Date SECTION MEASUREMENT AND CONTROL INSTRUMENTATION Project Name Page 1

Size: px
Start display at page:

Download "Date SECTION MEASUREMENT AND CONTROL INSTRUMENTATION Project Name Page 1"

Transcription

1 Project Name Page 1 PART 1 GENERAL 1.1 A. The Hach RTC-N/DN Real Time Controller is a factory tested, standardized optimization solution with over 750 installations. The system uses a proprietary pre-written control logic running on a dedicated processor to output a signal. The system can be operated in open or closed-loop configurations and uses inputs from the Hach AMTAX sc online ammonium analyzer, Hach ANISE sc ammonium nitrate and nitrate analyzer, Hach NITRATAX sc nitrate analyzer, Hach LDO2 dissolved oxygen probe, plant flow, and temperature with preprogrammed algorithms are used to calculate the optimum DO concentration to maintain the desired ammonium levels. The output signal is a 0-20 ma or 4-20 ma current loop signal. B. The system integrates Prognosys, Hach s proprietary predictive diagnostic software to show operators real-time system performance and indicate service needs. If a sensor fails the system automatically falls back to pre-configured static dose and notifies operators. C. End users are provided with a pre-written O&M manual and a dedicated project management resource to coordinate system installation. Customers are granted priority access to our dedicated technical support resources. In the event of a system alarm, the support team is notified via text and . System data is uploaded in five minute intervals and can be analyzed by system experts in Loveland, Colorado to provide customized optimization recommendations. If onsite repair is required, a local field service technician will be dispatched to the customer site Section includes: A. Hach RTC105 Nitrification/Denitrification-Module, an Industrial PC (IPC) that uses NH4-N influent concentration, nitrate, flow rate, mixed liquor suspended solids, dissolved oxygen and temperature and a preprogrammed algorithm to calculate the exact DO required for the aeration system to reach the desired discharge values. B. Hach ANISE sc Sensor, an analyzer continuous monitoring of ammonium nitrogen and nitrate nitrogen in one probe in wastewater treatment, with predictive diagnostics capability to monitor instrument status. C. Hach Filtrax Sample Filtration System, for sample filtration consisting of: 1. Filter module holder 2. Control unit 3. Sample delivery hose D. Hach NITRATAX sc Sensor, for continuously monitoring nitrate in water, with predictive diagnostics capability to monitor instrument status E. Luminescent Dissolved Oxygen (LDO, Model 2) sensor for continuous measurement of dissolved oxygen (DO) in aqueous solutions, with predictive diagnostics capability to monitor instrument status. F. Hach sc1000 Digital Controller, a multi-parameter that works with digital sensors, with optional predictive diagnostics capability to monitor instrument status. 1.4 Measurement Procedures A. RTC105 NDN-Module 1. The module operates when connected to the sc1000 controller. 2. The module can be used for both open- and closed-loop control of precipitant dosing. 3. Input from the AMTAX sc analyzer, Nitratax sc probe, NH4-N probe, LDO2 probe, and a flow meter, in conjunction with preprogrammed algorithms, are used to calculate the optimum DO concentration to maintain the desired discharge levels. 4. The module produces a signal to control the DO blowers for optimum control. B. ANISE sc Sensor

2 Project Name Page 2 1. The method of measuring ammonium nitrogen and nitrate nitrogen is by ion-selective electrodes (ISE). a. A differential ph electrode is used as the reference. b. A potassium ISE is used to correct the ammonium value for the presence of potassium ion. c. A chloride ISE is used to correct the nitrate value for the presence of chloride ion. C. AMTAX sc 1. The method of measuring ammonium will be by gas sensitive electrode (GSE) that uses liquid to gas- phase conversion. a. Sample is mixed with sodium hydroxide that converts all ammonium to ammonia which is expelled from the sample. b. Ammonia gas is re-dissolved in an indicator reagent, changing the ph value to produce a color change. c. A colorimeter measures the color change of the solution and the reading is converted to ammonia concentration. D. Filtrax sc 1. The filter module holder shall be immersed at the sampling point. 2. The module holder shall contain two filters that are each spanned by a 0.15 μm membrane. 3. An air-purge system underneath the two immersed filter modules shall provide a continuous air supply to automatically clean the filter elements by preventing adhesion of solids to the filter membranes. 4. The sample shall be drawn through the immersed membranes via two tube-metering pumps which are housed within the control unit. 5. Operating with no wetted parts, the metering pumps shall draw the sample alternately from the two filter modules into the control unit via a 5-m (15-ft.) heated suction hose. 6. The sample shall be pumped up to 30-m (90-ft.) from the control unit to the process-measuring unit. E. NITRATAX sc Sensor 1. The method of measuring nitrate will be ultraviolet (UV) light absorption at 210 nm. a. A reference beam at 350 nm will provide a reference standard to correct for interference by turbidity and organic matter. F. LDO, Model 2 sc 1. The method of measuring dissolved oxygen will be a probe using luminescent sensor technology. a. Blue LED light excites platinum based luminescent material in the probe. Red light is emitted by luminescent material with characteristics that are directly proportional to the amount of dissolved oxygen present. The red light is measured with a photo detector. b. Red LED light is used to zero the instrument between measuring cycles. G. sc1000 Digital Controller 1. Change sensors connected to the controller by unplugging and plugging sensors as necessary. 2. The controller accepts up to eight sensor inputs from digital sensors. 1.5 Alternates A. Other sensors that do not use a differential ph reference electrode are not acceptable. B. Other sensors that do not use both potassium ISE to correct the ammonium value and chloride ISE to correct the nitrate value are not acceptable. C. Other instruments that do not use a GSE are not acceptable. D. Other methods of nitrate measurement, such as colorimetric, amperometric, potentiometric, and iodometric with electrodes, or those that require reagents are not acceptable. E. Other methods of dissolved oxygen measurement such as galvanic, poloragraphic, or luminescent measurements using Ruthenium are not acceptable. F. Instruments that do not have predictive diagnostic capabilities are unacceptable

3 Project Name Page 3 G. Other controllers that do not have the option for predictive diagnostic capabilities on connected instruments are unacceptable. 1.6 System Description A. RTC105 NDN-Module Performance Requirements: 1. Analog input/output signal current: 4-20 ma for flow rate measurement and dosing pump 2. Power supply is 24 VDC 3. Measurement error is ± 0.1% 4. Analog output conversion time is ~ 1.5 ms B. ANISE sc Sensor Performance Requirements 1. Measurement range ammonium: 0.2 to 1000 mg/l NH4-N 2. Measurement range nitrate: 0.2 to 1000 mg/l NO3-N 3. Accuracy: 5% of measured value ±0.2 mg/l (with standard solution) 4. Detection limit: 0.2 mg/l 5. Response time: less than 3 minutes (T90) 6. When connected to a multi-parameter digital control the overall status of the instrument performance is displayed as a percentage value via a measurement indicator 7. When connected to a multi-parameter digital control the overall time remaining until maintenance tasks are due is displayed in days C. AMTAX sc Performance Requirements 1. When connected to a multi-parameter digital control the overall status of the instrument performance is displayed as a percentage value via a measurement indicator 2. When connected to a multi-parameter digital control the overall time remaining until maintenance tasks are due is displayed in days 3. Measurement range (depending on model): a to 20 mg/l, or b. 1 to 100 mg/l, or c. 10 to 1000 mg/l 4. Lower detection limit (depending on model): a mg/l, or b. 1 mg/l, or c. 10 mg/l 5. Accuracy (depending on model): a. 3% ±0.05 mg/l, or b. 3% ±1.0 mg/l, or c. 4.5% ±10 mg/l 6. Reproducibility (depending on model): a. 2% ±0.05 mg/l, or b. 2% ±1.0 mg/l, or c. 2% ±10 mg/l 7. Response time: Less than 5 minutes (T90), including sample preparation 8. Measurement interval: 5 to 120 minutes, adjustable D. Filtrax sc Performance Requirements 1. The sample extraction and filtration system shall consist of three components: filter module holder, control unit, and sample delivery hose. 2. The control unit must be an IP55 rated, heated enclosure, designed for outdoor installation. 3. The system shall deliver a sample at a rate of up to 900 ml/h for up to three process instruments. 4. The sample filtration system shall provide two programmable, potential free contacts (115 or 230 VAC, max. 3A) to monitor the flow rate across the filter media. E. NITRATAX sc Sensor Performance Requirements

