Classification Report
|
|
- Buddy Gregory
- 5 years ago
- Views:
Transcription
1 Classification Report BASEC Client Report No. Hubbell Inc. (Delaware) L1CPRT801-1 Classification Number of pages in this Report: 6 Issue Date 3 January 2018 Items Tested 1 sample of Copper Communication Cable Specification(s) BS EN :2014 Authorised by: Issue Date: I McGuinness 3 January 2018 Laboratory Manager This Classification Report does not represent type approval or certification of the product. This Classification Report shall not be reproduced except in full, without written approval of the laboratory. British Approvals Service for Cables Presley House Presley Way Crownhill Milton Keynes MK8 0ES UK T: F: Notified Body No E: mail@basec.org.uk W:
2 Introduction This classification report defines the classification assigned to the product, Copper Communication Cable, in accordance with the procedures given in BS EN :2014 CLASSIFICATION OF REACTION TO FIRE FOR ELECTRIC CABLES IN ACCORDANCE WITH BS EN :2014 Sponsor: Hubbell Inc. (Delaware) Prepared for: Hubbell Inc. (Delaware), Premise Wiring Division, Suite 103, 23 Clara Drive, Mystic, CT 06355, USA Prepared by: British Approvals Service for Cables, Presley House, Presley Way, Crownhill Milton Keynes, MK8 0ES, United Kingdom Notified Body No Cable Family Name: U/UTP Cat 6 24AWG LSZH Classification Report No. L1CPRT801-1 Classification Issue number: 1 Date of issue: 3 January 2018 This classification report consists of 6 pages and may only be used or reproduced in its entirety. Report Issue Date: 03/01/2018 Page 2 of 6
3 Details of classified product General The product U/UTP Cat 6 24AWG LSZH is classified in accordance with the procedures given in BS EN :2014 and is defined as a copper communication cable according to BS EN 50575:2014+A1:2016. Product description The copper communication cable U/UTP Cat 6 24AWG LSZH is as described in the Sample details below. Traceability The test sample was selected by UL on behalf of BASEC and received on 14 April 2107 Sample details Parameter Test sponsor Contact address Details Hubbell Inc. (Delaware) Premise Wiring Division, Suite 103, 23 Clara Drive, Mystic, CT 06355, USA Cables submitted for test U/UTP Cat 6 24AWG LSZH (Sample 62) Trade Name 4 pair 24AWG U/UTP cable. Class 1 (solid) copper conductors, HD-PE insulation, NHFR filler, NHFR jacket OD = 6.0mm SPEEDCHANNEL 4 PR/24AWG LSZH Category 6 U/UTP Cable Report Issue Date: 03/01/2018 Page 3 of 6
4 Reports & results in support of this classification Reports Name of Laboratory Name of test sponsor Test reports Nos. Test method/field of application rules BS EN 50399:2011+A1:2016 BASEC Hubbell Inc. (Delaware) L1CPRT773 BS EN :2004+A11:2016 BS EN :2005+A1:2013 L1CPRT773a BS EN :2014 Results Test method Parameter No. tests runs Continuous parameter Results Compliance parameters FS 1.09m 1.5m = B2ca compliant THR1200s 4.6MJ 15MJ = B2ca compliant 1 Peak HRR 15.5kW 30kW = B2ca compliant BS EN 50399:2011 +A1:2016 FIGRA 104.9W/s 150W/s = B2ca compliant TSP1200s 15.9m 2 50m 2 = s1 compliant 1 Peak SPR 0.06m 2 /s 0.25m 2 /s = s1 compliant Flaming droplets/particles 1 <10s Flaming <10s = d1 compliant BS EN :2004 +A11:2016 BS EN A1:2013 H 1 82mm 425mm = Eca compliant Minimum transmission % 80% = s1a compliant BS EN :2014 ph/conductivity 3 ph = 5.2*, conductivity = 0µS/mm* ph > conductivity <2.5µS/mm = a1 compliant * The least best result for all components tested Report Issue Date: 03/01/2018 Page 4 of 6
5 Classification and field of application Reference of classification This classification has been carried out in accordance with BS EN :2014 Classification The communication cable in relation to reaction to fire behaviour is classified: B2 ca The additional classification in relation to smoke production is: The additional classification in relation to flaming droplets / particles is: s1a The additional classification in relation to acidity is: d1 The format of the reaction to fire classification for electric cables is: a1 Fire Behaviour Smoke Production Flaming Droplets Acidity B2 ca - s 1a, d 1, a 1 Reaction to fire classification: B2 ca -s1a,d1,a1 The classification assigned to the products in this report is appropriate to a declaration of conformity by the manufacturer within the context of system 1+ attestation of conformity and CE marking under the Construction Products Regulation. Report Issue Date: 03/01/2018 Page 5 of 6
