1 Dr. Anton Poeltl, ABB PPHV, 5/19/2014 Condition Monitoring Approach Sensors, Methods, Data ABB Month DD, YYYY Slide 1
2 Introduction This presentation describes ABB breaker condition monitoring approach for a specific product line. Doble has asked not to use brand names. Although there are different approaches to breaker condition monitoring, this presentation details only one approach. The purpose of this presentation is to provide an understanding of what a breaker monitor does and what type of data it maintains
3 Monitoring Scope Diagnostic and monitoring system for SF6 single pressure power circuit breakers rated 38kV and above Interrupter Wear SF 6 Gas System SF 6 Mechanical System Electrical Controls & Auxiliaries M
4 Travel Sensor (Mech. Inside Cabinet) Rotary encoder mounted at end of auxiliary switch linkage
5 Phase Current Transformers Clamp-On CT s Integrated Burden Output Range: up to 5V output Typical Input Range(for 5V output): 140 A 357 A Does not interfere with protection or metering devices
6 Temperature Sensors For example Resistive temperature devices (RTD) Resistance change: 38.5 W/ 100 C Mounting locations: tank, mechanism, cabinet
7 Heater Current Transformers Measure Heater Current Determine on/off condition
8 Pressure Sensor For example 4-20 ma sensor PSIG, 0.5 PSI accuracy
9 Other Connection Points Control Coils Motor Auxiliary Switches
10 Close (Open) Operation Analysis Contact Travel Make/Break Distance Total Travel Speed Calc. Zone Contact Velocity Reaction Time Mechanism Time Coil Time Close Coil Energization
11 C/O Operation Analysis Total Travel Speed Calc. Zone Contact Velocity Contact Travel Reaction Time Mechanism Time Close Coil Time Trip Coil Time Close Coil Energization Trip Coil Energization
12 Interrupter Wear Calculation Main Nozzle Arcing Contacts Aux. Nozzle Arc initiation Aux. nozzle exposed to arc Main nozzle exposed to arc Contact Travel Aux. Nozzle Wear I 2 Main Nozzle Wear Phase Current Contact Wear
13 Coil Continuity Breaker Monitor S 1 C 1 L coil 12 V Does not trip breaker Tolerates additional coil monitoring measures Works with variety of coils Shorted Coil 200 ms Open Coil 12 V Threshold Good Coil
14 Temperature Compensated Pressure dynamic quasi-stationary r 7 Pressure Liquefaction Curve r 6 r 5 p 2 p comp p 1 r 4 r 3 r 2 r 1 Liquid SF 6 Gaseous SF 6 T 1 20 C T 2 Temperature
15 Temperature Compensated Pressure Gas Trending Seconds Minutes Hours No Trend No Trend False Trend Days Clear Trend Months Slight Trend Time
16 Quantitative vs. Functional Monitoring Quantitative Monitoring Value Quantity Ok? Measure Calculate Compare Alarm Functional Monitoring / Exceptions Measure Value Identify State State Identify Exception Count Time Check Ok? Alarm Measure Value Identify State State
17 Quantities: Expected Range and Margins Problem Margin Calculated Value Problem Alarm Caution Alarm Exp. Max. Caution Margin Caution Alarm Exp. Min. Problem Alarm Time
18 Auto Definition and Auto-Adjust of Expected Range Auto definition: Exp. range is defined when quantity is defined Auto adjust: Exp. range is adjusted to include calculated value Calculated Value Auto-Definition Auto-Adjust Expected Range Defined Exp. Range Time
19 Quantitative vs. Functional Monitoring (Con t) Quantitative Monitoring Value Quantity Ok? Measure Calculate Compare Alarm Functional Monitoring / Exceptions Measure Value Identify State State Identify Exception Count Time Check Ok? Alarm Measure Value Identify State State
