Liquid Level Controller

Size: px
Start display at page:

Download "Liquid Level Controller"

Transcription

1 Liquid Level ontroller Product Bulletin Type: HBLT-1/HBLT-1-E Purpose: The HBLT-1 provides remote liquid level management f industrial refrigeration systems. It can be used with the HBLT-A1 HBLT-Wire analog level probe other similar -wire sens with a 4-20 ma output signal. separats, inter coolers, economizers and receivers installed with an analog sens provide a current signal proptional to the vertical liquid level. The HBLT-1 controller serves as a stand alone programmable device, which converts the return signal and perfms a 4-20 ma output and three programmable relay functions. HBLT-1: ontroller only HBLT-1-E: HBLT-1 controller with encloser and transfmer ontact Infmation: Parker Hannifin pation Refrigerating Specialties Division 2445 South 25th Avenue Broadview, IL phone (708) fax (708) Product Features: ompatible with HB probes and legacy R/S depth tracker probes Two level alarms (high and low) status indicat Three digit display probe level output Visual valve position feedback with five LEDs Available with without enclosure Enclosure is resistant to atmospheric elements and UV rays Exclusive distributs f the Americas

2 Table of ontents 1.0 Technical Data HBLT-1 ontroller. 2 HBLT-1 ontroller with Enclosure Function and Design Installation Instructions Electrical Instructions ontroller Parameter Setup ON Mode ontroller Level s and Level Setup alibration Manual Override Trouble Shooting Menu Flow hart Technical Data HBLT-1 ontroller Mounting Panel Input Power V A/D±10% Frequency /60 Hz urrent Draw Max 40 ma Inputs Sens Analog Input ma Feedback Analog Input ma Relay Function (max level) Relay Voltage V D Outputs Analog Output ma Load A/24V D Relay A/D x A x 5 A x 5 A Solid State Output ,, 1 A/24V A/D Ambient Temperature to 70 (-4 F to 158 F) Relative Humidity Range % to 80% Approvals /ertificates EM Emission EN EM Emission EN GOST-R No Protection Rating IP65 Measurement (BxHxD) External x 96 x 94 mm (.78" x.78" x.70") ut-out x 92.8 mm (.65" x.65") Weight kg (0.44 lbs) HBLT-1 ontroller with Enclosure Mounting Wall Input Power V A (Mean Well RS-5-24 transfmer) urrent Draw Max 50 ma Protection Rating IP65 Measurement (BxHxD) External x 220 x 140 mm (8.07" x 8.66" x 5.51") Weight kg (.09 lbs) 1 HBLT-1-E 2 HBLT-A1 SRV w/ Manifold 1 2 Liquid Level ontroller Liquid Level Transmitter Electronic Valve LLSS Receiver MVS S4A w/ RSF separat installed with an HBLT-A1 analog sens f continuous level control of the vessel. The sens is connected to the HBLT-1 controller, controls the MVS modulating valve so that a constant level is maintained. Application Example: Low Pressure (LP) Liquid Level ontrol 2

3 2.0 Function and Design The HB liquid level controller (HBLT-1) is designed to continuously monit refrigerant levels in: vessels Separats Inter coolers Economizers Receivers Supplied with a microprocess-based design the controller is always delivered with the newest software. The software version can be viewed in the display by pushing on the [UP] [DOWN] at same time. ontroller Running Green LED Indicat Three-Digit Level Display The controller can be configured f a wide variety of level control applications in a industrial refrigeration system. A three-digit LED display provides level moniting and parameter setup. The setting of parameters is managed by using the simple menu push buttons, which consists of: Push Buttons Five LED Electronic Valve Position Indicat ON Provides access to the control parameters: set point, P-band, LP/ HP mode, ramp function and valve damping. ALARM AL Provides access to alarm level: low level, high level, as well as pump level and hysteresis. Provides access to minimum and maximum calibration. Low Level (red), High Level (red) and (green) LED Indicats ontroller Diagram: omponent Identification TEST MODE Starts the test mode, where all parameters are tested. Used to switch between the alarm parameters. onfirms/saves data and also functions as return/fward/enter to the next function. hanges the parameters in a positive direction with +1 increments f each click, through its scroll function by holding the button down. hanges the parameters in a positive direction with 11 increments f each click, through its scroll function by holding the button down. hange from operation mode to display of valve position in -digit display. Provides manual override f valve position. See manual override instructions later in this bulletin..0 Installation Instructions When installing the HBLT-1 HBLT-1-E avoid direct sunlight, heavy dust, heat. Do not expose the instrument to rain, high humidity, ammonia vap other crosive refrigerants. If installing the HBLT-1 controller, it must be installed on the front panel at eye level. The front is designed with a protection class of IP54 and the rear facing electronics are designed to a protection class of IP45. The HBLT-1 controller can be installed directly into a panel with a cut-out of 92.8 x 92.8 mm (.65" x.65"). Two mounting brackets, one located on each side of the controller, are used to secure the controller to the panel. 98.2mm [.65"] The HBLT-1 controller is equipped with three relay outputs, a 4-20 ma analog output and a 4-20 ma valve position feedback. The three relays monit and control the low level alarm, high level alarm and pump status. F liquid level control a 4-20 ma analog output is used to control the MVS electronic valve. Five yellow LED valve position indicats, located on the front of the controller, provides plug position feed back to the controller. If there are no yellow LEDs lit the valve is in the full closed position, three yellow LEDs the valve is 50% open and if all five yellow LEDs are lit the valve is in the full open position. 94mm [.70"] 96mm [.78"] 98.2mm [.65"] Additional LEDs, on the front of the controller, indicates the status operation the controller is in. A lit red LED indicates the low high level alarm has been tripped, a lit green LED indicates the pump is on, a lit yellow LED, on the push buttons, identifies which operation the controller is currently in and a lit green LED indicates the controller is in auto mode (RUN). 96mm [.78"] Dimensional Diagram: HBLT-1 ontroller Mounting Bracket