6 Field of application This classification is valid for the copper communication cables described in Sample details and listed below: Brand Name Cable Identification Product Code Hubbell Inc (Delaware) U/UTP Cat 6 24AWG LSZH C6SCBZFRB22cc SPEEDCHANNEL 4 PR/24AWG, LSZH, Category 6 U/UTP Cable Reaction to Fire Classification B2 ca-s1a,d1,a1 This classification is valid for all end-use applications. Limitations This classification will be valid whilst; The test methods remain unchanged, The product standard or technical approval remains unchanged, Constructional or material modifications do not exceed limits of the field of application. The manufacturer has made a declaration, which is held on file, that the product placed in the marketplace, named in the product description section of this report and produced at the manufacturing plant listed therein, is exactly the same as the product that was tested. This classification document does not represent type approval or certification of the product. - - END OF REPORT Report Issue Date: 03/01/2018 Page 6 of 6
DELTA Classification Report
DELTA Classification Report TEST Reg. no. 19 Reaction to fire classification report for electric cables: Cat 6A U/FTP 500 MHz FRNC Performed for Caleb Cable Industrial Ltd. no.: Page 1 of 9 19 December
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Sponsor Prepared by P.O. Box 70 NL-5750 AB DEURNE Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280 CB
More informationREACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013
SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE CLASSIFICATION REPORT No. RA140063 ACCORDING TO THE EUROPEAN STANDARD NF EN 135011+A1:2013 Notification by the French Government
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationCentrum stavebního inženýrství a.s.
Centrum stavebního inženýrství a.s. Fire Technical Laboratory AUTHORIZED NOTIFIED BODY No. 22 BODY No. 9 CLASSIFICATION OF REACTION TO FIRE IN ACCORDANCE WITH EN 5-:27+A:29 Applicant: Příhoda s.r.o. Za
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationTFI Report Classification
TFI Report Classification of the Reaction to Fire according to EN 13501-1:2010 Customer Unilin bvba, Division Flooring Ooigemstraat 3 8710 Wielsbeke BELGIUM Product wall covering Wall covering This report
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification no.
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
ISO/IEC 17065:2012 to provide product conformity certification Presley Way Crownhill Milton Keynes MK8 0ES Contact: Tracie Hunter Tel: +44 (0)1908 267300 Fax: +44 (0)1908 267255 E-Mail: mail@basec.org.uk
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com CLASSIFICATION CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Sponsor Prepared by P.O. Box 118 NL-2394 ZG HAZERSWOUDE Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280
More informationClassification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:
Classification of reaction to fire performance in accordance with EN 13501-1: 2007 +A1: 2009 on Superfoil SFNC Prepared for: Boulder Developments Ltd Black Horse Farm Main Street Norwell Nottinghamshire
More informationWhite paper. Construction Product Regulations* by Multimedia Connect. Which cables are concerned by these new regulations?
White paper by Multimedia Connect Construction Product Regulations* We are all concerned by the safety of persons and property. In 2010, 8 million fires were recorded: they are estimated to have caused
More informationTest Report No: ICL/H17/7967
2294 Notified Body No 2700 Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK Presley House Presley Way Crownhill Milton Keynes MK8 0ES United Kingdom Contact: Jeremy Hodge Tel: +44 (0) 1908 267300 Fax: +44 (0) 1908
More informationNew European Cable Testing and Classification
New European Cable Testing and Classification THE BENCHMARK IN FIRE TESTING New European Cable Testing and Classification Cables will be tested using 5 test methods, and classified by extending the provisions
More informationAdditional reaction to fire classification report No H
Additional reaction to fire classification report. 12700H Owner of the additional classification report Antalis International 8 Rue de Seine 92517 Boulogne Billancourt Cedex France Introduction This additional
More informationREACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013
SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE CLASSIFICATION REPORT ACCORDING TO THE EUROPEAN STANDARD NF EN 13501-1+A1:2013 Notification by the French Government to the European
More informationClassification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.
