SC Series Forced Draft Burners

Size: px
Start display at page:

Download "SC Series Forced Draft Burners"

Transcription

1 Webster Combustion Technology LLC 619 Industrial Road, Winfield, KS Installation, Startup, Operation and Maintenance Manual SC Series Forced Draft Burners Manual Part No R1 August, 2017 C 2017 All Rights Reserved

2 SAFETY PRECAUTIONS Good safety practices must be used when working on burner equipment. The potential energy in the electrical supply, fuel and related equipment must be handled with extreme care to prevent equipment failures, injuries and potential death. Throughout this manual, the following symbols are used to identify potential problems. WARNING This indicates a potential hazardous situation, which if not avoided, could result in personal injury or death. CAUTION This indicates a potentially hazardous situation which, if not avoided, could result in damage to the equipment. The following general safety precautions apply to all equipment work. WARNING IF YOU SMELL GAS, OPEN THE WINDOWS, ETINGUISH ANY OPEN FLAMES, STAY AWAY FROM ELECTRICAL SWITCHES, EVACUATE THE BUILDING AND IMMEDIATELY CALL THE GAS COMPANY. IN ACCORDANCE WITH OSHA STANDARDS, ALL EQUIPMENT, MACHINES AND PROCESSES SHALL BE LOCKED OUT PRIOR TO SERVICING. IF THIS EQUIPMENT IS NOT INSTALLED, OPERATED AND MAINTAINED IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS, THIS PRODUCT COULD EPOSE YOU TO SUBSTANCES IN FUEL OR FROM FUEL COMBUSTION WHICH CAN CAUSE DEATH OR SERIOUS ILLNESS AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM. IMPROPER SERVICING OF THIS EQUIPMENT MAY CREATE A POTENTIAL HAZARD TO EQUIPMENT AND OPERATORS. SERVICING MUST BE DONE BY FULLY TRAINED AND QUALIFIED PERSONNEL. BEFORE DISCONNECTING OR OPENING UP A FUEL LINE AND BEFORE CLEANING OR REPLACING PARTS OF ANY KIND: TURN OFF THE MAIN MANUAL FUEL SHUTOFF VALVES INCLUDING THE PILOT COCK, IF APPLICABLE. IF A MULTIPLE FUEL BURNER, SHUT OFF ALL FUELS. TURN OFF ALL ELECTRICAL DISCONNECTS TO THE BURNER AND ANY OTHER EQUIPMENT OR SYSTEMS ELECTRICALLY INTERLOCKED WITH THE BURNER. Service Organization Information: Company Name Address Date of Startup Lead Technician Phone Number Page 2 Safety Precautions

3 TABLE OF CONTENTS Safety Precautions... A. Introduction... Burner Model Number... SC Specifications... SC Model Configuration... Specification Data... Dimensional Data... B. Component ldentification... C. Installation... D. Special lnstructions For Canadian lnstallations... E. Burner Mounting Criteria... F. Fuel Systems... G. Initial Settings... H. Ignition Systems... I. Start-up & Operating Adjustments... J. Troubleshooting... K. General Maintenance And Care... L. Care of Burner During Shutdown... M. Replacement Parts... N. Warranty Validation & Field Start-up Report... This manual covers the Model SC burners offered by Webster Combustion Technology LLC. These burners can be used in a wide variety of Cast Iron, Firebox, Firetube, Flextube and other applications. They can fire gas, oil and combination gas and oil, with several different operating systems. READ AND SAVE THESE INSTRUCTIONS FOR REFERENCE. A. INTRODUCTION Figure A-1 Nameplate MAIMUM MODEL NUMBER SC12C-15-RM7840L-UL-IRI GAS INPUT RATING SERIAL NUMBER U81375A OIL INPUT RATING MBTU/HR IN.WC GPH PSI WARNING DO NOT ATTEMPT TO START, ADJUST OR MAIN- TAIN THIS BURNER WITHOUT PROPER TRAINING OR EPERIENCE. FAILURE TO USE KNOWLEDGE- ABLE TECHNICIANS CAN RESULT IN EQUIPMENT DAMAGE, PERSONAL INJURY OR DEATH. The startup and maintenance of the SC burner requires the skills of an experienced and properly trained burner technician. Inexperienced individuals should not attempt to start or adjust this burner. Every attempt has been made to accurately reflect the burner construction, however, product upgrades and special order requirements may result in differences between the content of this manual and the actual equipment. These special components will be described in the information provided with the burner and should be used as the controlling document. NOTE: This manual must be readily available to all operators and maintained in legible condition. 1. Nameplate Information Each burner has a nameplate with important job details, similar to the nameplates shown in Figure A-1. MINIMUM FUEL NATURAL GAS #2 FUEL OIL VOLTS AMPS HERTZ PHASE HP CONTROL CIRCUIT BURNER MOTOR OIL PUMP MOTOR /2 The serial number represents the unique number for that burner and is a critical number that will be needed for any communications with Webster Combustion. The input rates define the maximum and minimum inputs for that burner, given in MBH for gas and GPH for oil. Air atomized burners show both the oil pressure and air pressure. Pressure atomized burners only list the oil pressure. For gas firing, the gas manifold pressure is given in in wc which is inches of water column. The electrical ratings of the burner are given, with the voltage, current load, frequency and phase (this will either be single or 3-phase). For motors, the motor HP is listed. Page 3 Introduction

4 2. Ratings The ratings for each specific burner are given on the nameplate. The general burner ratings are given in Specification Sheets that follow this section. The maximum inputs are given, based on the type of fuel. Other conditions, like the supply gas pressure or the combination of fuels, emission requirements and control systems may prevent the burner from reaching the lowest firing rate. 3. Product Offering The SC burner can fire natural gas as well as #2 oil. DO NOT USE GASOLINE, CRANKCASE OIL OR ANY OIL CONTAINING GASOLINE. Figure A-2 lists the common variations and options available on this product. The minimum furnace conditions are given in Section C. 4. Your Complete Manual In addition to this manual, there are several other documents that should be considered as part of the complete manual for the burner. All of these documents are needed to support the installation and startup of the unit. These additional items include: a. The wiring diagram, which shows the limits and inter connection of the burner and vessel controls. b. The gas piping schematics, which show the components and their positions in the piping train. c. The unit material list which provides an overview of the burner requirements and a complete bill of material, including the part numbers and description for each item. d. The flame safeguard manual provides the operating sequence for the burner management system. This will be a critical document for troubleshooting any future problems. e. Catalog cuts of the major components. These provide details on the installation, adjustment and maintenance of the components used on the burner. 5. Service, Parts and other Information Service and parts are available from your local Webster Representative. For a list of Webster Representatives, please visit the Webster web site at: or call Page 4 Introduction

5 SC BURNER MODEL CONFIGURATION FIGURE A-2 SC12G -50-LMV51-M.25-M-MP-UL/CSD-1 BURNER SERIES SC G C O SC SERIES HEAD SIZE (INCHES) SC FUELS Gas Gas/Oil Oil BLOWER MOTOR HORSEPOWER / / VGD VGG M Blank M CODES AND LISTINGS UL ULc CSD-1 FM IRI NFPA-85 OIL SYSTEMS Pressure Atomizing MR Modulation By-Pass MP Modulation Simplex Air or Steam Atomization MA Air Atomization MS Steam atomizing GAS TRAIN VENDOR Siemens Siemens Maxon All Others (ASCO) - (std) GAS TRAIN SIZE /2 inches.20 2 inches /2 inches.30 3 inches.40 4 inches GAS SYSTEMS Modulation FLAME SAFEGUARD VENDOR DESIGNATION M Mark AutoFlame - mini mark Nexus Fireye LMV51 Siemens LMV52 Siemens The above represents the common model designations. Contact the factory for other options and special applications. Page 5 Model Configuration