4 Project Name Page 4 1. Performance Requirements a. Measurement range (depending on model): 0.1 to 100 mg/l for nitrate (NOX-N) b. Accuracy (depending on model): ± 5 percent of mean ± 1.0 or better c. Resolution (depending on model): 0.1 or 0.5 mg/l d. Detection limit (depending on model): 0.1 to 100 mg/l e. When connected to a multi-parameter digital control the overall status of the instrument performance is displayed as a percentage value via a measurement indicator f. When connected to a multi-parameter digital control the overall time remaining until maintenance tasks are due is displayed in days F. LDO, Model 2 sc Performance Requirements 1. Measurement range: 0.01 to mg/l 2. Resolution: 0.01 mg/l 3. Accuracy a. Less than 5 ppm: ± 0.1 ppm b. Greater than 5 ppm: ± 0.2 ppm 4. Repeatability: ± 0.1 ppm 5. Response Time: a. Less than 40 seconds to 90% at 20 C b. Less than 60 seconds to 95% at 20 C 6. Temperature sensor: PT100 integrated, external sensor 7. Temperature range: 0 to 50 C 8. Temperature accuracy: ± 0.2 C 9. When connected to a multi-parameter digital control the overall status of the instrument performance is displayed as a percentage value via a measurement indicator 10. When connected to a multi-parameter digital control the overall time remaining until maintenance tasks are due is displayed in days G. sc1000 Digital Controller Performance Requirements 1. Communication and relay options for the sc1000 controller can be configured to suit any situation. Available configurations for a single Probe Module include: a. Up to 4 relay contacts for alarm and control functions b. Up to 12 analog outputs for measured values c. Up to 12 analog or digital inputs from non-digital sensors (i.e., flow or pressure sensors) d. Up to 8 digital inputs from digital sensors 2. When paired with an enabled sensor, the overall status of the sensor performance is displayed as a percentage value via a measurement indicator 3. When paired with an enabled sensor, the overall time remaining until maintenance tasks are due for the sensor is displayed in days 1.7 Certifications A. RTC105 NDN-Module 1. Conforms to EN /EN /29 2. Conforms to EN /EN B. ANISE sc Sensor 1. CE approved C. AMTAX sc 1. CE conform. 2. Listed to UL and CSA safety standards by TUV D. Filtrax sc 1. TUV to UL and CSA C22.2 No

5 Project Name Page 5 2. TUV to EN CE per 73/23/EEC and 93/68/EEC 4. Conforms to EN 61326:1997 / A1:1998 E. NITRATAX sc Sensor 1. Not applicable F. LDO, Model 2 sc 1. General Purpose CSA/CSA NRTL and FM (UL Pending) when used with an approved controller. 2. Class 1, Div 2 Groups A thru D CSA/CSA NTRL and FM (UL Pending) when used with an approved controller. G. sc1000 Digital Controller 1. ctuvus to UL 61010A-1 and CSA C22.2 No TUV-GS to EN CE per 73/23/EEC and 89/336/EEC 1.8 Environmental Requirements A. RTC105 NDN-Module 1. Working temperature: 0 to 50 C (32 to 122 F) 2. Storage temperature: 25 to +85 C ( 13 to 185 F) 3. Operating humidity: 95% relative humidity, non-condensing B. ANISE sc Sensor 1. Operating temperature -20 to 45 C (-4 to 114 F) 2. Sample temperature: 2 to 40 C (35 to 104 F) 3. Sample ph: 5 to 9 4. Sensor immersion depth: 0.3 to 3.0 meters (1 to 10 feet) maximum 5. Sample pressure: 0.3 bar (4.4 psi) maximum C. AMTAX sc 1. Sample temperature: 4 to 40 C (39 to 104 F) 2. Sample ph: 5 to 9 ph 3. Operating temperature: -20 to 45 C (-4 to 114 F) 4. Operating humidity: 95% relative humidity, non-condensing D. Filtrax sc 1. Immersion depth: 9.8 feet (3 m), maximum 2. Sample flow rate: 900 ml/h 3. Filtrate flow rate: 5 ml/min, minimum E. NITRATAX sc Sensor 1. Operating temperature: 0 to 40 degrees C (36 to 104 degrees F) 2. Operating pressure: 0.5 bar (7.2 psi) maximum F. LDO, Model 2 sc 1. Operating temperature: 0 to 50 C 2. Relative humidity: 95%, non condensing 3. Immersion depth: 15 meters (50 ft.), maximum 4. Immersion pressure: 345 kpa, maximum 5. Sample ph range: 0.0 to Distance, analyzer to sensor: 1000 meters, maximum G. sc1000 Digital Controller 1. Operating temperature: -4 to F (-20 to 55 C) 2. Storage temperature: -20 to 70 C (-4 to 158 F)

6 Project Name Page Warranty A. The AMTAX, FILTRAX, NITRATAX, sc1000 Digital Controller and the RTC103 N-Module include a one-year warranty from date of shipment. B. LDO, Model 2 sc 1. The probe body is warranted for 3 years from date of purchase 2. The sensor cap is warranted for 2 year from date of purchase 1.10 Maintenance Service A. RTC105 NDN-Module Scheduled Maintenance 1. Replace CF card every 2 years 2. Replace battery every 5 years B. ANISE sc Sensor Scheduled Maintenance 1. Monthly: visual inspection, if necessary, clean with brush and clear water 2. Bi-annually: replace calibrated sensor cartridge C. AMTAX sc Scheduled Maintenance 1. Replace stirrer arm: yearly 2. Replace valve pumps: yearly 3. Replace cylinder and piston: yearly D. AMTAX sc Unscheduled maintenance 1. Replace chemicals as required 2. Replace filter element, fan housing, filter element, and compressor as required E. Filtrax sc Scheduled Maintenance 1. Continuous self-cleaning F. NITRATAX sc Sensor Scheduled Maintenance 1. Check condition of wiper blades: monthly 2. Change wiper blades: after approximately 20,000 cycles 3. Replace sensor seals: yearly G. NITRATAX sc Sensor Unscheduled Maintenance 1. Replace UV lamp H. LDO, Model 2 sc Scheduled Maintenance 1. Sensor cleaning: 90 days or depending on conditions 2. Sensor and sensor cap inspection: 90 days 3. Sensor cap replacement: once every 2 years 4. Calibration: per regulatory agency schedule, otherwise calibration-free I. LDO, Model 2 sc Unscheduled Maintenance 1. Replace fuse 2. Clean instrument enclosure J. sc1000 Digital Controller Scheduled Maintenance 1. Clean controller keypad

