/OIL COMMERCIAL BOILER/BURNER 00AR STEAM GAUGE OPERATING CONTROL MODULATING CONTROL HI LIMIT PRESSURE CONTROL 0" STEAM DRUM TEST COCK /"

More information

Important Safeguards (For your safety, please follow the instructions below.) Specification. Warning. Thermal mixing valve faucet.

Important Safeguards (For your safety, please follow the instructions below.) Specification. Warning. Thermal mixing valve faucet. INSTALLATION MANUAL Important Safeguards (For your safety, please follow the instructions below.) AUTOMATIC FAUCET Thermal mixing valve faucet Specification In this Instruction Manual, the following symbols

More information

FIREPLACE INSTALLATION

FIREPLACE INSTALLATION CHECK GAS TYPE Use proper gas type for the fireplace unit you are installing. If you have conflicting gas types, do not install fireplace. See retailer where you purchased the fireplace for proper fireplace

More information

INSTALLATION. Glass Panel Doors (select models) CAUTION

INSTALLATION. Glass Panel Doors (select models) CAUTION Location Do not install refrigerator near oven, radiator or other heat source. If not possible, shield refrigerator with cabinet material. Do not install where temperature falls below 55 F (13 C) or rises

More information

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ... Installation & Operating Manual RSIF Power Venter USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration... Chapter

More information

Do not use this vent pipe or fittings for venting incinerators of any kind.

Do not use this vent pipe or fittings for venting incinerators of any kind. ! CAUTION! Do not use this vent pipe or fittings for venting incinerators of any kind. C.S.A. Certified For Natural Gas Or Propane Tested For 100 LBS. ASME Working Pressure For correct installation of

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7. Model C Forced Draft Burners. Natural Gas or Propane MODEL C10

GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7. Model C Forced Draft Burners. Natural Gas or Propane MODEL C10 Model C Forced Draft Burners Natural Gas or Propane MODEL C10 MODEL C4 GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7 Telephone: (519) 620-0230 Telefax: (519) 620-0232

More information

Series 300 VTB. Installation Instructions

Series 300 VTB. Installation Instructions Series 300 VTB Installation Instructions Sizes 7 12 16 20 30 HP #2 Fuel Oil Gas (500 to 2500 BTU) Gas Light Oil Combination High Pressure Steam Sizes 7 thru 16 HP (125 PSI) Sizes 20 and 30 HP (150 PSI)

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Web Site: http//www.atomic4.com e-mail: thomas.stevens@cox.net INSTALLATION INSTRUCTIONS INDIGO ELECTRONICS AT-4T THERMOSTAT KIT ATOMIC 4 - ELECTRIC FWC This Indigo Thermostat Kit is designed for use with

More information

SuperKlean Washdown Products

SuperKlean Washdown Products February 2012 DURAMIX 8000 INSTALLATION AND MAINTENANCE INSTRUCTIONS **DO NOT THROW AWAY AFTER INSTALLATION** **SAVE AND DISPLAY PROMINENTLY WHERE THIS EQUIPMENT IS USED** WARNING HIGH PRESSURE AND HOT

More information

Inspection Checklist Mechanical Rough in

Inspection Checklist Mechanical Rough in Property Owner Name: Property Address: Permit Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans are on site and

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Web Site: http//www.atomic4.com e-mail: thomas.stevens@cox.net INSTALLATION INSTRUCTIONS INDIGO ELECTRONICS AT-4T THERMOSTAT KIT ATOMIC 4 - MECHANICAL FWC This Indigo Thermostat Kit is designed for use

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL OPERATING AND MAINTENANCE MANUAL NVPOM-0104 TABLE OF CONTENTS Section Page 1 SPECIFICATIONS...1 1.1 Nova Plus Specifications...1-1 1.2 Warranty...1-2 2 GENERAL BURNER DESCRIPTION...2 2.1 Burner...2-1 2.2

More information

INSTALLATION AND OPERATING INSTRUCTIONS TABLE OF CONTENTS IMPORTANT

INSTALLATION AND OPERATING INSTRUCTIONS TABLE OF CONTENTS IMPORTANT C US This manual must be left with owner and should be hung on or adjacent to the boilerfor reference. COMMON VENTING MODELS CHS-300 through CHS-399 INSTALLATION AND OPERATING INSTRUCTIONS TABLE OF CONTENTS

More information

INSTANT HOT WATER DISPENSER

INSTANT HOT WATER DISPENSER INSTANT HOT WATER DISPENSER Tank Installation Materials required (not provided) 2 mounting bracket screws (and 2 plastic anchors if attaching to drywall) Shut-Off valve and T fitting Components When you

More information

MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE

MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE PFS APPROVED FOR NATURAL GAS OR PROPANE GAS Z21.50-2014 If your plans do not allow for the venting system as outlined previously in the installing chimney/vent

