Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Size: px
Start display at page:

Download "Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants"

Transcription

1 Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants CHENNUCHETTY CHINNARAJ * Associate Professor in Mechanical Engineering, Government College of Engineering, Salem , Tamil Nadu, India PALANISAMY GOVINDARAJAN Department of Mechanical Engineering, Sona College of Technology, Salem, Tamil Nadu, India Abstract: A window air conditioner of 3.5 K.W capacity fitted with expansion devices such as capillary tube, thermostatic expansion valve and Electronic expansion valve was tested for its coefficient of performance, power required and refrigeration effect with respect to the refrigerants R22 and R407C under different operating conditions.initially evaporator temperature was maintained at 279 K and condenser temperature was varied and then the test was conducted again in the same window air conditioner with electronic expansion valve alone as expansion device and by varying the refrigerant super heat temperature at inlet to the compressor from 273K to 293K for the refrigerants R 22, R 407C and R 290 The performance of electronic expansion valve with eco friendly refrigerants shows a positive effect and enable the industry to favorably displace the R22 and other types of expansion devices. Keywords: Window air conditioner; Coefficients of Performance; Thermostatic Expansion Valve; Electronic Expansion Valve; Tonne of Refrigeration 1. Introduction Global concern over Ozone depletion and global warming have resulted Montreal and Kyota protocols. Use and production of Choloro fluro carbon (CFC) and Hydro choloro fluoro carbon (HCFC) have to be ceased in all over the World by the year The refrigerant R22 used in refrigeration and air conditioning field contains Chlorine and harms the Ozone layer. It must be replaced by eco-friendly refrigerants in future. The Electronic expansion valve(eev), driven by stepping motor controlled pulse signal generator, has widely used in refrigeration systems. The refrigerant flow through the evaporator is controlled by means of monitoring pressure and temperature of it at outlet of the evaporator. Hence it shows better overall performances compared to the capillary tube system and thermostatic expansion valve (TEV). Lazzarian and Noro (2008) proved that the EEV fitted in air conditioner with air cooled condenser enables appreciable energy saving with respect to same installations equipped with traditional thermostatic expansion valve and this is due to the fact that it allows a lower condensation pressure in systems equipped with air cooled condenser, which is adjusted to variations in outside air temperature. Chasis park et al (2007) in their work proved that the applications of electronic expansion valves into multi type heat pumps and inverter heat pumps in building air conditioning systems have increased for comfort environmental control and energy conservation. Ciro Aprea and Rita Mastrullo (2002) stated that, under steady conditions both EEV and TEV are equal in performance but under transit conditions EEV gives better overall performance compared to TEV.

2 Ma Shanwei et al (2005) have developed a correlation on the basis of the experimental data of electronic expansion valve for R22 and its alternatives R 407 C (R 32/125/134a, 23 /25/52 wt%) and R410A (R 32/125, 50/50 wt % ). Jinghui Liu et al (2008) have developed an one dimensional model in which the evaporation wave theory is employed to investigate the choking flow characteristics in EEV for R22, R407C and R 410A. The refrigerant mass flow characteristics of the EEV are an important issue in heat pumps / refrigeration system operation because the valve regulates the refrigerant flow to match various operating conditions. From the experimental data, Xue Zhifang et al (2008) developed a mass flow correlation for R134a through an EEV. Based on the throttling mechanism and thermodynamic analysis, the mass flow rate is a function of various parameters such as valve s geometric parameter, the inlet refrigerant pressure and temperature, outlet refrigerant pressure and the refrigerant thermo physical properties such as dynamic viscosity and surface tension. 2. Experimental Apparatus The experimental setup shown in Fig.1 is used to test the performance of EEV fitted in a window air conditioner of 3.5 kw capacity under variable operating conditions using the refrigerants R22, R 407C, R 290 as working fluids. Fig.1 Schematic diagram of the test facility The test rig consists of hermetic compressor, environmental chamber constructed as per BIS, 1391, (1992) to simulate the indoor and outdoor conditions with necessary instrumentation, two heat exchangers (condenser and evaporator) and expansion devices such as capillary tube, thermostatic expansion valve and electronic expansion valve. The EEV used in this test rig is a solenoid valve linked to an electronic controller and electronic controller s operation is based on temperature of refrigerant and air at inlet and outlet of evaporator Environmental Chambers The indoor and outdoor simulation chambers are made of double skin PUF insulators walls and the dimensions are chosen as per BIS, 1391 (1992). The heat load is provided by a 3000 Watts heater placed in the indoor chamber which is controlled by a variac. There is a Wattmeter of ± 0.5 % accuracy provided to measure the power supplied to the heater. To ensure uniform temperature distribution within the chambers air circulating fans are provided. A 2 TR split air conditioner is provided in the outdoor chamber to dissipate the heat from condenser. Humidifiers are provided in the both the chambers to maintain the required relative humidity Instrumentation The mass flow rate of refrigerant is measured using a corialis type flow meter of accuracy ± 0.25%. To measure the compressor power, a digital Wattmeter of accuracy ± 0.5% is provided. Pressure transducers with ±0.25 % accuracy and J- type thermocouples with ± 0.1% accuracy are provided to measure the respective refrigerant pressures and