20 Exceptions: Expected Time and Margins Exc. Heater Current Time Temperature Thermostat Deadband Time Heater Off Func. States Low Temperature Time Heater Off at Low Temperatures Time Exp. Caution Problem Time Time Log Entry Margin Caution Alarm Margin Problem Alarm
21 Heater Monitoring Heater Off (not thermostat controlled) Heater Off at Cold Temperatures Heater On at Warm Temperatures Alarm if longer than 15 minutes (Caution) Alarm if longer than 2 hours (Problem)
22 Today s Count / Yesterday s Count Motor Starts Max. Count Day 1 Day 2 Day 3 Day 4: Problem Fixed Wrong Monitoring Approach: Time Alarm Alarm Alarm Normal Normal Normal Normal Correct Monitoring Approach: With Acknowledge: User Acknowledges Normal Alarm Normal Without Acknowledge: Normal Alarm Alarm Clears Normal
23 Motor Starts Motor Starts without Operation: Alarm if longer than 30 seconds (default) Alarm if more than 10 per day (default) Motor Starts with Operation: Alarm if longer than 90 seconds (default) No limit on starts per day
24 Other Monitoring Features Tank Temperature Mechanism Temperature Trip Count (Informative) Breaker Current (Informative)
25 Complete List of Monitoring Features Coil Continuity Total Travel Contact Velocity Reaction Time Coil Energization Time Contact Wear Auxiliary Nozzle Wear Main Nozzle Wear Trip Count RMS Current Tank/Gas Temperature Mech./Cab. Temperature Leak Rate (5 time spans) Heater off a low temperature Heater on at high temperature Heater off (heater w/o thermostat) Pump starts w/o operation Pump starts w/ operation
26 GUI Device Settings
27 GUI Conditions
28 GUI Log
29 GUI Operations
30 GUI Gas Trending
31 Communication Using RS232 CMU 2000 System Power Clock CMU 2000 System Power Clock CMU 2000 System Power Clock Communication RS-232 RS-485 Communication RS-232 RS-485 Communication RS-232 RS-485 Overall Condition Problem Caution Normal Overall Condition Problem Caution Normal Overall Condition Problem Caution Normal Detailed Condition SF6-Gas Mechanism Interrupter Charging System Control Coils Heaters A BB Detailed Condition SF6-Gas Mechanism Interrupter Charging System Control Coils Heaters A BB Detailed Condition SF6-Gas Mechanism Interrupter Charging System Control Coils Heaters A BB f.o. CMU 2000 System Power Clock CMU 2000 System Power Clock CMU 2000 System Power Clock Communication RS-232 RS-485 Communication RS-232 RS-485 Communication RS-232 RS-485 Overall Condition Problem Caution Normal Overall Condition Problem Caution Normal Overall Condition Problem Caution Normal Detailed Condition SF6-Gas Mechanism Interrupter Charging System Control Coils Heaters A BB Detailed Condition SF6-Gas Mechanism Interrupter Charging System Control Coils Heaters A BB Detailed Condition SF6-Gas Mechanism Interrupter Charging System Control Coils Heaters A BB fiber optic connection f.o. Company Network
32 Communication Using Ethernet f.o. link fiber optic connection Control House Ethernet Switch Company Network
33 Communication Using RF Modems Control House Company Network
34 Communication using Cellular Modems Cell Tower Provider Company Network
35 Communications Protocols Native Protocol Proprietary protocol Very efficient Documentation available to customers Modbus De-facto industry standard Supported by most SCADA systems Modbus memory map available to customers DNP3 (Distributed Network Protocol) Set of communications protocols used between components in process automation systems. Main use is in utilities such as electric and water companies. Plays a crucial role in SCADA system Used by SCADA Master Stations (aka Control Centers), Remote Terminal Units (RTUs), and Intelligent Electronic Devices (IEDs). Primarily used for communications between a master station and RTUs or IEDs.