4 The controller is also available with a self containing enclosure f an independent setup. The mounting holes are 165 mm (6.50") vertical and 105 mm (4.1") hizontal. The enclosures must be opened to properly mount the enclosure. To open the main housing of the controller swing open the clear blue transparent protection cover, located on the front of the enclosure, and unscrew the four large plastic screws until they are loose. The front half of the encloser will swing open and provide access to the mounting holes and electrical connections. 15mm [5.1"] 4.0 Electrical Instructions All terminals are protected against wrong termination up to a supply voltage of 40 V. If the supply voltage is greater than 40 V, the controller will be damaged. F wiring instruction please reference the three wiring diagrams: HBLT-1 controller, HBLT-1-E controller with enclosure and remote moniting. Remote moniting must be wired in series and is wired in the same man f both the HBLT-1 and HBLT- 1-E. Use 20 AWG jacketed stranded wire. If purchased the controller with enclosure, HBLT-1-E, a V A transfmer is included. Electrical onnections Terminal Description Power In - 24 V A/D Supply voltage to the controller 210mm [8.25"] 165mm [6.50"] Sens Input In Input from the sens, e.g. HBLT-A1 Alar in (5..24 V D) can be used f extra high level alarm (GND from power in) P GND/INT P (no function) 226mm [8.88"] 105mm [4.1"] Dimensional Diagram: HBLT-1-E ontroller with Enclosure i Avoid direct sunlight, heavy dust, heat. Do not expose the instrument to rain strong humidity from ammonia vap other crosive refrigerants. ma Feedback Low Level - Out High Level - Out ontrol Out Solid State Relay Power In V A ma feedback (positioning of valve. GND is connected to control out) Low level alarm in the vessel High level alarm in the vessel Signal to start the pump 4-20 ma analog signal to the electronic valve pump N/A Supply voltage with power supply built in HBLT-A1 Liquid Level Transmitter Probe HBLT-1 ontroller ma Solid State Relay IN Solid State Relay OUT 4-20 ma OUT V OUT GND OUT 24V A/D (50/60 Hz) ma Feedback P GND P INT IN 4-20 ma V GND Power IN - Power IN + Out High Level Out Low Level Out GO G Y M U Z ON DIP MVS Relays Outputs The HBLT-1 controller provides three relay outputs f pump, high level alarm and low level alarm. The relays are available in the nmally open () nmally closed () position. Wiring Diagram: HBLT-1 ontroller 4

5 HBLT-A1 Liquid Level Transmitter Probe ma HBLT-1-E ontroller ma Feedback P GND P INT IN 4-20 ma V GND Power IN - Power IN + Solid State Relay IN Solid State Relay OUT 4-20 ma OUT V OUT GND OUT Out High Level Out Low Level Out GO G Y M U Z ON DIP MVS V A (50/60 Hz) L N GND -V +V (A) Transfmer (RS-5-24) Relays Outputs The HBLT-1 controller provides three relay outputs f pump, high level alarm and low level alarm. The relays are available in the nmally open () nmally closed () position. Wiring Diagram: HBLT-1-E ontroller with Enclosure PL 4-20 ma (POS) 4-20 ma (NEG) i When using remote moniting it must be current moniting only (i.e ma). The same wiring method can be used on the the HBLT-1-E. HBLT-A1 Liquid Level Transmitter Probe HBLT-1 ontroller ma Solid State Relay IN Solid State Relay OUT 4-20 ma OUT V OUT GND OUT 24V A/D (50/60 Hz) ma Feedback P GND P INT IN 4-20 ma V GND Power IN - Power IN + Out High Level Out Low Level Out GO G Y M U Z ON DIP MVS Wiring Diagram: HBLT-1/HBLT-1-E ontroller with Remote Moniting 5

6 Bulletin ontroller Parameter Setup Setting the ontrol Parameters Instructions Steps Operation 1 urrent Setpoint 2 Display Setup Instructions Notes Liquid level at 40% 10.4 ma return signal to the HBLT-1 controller. urrent refrigerant level from probe. Facty set at 040. Press the ON button to set up the HBLT-1 Provides access to the control parameters: setpoint, P-band, ramp function, as well as valve position. setpoint parameters To adjust the refrigerant level use the Setpoint Level range is from 0% to 100%. P-band (band percentage above and below the setpoint value). Equation: Setpoint * P-band Percentage 050 x 0% = 15% Range ± 7.5% To adjust the P-band use the 4 P-band In this example, with the setpoint of 50%, the P-band range is 42.5% to 57.5%. Percentage Range is from 0% to 100%. Facty set at P0. i The sum of the setpoint and the P-band may not exceed 100% To adjust the Ramp use the 5 Ramp When complete push the buttons. Since there can be fluctuations in the process parameters during process start-up, it is possible to establish a ramp function (at start up only). Percentage/second range is from 0% to 100%. Facty set at 005. When set at "000", the function is inactive. Analog Output Mode 6 Valve Damping 7 To change from LP/HP use the Analog output to the electronic valve. To adjust the damping use the LP: 4-20 ma (MVS electronic valve) Depending which valve is installed, it may be necessary to dampen the speed at which the valve opens. This is used especially when the valve react too quickly/ strongly. HP: 20-4 ma Percentage/Second Range is from 0% to 100%. Facty set at 005. When set at "000", the function is inactive. 8 9 New Setpoint Push the Does not apply. Facty set at 006. New refrigerant level setpoint. 120% Valve Opening 0% 100% Valve Safety lose 0% Valve Opening 100% LP Mode HP Mode Valve Opening 100% Valve at 0% closed 80% 50% Setpoint (% Liquid Level) 6 P-band % Liquid Level % ON Mode Both the Setpoint and P-band are set as a percentage (0-100%). If the sum is set so it causes the valve to close at 120% (Setpoint = 80% and P-band at 100%), the valve will close at 100% f safety reasons.