3 temperatures at salient points. Thermocouples are also placed inside the chambers to measure the average room temperatures. The relative humidity is measured using humidity sensor of accuracy ± 0.1%. All sensors are connected to a computerized data acquisition system (AGILENT A). 3. Experimentation To have a maximum COP, full charge condition was determined under a standard condition of condenser temperature at 323 K and evaporator temperature 279 K. By keeping the temperature of refrigerant entering the evaporator at 279K and varying its temperature at inlet to condenser as 313K, 318K, 323K and 328K, the tests for the window air conditioner using the refrigerantsr22 and R 407C with various expansion devices such as capillary tube, thermostatic expansion valve and EEV were conducted by setting the same full charge condition for all the three expansion devices and corresponding readings were recorded continuously for 40 minutes using the data acquisition system The refrigerant effect, compressor power and COP were calculated and results for R22and R407C were analyzed. Heat infiltration load into indoor chamber was determined. Again tests were conducted by varying the refrigerant super heat temperature at inlet to the compressor from 273K to 293K in steps of 2K by adjusting the EEV.The indoor and outdoor conditions were maintained by adjusting the power supply to the heaters and controlling the humidifiers. Refrigerant side and airside readings were noted and for better accuracy, the average values were used for computing various performance parameters. For calculating the refrigeration effect and compressor power, the enthalpy values of refrigerant at salient points were obtained from the refrigerant s thermodynamic property value tables using the pressure and temperature readings.all the three refrigerantsr22,r 407C and R290 under study were tested using electronic expansion valve alone and results were analyzed. 4. Results and Discussion By keeping the temperature of refrigerant entering the evaporator at 279K and varying its temperature at inlet to condenser as 313K, 318K, 323K and 328K, the tests for the window air conditioner using the refrigerants R22 and R 407C were conducted and the performance parameters such as refrigeration effect, compressor power and COP were calculated and compared for performance analysis. Figure 2 shows the variation of capacity for R22 capillary, R407C TEV and R407C EEV as a function of different condenser temperature. The capacity of the R407C EEV system is higher by 10.1% than that for the R22 capillary tube system. The capacity of the R407C TEV system is higher by 0.196% than Figure 2 shows the variation of capacity for R22 capillary, R407C TEV and R407C EEV as a function of different condenser temperature. The capacity of the R407C EEV system is higher by 10.1% than that for the R22 capillary tube system. The capacity of the R407C TEV system is higher by 0.196% than that for the R22 capillary tube system Fig 2: Capacity variations for R22 capillary, R407C TEV and R407C EEV at various condensing temperatures. Figure 3 shows the variation of compressor power for R22 capillary, R407C TEV and R407C EEV as a function of different condenser temperature. The compressor power of the R407C EEV system is lower by 14.8% than that for