7 Project Name Page 7 PART 2 PRODUCTS 2.1 Manufacturer A. RTC105 NDN-Module 1. Hach Company, Loveland, CO B. ANISE sc Sensor 1. Hach Company, Loveland, CO C. AMTAX sc Ammonium Analyzer 1. Hach Company, Loveland, CO D. Filtrax Sample Filtration System 1. Hach Company, Loveland, CO E. NITRATAX plus sc 1. Hach Company, Loveland, CO F. sc1000 Digital Controller 1. Hach Company, Loveland, CO 2.2 Manufactured Unit A. RTC105 NDN-Module consists of 1. Rail mounted PLC 2. Input and output connections B. ANISE sc Sensor consists of 1. The AN-ISE sc Ammonium and Nitrate Combination Sensor consists of a digital sensor with integrated, replaceable sensor cartridge. 2. The integrated sensor cartridge includes ammonium ISE, nitrate ISE, differential ph electrode, potassium ISE, chloride ISE, and temperature sensor. C. AMTAX sc Ammonium Analyzer consists of 1. Housing: ASA UV-resistant, IP55-rated, lockable 2. Gas sensitive electrode 3. Colorimeter D. Filtrax sc consists of 1. Filter module holder 2. Control unit 3. Sample delivery hose E. NITRATAX sc Sensor consists of 1. The NITRAX UV Nitrate Sensor consists of an immersible stainless steel probe with 10-meter cable. F. LDO, Model 2 sc 1. The Hach LDO system consists of submersible probe with stainless steel body, CPVC ends, replaceable sensor cap, and integral cable. G. sc1000 Digital Controller consists of 1. A microprocessor housed in an enclosure, rated IP65 2. The sc1000 controller is a modular system consisting of: a. Display module b. Probe module c. Connections for Hach digital sensors 2.3 Equipment A. RTC105 NDN-Module 1. Processor: Pentium 1, MMX compatible, 500 MHz clock rate 2. Flash memory: 2 GB compact flash card

8 Project Name Page 8 3. Internal working memory: 256 MB DDR-RAM 4. Interface: RJ 45 (Ethernet), 10/100 MBit/s 5. Diagnostic LEDs: Power, LAN speed, LAN activity, TC status, flash access 6. Expansion slot: Compact flash type II slot with ejection mechanism 7. Internal clock: Battery-buffered clock for time and date (battery can be replaced) 8. Operating system: Microsoft Windows 2 CE or Microsoft Windows Embedded Standard 9. Control software: TwinCAT PLC Runtime or TwinCAT NC PTP Runtime 10. System bus: 16 Bit ISA (PC/104 standard) 11. Power supply: Via system bus (through power supply module CX ) 12. Analog input: 4 20 ma for flow rate measurement 13. Analog output: 4 20 ma for dosing pump 14. Digital outputs: 1-channel: 1 for dosing pump and 1 alarm B. ANISE sc Sensor 1. The sensor is designed to connect to a universal digital controller. 2. The sensor cartridge is factory calibrated with all electrodes individually calibrated and also calibrated to each other. 3. The sensor does not require sample conditioning. 4. The sensor can perform one- or two-point inline matrix corrections to adapt it to a wastewater matrix. 5. The sensor is corrosion resistant and fully immersible. C. AMTAX sc 1. The analyzer calibrates and cleans itself automatically. 2. The analyzer is equipped with self-diagnostic routines. 3. The required power supply is 230 Vac/50Hz or optional 115 Vac/50-60Hz connected to a Hach model sc1000 multi-parameter universal controller. 4. Data transmission is made with a data cable with the controller. 5. Outputs include relay, current outputs, and bus interface via the controller. D. Filtrax sc 1. The system provides in-situ filtration. 2. The required power supply is via the analyzer 100 VA and electrical fuse protection. 3. Filter modules are exchangeable. 4. Continuous self-cleaning with air bubbles. 5. Particles larger than 0.15 μm are separated from the sample stream. 6. Available with 5 or 10 m heated filter probe hose E. NITRATAX sc Sensor 1. The sensor is equipped with a self-cleaning wiper system to prevent erroneous values and maintenance problems caused by surface films or particles. 2. The sensor uses no reagents. 3. The sensor compensates for interference from turbidity and organic contamination of up to 150 mg/l. 4. The sensor has the following characteristics: a. Enclosed in corrosion-resistant, V4A stainless steel. b. Uses 2-beam ultraviolet absorption technology with 2-mm path length. c. The measurement beam has a wavelength of 210 nm and is absorbed by nitrate and nitrite. d. The reference beam has a wavelength of 350 nm and is used to compensate for turbidity in the measured medium. 5. The measurement interval is user-selectable from one to 30 minutes. Up to 12 signals can be averaged. F. LDO, Model 2 sc 1. The Hach LDO Probe works with the sc100, sc200, or sc1000 controllers only.

9 Project Name Page 9 2. The sensor is made of polybutyl methacrolate. 3. The probe is made of CPVC and 316 stainless steel The probe is made with Viton o-rings. 5. The probe is entirely corrosion-resistant and fully immersible. 6. The probe utilizes a 1 NPT external thread for mounting hardware connections. 7. The probe does not require sample conditioning or electrolyte solutions. 8. The probe interface to the controller is MODBUS. 9. The operation of the probe is not affected by: H2S, ph, K+, Na+, Mg2+, Ca2+, NH4 +, Al3+, Pb2+, Cd2+, Zn2+, Cr (total), Fe2+, Fe3+, Mn2+, Cu2+, Ni2+, Co2+, CN, NO3, SO4 2, S2, PO4 3, Cl, Anion Active Tensides, Crude Oils, Cl2 < 4 ppm. 10. The probe is factory calibrated and needs no calibration or polarization prior to use. G. sc1000 Digital Controller 1. The sc1000 operates using 100 to 230 Vac, 50/60 Hz power or 24VDC. 2. The sc1000 uses a menu-driven operation system. 3. The display of the sc1000 is 1/4 VGA graphical backlit TFT color touch screen with 320 x 240 pixels resolution. 4. Each probe module of the sc1000 can support up to eight probes. Probe modules can be networked to accommodate more probes. 5. The sc1000 has a data logger. 6. The sc1000 can be equipped with four electromechanical SPDT relays, user-configurable contacts rated 100 to 230 Vac, 5 30 VDC resistive maximum. a. Additional relays are available via digital network connection. 7. The sc1000 can be equipped with up to 12 analog 0/4-20 ma outputs, maximum impedance 500 Ohms per probe module. a. Additional analog outputs are available via digital network connection. b. Optional digital communication via MODBUS (RS-485) or PROFIBUS DP. c. The sc1000 can be equipped with up to 12 analog 0-20 ma inputs, maximum impedance 500 Ohms per probe module. Additional analog inputs are available via digital network connection. 8. Alarms a. Low alarm point b. Low alarm point deadband c. High alarm point d. High alarm point deadband e. Off delay f. On delay 9. Controls a. PID b. High/low phasing c. Set-point d. Dead-band e. Overfeed timer f. Off delay g. On delay 10. Communication a. RS-485 (MODBUS) (optional) b. PROFIBUS DP (optional) c. Ethernet service port (standard) d. All user settings of the sc1000 are retained indefinitely in memory (non-volatile, EEPROM).