7 Bulletin ontroller Level s and Level Setup Setting the High, Low and Parameters Instructions Steps Operation 1 urrent Setpoint 2 Display Setup Instructions Notes urrent refrigerant level from probe. Liquid level at 50% 12 ma return signal to the HBLT-1 controller. Press the Provides access to the alarm levels: low level, high level, as well as pump level and hysteresis ALARM button to start setting the low level alarm, high level alarm and pump level 4 Low Level Low Level Hysteresis To adjust the low level alarm use the Level range is from 0% to 100%. To adjust the low level alarm hysteresis use the Facty set at 010. The low level alarm, based in this example, will turn on when the liquid level reaches 10%; shown in step. The low level alarm red LED, on the controller, will stay on at levels below 10% and will not turn off until it reaches a level of 15%. If the hysteresis level is increased decreased the range above 10%, from this example, will increase decrease. If the low level alarm hysteresis is changed to L10 (10%), in this example, the alarm would stay on below 10% to 20% level. i The sum of the low level alarm setpoint and the low level alarm hysteresis may not exceed 100%. 5 6 High Level High Level Hysteresis To adjust the high level alarm use the To adjust the high level alarm hysteresis use the Level Range is from 0% to 100%. Facty set at 085. The high level alarm, based in this example, will turn on when the liquid level reaches 85%; shown in step 5. The high level alarm red LED, on the controller, will stay on at levels above 85% and will not turn off until it reaches a level 80% below. If the hysteresis level is increased decreased the range below 85%, from this example, will increase decrease. If the high level alarm hysteresis is changed to H10 (10%) the alarm would stay on above 85% to 75% level. i The sum of the high level alarm setpoint and the high level alarm hysteresis may not exceed 100%. To adjust the pump use the 7 When complete push the Hysteresis Note: F a graphical interpretation see the following page. 7 In this example the pump is set to turn off when the level reaches 0%. Level Range is from 0% to 100%. To adjust the pump hysteresis use the 8 buttons. Facty set at 015. The pump, based in this example, will turn off when the liquid level reaches 25%; shown in step 7. The pump green LED, on the controller, will turn off indicating the pump is off. The pump will not turn back on until it reaches a level of 0% and will remain on at levels above 0%. If the hysteresis level is increased decreased the range below 0%, from this example, will increase decrease. If the pump hysteresis is changed to P10 (10%) the pump will turn off at 20% level. Again the pump will not turn back on until it reaches a level of 0%.

8 High level equipment cutout 85% High level setpoint High level equipment restart 80% High level hysteresis High, Low and Parameters Percentage Description 85 High level setpoint 5 High level hysteresis Level setpoint 50% Level setpoint 50 Level setpoint 0 level setpoint 5 level hysteresis restart cutout 0% 25% level setpoint level hysteresis 15 Low level setpoint 5 Low level hysteresis Low level equipment restart Low level equipment cutout 15% 10% Low level hysteresis Low level setpoint Note: The above valves are base from the controller parameter setup and controller level s and pump level setup examples. Level Parameter Diagram: Graphical interpretation of the alarm and pump parameters 7.0 alibration The calibration mode provides access to two point calibration. a two point calibration can be carried out on two randomly selected points from 0-100%. Based on these two values, the controller itself calculates the sens's full scale and 0-point. The idea is to be able to reposition the probe length if the entire length of the probe is not required. Minimum and Maximum alibration Instructions Steps Operation Setup Instructions Notes Provides access to calibrate the required probe length. 1 alubration Mode Press the AL button f 5 seconds. The 'RUN' LED is shut off and the red LED on the AL button turns on when in calibration mode. 2 Minimum alibration To adjust the minimum level use the buttons. When complete push the Probe range is from 0% to 100%. 0% - Minimum Level Maximum alibration To adjust the Maximum level use the buttons. When complete push the button twice. Probe range is from 0% to 100%. 100% - Maximum Level 8.0 Manual Override Manual Override Instructions Steps Operation Setup Instructions Notes 1 Manual Override Press the MODE button f 10 seconds. Provides manual override to the electronic valve plug position. 2 Adjustment To open close the electronic valve plug use the buttons. Valve range is from 0% to 100%. 0% - Full losed 100% - Full Opened Return to Auto Mode When complete push the Returns the HBLT-1 controller to auto mode. 8

9 9.0 Trouble Shooting Symptom Probable ause How to Detect/Repair Defect No light in the display and no LED lamps No power to the unit the wrong voltage Measure the power on 24 V input terminals. activated There is no change in display The valve the pump do not react to the signal from the controller The display shows too low/high level in relation to the actual level in the vessel High/low alarm occurs frequently The display flickers is unstable 1) Defective cable from sens 2) Defective sens ) Valve Shut 4) Wrong min./max. calibration Defective cable lack of a connection to the pump of the valve 1) The cable is defective there is no connection to the sens 2) alibration is not crect ) alibration is not carried out at the operating temperature 4) Sens not calibrated to the crect refrigerant 1) Turbulence in the liquid 2) set too close to the desired setpoint 1) Loose connection in the power supply the sens 2) EM interference from mobile telephones, frequency converters, other equipment that does not meet the legal requirements f EM 1-2) heck the sens. See err detection in the sens's instruction manual ) Look at the valve's position on the five LED on the front of the controller heck the connection to the sens the valve 1) Measure the signal from the sens 2) alibrate the controller ) alibrate at operational temperature 4) alibrate the sens. Look at the sens's instruction manual 1) heck the system's operational state 2) Set the high alarm at a greater difference in value to the desired setpoint. 1) heck f loose connections 2) Install insulated wire from sens to the controller 9

10 Bulletin Menu Flow hart urrent Setpoint/ Facty Setting ontroller Parameter Setup ontroller Level s and Leve Setup alibration ON ALARM AL Setpoint Low Level Min. alibration Hold f 5 sec. Low Level Hysteresis P-band Max. alibration Ramp Auto Mode High Level Hysteresis Valve Damping Hysteresis New Setpoint Note: Returned to Auto Mode. [RUN] LED on High Level Analog Output Mode Auto Mode Note: [RUN] LED on 10 Note: [RUN] LED on

11 urrent Setpoint/ Facty Setting Manual Override Test MODE Hold f 10 sec. TEST Valve Position Open lose Auto Mode Note: [RUN] LED on Auto Mode Note: [RUN] LED on 11