4 the R22 capillary tube system. The compressor power of the R407C TEV system is lower by 4.1% than that for the R22 capillary tube system. Fig 3: Compressor power variations for R22 capillary, R407C TEV and R407C EEV at Various condensing temperatures. Figure 4 shows the variation of COP for R22 capillary, R407C TEV and R407C EEV as a function of different condenser temperatures. The COP of the R407C EEV system is higher by 13.08% than that for the R22 capillary tube system. The COP of the R407C TEV system is higher by 1.23% than that for the R22 capillary tube system. By varying the degree of superheat, the experiments were carried out, for the refrigerants R22, R290, and R407C. The performance parameters such as mass flow rate of refrigerant, cooling capacity, compressor exit temperature, compressor power, volumetric efficiency and COP were compared between the refrigerants with the use of electronic expansion valve. Fig 4: COP variations for R22 capillary, R407C TEV and R407C EEV at various condensing temperatures. Figure 5 shows the variation of cooling capacity for R22, R290, and R407C using EEV as a function of different degree of super heat. The cooling capacity of R22 system is higher by 2.42% than that of R407C and 11.7% than that of R290. For R407C and R290 the latent heat is observed to be more in the evaporating temperature ranges and less in the condensing temperature ranges. The reduction of latent heat in the condensing temperature ranges are more predominant compared to the marginal increase in the evaporating temperature ranges. The combined effect of these is to reduce the overall heat carrying capacity of R407C and R290 thereby reducing the cooling capacities.

5 Cooling Capacity (kw) R22 R290 R407C Degree of Superheat Fig 5. Cooling Capacity variations of R22, R407C, and R290 at various degrees of super heat. Figure 6 shows the Comparison of the power consumption by R22 and R407C, at lower degrees of superheat there is a marginal increase for R407C whereas it is slightly less at higher degrees of superheat. At all operating conditions R290 shows a reduction in power consumption by 14% compared to R Power Input (kw) R22 R290 R407C Degree of Superheat Fig 6. Power input variations of R22, R407C, and R290 at various degrees of super heat. Figure 7 shows the variation of COP for R22, R290, R407C using EEV s as a function of different degree of super heat. The Coefficient of performance of R290 system is higher by 3.83%than that of R22 and 7.12% than that of R407C. COP is found to be the maximum with R290. Even though the cooling capacity and mass flow rate are found to be less for R290, a considerable reduction in compressor power, effects in improved COP values for the entire range of superheat.

6 COP R22 R290 R407C Degree of Superheat Fig 7 COP variations for R22, R407C, and R290 at various degrees of super heat. 5. Conclusions From the experimental study to evaluate the influence of electronic expansion valve on one TR capacity window air conditioner with refrigerants R22, R407C and R290, the following conclusions are drawn. Experimental results on R22, R407C and R290 produce results in favour of the last two refrigerants and electronic expansion valve as the best expansion device. It is observed that the flow rate of refrigerant and cooling capacity for R407C and R290 are lesser than R22 when electronic expansion valve is used in the system. The system using the refrigerant R290 with electronic expansion valve gives maximum COP due to lesser power consumption than that of R22 and R407C. Considering the Global warming and Ozone depletion, R407C and R290 can be used in place of R22. R290 is a better choice in terms of energy efficiency and ozone friendliness. But higher inflammability is a limitation for it. However detailed experimental study is needed on designing the leak proof system when it is used in the large Air conditioning systems 6. Acknowledgement The authors gratefully acknowledge the financial support provided by the World Bank, Government of India and State Government of Tamil Nadu through the Technical Education Quality Improvement Programme (TEQIP) for the establishment of experimental facility at Government College of Engineering, Salem, Tamil Nadu, India. 7. References [1] Lazzarin.R, Noro.M, (2008): Experimental Comparison of Electronic and Thermostatic Expansion Valves Performances in an Air Conditioning Plant. International Journal of Refrigeration 31, [2] Chasik Park, Honghyun Cho, Yontaek Lee, Yongchan Kim (2007): Mass flow Characteristics and Empirical Modeling of R22 and R410A flowing through Electronic Expansion Valves, International journal of Refrigeration 30, [3] Ciro Aprea, Rita Mastrullo (2002): Experimental Evaluation of Electronic and Thermostatic Expansion Valves Performances using R22 and R407C, Applied Thermal Engineering 22, [4] Ma Shanwei, Zhang Chuan, Chen Jiangping, Chen Zhiujiu (2005): Experimental research on Refrigerant Mass flow coefficient of electronic expansion valve, Applied Thermal Engineering 25, [5] Jinghui Liu, Jiangping Chen, Zhijiu Chen (2008): Investigation of Chocking Flow Characteristics in Electronic Expansion Valves. International Journal of Thermal Sciences 47, [6] Xue Zhifang, Shi Lin, Ou Hongfei (2008): Refrigerant Flow Characteristics of Electronic Expansion Valve based on the Thermodynamic Analysis and Experiment, Applied Thermal Engineering 28, [7] Bureau of Indian Standards. Room Air conditioners specification, part I: Unitary Air conditioners, BIS 1391, New Delhi, India [8] Ciro Apera, Rita Mastrullo (2002): An Experimental Evaluation of the Vapour Compression Plant Performances in presence of R407C leaks using an electronic expansion valve, Applied Thermal Engineering 22, pp