6 Model SC - Specification Data No. 2 Oil No. 2 Oil (1) STANDARD (2,400 STANDARD MBH - EQUIPMENT EQUIPMENT AND 28,800 MBH Input) AND IMPORTANT OPTIONS IMPORTANT STANDARD OPTIONS UL EQUIPMENT STANDARD UL EQUIPMENT AND IMPORTANT OPTIONS (1) AND IMPORTANT OPTIONS Motor, Fan and Air Inlet Control Main Manual Shutoff Motor, Fan and Air Inlet Control Main Manual Shutoff Air Flow Switch (2,400 Main MBH Safety Shutoff - 28,800 MBH Input) Air Flow Switch (also with oil systems using remote (2) Main Safety Shutoff pump) Burner Mounted Control Panel, Second Safety Shutoff Switch and Four Indicator Lights Main Gas Regulator Burner Mounted Control Panel, Switch and Indicator Second Safety Shutoff Flame Lights Safety (2) Control Gas Checking Ultra Flame Violet Safety Scanner Control High and Low Gas Main Pressure Gas Regulator Switches Motor Ultra Starter Violet with Scanner Overloads Metering Gas (modulating Checking systems) Motor Controller (single phase voltage) Dual Fuel Burners Normal Open Vent High and Low (above Fuel Selector Switch Gas Pressure Switches (st d Fuel Selector Switch Only 12,500 MBH) over 2500 MBH) Opt. Linkageless Control Proven Gas Pilot Ignition Oil Drawer Assembly with Diffuser Inverted Housing Proven Gas Pilot Ignition Oil Nozzles Pilot Solenoid Gas Alternate Control Cabinet Positioning Pilot Solenoid Gas Remote Oil Pump Opt. Pilot Gas Regulator & Manual Pilot Gas Regulator & Manual Remote Control Panel Two Safety Shutoff s Pilot Gas Ignition Transformer Pilot Gas Ignition Transformer Low Oil Pressure Switch Inverted Direct Housing Spark Oil Ignition Oil Pressure Gauge Alternate Direct Spark Control Oil Cabinet Ignition Positioning Transformer Oil Metering 1. The Remote configuration Control of Panel each unit will vary with specific job requirements such Air Compressor as input rating, electrical specification and special agency approval codes. The above chart shows those items standard to a basic burner plus a few options that may be added The Indicator configuration lights are of Power each unit On, will vary Call with for Heat, specific Fuel job requirements On and Flame such Fail as input for hard rating, wired electrical panels. specification Alarm, and Low special Water, agency Power, Call for approval Heat, Ignition codes. On, The above and Fuel chart On shows for circuit those items board standard light panels. to a basic burner plus a few options that may be added. 2. Indicator lights are Power On, Call for Heat, Fuel On and Flame Fail.?. Larger motors may be required for single phase or 208 volts Model SC - Specification Data Model SC - Specification Data General General Ignition Ignition Ignition Options Gas Pressure Atomized Air Atomized The above maximum ratings are based on 0 furnace pressure, an altitude of 1000 feet, 90 o F air temperature and 60 HZ electrical supply. Use the following corrections for higher temperatures and altitude. Capacity decreases by 17% for 50 Hertz. Capacity decreases by 4% for each 1000 feet above 1000 foot altitude. Capacity decreases by 5% for each 1 inch of furnace pressure. Capacity decreases by 2% for each 10 o F increase in air temperature over 90 o F. Gas input ratings based on 1000 BTU/cu ft. and 0.64 specific gravity. Sizes and pressure will vary with gas. Essential Ordering Information and Data: Power Supply - Confirm for control circuit and electrical supply for burner motor(s) (voltage, frequency and phase). Describe Boiler or Heater to be Fired - Including the manufacturer, model number, furnace pressure and furnace size. Firing Rate - Define firing rates in MBH for gas. Fuel to be Burned - Type of gas, including the BTU value. Approval Agency - UL, FM, IRI (GE GAP), CSD-1, NFPA, Mil spec and local codes, if applicable. Flame Safety Control Preferred - Honeywell or Fireye controls. Gas Train Components Preferred - ASCO/ITT, Honeywell or Landis Control System - ON-OFF, Low Fire Start, Low-High-Low, Modulation, Posi-Control Required Options - Mounting plate, limit controls, etc. Gas Gas Fuel Oil Fuel Oil Gas Fuel Optional Oil Fuel Gas Pressure Atomized Air Atomized Power Supply: Confirm for control circuit and electrical supply for burner motor(s) (voltage, frequency and phase). Describe Boiler or Heater to be Fired: Including the manufacturer, model number, furnace pressure and furnace size. Firing Rate: Define firing rates in MBH for gas. Fuel to be Burned: Type of gas and/or oil, including the BTU value. Approval Agency: UL, FM, IRI (GE GAP), CSD-1, NFPA, Mil spec and local codes, if applicable. Flame Safety Control Preferred: Honeywell, Fireye or Siemens controls. Gas Train Components Preferred: ASCO/ ITT, Honeywell or Landis Control System - Modulation, Posi-Control Required Options - Mounting plate, limiting controls, etc. Page 6 Specification Data

7 Model SC - Dimensional Data (Dimensions are +/- 1/4 inch) Fuels Burned and Control Systems - Natural Gas - Light #2 Oil, Mechanical Pressure - Modulating or Micro Modulation - Control Circuit Requires 120 vac, 60 Hz, Single Phase Voltage Supply Model SC burners can be packaged to meet specific requirements of IRI, FM, GE GAP, NFPA, MIL spec. or other special insurance or local code requirements. Page 7 Dimensional Data

8 B. COMPONENT IDENTIFICATION This secion shows the different common components used in the SC burner line and should be helpful to identify parts described elsewhere in this manual. Gas Separator Solenoid Oil Pressure Switch Oil Pressure Gauge Oil Lines Secondary Fuel Mod Motor Secondary Fuel Supply Figure B-1 SC Dual Fuel Burners Primary Fuel Butterfly Primary Fuel Supply Pilot Gas Regulator Louver Box Air Pressure Switch Control Cabinet Figure B-2 SC Burner Side View Oil Pressure Gauge Control Transformer Combustion Head IgnitionTransformer Blower Motor Page 8 Identification

9 UV Sight Port Secondary Gas Orifices Oil Nozzles Primary Gas Orifices Spark Plug Diffuser Assembly Figure B-3 SC Head Figure B-4 Control Panel Hard Wired Design Control Relays Burner Motor Starter Switch / Light Panel BMS Display Burner Management System Terminal Strip Pressure Gauge Air Chamber Belt Guard Air Filter Electric Motor Compressor Figure B-5 Air Compressor Air Discharge Connection Page 9 Identification

10 SECONDARY ORIFICE PLATE MOUNTING FLANGE SECONDARY GAS CONNECTION PRIMARY ORIFICE PLATE SECONDARY ORIFICE TUBES OUTER CYLINDER PRIMARY GAS CONNECTION HOUSING MTG. FLANGE GAS TUBE SECONDARY AIR SLOTS IGNITION HOLDER INNER CYLINDER PRIMARY GAS MANIFOLD DIMENSION WILL VARY DEPENDING ON VESSEL INSERTION DEPTH SECONDARY GAS MANIFOLD Gas Orifice Part Number and Description CHECK VALVE OIL NOZZLE ACCESS COVER OIL SUPPLY LINE Figure B-8 Drawer Assembly Page 10 Identification

11 C. INSTALLATION Prior to installing the burner, the site conditions and utilities need to be evalulated. This section provides some general questions that can help the review process. Inspect the burner for any undetected damage that may have occurred during shipment or by job-site handling. Special attention should be given to the control panel and protruding parts. Check wiring connections and fasteners for tightness. Verify that all ship loose (or separately shipped) items are on hand. This normally will be gas train components, mounting lugs and insulating rope. Also, front mounting plate and remote oil pump set, if supplied. The burner material list included with the instruction manual serves as a good checklist for this purpose. 1. Is there adequate outside ventilation to supply the needed air for safe combustion as required by your local regulatory agency? 2. If a burner mounting plate is required, is it available and does it meet specifications? (See Section E) 3. Is the correct voltage available for the control circuit and is the correct voltage available for the blower motor as well for the remote oil pump set and air compressor, if used? 4. Will the burner properly fit the boiler or heater with ample clearance on top, bottom and sides? 5. If a gas burner, will there be adequate gas pressure to assure the specified firing rate? 6. If a combination burner, is gas available at the burner location? 7. If a combination burner, what is the age and condition of the oil tank(s) and will there be special piping arrangements needed to deliver the oil to the burner? Important Note: The SC series burners must be operated with a two-pipe system. 8. If a retrofit installation, has the same oil grade always been used? Does it meet the grade specified on the burner s rating plate? 9. Is there adequate flue provisions to assure SAFE and proper venting of the burner? 10. All manuals should be reviewed and understood and stored in a convenient place. 11. Teflon tape should not be used on any field piping. 12. Rope gaskets should be used between vessel and mounting plate, and between mounting plate and burner. 13. Gas piping should be flushed (cleaned) prior to use. 14. Check minimum straight lengths for gas pressure regulator and/or sensing line. 15. Oil piping to be flushed (cleaned) prior to use. 16. Check pump suction pressure (max 10 Hg) or max press (3 psig) if transfer pump is used or tank elevation is higher than the pump. 17. Strainer before oil pump, sized for max pump suction capacity. 18. If multiple vessels connect to a single stack, are they sized and designed to maintain +/- 0.1 wc draft at the vessel outlet under all operating conditions. 19. Is stack designed to maintain +/- 0.1 wc at outlet during all operating conditions. WARNING DO NOT USE TEFLON TAPE OR COMPOUNDS CONTAINING TEFLON. THIS COULD DAMAGE THE VALVES CREATING AN UNSAFE OPERATION 20. Is the burner mounting plate and burner head sealed with rope gasket? (See Figure E-2) 21. Is there a drip leg in the gas supply to capture foreign material? (See Figure C-1) 22. Is the piping between the gas train and burner done in a manner that will minimize the pressure drop? 23. Has all of the piping been pressure checked for leaks? 24. Is the combustion chamber of proper size and is the center-line height of the burner head adequate? (See charts C-2 & C-3.) CAUTION THE COMBINATION BURNER SHALL ONLY BURN THAT GRADE OF OIL SHOWN ON THE RATING PLATE. DO NOT USE GASOLINE, CRANKCASE OIL, OR ANY OIL CONTAINING GASOLINE OR TOIC CONTAMINANTS. Page 11 Installation