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS 24-Month Maintenance Kit P/N 58015-02 For BMK2.0 (Nozzle Mix) Description of Document: This TID provides the procedures to perform recommended 24-Month maintenance on the following

More information

BASE-RAY CAST IRON BASEBOARD RADIATION

BASE-RAY CAST IRON BASEBOARD RADIATION INSTALLATION MANUAL FOR BASE-RAY CAST IRON BASEBOARD RADIATION TABLE OF CONTENTS PAGE 2 RATINGS 4 ASSEMBLY CHART 5 SYSTEM TYPES 6 SERIES LOOP SYSTEMS 7 SERIES LOOP DESIGN 8 INSTALLATION DETAILS 9 INSTALLATION

More information

215 Gallon Waste Oil Tank With Bypass Regulator Installation Instructions

215 Gallon Waste Oil Tank With Bypass Regulator Installation Instructions 215 Gallon Waste Oil Tank With Bypass Regulator Installation Instructions Lanair Products LLC 4109 Capital Circle Janesville, Wisconsin 53546 1-888-370-6531 www.lanair.com BEFORE YOU BEGIN INSTALLATION...

More information

Single stage operation oil burner

Single stage operation oil burner Installation & Operating Manual Single stage operation oil burner WARNING NON-RETROFIT APPLICATIONS If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow

More information

SCS SCS

SCS SCS Models: SCS-5-08-3 SCS-5-20-3 Manufactured by: DNS-0474 Rev A UTC Canada Corporation Division ICP 3400, Industrial Boulevard Sherbrooke, Quebec J1L 1V8 SEALED COMBUSTION SYSTEM OIL FIRED Save these instructions

More information

Instantaneous Oil-Fired Water Heater. Installation Manual OM-148. (Type D)

Instantaneous Oil-Fired Water Heater. Installation Manual OM-148. (Type D) Instantaneous Oil-Fired Water Heater Installation Manual MODEL OM-148 (Type D) IMPORTANT THIS APPLIANCE SHOULD BE INSTALLED BY A LICENSED, AUTHORIZED PERSON(S) DUE TO THE NECESSITY OF MAKING ELECTRICAL,

More information

Heat Exchanger Block Replacement Instructions

Heat Exchanger Block Replacement Instructions Series 1-4 Gas-fired water boiler Heat Exchanger Block Replacement Instructions Ultra-80 S1-4 Heat Exchanger Block Replacement Kit, Part No. 383-500-773 Ultra-105 S1-4 Heat Exchanger Block Replacement

More information

QHT Manual for: SU-2A Gas Burner

QHT Manual for: SU-2A Gas Burner 1 QHT Manual for: SU-2A Gas Burner 50,000 BTU/H to 250,000 BTU/H The burner shall be used only with NATURAL GAS or LP GAS. Warning: If the following instructions are not followed exactly, a fire or explosion

More information

Installation Manual. For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC )

Installation Manual. For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC ) Installation Manual For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC ) N404M.3 (128 liter 3-way operation with LP gas, 240 volts AC, or 12

More information

SERVICE MANUAL. Freestanding cooker 500 and 600 / Range Gas- gas Electric CFSGSV14 CFSGWH14 CFSESV14 CFSEWH14

SERVICE MANUAL. Freestanding cooker 500 and 600 / Range Gas- gas Electric CFSGSV14 CFSGWH14 CFSESV14 CFSEWH14 Freestanding cooker 500 and 600 / Range 2013 Gas- gas Electric CFSGSV14 CFSGWH14 CFSESV14 CFSEWH14 SERVICE MANUAL 2 Door assembly Removing the door assembly 1. Lift the lock of the left and right door

More information

PLEASE READ THIS MANUAL CAREFULLY BEFORE INSTALLING AND

PLEASE READ THIS MANUAL CAREFULLY BEFORE INSTALLING AND INSTALLATION OPERATION AND SERVICE MANUAL Old Salem Collection Vent Free Box with Classic Coals THIS ONLINE INSTALLATION MANUAL IS PROVIDED FOR PLANING PUPOSES ONLY. WE RESERVE THE RIGHT TO MAKE CHANGES

More information

Universal fuel unit for oil burners

Universal fuel unit for oil burners Universal fuel unit for oil burners Type U www.deltapumps.com European patent Certified Quality System rinted in Italy - DE115/0404 Universal Fuel Unit for oil burners Type U The DETA Universal Fuel Unit

More information

2012 INTERNATIONAL FUEL GAS CODE VENTS

2012 INTERNATIONAL FUEL GAS CODE VENTS 2012 INTERNATIONAL FUEL GAS CODE SECTION 502 (IFGC) VENTS 502.1 General. All vents, except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accordance with

More information

Fig. 1 - Unit PGD4, PGS4, WPG4

Fig. 1 - Unit PGD4, PGS4, WPG4 OWNER S MANUAL 14 SEER Single -Package Air Conditioner and Gas Furnace System with R -410A Refrigerant Single Phase 2 to 5 Nominal Tons Three Phase 3 to 5 Nominal Tons PGD4andPGS4SeriesE,WPG4SeriesB Fig.