10 Project Name Page Components A. Standard Equipment 1. ANISE sc Sensor 2. AMTAX sc 3. Filtrax 4. NITRATAX plus sc Sensor 5. LDO, Model 2 sc 6. sc1000 Digital Controller 7. RTC105 NDN-Module 8. Manual B. Dimensions 1. ANISE sc Sensor: 12.6 x 3.3 inches (320 mm x 84.5 mm) 2. AMTAX sc: 21.3 x 28.3 x 15.4 in. (540 x 720 x 390 mm) 3. Filtrax sc a. Control Unit: 17 x 21 x 9 in. (430 x 530 x 220 mm) b. Module Holder: 4 x 20 x 13 in. (92 x 500 x 340 mm) c. Suction Hose: 5 m (heated) d. Sample Delivery Hose: 2 m (heated or unheated), 10 m (heated) 4. NITRATAX plus sc Sensor a. Length: 13.1 inches (33.3 cm) b. Diameter: 2.8 inches (7.0 cm) 5. LDO, Model 2 sc a. Probe & Sensor Cap 1) Length: 10.0 in. (255 mm) 2) Diameter: 1.94 in. (49.3 mm) b. Integral cable: 30 ft. (10 m) 6. sc1000 Digital Controller: 5.6 x 12.5 x 9.8 in. (142 x 315 x 250 mm) 7. RTC105 NDN-Module: 6.5 in in in. (165 mm 120 mm 96 mm) C. Weight 1. ANISE sc Sensor: 5.3 lb. (2.4 kg) 2. AMTAX sc: 38 lb. (31 kg) 3. Filtrax sc: a. Control Unit: 49 lb. (22 kg) b. Module Holder with 5-m Suction Tube: 20 lb. (9 kg) c. Mounting pipe, 6.6-ft. (2-m): 11 lb. (5 kg) d. Sample Tube, 33-ft. (5-m): 11 lb. (5 kg) 4. NITRATAX sc: 8.2 pounds (3.7 kg) 5. sc1000 Digital Controller: 14.3 lb. (6.5 kg) 6. RTC105 NDN-Module: 1.9 lb (0.9 kg) 2.5 Optional Accessories A. ANISE sc Sensor 1. Cables and power cord 2. Mounting kit a. Rail Mount b. Chain Mount 3. Cleaning unit 4. High Output Air Blast Cleaning Compressor

11 Project Name Page 11 B. AMTAX sc 1. Mounting kits (rail or stand) C. Filtrax 1. Mounting kit for control unit 2. Wall mount kit for module holder D. NITRATAX sc Sensor 1. Bypass panel (flow-through sample cell) for use when direct immersion is sample is impractical 2. Replacement wipers 3. Fixed point installation kit 4. Calibration kit 5. Cable extensions E. LDO, Model 2 sc 1. Plug in extension cables to extend the distance between the sensor and controller up to 985 ft. (10 m). 2. Junction box for extension cables for lengths greater than 100 m. 3. Extension cables 4. Pole mount kit 5. Ball float mount kit 6. In-line union mount kit 7. Flow cell mount kit 8. Economy probe mounting hardware 9. Air blast cleaning assembly F. sc1000 Digital controller 1. Sun shield 2. Internal network connector and cables G. RTC105 NDN-Module 1. None PART 3 EXECUTION 3.1 Preparation A. RTC105 NDN-Module 1. Mount in PLC cabinet on DIN rail B. ANISE sc Sensor 1. The sensor must be installed with the head submerged at least 30 cm below the surface, at least 10 cm above the bottom of the tank, and at least 30 cm from the wall of the tank. C. AMTAX sc 1. Wall-mount indoors or outdoors 2. Rail- and stand-mounting options available D. Filtrax sc 1. The control unit can be wall-mounted or free-standing mounting kit for the control unit can be used. 2. An optional basin wall mount kit available for module holder mounting (submerged) in an aeration basin or effluent channel is also available. The control unit and sample suction hose are equipped with standard heating; also available unheated in several lengths. The filter module holder shall be immersed at the sampling point. E. NITRATAX sc Sensor 1. The optional fixed point installation kit recommended for mounting the probe. 2. The probe can be mounted to a bypass panel when direct immersion in a sample stream is impractical.

12 Project Name Page 12 F. LDO, Model 2 sc 1. Mounting: a. The sensor must be mounted to a Hach mounting assembly directly in the solution to be measured. b. Pole or ball-float mount 2. Distance, analyzer to sensor: 300 meters, maximum G. sc1000 Digital Controller 1. Mount on rail, panel, pipe, or wall 3.2 Installation A. Contractor will install the analyzer in strict accordance with the manufacturer s instructions and recommendation. B. Manufacturer s representative will include a half-day of start-up service by a factory-trained technician, if requested. 1. Contractor will schedule a date and time for start-up. 2. Contractor will require the following people to be present during the start-up procedure. a. General contractor b. Electrical contractor c. Hach Company factory trained representative d. Owner s personnel e. Engineer 3.3 Manufacturer s Service and Start-Up A. Contractor will include the manufacturer s services to perform start-up on instrument to include basic operational training and certification of performance of the instrument. B. Contractor will include a manufacturer s Service Agreement that covers all the manufacturer s recommended preventative maintenance, regularly scheduled calibration and any necessary repairs beginning from the time of equipment startup through to end user acceptance / plant turnover and the first 12 months of end-user operation post turnover. C. Items A and B are to be performed by manufacturer s factory-trained service personnel. Field service and factory repair by personnel not employed by the manufacturer is not allowed. D. Use of manufacturer s service parts and reagents is required. Third-party parts and reagents are not approved for use. END OF SECTION

Date SECTION MEASUREMENT AND CONTROL INSTRUMENTATION Project Name Page 1

Date SECTION MEASUREMENT AND CONTROL INSTRUMENTATION Project Name Page 1 Project Name Page 1 PART 1 GENERAL 1.1 Section includes: A. A modular single or dual channel controller that works with analog sensor modules and/or digital sensors. 1.2 Measurement Procedures A. Microprocessor-based

More information

Date SECTION MEASUREMENT AND CONTROL INSTRUMENTATION Project Name Page 1

Date SECTION MEASUREMENT AND CONTROL INSTRUMENTATION Project Name Page 1 Project Name Page 1 PART 1 GENERAL 1.1 Section includes: A. Phosphate process analyzer for semi - continuous monitoring of phosphate in water. 1.2 Measurement Procedures The phosphate analyzer shall be

More information

AquaLynx 200 ADX. Monitoring and Control System. Background. Operation

AquaLynx 200 ADX. Monitoring and Control System. Background. Operation AquaLynx 200 ADX Monitoring and Control System The RODI Systems AquaLynx 200 ADX is a unique monitoring system for water treatment applications. The AquaLynx 200 ADX offers a dependable yet affordable

More information

SECTION Free/Available Chlorine Analysis System

SECTION Free/Available Chlorine Analysis System SECTION 40 75 21 Free/Available Chlorine Analysis System PART 1 General 1.01 SUMMARY A. Requirements for a digital sensor system for free chlorine measurement for disinfection purposes in drinking water,

More information

Model Q45P/R. ph/orp Monitor...