12 Safe Operation (See Bulletin RSBV) People doing any wk on a refrigeration system must be qualified and completely familiar with the system and the Refrigerating Specialties Division valves involved, all other precautions will be meaningless. This includes reading and understanding pertinent Refrigerating Specialties Division Product Bulletins and Safety Bulletin RSB pri to installation servicing wk. Where cold refrigerant liquid lines are used, it is necessary that certain precautions be taken to avoid damage which could result from liquid expansion. Temperature increase in a piping section full of solid liquid will cause high pressure due to the expanding liquid which can possibly rupture a gasket, pipe valve. All hand valves isolating such sections should be marked, warning against accidental closing, and must not be closed until the liquid is removed. heck valves must never be installed upstream of solenoid valves, regulats with electric shut-off, n should hand valves upstream of solenoid valves downstream of check valves be closed until the liquid has been removed. 201 Parker Hannifin pation It is advisable to properly install relief devices in any section where liquid expansion could take place. Avoid all piping control arrangements which might produce thermal pressure shock. F the protection of people and products, all refrigerant must be removed from the section to be wked on befe a valve, strainer, other device is opened removed. Flanges with ODS connections are not suitable f ammonia service. Warranty All Refrigerating Specialties products are under warranty against defects in wkmanship and materials f a period of one year from date of shipment from facty. This warranty is in fce only when products are properly installed, field assembled, maintained, and operated in use and service as specifically stated in Refrigerating Specialties atalogs Bulletins f nmal refrigeration applications, unless otherwise approved in writing by the Refrigerating Specialties Division. Defective products, parts thereof returned to the facty with transptation charges prepaid and found to be defective by facty inspection, will be replaced repaired at Refrigerating Specialties option, free of charge, F.O.B. facty. Warranty does not cover products which have been altered, repaired in the field, damaged in transit, have suffered accidents, misuse, abuse. Products disabled by dirt other feign substances will not be considered defective. The express warranty set fth above constitutes the only warranty applicable to Refrigerating Specialties products, and is in lieu of all other warranties, expressed implied, written including any warranty of merchantability, fitness f a particular purpose. In no event is Refrigerating Specialties responsible f any consequential damages of any nature whatsoever. No employee, agent, dealer other person is authized to give any warranties on behalf of Refrigerating Specialties, n to assume, f Refrigerating Specialties, any other liability in connection with any of its products. 117 EN: /25/201 ISO 9001 ERTIFIED

Bulletin K. Type RSF. Size: 1/2" - 4" (13-100mm) Suitable For: Ammonia, R-22, R-134a, R-502 and Other Common Refrigerants

Bulletin K. Type RSF. Size: 1/2 - 4 (13-100mm) Suitable For: Ammonia, R-22, R-134a, R-502 and Other Common Refrigerants Refrigerant Strainer Type RSF Bulletin 00-10 K Size: 1/" - 4" (13-100mm) Suitable F: Ammonia, R-, R-134a, R-50 and Other Common Refrigerants Features Stainless Steel (60 Mesh) Screen Drain Connection f

More information

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12 PAGE 1 OF 12 TABLE OF CONTENTS PAGE 1. SAFETY PRECAUTIONS 1.1. Electrical shock 3 2. APPLICATION 3 3. INSTALLATION 3.1. Mount indoor alarm display 3.2. Mount the outdoor junction box 3.3. Install interconnecting

More information

Programmable Output Dual Relay Quad Relay. (Trip Points, High Alarm, Low Alarm, Failsafe, Non-Failsafe, Normally Open, Normally Closed)

Programmable Output Dual Relay Quad Relay. (Trip Points, High Alarm, Low Alarm, Failsafe, Non-Failsafe, Normally Open, Normally Closed) June 2004 Description The universal SPA 2 Programmable Limit Alarm Trips provide on/off control, warn of unwanted process conditions, alarm on rate-of-change and provide emergency shutdown. Very versatile,

More information

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT SECTION 23 09 33 SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT HARSCO INDUSTRIAL, PATTERSON-KELLEY NURO CONTROL CONVERSION KIT Part 1 - GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 / CSA 4.9

More information

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING Manual Contents Introduction...3 Valve compatibility...3 Features...3 Application examples...3 Ordering...3 Operating the EKC 347...4-5

More information

REFRIGERANT FLOAT SWITCH Type LL, LLC, LLS, LLSC, LLA, LLAC

REFRIGERANT FLOAT SWITCH Type LL, LLC, LLS, LLSC, LLA, LLAC REFRIGERANT FLOAT SWITCH Type LL, LLC, LLS, LLSC, LLA, LLAC Bulletin 61-10 J Suitable For: Ammonia, R-22, R-507, R134A and Other Common Refrigerants Features Hermetically Sealed, Fused Switch Assembly

More information

MICROtrac MICROPROCESSOR BASED WATER TREATMENT CONTROLLER. Installation and Operation Manual REV. L

MICROtrac MICROPROCESSOR BASED WATER TREATMENT CONTROLLER. Installation and Operation Manual REV. L MICROtrac MICROPROCESSOR BASED WATER TREATMENT CONTROLLER Installation and Operation Manual MICROtrac Warranty Pulsafeeder, Inc. warrants MICROtrac control systems (including the conductivity sensor) of

More information

225Ci/225i POWERSHRED. Quality Office Products Since Please read these instructions before use. Do not discard: keep for future reference.

225Ci/225i POWERSHRED. Quality Office Products Since Please read these instructions before use. Do not discard: keep for future reference. POWERSHRED 5Ci/5i Please read these instructions befe use. Do not discard: keep f future reference. Quality Office Products Since 97 ENGLISH Models 5Ci/5i A. B. I. C. D. E. F. H. J. L. K. KEY A. SafeSense

More information

Genus III Pool and Spa Controller

Genus III Pool and Spa Controller Genus III Pool and Spa Controller INSTALLATION & OPERATING INSTRUCTIONS AstralPool Australia Pty. Limited. A.B.N. 97 007 284 504 Infmation and specifications subject to change without notice. Melbourne:

More information

FW-RA-LED Remote Multiplex Annunciator Panels

FW-RA-LED Remote Multiplex Annunciator Panels FW-RA-LED Remote Multiplex Annunciator Panels WIRING and INSTALLATION INSTRUCTION LNOTICE All information, documentation, and specifications contained in this manual are subject to change without prior

More information

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Instruction Manual Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Manual PCT-3000 Revision 9/2014 The PCT-3000 series control console incorporates