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A ISSN: 2250-0138 (Online) NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A RANENDRA ROY a1, MADHU SRUTHI EMANI b AND BIJAN KUMAR MANDAL c abc Department

More information

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A [1] Ranendra Roy, [2] Madhu Sruthi Emani, [3] Bijan Kumar Mandal [1], [2],[3] Department of Mechanical

More information

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE Karthikeyan, K. et al.: Experimental Investigations on Automobile Air S515 EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE by Karthikeyan

More information

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore

More information

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Study

More information

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a ISSN (e): 0 00 Vol, 0 Issue, 8 August 0 International Journal of Computational Engineering Research (IJCER) Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants

More information

International Journal of Informative & Futuristic Research ISSN (Online):

International Journal of Informative & Futuristic Research ISSN (Online): Reviewed Paper Volume 2 Issue 9 May 2015 International Journal of Informative & Futuristic Research ISSN (Online): 2347-1697 Performance Comparison of R22 and R290 Refrigerants Using Smaller Paper ID IJIFR/

More information

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance

More information

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump urdue University urdue e-ubs International Refrigeration and Air onditioning onference School of Mechanical Engineering 2008 erformance haracteristic and Optimization of a Simultaneous eating and ooling

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 Ameya P. Shrivastava 1, Choudhari Chandrakishor S. 2 1,2 Mechanical Department, AISSMS College of Engineering, Pune 411001, (India) ABSTRACT HCFC

More information

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER University of Maiduguri Faculty of Engineering Seminar Series Volume 6, december 5 ASSESSMENT OF REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R34A REFRIGERANT IN LARGE CAPACITY FREEZER S. Shodiya*, M.B. Oumarou

More information

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 5161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article A Review

More information

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS Lalit Narayan, Abhishek Arya 2,2 M. Tech. Scholar, Associate Professor,,2 Scope College of Engineering, Bhopal, India Abstract: The

More information

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23 Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23 A. D. Parekh, P. R. Tailor Abstract The Montreal protocol and Kyoto protocol underlined the need of substitution

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Effect of capillary diameter on the power consumption of VCRS using different refrigerants Effect of capillary diameter on the power consumption of VCRS using different refrigerants Dr. A. G. Matani 1, Mukesh K. Agrawal 2 1 Asso. Professor, Mechanical Engineering Department, Govt. College of

More information

Purdue e-pubs. Purdue University

Purdue e-pubs. Purdue University Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 206 Experimental Investigation of the Refrigerant Flow Distribution Characteristic

More information

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures Experimental Study on Performance Parameters for Refrigerants, R41a and R44a at Various Air Outlet Temperatures P. Nagaraju P. G. Student Sanketika Institute of Technology and Management Ch. Kiran Kumar

More information

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C drop analysis of evaporator using refrigerants R-22, R-404A and R-407C #1 Pallavi Sawkar, #2 Dr. Pradeep Patil #12 Department of Mechanical Engineering, JSPM s JSCOE, Savitribai Phule Pune University,

More information

η second law = Second law efficiency

η second law = Second law efficiency EXERGY ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION CYCLE BASED AUTOMOTIVE AIR CONDITIONER USING ECO FRIENDLY REFRIGERANTS Vijender Singh Saini 1, Balvinder 2, Pardeep Kumar 3 1 M.Tech Scholar, 2,3 Assistant