Model Q45P/R. ph/orp Monitor... Model Q45P/R ph/orp Monitor... Sensor Mounting Configurations The Differential Difference ORP Monitor ATI's versatile Q45P/R ph/orp system is designed for use in all industrial and municipal applications.

More information

Series 5000 Hydrazine Analyzer Model 60002

Series 5000 Hydrazine Analyzer Model 60002 Series 5000 Hydrazine Analyzer Model 60002 T he patented* Series 5000 Hydrazine Analyzer is a continuous-reading instrument using the p-dimethylaminobenzaldehyde method of analysis for colorimetric measurement

More information

Improve Performance and Reduce Maintenance Costs. Model Q45D. Dissolved Oxygen Monitor...

Improve Performance and Reduce Maintenance Costs. Model Q45D. Dissolved Oxygen Monitor... Improve Performance and Reduce Maintenance Costs Model Q45D Dissolved Oxygen Monitor... Why Throw Away Money? Why Throw Away Money? ATI s Model Q45D Dissolved Oxygen monitor is designed to provide reliable

More information

Model Q45P/R. ph/orp Monitor...

Model Q45P/R. ph/orp Monitor... Model Q45P/R ph/orp Monitor... Sensor Mounting Configurations The Differential Difference ORP Monitor ATI's versatile Q45P/R ph/orp system is designed for use in all industrial and municipal applications.

More information

DL423 DirectLine Sensor Module for Conductivity Measurement Specifications

DL423 DirectLine Sensor Module for Conductivity Measurement Specifications DL423 DirectLine Sensor Module for Conductivity Measurement Specifications 70-82-03-47 January 2003 Overview DirectLine DL423 for Conductivity measurement is a family of sensors released by Honeywell as

More information

DL424/425 DirectLine Sensor Module for Dissolved Oxygen Probes Series DL5000 Specifications

DL424/425 DirectLine Sensor Module for Dissolved Oxygen Probes Series DL5000 Specifications DL424/425 DirectLine Sensor Module for Dissolved Oxygen Probes Series DL5000 Specifications 70-82-03-48 January 2003 Overview The DirectLine DL424/425 Sensor Modules are part of a family of products developed

More information

Figure 1 DirectLine DL423 Sensor. Description, continued

Figure 1 DirectLine DL423 Sensor. Description, continued DL423 DirectLine Sensor Module for Conductivity Measurement Overview 70-82-03-47 4/02 Page 1 of 8 Specification DirectLine DL423 for Conductivity measurement is a family of sensors released by Honeywell

More information

Steam and Water Analysers

Steam and Water Analysers Steam and Water Analysers A Comprehensive Range for Steam and Water Analysis System (SWAS) ANALYTICAL INSTRUMENTS Energy Conservation Environment Process Efficiency www.forbesmarshall.com Steam and Water

More information

ROYCE SUSPENDED SOLIDS SYSTEM MODEL 7011A AND SENSORS MODELS 72A, 72P, 73B, 74A, 75A & 76A

ROYCE SUSPENDED SOLIDS SYSTEM MODEL 7011A AND SENSORS MODELS 72A, 72P, 73B, 74A, 75A & 76A SPECIFICATIONS (Revised 1/12/2006) ROYCE SUSPENDED SOLIDS SYSTEM MODEL 7011A AND SENSORS MODELS 72A, 72P, 73B, 74A, 75A & 76A The system shall operate on the principle of light absorption. It shall consist

More information

SECTION Fluorescent Dissolved Oxygen Measuring System

SECTION Fluorescent Dissolved Oxygen Measuring System SECTION 40 75 43 Fluorescent Dissolved Oxygen Measuring System PART 1 General 1.01 SUMMARY A. Requirements for a high-performance, digital fluorescence sensor for measurement of dissolved oxygen in liquid.

More information

Figure 1 DirectLine DL423 Sensor. Description, continued

Figure 1 DirectLine DL423 Sensor. Description, continued DL423 DirectLine Sensor Module for Conductivity Measurement Overview 70-82-03-47 1/03 Page 1 of 8 Specification DirectLine DL423 for Conductivity measurement is a family of sensors released by Honeywell

More information

Dissolved Oxygen Measurement liquisys M COM 223 / 253

Dissolved Oxygen Measurement liquisys M COM 223 / 253 Technical Information TI 199C/24/ae Dissolved Oxygen Measurement liquisys M COM 223 / 253 Oxygen Controller Benefits at a glance Liquisys M COM 223 Liquisys M COM 253 Due to the modularity of its design,

More information

MultiMeter 44. Transmitter-regulator with 1, 2 or 3 channels. Quality at a reasonable price

MultiMeter 44. Transmitter-regulator with 1, 2 or 3 channels. Quality at a reasonable price MultiMeter 44 Transmitter-regulator with 1, 2 or 3 channels MultiMeter 44 is a modular meter that can be configured with one, two or three channels. It can be delivered with only one measuring channel,

More information

SECTION Process and Immersion Turbidity and Total Suspended Solids Sensor

SECTION Process and Immersion Turbidity and Total Suspended Solids Sensor SECTION 40 75 53 Process and Immersion Turbidity and Total Suspended Solids Sensor PART 1 General 1.01 SUMMARY A. Requirements for a digital sensor for process turbidity or Total Suspended Solids (TSS)

More information

WESTSIDE WASTEWATER TREATMENT PLANT - DIFFUSER REPLACEMENT JOLIET CONTRACT NUMBER:

WESTSIDE WASTEWATER TREATMENT PLANT - DIFFUSER REPLACEMENT JOLIET CONTRACT NUMBER: ADDENDUM NO. 3 FEBRUARY 24, 2017 WESTSIDE WASTEWATER TREATMENT PLANT - DIFFUSER REPLACEMENT JOLIET CONTRACT NUMBER: 2231-0417 FOR THE: CITY OF JOLIET, IL DATED: FEBRUARY 2017 PREPARED BY: CLARK DIETZ,

More information

AS950 PORTABLE SAMPLERS

AS950 PORTABLE SAMPLERS AS950 PORTABLE SAMPLERS Applications Wastewater Collections Industrial Pretreatment Environmental Monitoring Stormwater Sampling has never been this easy. The AS950 Portable Sampler makes programming,

More information

SCM. Micro. Streaming Current Monitor. Analyzer. Sensor/Sampler with light shield removed. The Analyzer. Instrument Overview

SCM. Micro. Streaming Current Monitor. Analyzer. Sensor/Sampler with light shield removed. The Analyzer. Instrument Overview Micro SCM Streaming Current Monitor A Watts Water Technologies Company Instrument Overview The instrument consists of the Analyzer and the SCM sensor. Analyzer The Analyzer The monitor has a built in graphic

More information

AS950 REFRIGERATED SAMPLERS

AS950 REFRIGERATED SAMPLERS AS950 REFRIGERATED SAMPLERS Applications Wastewater Collections Industrial Pretreatment Environmental Monitoring Stormwater Sampling has never been this easy. The AS950 Refrigerated Sampler makes programming,

More information

portable gas analyser

portable gas analyser www..com portable gas analyser The largest of s analysers equipped with electrochemical cells. It can fit even up to 7 EC cells and up to 3 sensors. GA-60 has a large (320*240), graphical LCD with backlighting.