Classification of reaction to fire performance in accordance with BS EN 13501-1: 2007 +A1: 2009 on Sandwich Panel, WP 50 Prepared for: Sandwich Panel Factory Jeddah Saudi Arabia 13 July 2011 0578 Page
More informationAFIREFENIX SZ1-K 0,6/1 kv PH120 (AS+)
Page 1 / 7 Construction and tests. Standards: UNE 211025 Compliance with the Low Voltage Directive (LVD): 2014/35 / EU Construction Products Regulation (CPR) - Regulation (EU) Nº 305/2011: Reaction to
More informationCPR: EUROCLASSIFICATION & TESTS FOR CABLES
Séance d information «Câbles dans la construction, quoi de neuf?» / Informatiesessie Kabels in de bouw, wat voor nieuws is er? CPR: EUROCLASSIFICATION & TESTS FOR CABLES ervé Breulet CPR & Cables June
More informationREACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013
SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE CLASSIFICATION REPORT ACCORDING TO THE EUROPEAN STANDARD NF EN 13501-1+A1:2013 Notification by the French Government to the European
More informationConstruction Products Regulation (CPR)
www.excel-networking.com S2 Construction Products Regulation (CPR) Section 2 In this Section: Pages What is CPR? 21 When will this happen? 21 Why the update? 21 Which products are affected? 21 Who is affected?
More informationREACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013
SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE CLASSIFICATION REPORT ACCORDING TO THE EUROPEAN STANDARD NF EN 50-+A:20 Notification by the French Government to the European Commission
More informationAdditional Reaction to Fire Classification Report
Additional Reaction to Fire Classification Report MDF Plate Client: Teknos A/S File no.: PCA10461Aad Date: 2018-01-09 Pages: 5 Encl.: 3 Ref: MPA / JAG Notified Body No. 0845 Danish Institute of Fire and
More informationREACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013
SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to fire REACTION TO FIRE CLASSIFICATION REPORT No. RA140265 ACCORDING TO THE EUROPEAN STANDARD NF EN 135011+A1:2013 ification by the French Government to
More informationÜntel is ready for CPR
2016 Üntel is ready for CPR Hakan Kubas Marketing Manager 01.11.2016 Construction Products Regulation What is the CPR? The Construction Products Regulation (CPR) lays down conditions for the placing or
More informationTest Report: ICL/CR15/11/087
Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk
More informationContact person Date Reference Page Richard Johansson P (2) Fire Research
issued by an Accredited Testing Laboratory Contact person Richard Johansson 215-8-13 5P4413 1 (2) Fire Research +46 1 516 56 75 richard.johansson@sp.se 12 ISO/IEC 1725 Sklejka-Pisz Paged S.A Ul. kwiatowa
More informationReaction to fire classification report No C
Reaction to fire classification report. 17911C Owner of the classification report Tapetex B.V. Distributor: Vescom bv Churchilllaan 10 Sint Jozefstraat 20 5705 BK Helmond 5750 AB Deurne The Netherlands
More informationConstruction Products Regulation (CPR) and BS 6701
Construction Products Regulation (CPR) and BS 6701 What you need to know Nancy De Clerck Product Manager Nexans Cabling Solutions Construction Products Regulation (CPR) Scope Performance classifications
More informationReaction to fire classification report No C-rev.1
Reaction to fire classification report. 17241C-rev.1 Owner of the classification report Distributor: Vescom bv Churchilllaan 10 Sint Jozefstraat 20 5705 BK Helmond 5750 AB Deurne The Netherlands The Netherlands
More informationClassification report
- Restricted Classification report Reaction to fire classification report of product Fibo-Trespo Bathroompanels / Respatex Bathroompanels Author Gunn Hofstad SINTEF NBL as Reaction to fire 2012-07-04 Table
More informationYOUR GUIDE TO UNDERSTANDING CPR
YOUR GUIDE TO UNDERSTANDING CPR WITH EXCEL NETWORKING SOLUTIONS ISSUE 2 UPDATED JANUARY 2018 WWW.EXCEL-NETWORKING.COM CONTENTS What is CPR? When will this happen? Why the update? Which products are affected?