36 DNP3 Data for Specific Product Makes each of its monitored conditions available via DNP3 protocol. This includes the calculated value, the set points, alarm status etc. Third party SCADA software can be configured to display monitoring data along with data from other IEDs Specific product is compliant with DNP3 level 2 but offers some level 3 functionality such as file transfer. Oscillographic data containing contact travel, phase current, and binary inputs is available via file transfer in COMTRADE format and can be viewed using a third part COMTRADE viewer
37 Modbus Data for Specific Product Larger set of data available Same as data structures as when using native protocol
38 Summary Types of Data Raw Data Operation Records Travel Curves Phase Current Waveforms Binary Traces (52a&b, close and trip coil energization) History for Gas Trending Pressure & temperature values Temperature compensated pressure values Intermediate Waveform Records Phase current snap-shots (2-period recording) Processed Data (Conditions) Calculated values (e.g. velocities, leak rates, interrupter wear etc.) Alarm state Various flags for status information and support functions Log Entries Alarms Sensor Changes User Intervention
39
5. CBS Alarms Responding to a CBS Alarm Understanding the Alarm Condition A-CBS-008 Circuit Breaker Sentinel Page 109 of 156
Page 109 of 156 5. CBS Alarms 5.1. Responding to a CBS Alarm The CBS uses its alarm contacts to signal the presence of alarm conditions. There are two alarm relays:one for Caution alarms and one for Problem
More informationNGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X
NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS Firmware versions up to V2.0.X INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGCUIT2Protocol-IM-H57880 06/15 1/32 Contents Section I Introduction
More informationCTT8 TEMPERATURE MONITOR DEVICE
INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible
More informationTYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM
2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40
More informationMO n : 12JMC rév A
CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES
More informationPROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS
PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min
More informationProcess & TeMPerATUre UniversAl input DigiTAl MeTers
Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min
More informationSpecification for On-Line UPS Battery Monitoring and Data Management System
1 Scope This specification defines the minimum requirements for a predictive on-line Battery Monitoring BMDMS with test, analysis, and remote monitoring control capabilities. Unless noted otherwise, the
More informationMoulded case circuit brakers
Moulded case circuit brakers CONTENT Range 1 Protection Releases 2 Salient Features 5 Accessories 7 Widest Range 10 Time Current Characteristics 12 Overall Dimensions 14 SN4 SN3 SN2 SN1 3 RANGE SN1 Rated
More informationi-con Switchgear Condition Monitoring HV Switchgear Integrated Substation Condition Monitoring ISCM Answers for Infrastructure & Cities.
i-con Switchgear Condition HV Switchgear Integrated Substation Condition ISCM Answers for Infrastructure & Cities. The challenge: Reliable energy supply is the key to success for every enterprise in a
More informationSetup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software
La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for A36D & TPSD Chargers with S2A-341S and S2A-383S communication cards. Option 21P,
More informationTEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.
TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL Microener- Copyright 2010 FW 2.1 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection
More informationMiniature Infrared Temperature Sensors with Optional Touch Screen Display. PSC-SSS-PM with touch screen display (-CRT version)
PSC-SSS-PM Series Miniature Infrared Temperature Sensors with Optional Touch Screen Display PSC-SSS-PM with touch screen display (- version) FEATURES Miniature sensing head and configurable electronics
More informationWind power Condition Monitoring. Condition Monitoring Systems (CMS) in wind turbines CMS. Authors: Martin Kluge Michael Danitschek
Systems (CMS) in wind turbines CMS Authors: Martin Kluge Michael Danitschek update: 22.07.2010 page 1 Intelligent vibration monitoring of wind turbines Targets Permanent plant/system protection Reduction
More informationI/O ZONE 560/583 USERS GUIDE
I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6
More informationSOLAR POWER PLANT AUTOMATIO
SOLAR POWER PLANT AUTOMATIO ON Submitted by:- I-Logicon Control Automation Pvt Ltd, Bangalore. CONTENTS: 1. Abstract 2. SCADA and Reporting System Architecture 3. SCADA Components 4. Reporting System.
More informationNGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1
NGC-40 Bridge Overview Raychem-AR-H58862-NGC40BridgeOV-EN-1805 nvent.com 1 Table of Contents 1. NGC-40 Overview... 9 1.1 Example NGC-40 System... 10 2. Legal stuff... 11 3. Protocols... 12 3.1 Data es...
More information1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection
Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication
More informationLCF Touch Modbus Datasheet Application Security Advice Caution
LCF Touch Modbus Electronic Fan Coil Thermostat with Touch Display (Flush mounting) Datasheet Subject to technical alteration Issue date: 3.11.214 Application Modern design flush mounting fan coil room
More informationModel A2100 Series Annunciator
Seekirk Model A2100 Series Annunciator Applications: For usage within transformers, switchgear, breakers and/or within any processing equipment or control room applications either attended or unattended
More informationFlameGard 5 UV/IR HART
FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized
More informationTRACENET TM TCM18 CONTROL AND MONITORING SYSTEM
TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM APPLICATION OVERVIEW Control and monitoring systems play an essential role in heat tracing applications which range from freeze protecting water lines to
More informationI/A Series 716C 1/16 DIN Temperature Controller
Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of
More informationCONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.
CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse
More informationHeating Cable. Description
ITLS Base Panel 10 VGA Touch Screen HMI 40 Amps/Loop @ 100 480 VAC 6 Loops to 72 Loops NEMA 4 or NEMA 4X Enclosure SCR Control Integral Circuit Panel with Circuit Breakers Optional Main Disconnect Soft
More informationM2500 Engine Controller Installation Manual
M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...