More information

UDA2182 Universal Dual Analyzer

UDA2182 Universal Dual Analyzer UDA2182 Universal Dual Analyzer Overview The UDA2182 Universal Dual Analyzer is a new, economical, dual input analyzer addition to Honeywell s Smart Sensor product family. The analyzer can accept single

More information

SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu)

SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu) PART 1 - GENERAL A. RELATED DOCUMENTS SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu) Federal, State, and local requirements as applicable. Attached Permit Attached drawings B. SUMMARY 1. Provide

More information

SECTION INDUCTIVE CONDUCTIVITY ANALYZERS

SECTION INDUCTIVE CONDUCTIVITY ANALYZERS SECTION 40 75 16 INDUCTIVE CONDUCTIVITY ANALYZERS PART 1 General 1.01 SUMMARY A. Requirements for a digital inductive conductivity sensor for standard, hazardous and hightemperature applications. The sensor

More information

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11 Table of Contents 1. OVERVIEW... 3 2. SYSTEM LAYOUT... 4 3. SPECIFICATIONS... 8 3.1 SYSTEM COMPONENTS...9 3.2 PLC INPUTS AND OUTPUTS...9 3.3 FUNCTION KEYS...10 3.4 DEFAULT SET POINTS AND TIMERS...10 4.

More information

AS950 ALL-WEATHER REFRIGERATED SAMPLERS

AS950 ALL-WEATHER REFRIGERATED SAMPLERS AS950 ALL-WEATHER REFRIGERATED SAMPLERS Applications Wastewater Collections Industrial Pretreatment Environmental Monitoring Stormwater Sampling has never been this easy. The AS950 All-Weather Refrigerated

More information

SAMPLE MANUAL - INSTALLATION - FOR REFERENCE ONLY. ChemScan mini Analyzer. Parameter. Method #### Installation, Operation & Maintenance Manual

SAMPLE MANUAL - INSTALLATION - FOR REFERENCE ONLY. ChemScan mini Analyzer. Parameter. Method #### Installation, Operation & Maintenance Manual Parameter Method ####, Operation & Maintenance Manual Rev 3/26/2018 Contact Information Document Information Customer Name: Plant Name/Location: Date: Analyzer Serial #: ASA, Inc. (Applied Spectrometry

More information

Concise catalogue Water-Industry

Concise catalogue Water-Industry 2008 Concise catalogue Water-Industry One-channel instruments to measure ph, EC, DO and free chlorine, panel and wall-mounting version. Transmitters - controllers very easy to utilize, the customer does

More information

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5

More information

UDA2182 Universal Dual Analyzer

UDA2182 Universal Dual Analyzer UDA2182 Universal Dual Analyzer Overview The UDA2182 Universal Dual Analyzer is a new, economical, dual input analyzer addition to Honeywell s Smart Sensor product family. The analyzer can accept single

More information

Data Sheet. >>AMTAX inter 2

Data Sheet. >>AMTAX inter 2 Data Sheet DOC053.52.03086.NOV02 - Subject to change without notice >>AMTAX inter 2 Ammonium Process Photometer 1 Technical data 1. Technical data Measuring technique: Indophenol blue method, derived from

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

OPTISENS TUR 2000 Technical Datasheet

OPTISENS TUR 2000 Technical Datasheet OPTISENS TUR 2000 Technical Datasheet Sensor for turbidity measurement in water and wastewater Rugged design for harsh applications Integrated transmitter with direct 4...20 ma output Near infrared light

More information

Hydrazine Analyzer Series 2171 Specifications

Hydrazine Analyzer Series 2171 Specifications Hydrazine Analyzer Series 2171 Specifications 70-82-03-64 November 2009 Introduction The 2171 is the most advanced hydrazine instrument specifically developed for use in continuous measurement and determination

More information

900MAX PORTABLE SAMPLERS

900MAX PORTABLE SAMPLERS 900MAX PORTABLE SAMPLERS Applications Wastewate Collections The Hach Sigma 900MAX Portable Sampler s advanced technology and comprehensive customer service can be summarized in five key concepts: accuracy,

More information

A New Standard of Excellence

A New Standard of Excellence A New Standard of Excellence PREVENTION IS SO EASY... LIVING THROUGH A DISASTER IS NOT The reliable identification of low combustion oxygen in a fired heater or boiler has always been critical to the effectiveness

More information

Temperature Controllers

Temperature Controllers Model TEC-4100 1/4 DIN Model TEC-4100 1/4 DIN Temperature Controller Ordering Code: Power Input BOX 1 4 = 90-250 VAC 5 = 11-26 VAC / VDC TEC-4100- Configurable for 4 Programmable Outputs and NEMA 4X/IP65

More information

Corporate Profile. needs and product demands. CON 08X /03 Rev 0

Corporate Profile. needs and product demands. CON 08X /03 Rev 0 Corporate Profile A leader in the field of electrochemical instrumentation, Eutech Instruments is a dynamic company rapidly positioning itself globally as a leading manufacturer of electrochemical instrumentation

More information

Krypton K CL2. Measuring and control system for free chlorine. applications. description. Low maintenance by automatic sensor cleaning

Krypton K CL2. Measuring and control system for free chlorine. applications. description. Low maintenance by automatic sensor cleaning Low maintenance by automatic sensor cleaning Pressure-proof up to 6 bar at 20 C Higher safety by integrated flow monitoring applications Drinking Water / Beverages Food Industry Disinfection Cooling And

More information

CLARITY II TURBIDIMETER

CLARITY II TURBIDIMETER Product Data Sheet PDS 71-T1055/rev.J January 2006 Model T1055 CLARITY II TURBIDIMETER COMPLETE SYSTEM includes single or dual input analyzer, sensor(s), and debubbler assembly CHOOSE U.S. EPA METHOD 180.1

More information

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6 Digital Gas Transmitters with Auxiliary s & Control Specifications subject to change without notice. USA 181011 Page 1 of 5 DESCRIPTION Digital RS-485 communicating, addressable toxic and combustible gas

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

MOVING FILTER AIR MONITOR ALPHA, BETA/GAMMA PARTICULATES

MOVING FILTER AIR MONITOR ALPHA, BETA/GAMMA PARTICULATES FEATURES: MOVING AIR FILTER AIRBORNE ALPHA LESS RADON AND BETA/GAMMA PARTICULATES RUGGED, 100% DUTY CYCLE SETTABLE ALARM HIGH THROUGH-PUT UNATTENDED OPERATION 12 WEEKS PRINTED RECORD (Optional) 4 CHANNEL

More information

Pump-Up Controller MODEL 4062

Pump-Up Controller MODEL 4062 Pump-Up Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4062 Pump-Up

More information

DFM. flow pressure temperature MULTI PARAMETER DIGITAL MASS FLOW METERS. Totalizer. Interface

DFM. flow pressure temperature MULTI PARAMETER DIGITAL MASS FLOW METERS. Totalizer. Interface Multi Parameter flow meters provide accurate data on three different fluid parameters: flow pressure temperature The flow rate can be displayed in volumetric flow or mass flow engineering units for standard