12 Figure C-1 Typical Gas Piping PILOT LINE (FIELD PIPED) PILOT GAS PRESSURE REGULATOR PILOT SHUTOFF VALVE GAS SUPPLY LOW PRESSURE SWITCH MANUAL GAS SHUTOFF VALVE PILOT SOLENOID VALVE HIGH PRESSURE SWITCH DRIP LEG GAS PRESSURE REGULATOR IF APPLICABLE, WEBSTER-SUPPLIED GAS TRAIN SHUTOFF VALVE SHUTOFF VALVE LEAK TEST VALVE BURNER Chart C-2 Chart C-3 TYPICAL COMBUSTION CHAMBER SIZE FOR FIREBO BOILERS, WATERTUBE & CAST IRON SECTIONAL TYPES TYPICAL COMBUSTION CHAMBER SIZE FOR SCOTCH MARINE FIRETUBE BOILERS D. SPECIAL INSTRUCTIONS FOR CANADIAN INSTALLATIONS 1. The installation of a burner shall be in accordance with the regulations of the provincial installation requirements, or in their absence, the following shall govern: Gas Burners--CGAB149.1 and CGAB149.2 Authorities having jurisdiction should be consulted before installations are made. 2. All electrical wiring shall be done in accordance with the Canadian Electrical Code, Part I. 3. The installer shall identify (label) the main electrical power disconnect and the manual shut-off valve on the gas and/or oil supply drop-line to the burner. 4. Oil and gas burning equipment shall be connected to flues having sufficient draft at all times, to assure safe and proper operation of the burner, no more than iwc. Page 12 Installation/Canadian Installations

13 E. BURNER MOUNTING CRITERIA It is of vital importance that the burner be properly mounted to the boiler or appliance being fired. Improper mounting can cause leakage of the hot gases back around the burner head resulting in warpage and deterioration. The following illustrations show the proper way the burner must be installed to validate warranty conditions. TYPICAL SC BURNER REFRACTORY FRONTPLATE Figure E-1 Refractory Dimension A B Dimensions - Inches MODEL DIM. A DIM. B SC SC SC SC SC SC SC SC SC SC SC SC SC Contact Webster for more detailed refractory drawings. BURNER MUST BE LEVEL REFRACTORY FRONT PLATE THIS SURFACE MUST BE SEALED AGAINST THE VESSEL. CHECK VESSEL MOUNTING REQUIREMENTS. THIS SURFACE MUST BE SEALED AGAINST THE VESSEL. CHECK VESSEL MOUNTING REQUIREMENTS. FILL VOIDS BETWEEN FRONT PLATE AND VESSEL WITH CERAMIC BLANKET 4 DEEP OR AS DEFINED BY VESSEL MANUFACTURER IF GAP IS OVER 3/16 WRAP BURNER NOSE WITH HIGH TEMPERATURE CERAMIC INSULATION ROPE ATTACHMENT TO VESSEL VARIES WITH MANUFACTURE. (FOLLOW VESSEL MANUFACTURER S RECOMMENDATION) THE GAS PIPING FROM THE BURNER TO THE TRAIN SHOULD HAVE AS FEW ELBOWS AS POSSIBLE TO REDUCE PRESSURE DROP. Figure E-2 Burner Mounting Instruction Page 13 Burner Mounting Criteria

14 F. FUEL SYSTEMS The SC burner can be equipped with a wide range of fuel and operating systems to control the fuel, air, modulation and pilots. This section describes how these systems operate. Burner start-up is expected to be done by service personnel who are qualified in the basics of mechanical know-how. The following illustrations and information is supplied to identify the various fuel; air and ignition devices that have Adjustment Features. All adjustments can be done with common place tools normally carried by burner and boiler service personnel. NOTE Refer to the bulletins included in the manufacturer s data section of the burner instructions manual for items below. 1. Pressure atomized oil systems MP - Modulating Simplex Nozzle Oil Metering 2 Low Oil Pressure Switch Main Oil Solenoid Safety Oil Solenoid 1 1 Gauge Port Adjustment Oil Nozzle Return to Tank, (No Manual s in this Line) Suction Supply Line Field Piped Check By Others Shutoff Check 1 Strainer By Others (Unless Specified on Order) Oil Pump 1 2 Notes & Options These Lines are Field Piped if a Remote Pump is Used Usage Requirement Varies with Code MR - Modulating Return Flow Nozzles Back Pressure Reg. 2 Low Oil Pressure Press. Sw. Gauge 1 Main Oil Solenoid Safety Oil Solenoid Suction Supply Line Shutoff 1 Check Strainer Gauge Port Oil Pump Inline Check Oil Nozzle (Bypassing) Notes & Options By Others (Unless Specified in Order) Return to Tank (No Manual s in this Line Check 1 Check Oil Metering Pressure Gauge 1 2 These Lines are Field Piped if a Remote Pump is Used Required Above 20 GPH if a Remote Pump is Used Field Piped Page 14 Fuel Systems

15 2. Air Atomized Oil Systems Air Filter Ball (man. set to adjust air volume & high fire air pressure) Compressor Safety Air Chamber Air pipe same size as discharge opening in air chamber (field Piped) Low Atomizing Pressure MA - Modulating #2 Oil Check Gauge Nozzle Pressure Gauge Oil Metering N.C. Main Oil Safety Oil Ball Oil Gauge Flexible Metal Hoses or Copper Tubing Low Oil Pressure Gauge Ball or Gate Gauge Relief Compound Gauge Strainer Check Check Gate Field Piped Return to Tank Oil Suction Field Piped MA or MS - Modulating House Air or Steam 125 PSIG Max. Atomizing Steam Condensate Return Steam Trap Ball or Gate Steam Syphon Steam Strainer Drip Leg 300 lb. Gauge Pressure Reducing Ball or Gate Field Piped Metering Lever Ball Linked to Mod. Motor N.C Atomizing Steam Syphon Low Atomizing Pressure Switch Check Steam Syphon Gauge NOTE: House air does not use steam Syphon or Steam Trap Page 15 Fuel Systems

16 2. Gas Systems Illustrated Gas Trains by Capacity and Code: The following illustrations show the Webster configuration for UL, FM and IRI as grouped by UL capacity ratings. Refer to the legend below for component part identification. These illustrations are not to be used for field erection and/or system design purposes. UL Capacity Range BTU/Hr. Operation Mode Webster Designation Code UL FM Illustration To 2,500,000 2,500,001 to 5,000,000 5,000,001 to 12,500,000 12,500,001 and Up Modulating Modulating Modulating Modulating Modulating Modulating Modulating M M M M M M M UL-FM Modulation Gas Piping Diagram - Up To 2,500 MBH Firing Rate UL Modulation Gas Piping Diagram - 2,500 To 5,000 MBH Firing Rate Page 16 Fuel Systems

17 FM Modulation Gas Piping Diagram - 2,500 To 5,000 MBH Firing Rate UL Modulation Gas Piping Diagram - 5,000 To 12,500 MBH Firing Rate FM Modulation Gas Piping Diagram - 5,000 To 12,500 MBH Firing Rate UL Modulation Gas Piping Diagram - Over 12,500 MBH Firing Rate Page 17 Fuel Systems

18 FM Modulation Gas Piping Diagram - Over 12,500 MBH Firing Rate G. INITIAL SETTINGS The burner will be set at the factory for normal initial settings. These are only rough settings that must be adjusted at startup to match the furnace, fuel pressure and environment of the specific application. These general settings are covered in this chapter as a means of checking the burner or readjusting the burner if the settings are lost. Presets can change during shipping. COMBUSTION AIR CONTROL Panel Adjusting Screw Air Proving Switch 1. OIL NOZZLE POSITION The oil nozzle will be adjusted at start-up and may be moved in or out from this initial setting. 2. AIR PROVING SWITCH The air proving switch has been adjusted at the factory for an initial setting. If the switch trips during initial start-up, turn the adjustment screw CCW two full turns to reduce the trip pressure setting. Air Flow Interlocking Switch CAUTION ACTUATOR MOUNTINGS CAN BE BENT OR MOVED DURING SHIPMENT AND INSTALLATION. THEY MUST BE CHECKED PRIOR TO OPERATION AND ANY FAULTS CORRECTED. FAILURE TO CORRECT A MISALIGNED CONTROL WILL RESULT IN PREMATURE FAILURE. Page 18 Initial Settings