More information

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications Instruction Manual Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications Manual PCT30006, Revision 9/20/2016 The PCT30006 control enclosure incorporates

More information

Configuration Manual. HBLT-Wire LEVEL SENSOR For analogue level measurements of NH3 & HFC in refrigeration systems

Configuration Manual. HBLT-Wire LEVEL SENSOR For analogue level measurements of NH3 & HFC in refrigeration systems Configuration Manual HBLT-Wire LEVEL SENSOR For analogue level measurements of NH3 & HFC in refrigeration systems Table of contents Safety Instructions... 2 Installation of HB Configuration Tool... 3 Configuration

More information

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual GG-VL-R REFRIGERANT VENT LINE SENSOR Installation and Operation Manual 2 GG-VL-R Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER

ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT

More information

Mark 25 Ultrapure Water Conductivity Analyzer

Mark 25 Ultrapure Water Conductivity Analyzer Martek Instruments, Inc. Mark 25 Ultrapure Water Conductivity Analyzer Instruction Manual WARRANTY POLICY Unless otherwise stated, MARTEK INSTRUMENTS, INC. warrants this equipment to be free from defects

More information

Static Pressure Control

Static Pressure Control The (model SPC-2) is a fully programmable controller that provides extensive flexibility for your curtain or awning control needs. The SPC-2 automatically controls the pressure in a room by operating a

More information

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector CAUTION & SYMBOL DEFINITIONS: CAUTION: Gives detailed description of different situations to avoid or not avoid for the proper operation of the

More information

Programmable Output Dual Relay Quad Relay. (Trip Points, High Alarm, Low Alarm, Failsafe, Non-Failsafe, Normally Open, Normally Closed)

Programmable Output Dual Relay Quad Relay. (Trip Points, High Alarm, Low Alarm, Failsafe, Non-Failsafe, Normally Open, Normally Closed) March 2008 Description The universal SPA 2 Programmable Limit Alarm Trips provide on/off control, warn of unwanted process conditions, alarm on rate-of-change and provide emergency shutdown. Very versatile,

More information

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

GG-EM ENTRANCE MONITOR. Installation and Operation Manual GG-EM ENTRANCE MONITOR Installation and Operation Manual 2 GG-EM Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL GASGUARD VENT LINE3 Ammonia Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual Warning Use this product only in the manner described in this manual. If the equipment is used in a

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

KNHE48 SERIES WATER-TO-AIR HEAT EXCHANGER

KNHE48 SERIES WATER-TO-AIR HEAT EXCHANGER Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents KNHE48 SERIES WATER-TO-AIR HEAT EXCHANGER

More information

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS... SECTION Table of Contents SECTION 1 INTRODUCTION...................... 1.1 Description............................... 1.2 Features................................. 1.3 Models..................................

More information

TG-10 Wall Mount Installation and Operation Manual. High Output Ozone Generator

TG-10 Wall Mount Installation and Operation Manual. High Output Ozone Generator TG-10 Wall Mount Installation and Operation Manual High Output Ozone Generator Ozone Solutions 451 Black Forest Road Hull, IA 51239 Phone: (712) 439-6889 Fax: (712) 439-6733 2 Table of Contents Safety

More information

DOL 31 Speed Controller Technical User Guide

DOL 31 Speed Controller Technical User Guide Technical User Guide For other language variants of this document we refer to your local dealer or http://docs.skov.com/1158. Available from April 2016. 612061 2016.09.20 Technical User Guide Program

More information

1 For All Programmable or Non-Programmable. Digital Thermostat. Meets Residential California Title 24

1 For All Programmable or Non-Programmable. Digital Thermostat. Meets Residential California Title 24 OWNER'S MANUAL P/N P374-1000FM 1 For All Programmable or Non-Programmable Switchable Digital Thermostat 72 74 Am AUTO 70 Mounts Flush to the Wall 1 Day Programmable or Non-Programmable 4 Time Periods per

More information

ACL TC 200 TEMPERATURE CONTROLLER

ACL TC 200 TEMPERATURE CONTROLLER TC 200 TEMPERATURE CONTROLLER TC 200 TEMPERATURE CONTROLLER WARNING This manual must be read in its entirety before installation of this controller. Installation must be performed by a qualified technician

More information

Remote Relay Module (RRM)

Remote Relay Module (RRM) Remote Relay Module (RRM) Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like

More information

SPA HEATER INSTALLATION, OPERATION AND MAINTENANCE

SPA HEATER INSTALLATION, OPERATION AND MAINTENANCE SPA INSTALLATION, OPERATION AND MAINTENANCE MODELS: ST SERIES 5.5 & 11kW 240V SINGLE PHASE BEFORE YOU BEGIN CHECK ALL ELECTRICAL CONNECTIONS TO ALL COMPONENTS WITHIN THE FOR TIGHTNESS. CONNECTIONS CAN

More information

LC1350 Level Controller

LC1350 Level Controller LC1350 Controller Description The Spirax Sarco LC1350 has two alarm channels that can be independently configured high or low to control the water level of a boiler, tank or vessel by operating a pump,

More information

S304 and S305 Dust Emission Monitors. User Manual. Distributor

S304 and S305 Dust Emission Monitors. User Manual. Distributor S304 and S305 Dust Emission Monitors User Manual Distributor Version 6.4 30/5/2012 Table of Contents 1. INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 4 1.3 Principle of operation... 4 2. INSTALLATION...