More information

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS Int. J. Chem. Sci.: 14(S2), 2016, 665-674 ISSN 0972-768X www.sadgurupublications.com PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS J. THAVAMANI *, MARRIPUDAGALA KOMALI, SHAIK

More information

Department of MCE, Islamic University of Technology 2. Abstract

Department of MCE, Islamic University of Technology 2. Abstract Paper ID: TE-85 Study of power consumption characteristics of LPG and R134a in a vapor compression refrigeration system Md. Abu Shaid Sujon 1, Rakibul Hossain Ahmed 2, Dr. A.K.M. Sadrul Islam 3, Sk. Suzauddin

More information

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis. Comparative performance analysis of Refrigeration Test RIG for R-12 & R-134a Parmesh 1, Mr. Amit Sharma 2 1 M.Tech. Scholar, Department of Mechanical Engineering, 2 Assistant Professor, Department of Mechanical

More information

*Corresponding author;

*Corresponding author; PERFORMANCE ANALYSIS OF AUTOMOTIVE AIR CONDITIONING SYSTEM WITH AN INTERNAL HEAT EXCHANGER USING R1234YF UNDER DIFFERENT EVAPORATION AND CONDENSATION TEMPERATURES by Mehmet DIREK a *and Alper KELESOGLU

More information

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Available online at   ScienceDirect. Energy Procedia 109 (2017 ) 56 63 Available online at www.sciencedirect.com ScienceDirect Energy Procedia 109 (2017 ) 56 63 International Conference on Recent Advancement in Air Conditioning and Refrigeration, RAAR 2016, 10-12 November

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants 454 Journal of Scientific & Industrial Research Vol. 72, July 2013, pp. 454-460 Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants P. Thangavel 1* and

More information

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes ISSN 2395-1621 A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes #1 N. Dhekale, #2 Dr. P. A. Patil 1 amardhekale@gmail.com #12 Research Laboratory, Department

More information

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Experimental Study on Performance of Condenser of Two Different Types Used in Window Air Conditioner Madhu Jhariya *1, P.K. Jhinge

More information

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION 1.1 CFC REFRIGERANTS Since the 1930s, chlorofluorocarbons (CFCs) have been widely used as foam blowing agents, aerosols and especially refrigerants due to their pre-eminent properties

More information

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015 Page77 Page78 COMPARATIVE ANALYSIS OF PERFORMANCE OF OZONE-FRIENDLY AND LOW GWP HFC REFRIGERANT IN A VAPOUR COMPRESSION REFRIGERATION CYCLE Kashid Hari T. 1,Khatpe Akshay R 1,Khile Parshuram N 1,Ligade

More information

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE PRESENTED BY J.SARAVANA PERUMAL 1 Saravananjsp005@gmail.com D.SATHEESH 2 Satheeshd123@gmail.com Contact no: 9789080381 DEPARTMENT

More information

Experimental Investigation of Hot water Fired R134A-DMAC VARS System at Various Heat Source Temperatures

Experimental Investigation of Hot water Fired R134A-DMAC VARS System at Various Heat Source Temperatures Journal of Energy Research and Environmental Technology pp. 20-25 Krishi Sanskriti Publications http://www.krishisanskriti.org/jeret.html Experimental Investigation of Hot water Fired R134A-DMAC VARS System

More information

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube ISSN: 2347-3215 Volume 1 Number 4 (2013) pp. 46-54 www.ijcrar.com Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube Richa Soni 1*, P.K.Jhinge

More information

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator Mr. Subodh S. Deshpande Department of Mechanical Engineering M.G.M.s College of Engineering

More information

DEEPAK PALIWAL, S.P.S.RAJPUT

DEEPAK PALIWAL, S.P.S.RAJPUT International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-15 623 EXPERIMENTAL ANALYSIS OF HYDROCARBON MIXTURES AS THE NEW REFRIGERANT IN DOMESTIC REFRIGERATION SYSTEM DEEPAK PALIWAL,

More information

Experimental investigation on the performance of air conditioner using R32 Refrigerant