19 H. IGNITION SYSTEM Every burner set-up is different, therefore the positions below are indications only and tuning must be done by fully trained and qualified personnel. 1. Pilot A crucial part of reliable burner operation is a dependable pilot. The way the SC burner operates is that the primary zone is lit first, thus acting as a pilot, before the secondary fuel valve is opened and the burner can operate the entire operating range. The spark plug position can be seen in figure H-1. Pilot gas pressure should be measured at the 1/8 port located downstream of the primary solenoid valve. 2. Air Damper Position The air damper should be near close at low fire and close to full open at high fire. 3. Gas Modulating Control Position The gas valve should be open about 10% at low fire and stroked at least 60% open at high fire. 4. Oil Modulating Control Position For pressure atomizing, the low fire position should be adjusted to get the correct low fire pressure, as stated on the rating label. Typically, this would be 100 psi for simplex systems and 65 psi for return flow nozzles. The high fire position should be about 45º to 60º travel from low fire. For air atomizing, the low fire should be on about #2 position and the high fire should be about the #8 position. Spark Plug Figure H-1 I. STARTUP AND OPERATING ADJUSTMENTS 1. Pre-Start Check List 2. Burner Drawer Adjustments 3. Gas Setup 4. Pressure Atomized Oil Setup 5. Air Atomized, #2 Oil Setup 6. Operating Control Adjustments 7. Limit Tests 8. Pilot Test 9. Burner Shutdown 10. Restarting After Extended Shutdown This section covers the startup and operating adjustments of the Webster Models. WARNING BURNER STARTUP, COMBUSTION ADJUSTMENTS AND LIMIT CONTROL ADJUSTMENTS SHOULD BE PERFORMED ONLY BY TRAINED, EPERIENCED SERVICE TECHNICIANS. ATTEMPTING TO PER- FORM THESE FUNCTIONS WITHOUT THE PROPER TRAINING CAN RESULT IN EQUIPMENT DAMAGE, PERSONAL INJURY OR DEATH. Before proceeding with startup and adjustment, be sure that overall installation is complete. Review the boiler operating and installation manual, as well as all control manuals to verify that equipment is ready for operation. These manuals must be read prior to start of equipment. If you are not qualified to service this equipment, DO NOT TAMPER WITH THE UNIT OR CONTROLS - CALL YOUR SERVICEMAN. A block diagram of the startup sequence for the SC burner can be found on page 25, Figure I-3. When finished with startup, document valve and linkage positions, pressures, and settings for future reference. READ AND SAVE THESE INSTRUCTIONS. During purge, all solenoids, including the gas separator solenoid valve, are closed and are to remain closed until called upon. After purging the system for at least 30 seconds, the spark plug is activated. Waiting for one second for the spark to initiate, the pilot solenoid valve is opened which will ignite the primary zone. When the flame safeguard system detects a strong signal, it will open the main fuel valve to start the ignition of the secondary zone. Following a 4-second delay, the gas separator solenoid valve will open and the pilot solenoid can be closed. From this point on, the burner can be driven to low fire. Page 19 Ignition Systems/ Startup and Operating Adjustments

20 1. Pre-Start Check List Before starting the burner, a complete review of the installation, wiring and piping of the burner, boiler and all supporting equipment must be complete and all of these items must be ready for operation prior to starting. The following is a general review: All wiring is connected. Gently pull on all the wires to make sure that they are connected properly. All fuel lines are connected and tight. Pilot gas is connected. Burner is mounted to vessel and floor, with all bolts secured. The stack is connected and routed to the outside. Draft controls are installed and operational, if needed. Gas vent lines are connected and routed to the outside, if required per code. Do not start the unit unless all cleanout doors are in place and secured. The vessel is completely installed, filled with water and operating controls checked. Support equipment is in place and ready (feed pumps, draft controls, steam/hot water systems, boiler limits and controls and feedwater systems). A load must be available for the burner startup and adjustment process. The burner must be operated at high rates for extended periods and the load must be able to use this energy. A combustion analyzer with O 2 and CO (for gas) must be available to tune combustion. A smoke spot tester must be available for oil firing. A NOx analyzer must be available. All of these analyzers must be recently calibrated and able to provide accurate readings. Other test equipment, including manometers, gauges and volt meter shall be available. Manometer or gauge on the gas manifold. Manometer or gauge before and after gas pressure regulator. Draft gauge or manometer (at stack outlet). Draft gauge or manometer for furnace pressure. 2. Burner Drawer Adjustments The burner drawer has several adjustments built into the design that allow the combustion to be tuned. While this can simplify the combustion tuning process, care must be used to retain the relative position of other components during this sequence. If these adjustments are required, follow the sequence listed to perform the adjustments. The burner drawer must be removed for access to components, follow the following steps: a. Loosen and remove the screws on the burner drawer. b. Disconnect the scanner by screwing it off of the scanner tube. In some cases, the scanner simply pulls out, with a spring tension. Secure the scanner so that it is protected from shock. c. Pull the drawer out, holding it centered in the opening to prevent it from hanging up while being pulled. d. Set the drawer down horizontally. To re-install the burner drawer, simply work the procedure in reverse. 3. Gas Setup a. Place the burner switch in the OFF position b. Place the burner management system in manual mode. If this is a combination fuel burner, make sure the fuel selector switch is on GAS. c. Place the burner management system in the low fire position. d. Close the downstream manual shutoff valve (closest to the burner head) on the gas train. e. Turn the electrical power on for the burner, boiler and related components. f. Verify that the gas metering valve is nearly closed, the vent valve (if equipped) is operating and the gas pilot valve is not open (the solenoid will hum and feel warm). g. Turn the burner switch on. This will start the blower motor and initiate the prepurge cycle. h. When the prepurge sequence is complete and the low fire start switch is made, the flame safeguard should indicate the presence of a flame. i. When the pilot flame is established, the flame safeguard will energize the main gas valve (indicated with the Fuel Light). This operation of the main fuel valves must be visually checked by observing the valve stem operation. j. After the timer has completed the trial for main flame, the burner will go out on alarm (the closed manual gas valve prevented the burner from lighting). At this time, the gas valves must be visually checked to verify that they have closed. This test sequence proves the proper operation of the primary control. k. Press the reset button and restart the burner. When the pilot has started, open the manual gas valve to allow the main flame to start. l. After a few seconds, the combustion analyzer should have an accurate reading of the O 2 in the stack. Fig. I-1 shows the typical range of O 2 at different firing rates, and the burner should be adjusted to be within this range. Rough settings for low and mid fire combustion settings are adequate at this time. Once the high fire is set, the other settings can be fine tuned. Page 20 Startup and Operating Adjustments

21 m. Operate the burner until the boiler is warmed up and near the operating pressure or temperature. Increase the firing rate. Put the low fire hold switch in auto mode, while monitoring and adjusting the O 2 level. Adjust the gas pressure regulator as needed to reach the high fire input. n. Adjust the high fire input to match the maximum input listed on the rating label. At high fire, the gas butterfly valve should be at least 75 degrees open (more if available gas pressure is low), and the gas pressure regulator adjusted to obtain the rating. The input should be measured using the following: Calculating Natural Gas Input Gas MBH = HHV x [(Patm + Pgas)/29.92] x [520/(Tgas +460)] x [measured ft3/sec] x [3600 sec/hr] Where: MBH = 1000 s of BTU/H input HHV = Higher heating value of gas, BTU/cubic feet Patm = Atmospheric pressure in inches Hg Pgas = Gas pressure before gas meter in inches Hg (inches HG = PSIG x 2.04) Tgas = Gas temperature at the flow meter, in degrees F Measured ft 3 = volume of gas measured by meter sec = Time for measured ft 3 to flow through meter Note: Some gas meters require a 6 inch wc correction to Pgas. Consult your meter calibration data. NOTE: The listed manifold pressures are an approximate value and can vary with operating conditions and normal tolerances. The fuel flow rate must be measured to obtain an accurate input value. o. Adjust the air damper to obtain the correct NOx and CO levels. p. Modulate the burner to low fire, adjusting the O 2 level as the burner modulates to match the desired emission level. q. Adjust the low fire input and air damper adjustments. If the NOx is too high, close the primary butterfly valve more. If the CO is too high, close the air damper in small increments. r. Re-adjust the midfire points for the correct emission level. s. Adjust the low gas pressure switch to be 10% below the lowest expected gas pressure. With a gauge or manometer at the same location as the low gas pressure switch, modulate the burner to determine the firing rate with lowest gas pressure. At the lowest gas pressure, adjust the low gas pressure setting up until the switch breaks and causes the burner to shutdown. From the scale reading of the switch, adjust the setting to a pressure that is 10% lower than the shutdown pressure. For example, if the switch opened at 10 inches as indicated on the low gas pressure switch, the switch should be adjusted to a reading of 9 inches. Remove gauge or manometer and plug opening. Cycle the burner on and off to determine if the limit works properly. If the limit causes nuisance shutdowns because of small pressure drops during startup, reduce the pressure setting an additional 5%. t. Adjust the high gas pressure switch to be 10% above the highest expected gas pressure. With a gauge or manometer at the same location as the high gas pressure switch, modulate the burner to determine the firing rate with the highest gas pressure. At the highest gas pressure, adjust the high gas pressure setting down until the switch opens and causes the burner to shutdown. From the scale reading of the switch, adjust the setting to a pressure that is 10% higher than the shutdown pressure. For example, if the switch opened at 10 inches as indicated on the high gas pressure switch, the switch should be adjusted to a reading of 11 inches. Remove the gauge or manometer and plug the opening. Cycle the burner on and off to determine if the limit works properly. If the limit causes nuisance shutdowns because of small pressure changes during startup, increase the pressure setting an additional 5%. u. The burner should be operating at low fire to adjust the air proving switch. Turn the adjusting screw cw (in) until the burner trips out (shutdown caused by the air flow switch). Turn the adjustment screw ccw (out) 1 1/2 turns from the point of shutdown. Check the operation at higher rates. 4. Pressure Atomized Oil Setup The pressure atomized oil system has a limited range of adjustment for low and high fire, dictated by the operation of the oil nozzle. The combustion air must be adjusted to match these rates. a. Place the burner switch in the OFF position. b. Place the burner management system in manual mode. If this is a combination fuel burner, make sure the fuel selector switch is on OIL. c. Place the burner management system in the low fire position. d. Turn the electrical power for the burner, boiler and related components on. e. Verify that the oil metering valve is nearly opened (the valve will be closed at high fire). f. Turn the burner switch on. This will start the blower motor and initiate the purge cycle. Page 21 Startup and Operating Adjustments