More informationBelcom Cable excellence engineered through quality. CPR Construction Products Regulation
CPR Construction Products Regulation Index Construction Products Regulation... 3 What is the Construction Products Regulation (CPR)... 4 What is the objective of the CPR... 4 Who does the application of
More informationBS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests
More informationWORLDWIDE CABLE EXPERTS
WORLDWIDE CABLE EXPERTS An introduction to our cable testing and certification services CORPORATE BROCHURE PAGE I TWO Contents 2 Introducing BASEC 3 What we do 4 Management Systems Certification 5 Product
More informationCentrum stavebního inženýrství a.s.
Centrum stavebního inženýrství a.s. Fire Technical Laboratory AUTHORIZED NOTIFIED BODY No. 22 BODY No. 90 CLASSIFICATION OF REACTION TO FIRE IN ACCORDANCE WITH ČSN EN 50-+A:200 Applicant: Příhoda s.r.o.
More informationTFI Report Classification
TFI Report Classification of the Reaction to Fire according to EN 13501-1:2010 Customer Stuttgarter Straße 75 74321 Bietigheim-Bissingen GERMANY Product resilient floor covering Product 1: Scala 55 Connect
More informationCLASSIFICATION REPORT
CLASSIFICATION REPORT NUMBER 251.C.1804.020.EN.01 Work sheet: 21801003 DATE OF ISSUE April 10 th, 2018 NOTIFIED BODY PAGE TEST SPECIMEN CONCERNING TO APPLICANT DATE/S OF TEST AUTORIZED SIGNATORIES Notified
More informationNew European Fire Testing Classification for Construction Products
New European Fire Testing Classification for Construction Products THE BENCHMARK IN FIRE TESTING EU Construction Products Directive The EU Construction Products Directive (CPD), is the basis of construction
More informationBS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests
More informationCopper and Fibre Cabling Infrastructure Offering - Europe
Copper and Fibre Cabling Infrastructure Offering - Europe Panduit Enterprise Network Cabling Solutions provide the industry s most comprehensive portfolio of products and services that enable sustainable,
More informationBT Cables Technical Seminar CIBSE South Wales Region. Nov 17
BT Cables Technical Seminar CIBSE South Wales Region Nov 17 Agenda Introductions and BT Cables overview Construction Products Regulation Cables for BMS: A Technical Overview Q&A s Toby Collins Mark Froggatt
More informationClassification Report Reaction to fire of building elements DIN EN :2007. Class E
Classification Report Reaction to fire of building elements 10-001641-KB02-K06-01-e-01 Translation of Classification report 10-001641- KB02-K06-01-de-01 dated 16. May 2011 Client Deventer Profielen CV
More informationAnalysis Report
Prestige Carpets bvba Dhr. Dirk Santens Klein Frankrijk 38 9600 RONSE Your notice of Your reference Date 19-06-2013 24-07-2013 Required tests : Identification number T1309624 Information given by the client
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationConstruction Products Regulation (CPR) and cables. British Cables Association Guidance to Specifiers
Construction Products Regulation (CPR) and cables British Cables Association Guidance to Specifiers 1 Outline In January 2017 BCA issued its Guidance to Specifiers. A key consideration at the time was
More informationReaction to fire testing of Vescom vinyl wall covering with a Fibre Structure, a total weight of 550 g/m 2 according to EN 13823:2002
Efectis Nederland BV Efectis Nederland report 2008-Efectis-R0431[Rev.1](E) Reaction to fire testing of Vescom vinyl wall covering with a Fibre Structure, a total weight of 550 g/m 2 according to EN 13823:2002
More informationUK Direction BS7671 BS 8492 BS /01/2018
UK Direction BS7671 BS 8492 BS6701 23/01/2018 BS7671:2015 The 17 th Edition Revision 3 details the requirements for an improved fire rating on all cables within a fire route. 422.2.1 In conditions BD2