Experimental investigation on the performance of air conditioner using R32 Refrigerant IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 12, Issue 4 Ver. V (Jul. - Aug. 2015), PP 139-144 www.iosrjournals.org Experimental investigation

More information

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India DESIGN OF HYBRID AIR COOLER USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Vimalkirti Shende 1, Sushil Borkar 2, Touseef Iqbal Qureshi 3 Asst. Prof. Nikhil Bhende 1 1,2,3 U.G. Student, Department of Mechanical

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information

ISSN: [Sachuthananthan * et al., 5(10): October, 2016] Impact Factor: 4.116

ISSN: [Sachuthananthan * et al., 5(10): October, 2016] Impact Factor: 4.116 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A PERFORMANCE OF A WINDOW AIR CONDITIONER USING ALTERNATIVE REFRIGERANTS R22 AND R290 Dr. B. Sachuthananthan,*, T. Naresh Kumar,

More information

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP Paul Maina and Zhongjie Huan mainap@tut.ac.za and huanz@tut.ac.za Department of Mechanical Engineering, Tshwane University of Technology P.O Box Private Bag X680

More information

A study of Transient Performance of A Cascade Heat Pump System

A study of Transient Performance of A Cascade Heat Pump System Available online at www.sciencedirect.com ScienceDirect Energy Procedia 79 (2015 ) 131 136 2015 International Conference on Alternative Energy in Developing Countries and Emerging Economies A study of

More information

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 26 Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Jit Guan

More information

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump Available online at www.sciencedirect.com Procedia Engineering 8 (2011) 165 170 2 nd International Science, Social-Science, Engineering and Energy Conference 2010: Engineering Science and Management Hot

More information

Oyelami S., Bolaji B. O.

Oyelami S., Bolaji B. O. International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-2015 1158 Experimental Investigation of the Performance of Liquefied Petroleum Gas (LPG) Refrigerant in A Vapour Compression

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,

More information

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature International Journal Of Computational Engineering Research (ijceronlinecom) Vol 3 Issue 3 Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

More information

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM Sachin Kumar 1, Vicky Ranga 2 1Assistant Professor, Department of Mechanical Engineering, Jagan Nath University Jhajjar, Haryana, India. 2Scholar.

More information

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A ,, IJAET International Journal of Application of Engineering and Technology ISSN: 33 Vol No. A COMPARATIVE STUDY FOR RETROFITTING OF R VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO FRIENDLY REFRIGERANTS

More information

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf Gaurav #1, Raj Kumar* 2 1# Research Scholar, Department of Mechanical Engineering,

More information

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT Proceedings of the International Conference on Mechanical Engineering and Renewable Energy 217 (ICMERE217) 18 2 December, 217, Chittagong, Bangladesh ICMERE217-PI-48 IR-REVERSIBILITY ANALYSIS OF A SPLIT

More information

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS International Journal of Scientific & Engineering Research Volume 3, Issue 7, July-2012 1 EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS Rahul ukey, Sharad chaudhary Abstract Electricity

More information

ANKUSH SHARMA & JAGDEV SINGH Department of Mechanical Engineering, Beant College of Engineering and Technology, Gurdaspur, Punjab, India

ANKUSH SHARMA & JAGDEV SINGH Department of Mechanical Engineering, Beant College of Engineering and Technology, Gurdaspur, Punjab, India International Journal of Mechanical and Production Engineering Research and Development (IJMPERD) ISSN 2249-6890 Vol. 3, Issue 1, Mar 2013, 85-94 TJPRC Pvt. Ltd. EXPERIMENTAL INVESTIGATION OF REFRIGERANT

More information

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C H. Abdesselam, et al / International Energy Journal 9 (8) 7-7 7 Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures www.serd.ait.ac.th/reric H. Abdesselam *, H.H.