22 g. When the prepurge sequence is complete and the low fire start switch (if used) is made, the pilot valve will open and the pilot flame should be visible through the burner sight port. h. When the pilot flame is established, the flame safeguard will energize the main valves (indicated with the Fuel Light), and the burner should ignite at low fire. This operation of the fuel valves must be visually checked by observing the valve stem moving up with a motorized valve or hearing the clicking noise from a solenoid valve. NOTE: If the burner is not operating as indicated, follow the troubleshooting steps to determine the problem and corrective action. i. The main flame may not light on the first attempt, because it must fill the oil lines before providing oil to the nozzle. Press the reset button on the flame safeguard to restart the burner. j. In a few seconds, the combustion analyzer should have an accurate reading of the O 2 in the stack. The O 2 level should be between 4% and 7%, and the nozzle oil pressure should be between 50 and 70 PSIG return line pressure. Do not attempt to fine tune combustion until the high fire has been set. WARNING DO NOT ATTEMPT TO START THE BURNER WHEN ECESS OIL HAS ACCUMULATED, WHEN THE UNIT IS FULL OF VAPOR, OR WHEN THE COMBUSTION CHAMBER IS HOT. k. Operate the burner until the boiler is warmed up and near the operating pressure or temperature. l. Increase the firing rate, using the potentiometer or put the low fire hold switch in auto position, while monitoring and adjusting the O 2 level. m. At high fire (end of the modulating motor travel), adjust the high fire input (open or close the fuel valve) to match the maximum input and/or pressure listed on the rating label. The fuel metering valve should be nearly closed (or closed) at this point and the nozzle pressure should be at the pressure rating indicated on the rating label (return line) for the SC. n. Modulate the burner to low fire, adjusting the O 2 level as the burner modulates. p. Adjust the low fire input and air damper adjustments. q. Re-adjust midfire points for correct emission levels. r. Adjust the NOx levels at low and midfire rates to be about 10% under the guaranteed levels or as required for the gas firing. s. The burner should be operating at low fire to adjust the air proving switch. Turn the adjusting screw cw (in) until the burner trips out (shutdown caused by the air flow switch). Turn the adjustment screw ccw (out) 1 ½ turns from the point of shutdown. Check the operation at higher rates. t. Adjust the oil pressure switch to trip and shutdown the burner at a pressure that is 10% lower than the supply oil pressure. 5. Air Atomized, #2 Oil Setup The air atomized oil system has the potential for a large turndown range similar to gas and has the potential to be adjusted to different low fire rates. See the burner nameplate for details on actual rates for this burner. a. Place the burner switch in the OFF position. b. Place the burner management system in manual mode. c. Place the burner management system in the low fire position. d. Turn the electrical power for the burner, boiler and related components on. e. Verify that the oil metering valve is at the nearly closed position. f. Turn the burner switch on. This will start the blower motor and initiate the purge cycle. g. When the prepurge sequence is complete and the low fire start switch is made, the pilot valve will open and the flame should be visible through the sight port. h. When the pilot flame is established, the flame safeguard will energize the main oil valves (indicated with the Fuel Light), and the burner should ignite at low fire. This operation of the main fuel valves must be visually checked by observing the valve stem moving up with a motorized valve or hearing the clicking noise from a solenoid valve. NOTE: If the burner is not operating as indicated, follow the troubleshooting steps to determine the problem and corrective action. WARNING DO NOT ATTEMPT TO START THE BURNER WHEN ECESS OIL HAS ACCUMULATED, WHEN THE UNIT IS FULL OF VAPOR, OR WHEN THE COMBUSTION CHAMBER IS HOT. i. After a few seconds, the combustion analyzer should have an accurate reading of the O 2 in the stack. The O 2 level should be between 4% and 7% (see Figure I-1 for O 2 rates), and the nozzle oil pressure should be between 5 and 15 PSIG. Do not attempt to fine tune combustion until the high fire input has been set. The air damper should be positioned for the correct low fire settings. The atomizing air pressure can be adjusted using the air bleed valve. j. Operate the burner until the boiler is warmed up and near the operating pressure or temperature. k.increase the firing rate, using the manual potentiometer, while monitoring and adjusting the O 2 level. Adjust the oil pressure and atomizing air pressure as needed to reach high fire position. Page 22 Startup and Operating Adjustments

23 Natural Gas < 9 ppm NOx < 30 ppm NOx #2 Oil Figure I-1 Typical O 2 levels % Power Rate Min O 2 Max O 2 Min O 2 Max %O 2 Min O 2 Max %O 2 30% % % % l. At high fire (end of the modulating motor travel), adjust the high fire input to match the maximum input listed on the rating label. Using a flow meter, the fuel input may be measured using the following equation, Oil GPH = [Gal end Gal start] x [3600 sec/hr] / [measured sec] Where Gal end = meter gallons at end of test Gal start = gallons at start of the test Measured sec = measured time of test GPH = Gallons of oil per hour FIGURE I-2 Typical Atomizing Air Pressure % Rate Minimum m. Adjust the NOx level to be about 10% below any guaranteed NOx performance. n. Modulate the burner to low fire, adjusting the O 2 level as the burner modulates. o. Adjust the low fire input, using the fuel and air damper adjustments. p. Re-adjust the midfire points for the correct O 2 levels. See Figure I-2 for Atomizing Air Pressure. q. The burner should be operating at low fire to adjust the air proving switch. Turn the adjusting screw cw (in) until the burner trips out (shutdown caused by the air flow switch). Turn the adjustment screw ccw (out) 1 ½ turns from the point of shutdown. Check the operation at higher rates. 6. Operating Control Adjustments The operating controls must be adjusted to properly cycle the burner ON and OFF and provide modulation. The controls should not force the burner into rapid ON-OFF cycles, as this will cause premature failure of the motor and operating equipment. The operating control must be adjusted to provide the ON pressure or temperature desired. It must allow the burner to come on and start before the temperature or pressure drops into the modulating range. The OFF pressure or temperature must be sufficiently above the ON point to allow a reasonable run time. The modulating control must be adjusted to start modulation at some reasonable point below the ON temperature or pressure and provide modulation to high fire at the lowest temperature or pressure. 7. Limit Tests Once the burner has been started and the operating pressures and temperatures have been set, the limit switches need to be adjusted so that they will trip if the pressure or temperature exceeds the operating value, but will not trip with normal variations. The switch should be checked for proper operation by allowing the temperature or pressure to vary below (or above) the recommended level to insure that they provide safe shutdown before the burner operation is affected. In some high pressure or temperature switches, where the temperature or pressure cannot be set high enough to trip the switch, the switch can be checked by lowering the set point to prove that the switch will provide safe shutdown. The limit switches include the air proving interlock switch on the burner. Limits for gas operation could include the high and low gas pressure switches and for oil firing, the high and low oil pressure switches, high and low oil temperature switches and the atomizing air pressure switch. If in doubt about which limits are on a burner, refer to the wiring diagram that will show each item. Limit switches need to be checked regularly to ensure they are operating properly. See the maintenance section. Page 23 Startup and Operating Adjustments