More informationLSOH Wiring Cables. LSOH Conduit Wire (HO7Z-R) Low Voltage (450/750 V) Cable Approvals. Key Applications. Conductor. Insulation. Core Identification
LSOH Wiring Cables Low Voltage (450/750 V) LSOH Conduit Wire (HO7Z-R) Cable Approvals Cable approved to BS7211 Key Applications > Manufactured to BS EN 50525-3-41 90 C cross linked (previously BS 7211)
More informationPUBLIC SUMMARY REPORT OF THE EGOLF EN 13823
PUBLIC SUMMARY REPORT OF THE EGOLF EN 13823 ROUND ROBIN 2015-2016 Authors: Anne Steen-Hansen, RISE Fire Research Nick Neumann, MFPA Leipzig Richard Johansson, RISE Safety Marina Andersson, RISE Safety
More informationForm: KSD-100:10 Page 1 of 3
/Translation from the Lithuanian language/ Form: KSD-100:10 Page 1 of 3 /Logo: GTC; DBS/ REACTION TO FIRE TESTING DIVISION FIRE REASEARCH CENTRE FIRE AND RESCUE DEPARTMENT UNDER THE MINISTRY OF THE INTERIOR
More informationCONSTRUCTION PRODUCTS REGULATION MOLEX CES COPPER AND FIBRE CABLE
CONSTRUCTION PRODUCTS REGULATION MOLEX CES COPPER AND FIBRE CABLE Carol Harris, EMEA Product Manager WHITE PAPER Molex Connected Enterprise Solutions EXECUTIVE SUMMARY Combustible construction materials
More informationTNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft. T F
ederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / etherlands Organisation for Applied Scientific Research TO report Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box 49
More informationBS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.
BS EN 60332-1-2:2004 Test On Electric And Optical Fibre Cables Under Fire Conditions WF Report Number 177603 Date: 14 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249 Page 2 of
More informationBS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.
BS EN 60332-1-2:2004 Test On Electric And Optical Fibre Cables Under Fire Conditions WF Report Number 177604 Date: 14 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249 Page 2 of
More informationCentexbel. General certification regulations. Construction products
Centexbel Scientific and Technical centre of the Belgian Textile Industry General certification regulations Construction products 22/03/17 blz. 1 / 8 Contents 1 Introduction 3 2 Object 3 3 Definitions
More informationThe new Gas Appliances Regulation (EU) 2016/426
The new Gas Appliances Regulation (EU) 2016/426 Background and overview A Whitepaper What is happening? As of 21 April 2018, the Gas Appliances Directive 2009/142/EC (GAD) will be replaced by the new Gas
More informationGuide to Gate Safety Legislation & the Machinery Directive
Guide to Gate Safety Legislation & the Machinery Directive Guide to Gate Safety Legislation & Machinery Directive Gate Safety in the UK market In June 2010 the tragic deaths of 2 young children in separate
More informationBS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:
BS EN 61034-2: 2005 Measurements Of Smoke Density Of Electric Cables WF Report Number 177599 Date: 17 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249 Page 2 of 13 Bodycote warringtonfire
More informationGuide to Gate Safety Legislation & the Machinery Directive. In Association with:
Guide to Gate Safety Legislation & the Machinery Directive In Association with: Tel: 0845 054 5070 asosafety@egduk.com Guide to Gate Safety Legislation & Machinery Directive Gate Safety in the UK market
More informationCatalogue Telecommunication Cables INTRODUCCIÓN
Catalogue Telecommunication Cables INTRODUCCIÓN Conductores Tecnológicos S.A. www.contecsa.es Index of Cables Page Introduction 3 EAP / EAP-R 4 EAPSP / EAPSP-R 5 ISP / ICP 6 Conductores Tecnológicos S.A.
More informationSelecting the AFUMEX range guarantees quality and offers the widest choice and the greatest safety.