More information

NMG NOZZLE MIX GAS BURNERS

NMG NOZZLE MIX GAS BURNERS INSTRUCTIONS NMG NOZZLE MIX GAS BURNERS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components, by

More information

Specifications 3. Bladder 5. Chimney 12. Air Supply 12. Anti-Rollout Device and Ash Auger Tube 14. Timer 15

Specifications 3. Bladder 5. Chimney 12. Air Supply 12. Anti-Rollout Device and Ash Auger Tube 14. Timer 15 TABLE OF CONTENTS Page No. Specifications 3 Bladder 5 Fire Door 7 Chimney 12 Air Supply 12 Anti-Rollout Device and Ash Auger Tube 14 Timer 15 Supply Line and Return Line Threaded Connectors 15 Low Water

More information

B.C.S. Shop Heaters 26, 30 & 36 (36 shown)

B.C.S. Shop Heaters 26, 30 & 36 (36 shown) BIOMASS COMBUSTION SYSTEMS, INC. 67 MILLBROOK ST., SUITE 502 WORCESTER, MA 01606 508-798-5970 - FAX 508-798-5971 B.C.S. Shop Heaters 26, 30 & 36 (36 shown) INSTALLATION MANUAL HAND FIRED SYSTEMS 8-09 Biomass

More information

Malm Fireplaces, Inc. 368 Yolanda Avenue, Santa Rosa, CA (707) Fax: (707)

Malm Fireplaces, Inc. 368 Yolanda Avenue, Santa Rosa, CA (707) Fax: (707) Malm Fireplaces, Inc. 368 Yolanda Avenue, Santa Rosa, CA 95404 (707) 523-7747 - Fax: (707) 571-8036 info@malmfireplaces.com Fire Drum 2 Tested to U/L Standards 1482 and 737 Assembly And Installation Instructions

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Series Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life,

More information

INSTALLATION INSTRUCTIONS FOR FREESTANDING DUAL FUEL

INSTALLATION INSTRUCTIONS FOR FREESTANDING DUAL FUEL INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER. IMPORTANT: SAVE FOR LOCAL ELECTRICAL INSPECTOR'S USE. READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. If the information in this

More information

Oil TRIANCO. EuroStar Range BURNER DETAILS TRIANCO - OIL BURNER. To be retained by householder

Oil TRIANCO. EuroStar Range BURNER DETAILS TRIANCO - OIL BURNER. To be retained by householder TRIANCO Oil TRIANCO - OIL BURNER BURNER DETAILS EuroStar Range To be retained by householder TECHNICAL DATA NOZZLE OUTPUT MODEL Output Burner Nozzle Pump Model pressure CO 2 (%) EUROSTAR UTILITY 50/65

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X500-2 Low voltage 12v dc Brushed motor E90-803-001-005-01 Rev 4-1 - Contents Technical specifications Technical data...3 Working field...3 Dimensions...4 Head

More information

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GBI 201-5 3C For a proper installation and in order to receive the best in operating life and efficiency from your

More information

OIL-FIRED CENTRAL FURNACE

OIL-FIRED CENTRAL FURNACE OIL-FIRED CENTRAL FURNACE Installation, Operation, and Service Manual With Users Information Section Models: CSHB60-90XE CSHB60-90XP c WARNING: Do NOT store or use gasoline or other flammable vapors and

More information

Instantaneous Oil-Fired Water Heater. Installation Manual OM-148. (Type B)

Instantaneous Oil-Fired Water Heater. Installation Manual OM-148. (Type B) Instantaneous Oil-Fired Water Heater Installation Manual MODEL OM-148 (Type B) IMPORTANT THIS APPLIANCE SHOULD BE INSTALLED BY A LICENSED, AUTHORIZED PERSON(S) DUE TO THE NECESSITY OF MAKING ELECTRICAL,

More information

Conversion: Coal to Oil

Conversion: Coal to Oil Conversion: Coal to Oil - 41 CHAPTER 7 Conversion: Coal to Oil Some types of cast iron boilers designed to burn coal are not suited to burn, oil. Aside from adapting the furnace for oil burning, changes

More information

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners 1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):

More information

CLM FORCED DRAFT STEAM BOILER

CLM FORCED DRAFT STEAM BOILER FORM 1728 3/25/2004 CLM FORCED DRAFT STEAM BOILER TABLE OF CONTENTS 1. KNOCK-DOWN TYPES AND DEFINITIONS 1 2. BOILER FOUNDATION 1 3. BOILER FRAME & TUBE INSTALLATION 2 REFRACTORY TILE INSTALLATION 3 4.