24 8. Pilot Test Once the burner has been set for the firing rates intended, the pilot must be checked for proper operation and safety. The minimum pilot test is done to insure that a pilot which can be seen by the scanner will light the main flame. a. During a startup sequence, measure the time required to light the main flame after the fuel valves have been energized. This will be used to monitor the test with reduced pilot. b. Lock the flame safeguard into the pilot position (refer to the manual for the flame safeguard for this setting) c. Adjust the gas pressure regulator to the pilot for a minimum value while still holding the minimum signal strength for the scanner. d. Release the flame safeguard from the pilot position and allow it to cycle though the main flame proving sequence. e. This reduced pilot must reliably light the main flame. Monitor the time from the main fuel valve opening and do not allow the burner to continue if the time is more than an additional two to three seconds from the initial time measured above. f. Run through two or three cycles. g. Failures due to reduced scanner signal are also acceptable. WARNING THE MINIMUM PILOT TEST REQUIRES CLOSE SUPERVISION OF THE COMBUSTION PROCESS. FAILURE TO CLOSELY MONITOR THE MAIN FLAME TEST TIME COULD RESULT IN DAMAGE, INJURY OR DEATH. h. If the pilot does not light the main flame under these test conditions, adjust the fuel pressure to the primary (pilot) zone i. The infrared detector must be tested for hot refractory pickup. This test is performed to make sure that the scanner does not see hot refractory that could be mistaken for a flame. j. After the burner has been operating for some time at high input levels and the refractory in the vessel is hot, the burner should be cycled off while monitoring the scanner signal. k. The flame signal should drop off quickly as the flame goes out and should be well below the minimum level (indicating a flame) at the end of the post purge cycle. l. The UV detector must be tested for spark pick-up. Turn the burner on, with the pilot shut off, during the ignition cycle the flame signal should be well below the minimum level (indicating a flame). m. If the flame signal does not drop out as required, this may indicate a faulty scanner or amplifier. 9. Burner Shutdown Normal operation of the burner will allow the operating controls to shut the burner down when the load demand is satisfied. If the burner needs to be shut down for any reason, the ON-OFF switch can be used to quickly turn the burner off. This will instantly cause the fuel valves to close and start a post purge cycle to remove any unburned fuel from the vessel. In an emergency shutdown, all fuel and electrical power should be de-energized or turned off to secure the burner. This would include the main power disconnect, the manual gas shutoff valve at the drop down line and if equipped, the manual oil valve to the nozzle. It is recommended that the burner be manually driven to low fire before turning the burner off, as this reduces the dynamic and thermal stress. If the burner will remain off for some time, the manual fuel valves, fuel pumps and power supply should be turned off. CAUTION ALWAYS KEEP THE FUEL SUPPLY VALVE SHUT OFF WHEN THE BURNER IS SHUT DOWN FOR AN ETENDED PERIOD OF TIME. 10. Restarting After Extended Shutdown Extended shutdowns require the same startup process as those outlined above. In addition, the following advanced cleaning must be done: a. The air atomized oil nozzle should be removed and cleaned, if pressure atomized they should be replaced. Use care in cleaning to preserve the sharp edges of the nozzle, which are required to maintain good atomization. b. The oil filter and strainer must be removed and cleaned prior to starting. CAUTION DO NOT START THE BURNER UNLESS ALL CLEANOUT DOORS ARE SECURED IN PLACE. Page 24 Startup and Operating Adjustments

JBFX/HDFX Series Forced Draft Burners

JBFX/HDFX Series Forced Draft Burners Price: $50.00 US $75.00 Canadian Webster Combustion Technology, L.L.C. 619 Industrial Road, Winfield, KS 67156 Installation, Startup, Operation and Maintenance Manual JBFX/HDFX Series Forced Draft Burners

More information

FGR. Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM. FGR-8 through FGR-22 (25 HP to 1000 HP)

FGR. Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM. FGR-8 through FGR-22 (25 HP to 1000 HP) FGR Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM FGR-8 through FGR-22 (25 HP to 1000 HP) Gas, Light Oil or Combination MANUFACTURED BY JOHN ZINK COMPANY, LLC

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas

More information

Type CG Series Forced Draft Gas Burner

Type CG Series Forced Draft Gas Burner Type CG Series Forced Draft Gas Burner Designed and built by Canadians for Canadian Winters By PENDELL BURNERS Office & Plant Address: 155 Regina Road, Unit #3 Woodbridge, Ontario L4L 8L9 Telephone: (416)

More information

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not

More information

Product Information. Model: HG, HL, HLG Burner Sizes: 10, 13, 15, 17, 20, 21, 25 GENERAL DESCRIPTION U.L. STANDARD EQUIPMENT

Product Information. Model: HG, HL, HLG Burner Sizes: 10, 13, 15, 17, 20, 21, 25 GENERAL DESCRIPTION U.L. STANDARD EQUIPMENT The H/Series gas, oil, and combination gas/oil burner is a forced draft packaged burner system. A backward curved impeller mounted in a machined housing provides combustion air for various furnace pressures

More information

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler ClearFire Model CFH Horizontal Steam Boiler Startup Guide 750-293 www.cleaverbrooks.com Improper installation, adjustment, service, or maintenance can cause equipment damage, personal injury, or death.

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired Form No. 8700 Bryan Flexible Water Tube TM Triple-Flex Series Ultra-High Efficiency Condensing Hot Water Boilers 3,000,000 BTUH Natural Gas Fired Minimum 90% Thermal Efficiency at 160 F Return with 20

More information

GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7. Model C Forced Draft Burners. Natural Gas or Propane MODEL C10

GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7. Model C Forced Draft Burners. Natural Gas or Propane MODEL C10 Model C Forced Draft Burners Natural Gas or Propane MODEL C10 MODEL C4 GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7 Telephone: (519) 620-0230 Telefax: (519) 620-0232

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners 1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):

More information

Section B1. Flexible Watertube Boilers TABLE OF CONTENTS

Section B1. Flexible Watertube Boilers TABLE OF CONTENTS Section B1 Flexible Watertube Boilers TABLE OF CONTENTS FEATURES AND BENEFITS.................................................. B1-3 PRODUCT OFFERING......................................................

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL OPERATING AND MAINTENANCE MANUAL NVPOM-0104 TABLE OF CONTENTS Section Page 1 SPECIFICATIONS...1 1.1 Nova Plus Specifications...1-1 1.2 Warranty...1-2 2 GENERAL BURNER DESCRIPTION...2 2.1 Burner...2-1 2.2

More information

PBG PACKAGED GAS BURNER

PBG PACKAGED GAS BURNER INSTRUCTIONS PBG PACKAGED GAS BURNER WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components by unqualified

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated HAC INSTALLATION AND OPERATION MANUAL THE POWER TO MANAGE ENERGY 2001 South 21 st Street, Parsons, Kansas 67357 Telephone 620-421-0480, Fax 620-421-0948 Web Site: www.powerflame.com

More information

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. To obtain maintenance and repair standards for boiler burners (Section 15555A) and boiler tubes (Section 15555B), contact the DPS Project

More information

SERIES 19A. mith PRESSURIZED WET BASE

SERIES 19A. mith PRESSURIZED WET BASE SERIES 19A mith series19a BOILER/BURNER PRESSURIZED WET BASE UNIT series 19A STANDARD EQUIPMENT All s Cast iron wet-base sections tested for 80psi. Insulated metal jacket Cast iron smokehood with integral

More information

ECLIPSE INFORMATION GUIDE

ECLIPSE INFORMATION GUIDE ECLIPSE INFORMATION GUIDE JUNIOR INDUSTRIAL BURNERS Models 0 & 6 JIB Info 80 0/9 Easy to install and operate. Rugged construction for long life in industrial environments. Protection against overheating

More information

W 8ST R. Webster Combustion Technology 619 Industrial Road, Winfield, KS 67156

W 8ST R. Webster Combustion Technology 619 Industrial Road, Winfield, KS 67156 W 8ST R COMBUSTION A Selas Heat Technology Company Webster Combustion Technology 619 Industrial Road, Winfield, KS 67156 Air Density Control System Installation, Operation & Maintenance Manual Manual Part

More information

Installation Instructions

Installation Instructions Model 500-SP OVENPAK Burners Page 2300-S-1 Installation Instructions General Instructions Important: Do not discard packing material until all loose items are accounted for. To prevent damage in transit,

More information

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004 Engineering Bulletin Gas Heat for M-Series and T-Series Climate Changer Air Handlers March 2004 CLCH-PRB010-EN Preface Gas heat can be a good heating option for any of the following applications: Climates

More information

STR-Series Indirect-Fired Air Turnover Units

STR-Series Indirect-Fired Air Turnover Units STR-Series Indirect-Fired Air Turnover Units Equipment Specifi cations 1.800.589.3691 www.weather-rite.com GAS/OIL HEATING ONLY INDIRECT-FIRED AIR TURNOVER UNIT GUIDE SPECIFICATIONS PART 1 GENERAL [Gas][Oil][Gas/Oil

More information

Power Flame Incorporated CMAX. Installation and Operation Manual

Power Flame Incorporated CMAX. Installation and Operation Manual Power Flame Incorporated CMAX Installation and Operation Manual Cmax Installation & Operation Manual - POWER FLAME INCORPORATED POWER FLAME MODEL Cmax BURNER For use by Qualified Service Personnel Only

More information

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GBI 201-5 3C For a proper installation and in order to receive the best in operating life and efficiency from your

More information

Copyright 2009 Power Flame Incorporated

Copyright 2009 Power Flame Incorporated Power Flame Incorporated Installation and Operation Manual Ultra CMax Copyright 2009 Power Flame Incorporated 2001 South 21 st Street, Parsons, KS 67357 Telephone: 620-421-0480 FAX: 620-421-0948 Website:

More information

EBC 10 Fan Control USA CAN. Product Information. ... Chapter 1+2. Mechanical Installation. ... Chapter 3. Electrical Installation. ...