More information

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL GASGUARD LEL 3 Ammonia Sensor OPERATING & INSTALLATION MANUAL GasGuard LEL 3 Operating and Installation Manual 2 Table of Contents 3GasGuard LEL Operating and Instruction Manual General description. 4

More information

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor Model TFH24FXYZ2 Stand-alone with Internal Humidity Sensor Description The TFH24FXYZ2 is a fully configurable controller designed specifically for 2 pipe and 4 pipe fan coil applications. No additional

More information

HR-Robus. Included INSTALLATION INSTRUCTIONS. Industrial Door Microwave Motion Sensor

HR-Robus. Included INSTALLATION INSTRUCTIONS. Industrial Door Microwave Motion Sensor Section 1 General Description The is a microwave motion sensor for activating automatic industrial doors. Features include a speed selectable switch that makes the unit capable of detecting pedestrians

More information

RS Pro Infrared Temperature Sensor

RS Pro Infrared Temperature Sensor Instruction Manual RS Pro Infrared Temperature Sensor Stock Number: 161-8103 Introduction The RS Pro Infrared Temperature Sensor is a device for measuring the temperature of the surface of a solid or liquid

More information

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB Summary 1 CONNECTIONS... 3 1.1 TEMPERATURE PROBES...3 1.2 LOW VOLTAGE DIGITAL INPUTS...3 1.3 LIVE DIGITAL INPUTS...4 1.4 RELAY OUTPUTS...5 2 POWER SUPPLY... 6 3 SERIAL CONNECTIONS... 6 4 SOFTWARE... 7

More information

LiqTec, V GRUNDFOS INSTRUCTIONS

LiqTec, V GRUNDFOS INSTRUCTIONS GRUNDFOS INSTRUCTIONS LiqTec, 80-130 V Installation and operating instructions Notice d installation et d entretien Instrucciones de instalación y funcionamiento LIMITED WARRANTY Products manufactured

More information

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL GASGUARD NH 3 Ammonia Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual 2 Table of Contents GasGuard NH 3 Operating and Instruction Manual General description. 4 Installation.. 4

More information

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

More information

Series 5000 Hydrazine Analyzer Model 60002

Series 5000 Hydrazine Analyzer Model 60002 Series 5000 Hydrazine Analyzer Model 60002 T he patented* Series 5000 Hydrazine Analyzer is a continuous-reading instrument using the p-dimethylaminobenzaldehyde method of analysis for colorimetric measurement

More information

Instruction Manual and Warranty

Instruction Manual and Warranty Instruction Manual and Warranty Copyright 2015, Ozeri GENERAL SAFETY Thank you for purchasing the Ozeri 3x Tower Fan. This product has passed extensive quality assurance tests for residential use. Every

More information

MST-1. Varifan USER S MANUAL MST-1 ADJUST. 9 per day HI F2. DIFF on off TIMER. reduc.

MST-1. Varifan USER S MANUAL MST-1 ADJUST. 9 per day HI F2. DIFF on off TIMER. reduc. USER S MANUAL ALARM HI F2 COOL / HEAT ALARM LO DIFF on off PERIOD TIMER L IMIT reduc. 9 per day 88 ADJUST Varifan + Although the manufacturer has made every effort to ensure the accuracy of the information

More information

Protocol Station Remote Alarm

Protocol Station Remote Alarm ADI 5135-C Certified ISO 9001 Protocol Station Remote Alarm 529 5135-01-120 529 5135-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

flexibility programmed settings.

flexibility programmed settings. Phason Natural Ventilation Control The Natural Ventilation Control (NVC-2) is a fully programmable controller that provides extensive flexibility for your curtain or awning control needs. The NVC-2 automatically

More information

DR Series. Installation & Operations Manual. Model: DR-10 HIGH OUTPUT SHOCK TREATMENT OZONE GENERATOR

DR Series. Installation & Operations Manual. Model: DR-10 HIGH OUTPUT SHOCK TREATMENT OZONE GENERATOR DR Series HIGH OUTPUT SHOCK TREATMENT OZONE GENERATOR Model: DR-10 Installation & Operations Manual 451 Black Forest Road, Hull, Iowa, 51239 712.439.6880 info@ozonesolutions.com www.ozonesolutions.com

More information

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector IMPORTANT READ THIS FIRST....3 CAUTIONS... 3 AVOIDING NUISANCE ALARMS... 3 STANDARD FEATURES... 4 AVAILABLE OPTIONS... 4 PARTS DESCRIPTION... 5 FRONT PANEL

More information

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual GG-CO-EXP CARBON MONOXIDE SENSOR Installation and Operation Manual 2 GG-CO-EXP Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS FLOSENTRY 3 MFFS3 PVC & CPVC FLOW METER (877) 356-5463 (p) 330-331-7331 (f) 330-331-7172 www.flo-corp.com 2017 FLO-CORP REVA 1116 1 DESCRIPTION Compatible with most MEMFlo meters,

More information

VENSTAR T1070 FAN COIL THERMOSTAT PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

VENSTAR T1070 FAN COIL THERMOSTAT PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS VENSTAR FAN COIL THERMOSTAT FAN COIL THERMOSTAT T1070 NON- PROGRAMMABLE 2 OR 4 PIPE SYSTEMS Remote sensor ready 3 speed fan control Self-prompting adjustment Auto 2-pipe changeover when used with ACC-SENFC

More information

Buzzer Unit. TAN-5000 Series. Operating Manual

Buzzer Unit. TAN-5000 Series. Operating Manual PT1E-1040 Buzzer Unit TAN-5000 Series Operating Manual Request for the Customers Read and understand this operating manual before using the buzzer unit. Use the buzzer unit in accordance with the operating

More information

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel

More information

Operating Instructions. Temperature and Humidity EC Control. Model 35YV93

Operating Instructions. Temperature and Humidity EC Control. Model 35YV93 Operating Instructions EN Temperature and Humidity EC Control Model 35YV93 479702 PLEASE READ AND SAVE THESE INSTRUCTIONS. READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE

More information

MC 31 Speed Controller Technical User Guide Code no GB

MC 31 Speed Controller Technical User Guide Code no GB Technical User Guide Code no. 99-97-0968 GB Ausgabe: 0 /201 Technical User Guide Program Version The product described in this manual holds software. This manual corresponds to: Software version 1.3 It

More information

Blue Air. Commercial Refrigeration Inc. Installation & Operation Manual Ice Cream Freezers

Blue Air. Commercial Refrigeration Inc. Installation & Operation Manual Ice Cream Freezers Blue Air Commercial Refrigeration Inc. Installation & Operation Manual Ice Cream Freezers Please read this manual completely before installing or operating this unit! BACF11 BACF15 BACRF14 Blue Air reserves