More information7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management
Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current
More informationTRACENET TM TCM18 CONTROL AND MONITORING SYSTEM
TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM APPLICATION OVERVIEW Control and monitoring systems play an essential role in heat tracing applications which range from freeze protecting water lines to
More informationLift Station Level Controller
Lift Station Level Controller Installation and Operation Manual 1 California Motor Controls, Inc. Benicia, CA Table of Contents 1. Features Product Overview... 4-6 Access Security... 7 Optional Features...
More informationTraceNet ECM Series Control System
TraceNet ECM Series Control System ECM Operating Guide Thermon Manufacturing Company TraceNet is a registered trademark of Thermon Manufacturing Company. ECM Operating Guide 2014, 2015 Thermon Manufacturing
More informationABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements
Specifications COMMANDER 150 Universal Process Indicator High visibility 6-digit LED display the clearest view of your process status 0.1% measurement accuracy precise indication of process measurement
More informationUV Sentry. Cost Effective Perimeter & LDAR Monitoring. ...Precise, Species Specific Fugitive Emissions Quantification
UV Sentry Open Path Multi-gas UVDOAS Analyzer Ammonia Benzene Carbon Disulfide Chlorine Cost Effective Perimeter & LDAR Monitoring The UV Sentry offers perimeter monitoring with among the lowest cost per
More informationDew point set DS 400
set DS 400 Dew point set DS 400 for stationary dew point monitoring of refrigeration or adsorption dryers. The touch screen graphic display enables an intuitive operation and shows the progress of the
More informationFor Raychem ACS-30 Controls Systems
ACS-30 Protocol Interface Mapping For Raychem ACS-30 Controls Systems Firmware Version 5.05 THERMAL BUILDING SOLUTIONS EN-RaychemACS30-AR-H58324 03/16 Table of Content Section 1. Introduction... 3 1.1
More informationAIS750 Series Alarm Annunciator User Manual (Ver. 2.3 / JUNE. 2014)
AIS750 Series Alarm Annunciator User Manual (Ver 23 / JUNE 2014) 3-350 John Street, Thornhill, tario L3T 5W6 Phone: 289 597 APEX (2739) Fax: 289 597 2200 Toll Free: 1 866 776 2943 Email: mail@annunciatorca
More informationRS Pro Infrared Temperature Sensor
Instruction Manual RS Pro Infrared Temperature Sensor Stock Number: 161-8103 Introduction The RS Pro Infrared Temperature Sensor is a device for measuring the temperature of the surface of a solid or liquid
More informationRC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control
O M N I S T A T ELECTRONIC COMMUNICATING THERMOSTAT Installation Manual RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control Document Number 13I00-5 November, 1997 CONTENTS
More informationFlameGard 5 MSIR HART
FlameGard 5 MSIR HART Multi-Spectral Infrared Flame Detector HART Communication with the FlameGard 5 Multi-spectral Infrared Detector The information and technical data disclosed in this document may be
More informationAIS750 Series Alarm Annunciator
Unparallel, modular, multipoint design with Integrated controllers Two Operation Modes (Stand-alone & Serial) All sizes confi gurable up to 440 Alarm Points RS485 / RS232 Serial Communication Manual &
More informationAQ 100 Series. Arc Flash Protection System
AQ 100 Series Arc Flash Protection System THE CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR THE CONSEQUENCES OF AN ARC FAULT IN OIL-FILLED SWITCHGEAR Arc Phenomena Arc Phenomena Arc fault - facts
More informationA36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS
SCADA INTERFACE INSTRUCTIONS - OPTION 21S - FOR A36D/TPSD SYSTEMS with option 500 and 550. A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE OPTION 21S INSTRUCTIONS This manual is valid for A36D/TPSD Chargers
More informationImportant Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.