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

Nov 08 PRODUCT SPECIFICATION SHEET

Nov 08 PRODUCT SPECIFICATION SHEET Honeywell UDC1200 and UDC1700 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS 51-52-03-35 Nov 08 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1200 & UDC1700 are microprocessor-based 1/16 DIN and 1/8 DIN

More information

02/11/2015

02/11/2015 MIC48 With RS 485 link Part number 89422418 Heating and / or cooling function 2 independent alarms Load break detection 2 setpoint which can be selected remotely Manual / automatic power adjustment RS

More information

SECTION ph/orp Sensors

SECTION ph/orp Sensors SECTION 40 75 13 ph/orp Sensors PART 1 General 1.01 SUMMARY A. Requirements for a ph/orp sensor for in-process measurement. The sensor will incorporate Memosens digital technology for maximum process and

More information

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

Model 144H. Product Data Sheet , Rev DB February Content

Model 144H. Product Data Sheet , Rev DB February Content Rosemount 144 PC-Programmable Temperature Transmitter Provides an installation-ready solution for temperature monitoring applications using Complete Point Solutions (CPS) Increases measurement accuracy

More information

Pump-Down Controller MODEL 4052

Pump-Down Controller MODEL 4052 Pump-Down Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4052 Pump-Down

More information

APPLIED. OMA-300 Hydrogen Sulfide Analyzer H 2. Ex p. Ex d. The world s safest continuous H 2. S analyzer. The OMA continuously measures H 2

APPLIED. OMA-300 Hydrogen Sulfide Analyzer H 2. Ex p. Ex d. The world s safest continuous H 2. S analyzer. The OMA continuously measures H 2 H 2 S Ex p Ex d The world s safest continuous H 2 S analyzer. The OMA continuously measures H 2 S concentration using a full-spectrum UV-Vis spectrophotometer, harvesting the power of collateral data to

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET Control Systems Transmitters Sensors Accessories Wall, 19 Rack or Panel Mounting Units 110/230V 50/60Hz AC operation 250 Addressable devices as: Relays, 4-20 Inputs or Gas Detectors

More information

Mark 25 Ultrapure Water Conductivity Analyzer

Mark 25 Ultrapure Water Conductivity Analyzer Martek Instruments, Inc. Mark 25 Ultrapure Water Conductivity Analyzer Instruction Manual WARRANTY POLICY Unless otherwise stated, MARTEK INSTRUMENTS, INC. warrants this equipment to be free from defects

More information

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 4/01 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1000 and UDC1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers

More information

for Drinking Water Systems

for Drinking Water Systems Water Quality Measurement Solutions Instrument Overview Online UV%Transmission Analyzer for Drinking Water Systems HF scientific developed the AccUView UV%Transmission Analyzer specif ically to f ill the

More information

DTM Distributed Transmitter-Monitor

DTM Distributed Transmitter-Monitor DTM Distributed Transmitter-Monitor DTM10 Proximity Distributed Transmitter-Monitor (Shaft Vibration, Thrust Position and Speed) The DTM10 distributed vibration transmitter-monitor is ideal for monitoring

More information

Danfoss gas detection unit Type GD Heavy Duty

Danfoss gas detection unit Type GD Heavy Duty Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx

More information

Smart Sensors and Analytical Instruments Honeywell Solutions for Analytical Measurement and Control

Smart Sensors and Analytical Instruments Honeywell Solutions for Analytical Measurement and Control Industrial Measurement and Control Smart Sensors and Analytical Instruments Honeywell Solutions for Analytical Measurement and Control EASY TO INSTALL... EASY TO USE... EASY TO MAINTAIN... EASY TO OWN.

More information

WASTEWATER Online UV%Transmission Analyzer

WASTEWATER Online UV%Transmission Analyzer Water Quality Measurement Solutions Online UV%Transmission Analyzer Detailed Specifications Instrument Overview With over 30 years of optical design technology expertise HF scientific has developed it's

More information

gas monitoring system

gas monitoring system www..com gas monitoring system Photon S is s most recent and most sophisticated apparatus. It was created based on portable gas analyser - Photon. As its sucessor it also uses gas sensors as the main measurement

More information

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements Specifications COMMANDER 150 Universal Process Indicator High visibility 6-digit LED display the clearest view of your process status 0.1% measurement accuracy precise indication of process measurement

More information

Free Chlorine Measuring System

Free Chlorine Measuring System Product Data Sheet PDS 71-FCL/rev.H September 2008 Model FCL Free Chlorine Measuring System COMPLETE SYSTEM INCLUDES sensor, connecting cable, analyzer, and flow controller. CONTINUOUS ph CORRECTION eliminates

More information

2100 Series Laboratory Turbidimeters. Pioneering technology in turbidity monitoring.

2100 Series Laboratory Turbidimeters. Pioneering technology in turbidity monitoring. 2100 Series Laboratory Turbidimeters Pioneering technology in turbidity monitoring. Superior performance Easier operation Hach turbidimeters are the preferred choice of water quality managers around the

More information

Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping. Touch Panel PPI

Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping. Touch Panel PPI HumiTherm Ultra Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping Mapping Unit Micro PLC Control Unit Touch Panel Touch Operation Panel PPI HumiTherm Ultra GSM Module

More information

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM User Instructions For The Model 5200 Gas Monitor System To completely customize the specifications to your exact application, modifications to the following

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly

DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly DREXELBROOK A Leader In Level Measurement Solutions USonic-R Series Ultrasonic Level Measurement System User Friendly Set the measurement range directly in inches, feet, millimeters, centimeters, or meters

More information

Dräger Polytron 8000 Stationary gas detector (EC)

Dräger Polytron 8000 Stationary gas detector (EC) Dräger Polytron 8000 Stationary gas detector (EC) The microprocessor-based transmitter can be equipped with various electrochemical DrägerSensors. This way, you can easily detect oxygen and various toxic

More information

EMS510 PS-1 COMPLIANT OPACITY/DUST MONITOR

EMS510 PS-1 COMPLIANT OPACITY/DUST MONITOR EMS510 PS-1 COMPLIANT OPACITY/DUST MONITOR The EMS510 provides continuous, low maintenance, precision measurement of Opacity and Dust (mg/m3). It is designed for monitoring visible smoke in the exhaust

More information

AH3000 SERIES 180MM CHART PEN TYPE HYBRID RECORDER

AH3000 SERIES 180MM CHART PEN TYPE HYBRID RECORDER AH3000 SERIES 180MM CHART PEN TYPE HYBRID RECORDER MODEL AH3 7 P - - A AH3000 series conforming to CE, UL and CSA are 180mm pen type hybrid recorders with a simultaneous display of multi-channel data,

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

HIGH CAPACITY PRODUCT LINE

HIGH CAPACITY PRODUCT LINE HIGH CAPACITY PRODUCT LINE Highest Quality, Best Service Manufacturing chlorination equipment and related products since 1978 PROUDLY MADE IN USA 600 Emlen Way, Telford, PA 18969 Telephone: (215) 799-0980

More information

Serie Rugghölzli 2 CH Busslingen. Tel. +41 (0) Fax +41 (0)

Serie Rugghölzli 2 CH Busslingen. Tel. +41 (0) Fax +41 (0) Serie 5000 Tel. +1 (0)5 222 Fax +1 (0)5 222 12 PRODUCT INTRODUCTI PRODUCT INTRODUCTI 5 Series programmable temperature controller is FineTek's mid-range series of controllers. It uses a 12bit analog /

More information

UDC100 Universal Digital Controller Specifications

UDC100 Universal Digital Controller Specifications UDC100 Universal Digital Controller Specifications 51-52-03-29 November 1999 Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

portable gas analyser

portable gas analyser www..com portable gas analyser Professional flue gas analyser that combines high quality of sample conditioning with great measurement accuracy. The device is contained in a compact soft casing. Analyser

More information

New Features TDLS 200. The Process TDLS Solution. Tunable Diode Laser Spectroscopy (TDLS) Analyzer.