More information

1 For All Programmable Digital Thermostat. Meets Residential California Title 24

1 For All Programmable Digital Thermostat. Meets Residential California Title 24 OWNER'S MANUAL P/N P374-1100FM 1 For All Programmable Digital Thermostat 72 74 Am I2:00 AUTO 70 unts Flush to the Wall 7 Day Programmable 4 Time Periods per Day Auto Changeover Large, Easy To Read Display

More information

RATIO:GUARD Model E-1S EC Monitor

RATIO:GUARD Model E-1S EC Monitor EC probe Probe tees Probe retention clips Temperature probe E-1S monitor box UNPACKING Please open and inspect your package upon receipt. Your package was packed with great care and all the necessary packing

More information

Instruction Manual PCS-400-XY. Pump Controller. Y=2: 4-20 ma Y=6: 0-10 VDC X=5: 1-5 VDC. 4 Pump Control Relays 1 Alarm Relay 1 Signal Fail

Instruction Manual PCS-400-XY. Pump Controller. Y=2: 4-20 ma Y=6: 0-10 VDC X=5: 1-5 VDC. 4 Pump Control Relays 1 Alarm Relay 1 Signal Fail Manufacturers of Process Controls and Instrumentation Instruction Manual Model: Function: Input: PCS-400-XY Pump Controller X=2: 4-20 ma X=5: 1-5 VDC X=6: 0-10 VDC X=7: Output: Power: 4 Pump Control Relays

More information

Installation and Operations Manual

Installation and Operations Manual Installation and Operations Manual H-IM-LLC February 2018 Part No. 25092501 Replaces H-IM-LLC (01/2014) Lead Lag Control System Table of Contents General Safety Information 2 Inspection 2 Warranty Statement

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL GASGUARD Cl 2 Chlorine Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual 2 Table of Contents GasGuard Cl 2 Operating and Instruction Manual General description. 4 Installation..

More information

Environmental Monitoring Card

Environmental Monitoring Card Environmental Monitoring ard AP9612TH Installation and Quick-Start Manual ontents Introduction............................. 1 Overview............................. 1 Product inventory......................

More information

7EF/7HF/7EC/7ES Temperature Controllers

7EF/7HF/7EC/7ES Temperature Controllers 7EF/7HF/7E/7ES Temperature ontrollers Dual 4 Digit LED Display Universal Input (6 T/, RTD, mv, V, ma) Autotuning NEMA 4X 100 to 240 Vac Switching Power Supply Algorithms for Heat or Heat/ool ontrol 2 Independent

More information

Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C

Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C 1. General The hand-held micro terminal is used for setting the motor parameters of the SILVER C. 2. Installation

More information

USER S OPERATING AND INSTRUCTION MANUAL

USER S OPERATING AND INSTRUCTION MANUAL Grand Rapids, Michigan, U.S.A. 49504-5298 USER S OPERATING AND INSTRUCTION MANUAL MODEL 1508-NLG SELF-ACTUATING TRAY LIDDER 1508S20000CV2 INDEX SAFETY INSTRUCTIONS... 1508S20002 SET UP... 1508S20003 OPERATING

More information

JENCO ELECTRONICS, LTD.

JENCO ELECTRONICS, LTD. OPERATION MANUAL THE JENCO MODEL 3677 1/8 DIN ph/orp CONTROLLER JENCO ELECTRONICS, LTD. MANUFACTURER OF PRECISON INSTRUMENTS GENERAL INTRODUCTION The model 3677 is a precise instrument for the measurement

More information

Product Manual SZ1144

Product Manual SZ1144 Product Manual SZ1144 Refrigeration Temperature Monitor Communicating Controls Description The SZ1144 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum

More information

M-Sens 2. Online-Moisture Meter for Solids. Operating Instructions. SWR engineering Messtechnik GmbH

M-Sens 2. Online-Moisture Meter for Solids. Operating Instructions. SWR engineering Messtechnik GmbH EN M-Sens 2 Operating Instructions Online-Moisture Meter for Solids SWR engineering Messtechnik GmbH CONTENTS Page 1. System Overview......................................................................

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL. Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH AND LOW LEVEL ALARM 2.2 PUMP DOWN CONTROLLER 2.3

More information

ES2-HB. Ordering Information. Dimensions. Specifications. Humidity Sensor Temperature/Humidity Sensor

ES2-HB. Ordering Information. Dimensions. Specifications. Humidity Sensor Temperature/Humidity Sensor Humidity Sensor Temperature/Humidity Sensor ES2-THB CSM ES2-THB_DS_E_3_2 Detect Humidity within an Accuracy of ±3% in a Compact Body. Set Provides Superior Humidity Control and Temperature/ Humidity Control.

More information

Carrier NON-PROGRAMMABLE DIGITAL THERMOSTAT. Dual Setpoint Thermoglow Backlight No Batteries Required Auto Changeover Locking Keypad

Carrier NON-PROGRAMMABLE DIGITAL THERMOSTAT. Dual Setpoint Thermoglow Backlight No Batteries Required Auto Changeover Locking Keypad Carrier Heating & Cooling TSTATCCNB00 NON-PROGRAMMABLE DIGITAL THERMOSTAT USER INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW THERMOSTAT NON-PROGRAMMABLE DIGITAL THERMOSTAT AUTO 74 Dual

More information

HIDE-A-BLAST HB615X / HB915X INSTALLATION & OPERATION MANUAL IMPORTANT: 6 LED and 9 LED WARNING LIGHT

HIDE-A-BLAST HB615X / HB915X INSTALLATION & OPERATION MANUAL IMPORTANT: 6 LED and 9 LED WARNING LIGHT INSTALLATION & OPERATION MANUAL Hide-A-BlasT LED Warning Light HIDE-A-BLAST HB615X / HB915X 6 LED and 9 LED WARNING LIGHT IMPORTANT: Read all instructions and warnings before installing and using. INSTALLER:

More information

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

More information

Single Station Remote Alarm

Single Station Remote Alarm ADI 5106C Certified ISO 9001 Single Station Remote Alarm 529 5106-01-120 529 5106-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation

More information

TEC1100 Series Thermostats

TEC1100 Series Thermostats Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0601 TEC1100 Series Thermostats TEC1100 is a series of non-programmable thermostats with a