1 P age Ezeio v9-120317 Eze Cloud Based Monitoring Systems. Created by Intech Instruments Ltd December 2014 Important Supplementary Manual to the main Ezeio manual. Ezeio Controller and the 2400-A16 input
More informationMYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL
MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TPC VISIT OUR WEBSITE SIGMACONTROLS.COM MYRIADI&O062705 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 7,8
More informationSM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option
SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow
More informationACTIVE INFRARED BARRIER
Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology
More informationSeries Digital Controller Instruction Sheet
216/3/11 Series Digital Controller Instruction Sheet Thank you very much for purchasing DELTA DTC Series Temperature Controller. Please read this instruction sheet before using your DTC series to ensure
More informationAmpLight group management
AmpLight System Guide AmpLight group management Table of Contents System description.... 3 Benefits...4 Features....4 Central dimming....5 Benefits....5 Features....5 AmpLight Modules...6 Coded mains...8
More informationTraceNet TM TCM2 CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE
TraceNet TM TCM2 CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE TraceNet TM TCM2 CONTROL AND MONITORING SYSTEM APPLICATION OVERVIEW Control and monitoring systems play an essential role in heat tracing
More information4/8/12/16 Channel Temperature Scanner with FREE Data Logging PC Software RS485
Select Option Device Wise Device/Group HumiLog Y-Axis Text Show/Hide Ledgends MIN MAX Scale Y Max 08-05-2015 15:17:59 PV_C PV_RH Color default default Graph Refresh Interval 2 Set Interval PV Low Alarm
More informationJon Longtin Department of Mechanical Engineering SUNY Stony Brook
Jon Longtin Department of Mechanical Engineering SUNY Stony Brook Jon Longtin Department of Mechanical Engineering SUNY Stony Brook jlongtin@ms.cc.sunysb.edu 631 632-1110 Overview The Neglected Gas Meter
More informationSafety Instructions MS 10B ALARM UNIT MS 10B ALARM UNIT. Used symbols. Always observe this information to prevent damage to the device
Safety Instructions Used symbols Important Comments Before starting with installation of the MS 10B Alarm Unit, we recommend you to read the important information beneath. Qualification The installation
More informationProcess Alarm Solutions
Process Alarm Solutions Reliable Supervision and Control» Control. Monitor. Protect. SELCO Flexible alarm panels for supervision and control SELCO provides efficient and reliable solutions for alarm monitoring
More informationModbus RTU RS485 Manual
Modbus RTU RS485 Manual AUTOMATED FUEL MAINTENANCE SYSTEMS FTI-5A, FTI-10A, FTI-20A FUEL TECHNOLOGIES INTERNATIONAL 06/10/2014 Rev B - Fuel Technologies - Modbus The Modbus Communications Setup Button
More informationCAREL heatersteam Electric Element Steam Humidifiers
Suggested Engineering Specifications Section 23 84 13 CAREL heatersteam Electric Element Steam Humidifiers 1. GENERAL SCOPE 1. Furnish and install as indicated on the drawings and plans, in-duct [space]
More informationSubstation Monitoring System
Substation Monitoring System UHF Partial Discharge Monitoring System Description Introduction The UHF PDM System is the third generation, spanning 20 years, of monitoring systems developed for GIS partial
More informationSEL-2523 Advanced Annunciator Panel
SEL-2523 Advanced Annunciator Panel Complete Alarm Monitoring, Annunciation, and Communication Major Features and Benefits High Reliability, Low Price Ten-Year, Worldwide Warranty 40 to +85 C Operating
More informationSubstation Monitoring System
Substation Monitoring System SF6 Gas Density Monitoring System Description Introduction As a result of recent European legislation on the control of greenhouse gasses, utilities and manufacturers alike
More informationElectrical installation solutions for buildings Technical details Energy efficiency
/1 Electrical installation solutions for buildings Technical details Energy efficiency Index Multimeters and network analyser /2 DMTME multimeters /5 ANR Network analyser / M2M Network analyser /9 EQ meters
More informationAPP 721 MODBUS Mapping
SUMMARY This document is intended to be a reference for communicating with the Flygt APP721 controller using MODBUS RTU communication. Communication settings to the unit are as follows: MODBUS RTU, 8 data
More informationLift Station Monitoring & Control The process begins here
Lift Station Monitoring & Control The process begins here Standards Certification Education & Training Publishing Conferences & Exhibits Speakers: Alan Vance E+H Industry Mgr W/WW Terry Sages Rockwell
More informationFire Operator Workstation (Fire OWS) User s Guide
Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of
More informationVTScadaLIGHT for Small Water & Wastewater Systems
The Webinar will begin shortly. Start time is 1:00 pm EST VTScadaLIGHT for Small Water & Wastewater Systems Bedford, Canada (Head Office) Aberdeen, UK Orlando, USA Calgary, Canada Houston, USA Birmingham,