More information

Weil-McLain part numbers are found in Weil-McLain Boilers and Controls Repair Parts Lists.

Weil-McLain part numbers are found in Weil-McLain Boilers and Controls Repair Parts Lists. gas-fired water boiler Manual Replacement parts Replacement parts must be purchased through a local Weil-McLain distributor. When ordering, specify boiler model and size and include description and part

More information

Installation Instructions

Installation Instructions Installation Instructions For Fully Integrated NoFrost Combined Refrigerator-Freezers HC 2062 HCB 2062 HC/HCB 20 7082 373-00 Important PLEASE READ AND FOLLOW THESE INSTRUCTIONS These instructions contain

More information

24 VAC SYSTEM CONTROL KIT

24 VAC SYSTEM CONTROL KIT 24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG Designed for use with the SWG Series Power Venter for controlling Natural Gas or L.P. Gas draft induced appliances with a 24 VAC Gas Valve and a 30-millivolt

More information

FEATURES. Other Fed-Flush Arrangements

FEATURES. Other Fed-Flush Arrangements Brochure # 0710 TYPE TYPE... VSAF SEWAGE EJECTOR SYSTEM Flows to 600 gpm, Heads to 120, 1 thru 40 HP. Discharge size 4, 1750 and 1150 RPM, strainer in discharge pipe. HIGHLIGHTS Installations where rags

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

C O D E S & A M M E N D M E N T S

C O D E S & A M M E N D M E N T S SEVIER COUNTY UTILITY DISTRICT SEPTEMBER 2, 2014 Sevier County Utility District has adopted the 2009 International Fuel Gas Code for gas inspections. The following pages contain frequently used codes and

More information

Incinerator Model A1600 -Oil

Incinerator Model A1600 -Oil Incinerator Model A1600 -Oil Operators Manual Important Failure to cure refractory Before using will void warranty (See refractory curing procedure) Tampering with orifices in the burner will void warranty

More information

THE THOMPSON MODEL A STEAMER NEW UNIT ASSEMBLY INSTRUCTIONS

THE THOMPSON MODEL A STEAMER NEW UNIT ASSEMBLY INSTRUCTIONS THE THOMPSON MODEL A STEAMER NEW UNIT ASSEMBLY INSTRUCTIONS Included with this unit are 1 propane regulator, 1 propane hose assembly, 1 filler plug wrench and 100' of steam hose. In order to operate this

More information

24 VAC SYSTEM CONTROL KIT

24 VAC SYSTEM CONTROL KIT 24 VAC SYSTEM CONTROL KIT Model: CK-43 Tubing MG1 Barometric Draft Control The CK-43 is designed for use with the SWG Series Power Venter for controlling Natural Gas and L.P. Gas Draft Induced appliances.

More information

COPYRIGHTED MATERIAL. Chapter 1. Oil Burners

COPYRIGHTED MATERIAL. Chapter 1. Oil Burners Chapter 1 Oil Burners An oil burner is a mechanical device used to prepare the oil for burning in heating appliances such as boilers, furnaces, and water heaters. The term oil burner is somewhat of a misnomer

More information

AmazonBasics Patio Heater B00LILH3V4 B00LILH47C B010VFKZEO

AmazonBasics Patio Heater B00LILH3V4 B00LILH47C B010VFKZEO AmazonBasics Patio Heater B00LILH3V4 B00LILH47C B010VFKZEO English......................5 2 Safety and compliance 3 4 English Instruction Manual English Patio Heater Contents Make sure that the package

More information

Owner s Information Manual

Owner s Information Manual 48ES---A and 48VL---A Comfort and Performance 13 and 14 SEER Single Packaged Air Conditioner and Gas Furnace System With Puron (R---410A) Refrigerant Single and Three Phase 2---5 Nominal Tons (Sizes 24---60)

More information

Guidelines for Earthquake Bracing of Residential Water Heaters

Guidelines for Earthquake Bracing of Residential Water Heaters Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)

More information

ST 40 Oil Burner. Installation & Maintenance Manual

ST 40 Oil Burner. Installation & Maintenance Manual ST 40 Oil Burner Installation & Maintenance Manual 178 093 13 Thank you for choosing a Nu-way burner. As you would expect from a Company who has a pedigree of more than 75 years in the heating industry,

More information

ECLIPSE INFORMATION GUIDE

ECLIPSE INFORMATION GUIDE ECLIPSE INFORMATION GUIDE JUNIOR INDUSTRIAL BURNERS Models 0 & 6 JIB Info 80 0/9 Easy to install and operate. Rugged construction for long life in industrial environments. Protection against overheating

More information