New Features TDLS 200. The Process TDLS Solution. Tunable Diode Laser Spectroscopy (TDLS) Analyzer. The Process TDLS Solution New Features TDLS 200 Tunable Diode Laser Spectroscopy (TDLS) Analyzer Bulletin 11Y01B01-01E-A www.yokogawa.com/an/index.htm The first Tunable Diode Laser analyzer Innovative

More information

MOVING FILTER AIR MONITOR ALPHA, BETA/GAMMA

MOVING FILTER AIR MONITOR ALPHA, BETA/GAMMA - FEATURES: MOVING AIR FILTER AIRBORNE ALPHA LESS RADON AND BETA/GAMMA PARTICULATES RUGGED, 100% DUTY CYCLE SETTABLE ALARM HIGH THROUGH-PUT UNATTENDED OPERATION Up to 6 WEEKS PRINTED RECORD (Optional)

More information

OMA-300 Process Analyzer

OMA-300 Process Analyzer A window into your process since 1994. The OMA Process Analyzer continuously measures chemical concentrations and physical properties that can be correlated from the 200-1100 nm (UV-Vis / SW-NIR) absorbance

More information

Dissolved Oxygen Measurement liquisys S COM 223 / 253

Dissolved Oxygen Measurement liquisys S COM 223 / 253 Technical Information TI 199C/07/en No. 51500281 Dissolved Oxygen Measurement liquisys S COM 223 / 253 Oxygen Transmitter Benefits at a glance Measuring transmitter in field or panel-mounted housing Universal

More information

Sitron s CF Line of Flow Switch Monitors

Sitron s CF Line of Flow Switch Monitors Sitron s CF Line of Flow Switch Monitors Models: CF 12AC CF 12DC CF 420 F 420 RCF 420 Introduction Sitron s versatile and intelligent line of Thermal Dispersion Flow Switch Monitors are compact switches,

More information

Miniature Infrared Temperature Sensors with Optional Touch Screen Display. PSC-SSS-PM with touch screen display (-CRT version)

Miniature Infrared Temperature Sensors with Optional Touch Screen Display. PSC-SSS-PM with touch screen display (-CRT version) PSC-SSS-PM Series Miniature Infrared Temperature Sensors with Optional Touch Screen Display PSC-SSS-PM with touch screen display (- version) FEATURES Miniature sensing head and configurable electronics

More information

HIGH CAPACITY PRODUCT LINE

HIGH CAPACITY PRODUCT LINE HIGH CAPACITY PRODUCT LINE Highest Quality, Best Service Manufacturing chlorination equipment and related products since 1978 PROUDLY MADE IN USA 600 Emlen Way, Telford, PA 18969 Telephone: (215) 799-0980

More information

Industrial Grade Gas Detection Detecting The Difference

Industrial Grade Gas Detection Detecting The Difference detcon inc. Industrial Grade Gas Detection Detecting The Difference PO Box 8067 The Woodlands, TX 77387 888-367-4286 (toll free) 713-559-9200 281-292-2860 (fax) sales@detcon.com Catalog #CB-0409 www.detcon.com

More information

Zircomat Oxygen Analyzers

Zircomat Oxygen Analyzers Zircomat Oxygen Analyzers Finally Hassle Free Stack Gas Oxygen Measurement Many of the top fortune 500 companies have already discovered that installing a ZIRCOMAT Oxygen analyzer is the smart way to measure

More information

02/11/2015

02/11/2015 CTH 46 - CTD 43 / 46 CTD 46 Part number 89422108 CTH 46 Heating / cooling function Measurement and setpoint display CTD 43 Heating or cooling function Measurement display Measurement deviation display-setpoint

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

YOUR PARTNER IN FIRE & GAS DETECTION

YOUR PARTNER IN FIRE & GAS DETECTION YOUR PARTNER IN FIRE & GAS DETECTION OGGIONI s.a.s. Via Lavoratori Autobianchi, 1 - P.T.B. Edif.13/O - 20832 Desio (MB) Italy Tel.+39 0362 629135 Fax. +39 0362 622531 www.oggionisas.com - info@oggionisas.com

More information

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER MODEL AL3 7 5 - AL3000 series conforming to CE, UL and CSA are 100mm multi-point type hybrid recorders with a simultaneous display of multi-channel

More information

SEC 2000 Millenium Infrared Gas Detector

SEC 2000 Millenium Infrared Gas Detector SEC 2000 Millenium Infrared Gas Detector Instruction and Operation Manual Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 USA (952) 938-9486 Fax (952) 938-9617 Email: sales@sensorelectronic.com

More information

SECTION ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM

SECTION ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM SECTION 40 71 66 ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM PART 1-GENERAL 1.01 SUMMARY A. Ultrasonic clamp-on flow measurement system designed for non-intrusive external to pipe measurement

More information

4/8/12/16 Channel Temperature Scanner with FREE Data Logging PC Software RS485

4/8/12/16 Channel Temperature Scanner with FREE Data Logging PC Software RS485 Select Option Device Wise Device/Group HumiLog Y-Axis Text Show/Hide Ledgends MIN MAX Scale Y Max 08-05-2015 15:17:59 PV_C PV_RH Color default default Graph Refresh Interval 2 Set Interval PV Low Alarm

More information

PRODUCT LINE. Highest Quality, Best Service

PRODUCT LINE. Highest Quality, Best Service PRODUCT LINE Highest Quality, Best Service Manufacturing chlorination equipment and related products since 1978 PROUDLY MADE IN USA 600 Emlen Way, Telford, PA 18969 Telephone: (215) 799-0980 Fax: (215)

More information

Recent Improvements in Process GC Instrumentation

Recent Improvements in Process GC Instrumentation ISA Houston, TX Oct., 15 2003 Recent Improvements in Process GC Instrumentation Dr. Jack Driscoll PID Analyzers, LLC copyright 2000-2006 PID Presentation Objectives A new Process GC has been developed

More information

ChemScan mini Analyzer for Low Ammonia Monitoring Installation, Operation and Maintenance Manual

ChemScan mini Analyzer for Low Ammonia Monitoring Installation, Operation and Maintenance Manual ChemScan mini Analyzer for Low Ammonia Monitoring Installation, Operation and Maintenance Manual asaanalytics.com ChemScan mini Low Ammonia Analyzer O&M Manual - Rev 223K TABLE OF CONTENTS ANALYZER DESCRIPTION

More information

Analog Input Module IC670ALG630

Analog Input Module IC670ALG630 1 IC670ALG630 The Thermocouple (IC670ALG630) accepts 8 independent thermocouple or millivolt inputs. Module features include: Self calibration Two data acquisition rates based on 50 Hz and 60 Hz line frequencies

More information