More information

Design & Fabrication of Hybrid Cooler

Design & Fabrication of Hybrid Cooler IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 11 April 2016 ISSN (online): 2349-6010 Design & Fabrication of Hybrid Cooler Shashank Chauragade Mukul Kshirsagar

More information

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants [VOLUME 5 I ISSUE 3 I JULY SEPT 2018] e ISSN 2348 1269, Print ISSN 2349-5138 http://ijrar.com/ Cosmos Impact Factor 5.75 Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a

More information

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Dr. R. A. Kathar 1, S. D. Surushe 2 1 Associate Professor, Mechanical

More information

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018), 201-208 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance #1 Jaydev S. Bade, #2 Dr. Nitin U. Korde 1 Department of Mechanical Engineering, Savitribai Phule

More information

Low GWP Refrigerants for Air Conditioning Applications

Low GWP Refrigerants for Air Conditioning Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta

More information

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a) EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a) Abstract- With the recent government regulations, of banning the ozone depleting substances and Kyoto protocol

More information

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER Gourav Roy; Taliv Hussain; Rahul Wandra Department of Mechanical Engineering, Lovely Professional

More information

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation Volume 6, Issue 3(201)199-204 ISSN 2347-325 Comparative Performance Evaluation of Vapor Compression Refrigeration System for drop-in Replacement of R22 Vaibhav Jain *, Dhruva Gupta, Himank Gupta, Anirudh

More information

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Comparative assessment for drop in replacement of R134a in domestic refrigerator. Comparative assessment for drop in replacement of R134a in domestic refrigerator. Pravin K. Katare Research Scholar, Department of Mechanical Engineering, G.H.Raisoni College of Engineering Digdoh Hill,

More information

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Research On Gas Injection High Temperature Heat Pump With

More information

Air & Water Heat Pump R832

Air & Water Heat Pump R832 Figure 1 : R832 P.A. Hilton Ltd Air & Water Heat Pump R832 Vapour Compression Heat Pump that allows Performance Investigation from both Air and Water Sources. Rapid Stabilisation enables detailed Investigation

More information

Enhancement of COP in Vapour Compression Refrigeration System

Enhancement of COP in Vapour Compression Refrigeration System Enhancement of COP in Vapour Compression Refrigeration System M. Krishna Prasanna #1 M.E student, Heat Transfer studies in Energy Systems Department of Mechanical Engg., Andhra University Visakhapatnam-530003,

More information

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for

More information

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation Methods for Improving Thermodynamic Energy and Exergy Performance of Vapour Compression Refrigeration Systems using Thirteen Ecofriendly Refrigerants in Primary Circuit and TIO 2 Nano Particles Mixed with

More information

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT Sivakumar.N a*, Agathiyan.V, Dhanush.S, Gokulnath.V, Jagadhesan.R b, c, d, e UG Scholar, Department of Mechanical Engineering, Gnanamani College

More information

HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT

HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT THERMAL SCIENCE, Year 2011, Vol. 15, Suppl. 2, pp. S391-S398 391 HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT by Thirupandiyur Selvanambi RAVIKUMAR a* and Dhasan MOHAN LAL b a Department

More information

Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression Refrigeration System

Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression Refrigeration System IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 10 April 2016 ISSN (online): 2349-784X Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression

More information

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 Volume 4 Issue 6 ǁ June. 2016 ǁ PP. 52-57 Performance analysis of a vapour compression

More information

Performance investigation of Air-conditioning system using ejector as expansion device

Performance investigation of Air-conditioning system using ejector as expansion device International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Performance

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Shoeb Inamdar 1, H. S. Farkade 2 P.G. Student, Department of Mechanical Engineering, Govt. College of Engg. Amravati. Maharashtra,

More information

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #43 System Drop-in Tests of Refrigerants L-41-1, L-41-2, and

More information

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate International Journal of Research in Engineering and Innovation (IJREI) Vol-1, Issue-2, (2017), 49-53 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning Journal of Physics: Conference Series PAPER OPEN ACCESS Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning To cite this article: Putu Wijaya Sunu et

More information

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 14, Issue 1 Ver. V (Jan. - Feb. 2017), PP 75-82 www.iosrjournals.org Experimental Evaluation of

More information

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System Available online at www.ijapie.org International Journal of Advanced Production and Industrial Engineering IJAPIE-SI-IDCM 606 (2017) 24 30 Special Issue on INNOVATIVE DESIGN & COMPUTATIONAL MODELLING Assessment