EBC 10 Fan Control USA CAN. Product Information. ... Chapter 1+2. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Installation & Operating Manual EBC 10 Fan Control USA CAN Product Information... Chapter 1+2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration... Chapter

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVN/P-400 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per Standard ANSI Z83.7/CSA 21.4 2000 Gas Fired Construction

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-200 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per CSA B140.8 Portable Oil Fired Heaters / CSA B140.02003

More information

Model CB-LE. Packaged Boiler HP. Operation, Service, and Parts Manual /09. and Model CB Ohio Special HP

Model CB-LE. Packaged Boiler HP. Operation, Service, and Parts Manual /09. and Model CB Ohio Special HP Model CB-LE Packaged Boiler 125-200 HP and Model CB Ohio Special 125-225 HP Operation, Service, and Parts Manual 750-184 04/09 ii CLEAVER-BROOKS Model CB-LE Packaged Boiler 125-200 HP Light Oil, Heavy

More information

40 SERIES GAS BURNER MODEL 400 NATURAL GAS/PROPANE INSTALLATION INSTRUCTIONS AND OWNER S HANDBOOK

40 SERIES GAS BURNER MODEL 400 NATURAL GAS/PROPANE INSTALLATION INSTRUCTIONS AND OWNER S HANDBOOK 40 SERIES GAS BURNER MODEL 400 NATURAL GAS/PROPANE INSTALLATION INSTRUCTIONS AND OWNER S HANDBOOK CAUTION: All gas burners MUST be installed by trained and licensed technicians. WARNING: Installation of

More information

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler Gas boiler UPON COMPLETION OF THE INSTALLATION THE INSTALLER MUST INSTRUCT THE OWNER AND OPERATOR ON THE FUNCTIONALITY AND THE PROPER OPERATION OF THE BOILER AND THE HEATING SYSTEM. INSTALLER MUST REVIEW

More information

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job SERIES Commercial, Forced Draft, Hot Water or Steam Boiler Sizes from to,8 MBH output The right fit for any commercial job The Series is built to handle any installation - businesses, institutions, apartments,

More information

CSD-1 COMMERCIAL BOILER CONTROLS

CSD-1 COMMERCIAL BOILER CONTROLS SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS CSD- COMMERCIAL BOILER CONTROLS P/N 400043, Rev. A [/03] CSD- COMMERCIAL BOILER CONTROLS! WARNING Fire, explosion, asphyxiation and electrical shock

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 2000.932C Effective: 04-01-14 Replaces: 07-15-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

mith Mills Smith Mills 6500A 6500A-4 OIL OR GAS CAST IRON BOILER/BURNER CAST IRON

mith Mills Smith Mills 6500A 6500A-4 OIL OR GAS CAST IRON BOILER/BURNER CAST IRON mith Mills Mills 00A OIL OR GAS CAST IRON BOILER/BURNER Smith CAST IRON 00A- - Gas I=B=R Ratings: Gross Output 7,19 to 1, FRONT VIEW WITH INDUS COMB BURNER SIDE VIEW WITH INDUS COMB BURNER SIDE VIEW -

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL HOT WATER HEATING BOILERS DOMESTIC WATER HEATERS 150,000-300,000 Btu/hr MODELS EB-EWU-02 IMPORTANT INSTALLER - AFFIX INSTALLATION MANUAL ADJACENT TO THE BOILER CONSUMER - RETAIN

More information

PROFIRE -E SERIES BURNERS

PROFIRE -E SERIES BURNERS PROFIRE -E SERIES BURNERS 8.4-42.0 MMBTU/HR High-efficiency burner technology for the most stringent emissions requirements Integration Starts with the Burner Suitable for firetube, firebox and watertube

More information

Forced draught natural gas/propane burner

Forced draught natural gas/propane burner Installation, use and maintenance instructions GB Forced draught natural gas/propane burner Single stage operation CODE MODEL 20096942 G400 (2) - 11/2015 Original instructions TABLE OF CONTENTS Installation

More information

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION INSTALLATION AND OPERATING INSTRUCTIONS FOR THE HARDY Fuel Oil Furnace Models D-140 & D-350 HARDY MANUFACTURING COMPANY, INC. 12345 ROAD 505 PHILADELPHIA, MS 39350 PHONE: (601) 656-5866 FAX: (601) 656-4559

More information

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS MVB, TYPE WH - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 3500.952C Effective: 06-25-15 Replaces: 12-22-09 DIVISION 23 34 36.29 COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

More information

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures.

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures. Issued 2005/06/01 Section 15510 Packaged Boilers Page 1 of 13 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3 Section 01780 Closeout

More information

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS: INSTALLATION AND OPERATION MANUAL GAS BOILERS MODELS: CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) southbend A MIDDLEBY COMPANY 1100 Old Honeycutt Road Fuquay-Varina, NC 27526 (919) 552-9161

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 504A-2004A SUGGESTED SPECIFICATIONS Catalog No.: 2000.933C Effective: 06-25-15 Replaces: 12-21-09 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

Distributed By: M&M Control Service, INC

Distributed By: M&M Control Service, INC APPROVED The UV1A3/6, UV2/UV2A6/UV2C, 45UV2, 45UV3, UV90-3/6/9 Scanners are used with the M-Series, M-Series II, MicroM, FlameWorx, MB-2 and D-Series controls as well as the Fireye FLAME-MONITOR TM, BurnerLogix

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 2505-4005 SUGGESTED SPECIFICATIONS Catalog No.: 6000.70 Effective: 09-15-16 Replaces: NEW WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes condensing, gas-fired

More information

Cambridge Engineering, Inc. 24 S-Series Technical Manual

Cambridge Engineering, Inc. 24 S-Series Technical Manual Start-Up Instructions START-UP PROCEDURE 1. Visual Inspection Of Equipment (page 24) 2. Electrical Supply Voltage Verification (page 24) 3. Gas Supply Pressure Verification (page 24) 4. Blower Rotation

More information

SECTION WATER-TUBE BOILERS

SECTION WATER-TUBE BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections

More information

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

ELECTRONIC FLAME SUPERVISION MULTI-BURNER MULTI-BURNER MODEL: SENS-A-FLAME II Revision: 0 7112 DESCRIPTION Model 7112 Sens-A-Flame II is a second generation solid-state programmable combustion safeguard for supervising multiple burner ovens, furnaces,

More information

Columbia Boiler Company

Columbia Boiler Company EMG Series Boilers Available in Natural Gas & Propane Rev 12012 Columbia Boiler Company PO Box 1070 Pottstown, PA 19464 Tel (610) 473-8457 Fax (610) 367-6800 Website www.columbiaboiler.com Email cbcsales@ptd.net

More information

Single stage operation forced draught natural gas/propane burner

Single stage operation forced draught natural gas/propane burner Installation & Operating Manual Single stage operation forced draught natural gas/propane burner The following pages contain information, descriptions and diagrams for the proper installation and wiring

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 2503-4003 SUGGESTED SPECIFICATIONS Catalog No.: 2000.934A Effective: 04-01-14 Replaces: 06-01-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

DESCRIPTION, CAPACITIES, SPECIFICATIONS, APPLICATIONS

DESCRIPTION, CAPACITIES, SPECIFICATIONS, APPLICATIONS INTEGRAL FAN BURNERS 43, 53, 63 Supplement 600- July 996 DESCRIPTION, CAPACITIES, SPECIFICATIONS, APPLICATIONS Integral Fan (and) Shutter Section (hinged for quick access to internals) Combustion Air Interlock

More information

ClearFire - Hydronic Startup Report

ClearFire - Hydronic Startup Report ClearFire - Hydronic Startup Report Date Serial No. THIS FORM IS FOR MODEL CFC / CFW CLEARFIRE BOILERS Customer s Name Location Model Design Pressure Working Pressure Rated Input (nameplate rating) BTU/hr

More information

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 0204 L2 Revised 11 2006 G60UH(X) G60UH(X) SERIES UNITS G60UH(X) series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS HI DELTA, TYPE WH - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 3500.932A Effective: 04-01-17 Replaces: 10-31-16 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY A.

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System. The Fireye EP260, EP270 (early spark termination), or EP265 (pilot stabilization) programmer modules are used with the FLAME-MONITOR Burner Management Control System (P/N E110). Several operational characteristics

More information

Installation, Operation and Service Manual

Installation, Operation and Service Manual Installation, Operation and Service Manual KLF-100 85% + EFFICIENCY OIL FIRED LOWBOY FURNACE INSTALLATIONS MUST MEET ALL LOCAL AND FEDERAL CODES THAT MAY DIFFER FROM THIS MANUAL Please read the manual

More information

ENERVEX ADC100 DRAFT CONTROL

ENERVEX ADC100 DRAFT CONTROL ENERVEX ADC100 DRAFT CONTROL 3916067 04.16 Installation & Operating Manual READ AND SAVE THESE INSTRUCTIONS! ENERVEX Inc. 1685 Bluegrass Lakes Parkway Alpharetta, GA 30004 USA P: 770.587.3238 F: 770.587.4731

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-400 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-400 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-400 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per CSA B140.8 Portable Oil Fired Heaters / CSA B140.02003

More information

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit Packaged Gas/Electric Units Owner s Guide to Operating and Maintaining Your Gas/Electric Unit ELECTRICAL SHOCK HAZARD. FIRE OR EXPLOSION HAZARD Disconnect power at fuse box or service panel before performing

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 1005A-2005A SUGGESTED SPECIFICATIONS Catalog No.: 6000.63B Effective: 3-01-15 Replaces: 9-01-09 WATER-TUBE POOL HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes condensing,

More information

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Boiler specifications A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Burner General: Q. Burner and burner safeguards shall comply with the CGA