When it matters most, you can be sure of a company that has an unrivalled reputation for high quality, British Standard compliant and cost effective Low Smoke, Zero Halogen (LSOH) cables. Our customers
More informationHigh Performance LSZH Fire Resistant Cable
High Performance LSZH Fire Resistant Cable www.cavicel.com 104/2 FIRECEL SR 114H is the long and well established CAVICEL fire resistant cable in the market, since many years. These cables are third party
More informationCPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation
CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation Speaker: Dr. L. K. Sze, Lipmann Technical Director of Date: 23 January, 2018 Disclaimer:
More informationCopper LAN cable. This specification describes the general requirements for AMP NETCONNECT* copper LAN cable.
Product Specification 108-93018 25/Aug/2011 Rev H Copper LAN cable 1. SCOPE 1.1. Content This specification describes the general requirements for AMP NETCONNECT* copper LAN cable. 2. APPLICABLE DOCUMENTS
More informationPassive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection
6 Inside buildings there are two types of fire protection systems: Active Fire Protection and Passive Fire Protection. Both systems should actively work together in the event of a fire. 6.1.1 The four
More informationDID YOU GET USED TO THE NEW CPR? HERE S A QUICK REVIEW!
June 2018 DID YOU GET USED TO THE NEW CPR? HERE S A QUICK REVIEW! How to recognize compliant cables? The new CPR defines the rules and the requirements of construction products to be manufactured, distributed
More informationSBI. Single Burning Item - EN THE BENCHMARK IN FIRE TESTING
SBI Single Burning Item - EN 13823 THE BENCHMARK IN FIRE TESTING FTT Single Burning Item (SBI) The importance of the SBI The European Construction Products Directive requires that all European Member states
More informationBS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2002 Fire Tests For
More informationREVIEW ON TWO PERFORMANCE-BASED TESTS FOR ASSESSING FLAME SPREAD IN HONG KONG
, Volume 5, Number 3, p.69-81, 2003 REVIEW ON TWO PERFORMANCE-BASED TESTS FOR ASSESSING FLAME SPREAD IN HONG KONG C.W. Leung Department of Building Services Engineering, The Hong Kong Polytechnic University,
More informationAbrasion Resistance of Fluoropolymer and polyester Coatings
Abrasion Resistance of Fluoropolymer and polyester Coatings British Standards British Standard 476 refers to fire tests on building materials and structures. The parts of this standard that are of most
More informationBCTC CARPET TECHNICAL CENTRE
Wira House West Park Ring Road Leeds, LS16 6QL Tel: +44 (0)113 259 1999 Fax: +44 (0)113 278 0306 Web: http://www.bttg.co.uk/bctc Email: CSLeeds@bttg.co.uk 7 September 2010 Page 1 of 7 Client: Rectory Farm
More informationgent warn nfire No, 16209C Reaction to fire class ification report lntroduction Owner of the classification report
a warn nfire global safety gent Reaction to fire class ification report No, 16209C Owner of the classification report TAPETEX bv VESCOM bv (Distributor) Churchilllaan 10 Sint-Jozefstraat 20 5705 BK Helmond
More informationbest practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to
best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to BS EN 16034: 2014 Permission to reproduce extracts from BS EN 16034 : 2014 is granted by BSI. DHF BEST PRACTICE
More informationTotal Fire Solutions. Includes BS 8519 and the updated BS :
Total Fire Solutions Includes BS 8519 and the updated BS 5266-1:2011 www.aeicables.co.uk Introduction: Total Fire Solutions Power and control cable systems for life safety and fire-fighting applications
More informationBS EN ISO : 2010
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2010 Fire Tests For Determination
More information~~oeti. Report VN71 O Classification Report. Reference
~~oeti Report VN71 O 137840.3 Classification Report Applicant EGETAEPPER NS lndustrivej Nord 25 7400-Herning Denmark Reference Lenette Ormstrup Application Classification of burning behaviour according
More informationCLASSIFICATION IN REGARD OF REACTION TO FIRE according to EN :2007
SWORN TRANSLATOR & INTERPRETER OF THE ENGLISH LANGUAGE Provincial Court Gdansk, Poland EWA KOCIK 7/9 Czubinskiego Street 80-215 Gdansk tel. (48) 58 345 50 76, (48) 509 209 454 logo : Certified translation
More informationBS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy
BS 476: Part 7: 1997 on K-Flex IN Clad Foil Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, 36 20877 RONCELLO (MB) Italy 30 th October 2012 0578 Page 1 of 6 Prepared on behalf of BRE Global
More informationIEC ; EN ; DIN VDE ; CEI 20-37/2-1 ; BS * No Corrosive Gas Emission
ADDISON Flame Retardant CAT5e Data Cables FTX-CAT5e U/UTP4P24 FTX-CAT5e f/utp4p24 FTX-CAT5e sf/utp4p24 LSZH Outer Aluminium/Polyester Tape Solid Copper Conductor PE Insulation Tinned Copper Drain Wire
More informationCAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?
CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? Marcelo M. Hirschler GBH International, USA ABSTRACT The results of three
More informationTelecommunication Cables
Telecommunication Cables Telecommunication Cables Introduction 3 EAP / EAP-R 4 EAPSP / EAPSP-R 5 ISP / ICP 6 Page ELECWIRES 2 www.elecwires.es INTRODUCCIÓN Telecommunication Cables Telephone cables suitable
More informationEN 1155:1997 TESTS OF : PERKO R106 FS CONCEALED FIXED ELECTRICALLY POWERED FREE SWING DEVICES FOR SWING DOORS. Leopold Street, Birmingham.
Exova Warringtonfire Key Industrial ark Fernside Road Willenhall West Midlands WV13 3YA T : +44 (0) 1902 722 122 F : +44 (0) 1902 727 242 E : willenhall@exova.com W: www.exova.com EN 1155:1997 TESTS OF
More informationBS EN : 2001 & IEC :2000
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 60695-2-11: 2001 & IEC 60695-2-11:2000
More information~,oeti. Report VN Classification Report. Reference
~,oeti Report VN710 140527.2 Classification Report ~ ~ 1so111:e 1102s "\ Applicant EGETAEPPER A/S lndustrivej Nord 25 7400-Herning Denmark Reference Lenette Ormstrup Application Classification of burning
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More informationBS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 1716: 2010 Determination Of The
More informationHavells Fire Survival Cables
Fire Survival Cables Designed for Critical Installation of National Importance Airports / Thermal Power Plants Metro Rail Projects / Rail Terminals / Nuclear Interstate Bus Terminals / Installation Prone
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More informationComtran Cable. Hub-LINK Cables for Transit Applications
Comtran Cable Hub-LINK Cables for Transit Applications Overview Hub-LINK rail transit cables are designed to resist the rugged conditions of the underground and at-grade environments, including: Temperature
More informationSUPPLEMENTARY REGULATIONS SPECIFIC TO CERTIFICATION OF PERSONAL PROTECTIVE EQUIPMENT (PPE)
SUPPLEMENTARY REGULATIONS SPECIFIC TO CERTIFICATION OF PERSONAL PROTECTIVE EQUIPMENT (PPE) SCS/SF/053-8 Issue 1 Sira Certification Service INTRODUCTION One of the conditions placed on all holders of Sira
More informationIEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IEC 60331-11-21 Method of test defined in
More informationBS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited
BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 153420 Date: 28 th April 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 153420 BS 476: Part
More informationEuropacable FAQ on CPR Status: 26/01/17
Europacable FAQ on CPR Status: 26/01/17 DISCLAIMER This FAQ document reflects the best knowledge of industry experts across Europe and the state of the art at the time of writing (July 2016). It represents
More informationBS EN ISO : 2010
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Fire Tests For Determination Of The Burning
More informationRegulation 574_2014: Annex III CPR. and. Regulation 568_2014: Annex V CPR
TF N 635 Regulation 574_2014: Annex III CPR and Regulation 568_2014: Annex V CPR 30-05-2014 28.5.2014 L 159/41 REGULATIONS COMMISSION DELEGATED REGULATION (EU) No 574/2014 of 21 February 2014 amending
More information