More information

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

More information

JJMIE Jordan Journal of Mechanical and Industrial Engineering

JJMIE Jordan Journal of Mechanical and Industrial Engineering JJMIE Jordan Journal of Mechanical and Industrial Engineering Volume 9 Number 4, August.21 ISSN 199-666 Pages 289-296 Thermodynamic Analysis of R12a and Dimethylether Refrigerant Mixtures in Refrigeration

More information

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor Mingyue Huang a, Xiangfei Liang a,b *, Rong Zhuang a a Gree Electric Appliances, Inc.of Zhuhai,Zhuhai 519070,China

More information

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor

More information

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Prof. S.V.Rao 1, Hitesh Sharma 2, Pankaj Kumar Gound 3, Tukaram Walgude 4, Shekhar Gavas 5 1 Prof.

More information

COMPRESSOR LESS SOLAR REFRIGERATOR

COMPRESSOR LESS SOLAR REFRIGERATOR COMPRESSOR LESS SOLAR REFRIGERATOR Om Prakash Umrao (Assistant Professor, ME) & Rajat Kumar Rajpoot, Siddhartha Verma, Shubham Tyagi, Yash Gupta, Yash Mishra Department Of Mechanical Engineering IMS Engineering

More information

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn: Comparison of Second Law Efficiency and Exergy Analysis of Refrigerants R-12, R-22, R-407C Influenced by Evaporator Temperature for Vapour Compression Refrigeration System Md Ozair Arshad Guest Faculty,

More information

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Mukesh K. Agrawal, Dr. Ashok G. Matani Abstract- The performance of heat transfer is one of the most important research

More information

Design of LPG Refrigeration System

Design of LPG Refrigeration System Design of LPG Refrigeration System Sethu Sathayan 1, Gopakumar M G 2, Jaya Krishnan S 3, Nanda Gopan 4, Nithin S 6 Assistant Professor, Department of Mechanical Engineering, SNIT Adoor, Kerala, India 1

More information

Mechanical Heat Pump R515

Mechanical Heat Pump R515 P.A.Hilton Ltd Mechanical Heat Pump R515 Above: R515 shown fitted with standard wattmeter Stabilises in minutes allowing many tests to be conducted in a typical laboratory period. Allows a complete refrigerant

More information

Performance Evaluation of Vapour Compression System with R22 and Environment-Friendly Refrigerant

Performance Evaluation of Vapour Compression System with R22 and Environment-Friendly Refrigerant Performance Evaluation of Vapour Compression System with R22 and Environment-Friendly Refrigerant A.N. Korshetti 1, Dr.V.N.Raibhole 2, N.A. Kumbhar 3 KJ s Trinity C.O.E., Pune, Maharashtra, India 1 M.E.S.

More information

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT R. Prapainop 1* and K. O. Suen 2 1 Department of Mechanical Engineering, Kasetsart University, Si Racha Campus, Chonburi, Thailand 2 Department

More information

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015 International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015 ISSN: 2289-4152 Performance Evaluation of Vapour Compression Refrigeration System Using Double Effect Condensing

More information

Numerical Simulation of Window Air Conditioner

Numerical Simulation of Window Air Conditioner Numerical Simulation of Window Air Conditioner Mathewlal T 1, Kalpesh Patil 2, Gauri Thorat 3, Anisha Ankush 4, Ambarish Pote 5, Kartik Doshi 6 ( 1 Associate ProfessorMechanical Engineering Department,

More information

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System A D Parekh, and P R Tailor Abstract Because of damaging effect of CFC refrigerants on stratospheric

More information

EXPERIMENTAL STUDY ON R1234YF HEAT PUMP AT LOW AMBIENT TEMPERATURE AND COMPARISON WITH OTHER REFRIGERANTS

EXPERIMENTAL STUDY ON R1234YF HEAT PUMP AT LOW AMBIENT TEMPERATURE AND COMPARISON WITH OTHER REFRIGERANTS EXPERIMENTAL STUDY ON R1234YF HEAT PUMP AT LOW AMBIENT TEMPERATURE AND COMPARISON WITH OTHER REFRIGERANTS Shuxue Xu 1, Jianhui Niu 2, Guoyuan Ma *1, 1 College of Environmental and Energy Engineering, Beijing

More information