More information

Equipment Maintenance Checklist

Equipment Maintenance Checklist The Hartford Steam Boiler Inspection and Insurance Co. One State Street P.O. Box 5024 Hartford, CT 06102-5024 Tel: 800-333-4677 Fax: 484-582-1811 Internet: http://www.hsb.com Equipment Maintenance Checklist

More information

Eclipse Self-Check UV Scanner

Eclipse Self-Check UV Scanner 856 Instruction Manual 10/18/2010 Eclipse Self-Check UV Model 5602-91 Version 1 Introduction The self-check UV is used for continuous gas or oil flames. A mechanical shutter in the scanner closes briefly

More information

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING See unit nameplate for manufacturer and address. 507350-03 3/2016 Supersedes 9/2015 KG 024, 030, 036, 048, 060, 072, 074, 090 (2, 2-1/2, 3, 4, 5, 6 and 7-1/2 Tons) KG 092, 102, 120, 150 (7-1/2, 8 1/2,

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING See unit nameplate for manufacturer and address. 507258-04 7/2018 Supersedes 10/2017 ZG 036, 048, 060, 072, 074 (3, 4, 5 and 6 Tons) ZG 092, 102, 120, 150 (7-1/2, 8-1/2, 10 and 12 Tons) ROOFTOP UNITS ZG

More information

FINNED WATER-TUBE POOL HEATERS

FINNED WATER-TUBE POOL HEATERS HI DELTA, TYPE P - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 6000.611 Effective: 10-31-16 Replaces: NEW FINNED WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes gas-fired,

More information

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000 s AV(W)0500 AV(W) The domestic hot water boiler shall be a Camus ADVANTUS TM model having a recovery capacity of gph (lph) at 100ºF (56ºC) for DHW The domestic hot water boiler shall be design certified

More information

mith Mills 4500A Smith Mills 4500A 4500A-3R OIL, GAS OR COMBINATION GAS/OIL COMMERCIAL BOILER/BURNER CAST IRON

mith Mills 4500A Smith Mills 4500A 4500A-3R OIL, GAS OR COMBINATION GAS/OIL COMMERCIAL BOILER/BURNER CAST IRON Mills 00A mith Mills 00A Smith CAST IRON OIL, GAS OR COMBITION GAS/OIL COMMERCIAL BOILER/BURNER 00AR STEAM GAUGE OPERATING CONTROL MODULATING CONTROL HI LIMIT PRESSURE CONTROL 0" STEAM DRUM TEST COCK /"

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVN/P-400 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per Standard ANSI Z83.7/CSA 21.4 2000 Gas Fired Construction

More information

Diocese of Cleveland Facilities Services Corporation

Diocese of Cleveland Facilities Services Corporation Diocese of Cleveland Facilities Services Corporation BOILER MAINTENANCE and SERVICING SEASONAL MAINTENANCE - to be performed by trained boiler technician or boiler contractor only: 1. Disassemble the low

More information

DOMESTIC WATER HEATER OIL FIRED

DOMESTIC WATER HEATER OIL FIRED DOMESTIC WATER HEATER OIL FIRED Models : CMO32-II CMO32-II-R CMO50-II CMO32-II & CMO32-II-R INSTALLER / SERVICE TECHNICIAN: USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE

More information

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000 s AV(W)0500 AV(W) The domestic hot water boiler shall be a Camus ADVANTUS TM model having a recovery capacity of gph (lph) at 100ºF (56ºC) for DHW The domestic hot water boiler shall be design certified

More information

FLEXCORE SERIES MASTERSPEC

FLEXCORE SERIES MASTERSPEC FLEXCORE SERIES MASTERSPEC MSFC-2 SECTION 23 52 16 - CONDENSING HIGH EFFICIENCY STAINLESS STEEL FIRETUBE BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

Take The Test! Does Your Boiler Meet Code?

Take The Test! Does Your Boiler Meet Code? ASME SAFETY STANDARD #CSD- CONTROLS & SAFETY DEVICES GUIDELINES FOR AUTOMATICALLY GAS FUEL FIRED BOILERS INSTALLED NOT NOT INSTALLED REQUIRED SYSTEM CONTROL SPECIFICATIONS POWER & MECHANICAL DRAFT BURNERS

More information

Eclipse 90 UV Scanner Model A Version 1

Eclipse 90 UV Scanner Model A Version 1 85 Instruction Manual 10/14/010 Eclipse 90 UV Model 5600-90A Version 1 C US Introduction This sensor features a high sensitivity ultraviolet (UV) tube for monitoring gas or oil flames that cycle on and

More information

DIRECTIVE NO: D-B

DIRECTIVE NO: D-B DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting

More information

CEI Jacketed Firebox Heater Operation, Service & Parts Manual

CEI Jacketed Firebox Heater Operation, Service & Parts Manual CEI Jacketed Firebox Heater Operation, Service & Parts Manual Heater models 1200 ~ 6300 CEI Enterprises Albuquerque, New Mexico, U.S.A. ii Jacketed Firebox Heaters Contents Section 1: Introduction... 1

More information

MULTIPLEX SELF RECUPERATIVE gas burner

MULTIPLEX SELF RECUPERATIVE gas burner Installation - Maintenance MULTIPLEX SELF RECUPERATIVE gas burner SERIES MPSR The Nu-way Multiplex Recuperative System offers the alternative of a self-recuperative burner or a separate recuperator and

More information

S150 S300 CONSTRUCTION HEATERS. Rev: August 15, 2008 SERVICE AND MAINTENANCE MANUAL No PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS

S150 S300 CONSTRUCTION HEATERS. Rev: August 15, 2008 SERVICE AND MAINTENANCE MANUAL No PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS S150 & S300 CONSTRUCTION HEATERS Rev: 2.7.2 August 15, 2008 SERVICE AND MAINTENANCE MANUAL No. 934-6637 PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS A DIVISION OF HAUL-ALL EQUIPMENT LTD. 4115-18 Avenue

More information

ADC150 Automatic Draft Control

ADC150 Automatic Draft Control Installation & Operating Manual ADC150 Automatic Draft Control USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...

More information

Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference.

Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference. Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference. Operating Instructions and Owner s Manual READ INSTRUCTIONS CAREFULLY: Read and follow all instructions.

More information

WASTE WATER EVAPORATOR WITH ANY FUEL OPTIONS

WASTE WATER EVAPORATOR WITH ANY FUEL OPTIONS WASTE WATER EVAPORATOR WITH ANY FUEL OPTIONS Product: Manufacturer: Engineer: Sales Contact: Technical Contact: Mechanical Contractor: INOV8 Evaporators with INOV8 burners are designed to reduce or eliminate

More information

VCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower

VCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower VCLEARFIRE High-Efficiency, Commercial Steam Boiler 9.5-60 Horsepower High-Efficiency, Low-Emissions Steam Boiler in a Compact Footprint The Cleaver-Brooks compact, gas-fired ClearFire -V vertical boiler

More information

SECTION HEATING BOILERS

SECTION HEATING BOILERS SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,

More information

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh WATER HEATERS / BOILERS COWB3 Oil-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 0654 March 08 Supersedes September 05 AFUE up to 85.% Heating Input 05,000 to 45,000 Btuh MODEL NUMBER IDENTIFICATION

More information

THC- 355DF (Dual Fuel)

THC- 355DF (Dual Fuel) OPERATING INSTRUCTIONS MANUAL THC- 355DF (Dual Fuel) INDUSTRIAL / COMMERCIAL DIRECTIONAL SPACE HEATER (OPERATOR MUST RETAIN FOR FUTURE REFERENCES) Certified to / Certifié à ANSI std Z83.7 2000 Suitable

More information

INDITHERM. Low temperature gas burners

INDITHERM. Low temperature gas burners INDITHERM Low temperature gas burners 1-2.3-1 High turndown for maximum operation flexibility. Maximum capacities up to 1800 kw. Designed for firing in indirect fired processes. Excellent combustion throughout

More information

QHT Manual for: SU-2A Gas Burner

QHT Manual for: SU-2A Gas Burner 1 QHT Manual for: SU-2A Gas Burner 50,000 BTU/H to 250,000 BTU/H The burner shall be used only with NATURAL GAS or LP GAS. Warning: If the following instructions are not followed exactly, a fire or explosion

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY

More information

Series 300 VTB. Installation Instructions

Series 300 VTB. Installation Instructions Series 300 VTB Installation Instructions Sizes 7 12 16 20 30 HP #2 Fuel Oil Gas (500 to 2500 BTU) Gas Light Oil Combination High Pressure Steam Sizes 7 thru 16 HP (125 PSI) Sizes 20 and 30 HP (150 PSI)

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-200 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per CSA B140.8 Portable Oil Fired Heaters / CSA B140.02003

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVN/P-400 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per Standard ANSI Z83.7/CSA 21.4 2000 Gas Fired Construction

More information

A. Product Data: Include rated capacities, furnished specialties and accessories.

A. Product Data: Include rated capacities, furnished specialties and accessories. BASE BID: SECTION 15542 FUEL-FIRED RADIANT HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install a Co-Ray-Vac Low Intensity Vented Infrared Radiant Vacuum Gas Heating System. System must be certified

More information