More information

Chore-Tronics Load Cell Indicator

Chore-Tronics Load Cell Indicator Chore-Tronics Load Cell Indicator June 2008 CTB Inc. Warranty Load Cell Indicator CTB Inc. Warranty CTB Inc. warrants each new product manufactured by it to be free from defects in material or workmanship

More information

Installation & Operation Manual Ice Cream Freezers

Installation & Operation Manual Ice Cream Freezers Installation & Operation Manual Ice Cream Freezers Please read this manual completely before installing or operating this unit! BACF11 BACF15 Blue Air reserves the right to make product modification at

More information

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

More information

Compressed Air Filtration

Compressed Air Filtration Ultramat MAIN FEATURES & BENEFITS: without pressure losses dirt condensate penetration of dust water into the controller housing possible Condensate drain without compressed air loss INDUSTRIES: construction

More information

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- 8610 Production Avenue San Diego, California 92121 (858) 566-7465 Fax (858) 566-1943 WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- Thank you for choosing a BREEZAIRE cooling unit. We believe

More information

1. Instruction. 1.5 Warranty Comar Condensatori S.p.A. guarantees its own products for twelve months from purchase

1. Instruction. 1.5 Warranty Comar Condensatori S.p.A. guarantees its own products for twelve months from purchase Index 1 Instruction p.20 1.1 Introduction p.20 1.2 Operator safety p.20 1.3 Instruction for proper installation p.21 1.4 leaning p.21 1.5 Warranty p.21 2 General p.22 2.1 Unit description p.22 2.2 Mechanical

More information

F4 Process Controller Installation and Operation Guide

F4 Process Controller Installation and Operation Guide F4 Process Controller Installation and Operation Guide 1.Introduction 1.1.Highlight Features Space saving, only 55mm panel depth required Higher sampling rate (1mS) results in better control performance

More information

AS570 Chill-Out Combination Sensor Installation and Operating Instructions

AS570 Chill-Out Combination Sensor Installation and Operating Instructions AS570 Chill-Out Combination Sensor Installation and Operating Instructions Tel: 763. 571.3121 Fax: 763. 571.0927 www.minco.com Description: Model AS570 is a combination sensor, which includes a low-temperature

More information

ACT2-CS Convenience Store Controller

ACT2-CS Convenience Store Controller Refrigeration Systems Technical Manual 804 Product Bulletins Section Product Bulletin Issue Date 0899 ACT2-CS Convenience Store Controller The ACT2-CS Convenience Store Controller is a fully programmable,

More information

Industrial Refrigeration Defrost Solutions TM Package. Brochure R-222

Industrial Refrigeration Defrost Solutions TM Package. Brochure R-222 aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding Industrial Refrigeration Defrost Solutions TM Package Brochure R- R-

More information

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual 65-2434RK Carbon Monoxide Transmitter Operator s Manual Part Number: 71-0061RK Edition: First, Revision C Released: December 2001 65-2434RK CO Transmitter 1 Product Warranty RKI Instruments, Inc., warranties

More information

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual GG-NH3 AMMONIA GAS SENSOR Installation and Operation Manual 2 GG-NH3 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

Controllers. Instruction Manual WARNING

Controllers. Instruction Manual WARNING Controllers Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like any piece of

More information

CSD-1 CRN Electra Steam, Inc. Instruction Manual for JR06 Steam Generator, JG- and JJ- Models

CSD-1 CRN Electra Steam, Inc. Instruction Manual for JR06 Steam Generator, JG- and JJ- Models ASME CSD-1 CRN Electra Steam, Inc. Instruction Manual for JR06 Steam Generator, JG- and JJ- Models RETAIN THIS OPERATING MANUAL WITH BOILER. DO NOT DISCARD READ THIS FIRST: The safeguards and instructions

More information

Warranty Registration

Warranty Registration WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship and materials for a period

More information

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual GG-NH3-2% AMMONIA GAS SENSOR Installation and Operation Manual 2 GG-NH3-2% Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

Instruction Manual WARNING

Instruction Manual WARNING Controllers Instruction Manual WARNING THIS MANAUL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like any piece of

More information

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL GASGUARD H2S EXP Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual Warning Use this product only in the manner described in this manual. If the equipment is used

More information

Programmable Digital Thermostat

Programmable Digital Thermostat OWNER'S MANUAL P/N P474-2150 1 For All Programmable Digital Thermostat Mo TOTALINE 72 74 COOL AUTO HEAT 70 Optional Locking Cover Meets California Title 24 Dual Setpoint 5+1+1 Day Programmable 3 Occupied,

More information

MODEL TSTATBBPB101 PROGRAMMABLE DIGITAL THERMOSTAT. Heat Pump & Heat Cool. Meets California Title 24 Residential USERS INFORMATION MANUAL

MODEL TSTATBBPB101 PROGRAMMABLE DIGITAL THERMOSTAT. Heat Pump & Heat Cool. Meets California Title 24 Residential USERS INFORMATION MANUAL USERS INFORMATION MANUAL Heating & Cooling Systems L TSTATBBPB101 PROGRAMMABLE DIGITAL THERMOSTAT NOTE TO INSTALLER: This manual must be left with the equipment user. AUTO Heat Pump & Heat Cool Dual Setpoint

More information

LC2200 Level Controller Installation and Maintenance Instructions

LC2200 Level Controller Installation and Maintenance Instructions 4025250/9 IM-P402-77 AB Issue 9 LC2200 Level Controller Installation and Maintenance Instructions LC2200 ALARM TEST >50% >100%

More information

Software Version 2.01 LEVEL MONITOR MODEL 220

Software Version 2.01 LEVEL MONITOR MODEL 220 Software Version 2.01 LEVEL MONITOR MODEL 220 19 April 2000 CONTENTS 1. Introduction 1 1.1 Model Number Designation 2 1.2 Intrinsic Safety Considerations 3 2. Specification 4 3. Operation 6 3.1 Display

More information

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N CLIMAGUARD Air-to-Air Outdoor Heat Exchangers TX23, TX33, TX38, TX52 Model INSTRUCTION MANUAL Rev. H 2015 Pentair Equipment Protection P/N 10-1008-221 87976519 TABLE OF CONTENTS RECEIVING THE HEAT EXCHANGER...3

More information