More informationAcross-the-Line SERIES MP300 Combined Manual and Automatic
Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps
More informationReplaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge
Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays
More informationOn-line Side Stream Oil in Water Analyser - Model OIW-EX 100 or OIW-EX 1000
brochure On-line Side Stream Oil in Water Analyser - Model OIW-EX 100 or OIW-EX 1000 Advanced Sensors Ltd Oil in Water Analyser System known as the OIW-EX100 or OIW-EX 1000. The system is designed to monitor
More informationHoneywell SLATE ICM Platform
Honeywell SLATE ICM Platform SUBMITTAL SPECIFICATION Note to specifiers: To specify Honeywell SLATE Integrated Combustion Management System with specified packaged boiler manufactures, Copy and Paste both
More informationPowerWizard. Level 1.0 & Level 2.0 Control Systems Training
PowerWizard Level 1.0 & Level 2.0 Control Systems Training New Systems Current Systems Systems Comparison Level 1 Level 2 Level 3 Level 4 PowerWizard Level 3.0 PowerWizard Level 4.0 Overview Common parts
More informationFlow Level Pressure Temperature. Rugged tactile response keys. Try the all new Fluidwell Configurator at:
Fluidwell F-Series Flow Level Pressure Temperature Trend indication Displayed function Clear 0.7 or 1 digits Measurement units for TOTAL Large LCD with backlight option NEMA 4X aluminum or plastic field
More informationManual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:
Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description
More informationE340 BOILER CONTROL INSTALLATION MANUAL
E-3451 JUNE 1999 E340 BOILER CONTROL INSTALLATION MANUAL DESCRIPTION The E340 Boiler Room Control is a microprocessor-based Boiler Management System designed to interface with existing Fireye D Series
More informationDSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE
DSGH Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE Revision History Revision History Version of manual Description Date 1.0 Initial release 051025 1.1
More informationType TEC, Transformer Electronic Control System
Type TEC, Transformer Electronic Control System Technical Guide 1ZSC000857-AAB en, Rev. 2, 2006-06-15 Declaration of conformity The manufacturer ABB Power Technologies AB Components SE-771 80 LUDVIKA Sweden
More informationDew point. Special features: Dew point monitoring DS 400. Technical data DS 400. Technical data FA 510
Dew point monitoring DS 400 for stationary dew point monitoring of refrigeration or desiccant driers. The touch screen graphic display enables an intuitive operation and shows the progress of the measured
More informationPump-Up Controller MODEL 4062
Pump-Up Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4062 Pump-Up
More informationCompressed air quality meas. according to ISO 8573 Residual oil content - particles - moisture
meas. according to ISO 8573 Residual oil content - particles - moisture DS 500 - the intelligent chart recorder of the next generation. The centerpiece of compressed air quality measurement is the chart
More informationPACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011
October 2011 PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412 The PACSystems * Thermocouple Input module IC695ALG412 provides twelve isolated differential thermocouple input channels.
More informationTable of Contents. T538 Instruction Manual Rev # 6 June R6T538 June rtf E L Switchgear and Control Inc
Table of Contents Introduction...2 Mounting...2 Dimensions...2 Controls...3 Screen Displays...3 Screen Messages...4 Light Test...5 Control Power...5 Wiring...5 Inputs...7 Outputs...7 Programming...8 Technical
More informationREA 105 Arc Protection Module. Operator s Manual
REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5
More informationRemote fiber testing to improve SLA s
Remote fiber testing to improve SLA s Presented by : Kamel SOUILAH System Sales Engineer kamel.souilah@exfo.com 2010 EXFO Inc. All rights reserved.. 1 EXFO is the leader in the test and measurement solutions
More informationNGC-20 LOCAL CONTROL CENTRAL MONITORING
LOCAL CONTROL CENTRAL MONITORING NVENT RAYCHEM THE RAYCHEM IS A FIELD-MOUNTED ELECTRONIC TEMPERATURE CONTROL UNIT PROVIDING LOCAL CONTROL AND CENTRAL MONITORING CAPABILITIES FOR INDUSTRIAL HEAT-TRACING
More informationContinuous, real-time detection, alarming and analysis of partial discharge events
DMS PDMG-R Partial discharge monitor for EHV GIS Continuous, real-time detection, alarming and analysis of partial discharge events Automatic PD fault classification Robust design allows for reliable operation
More informationHTC-915-CONT. Heat-Trace Control system
Heat-Trace Control system Product overview The Raychem HTC-915 system is a compact, full-featured microprocessor-based single-point heat-trace controller. The HTC-915-CONT provides control and monitoring
More informationManual for the integration in BMS/GTC
Manual for the integration in BMS/GTC Communication parameters MODBUS RTU and BACNET COMMUNICATION UTBS PRO-REG Software Version 3.6 EN ÍNDEX 1. GENERALITIES...2 1.1. Introduction...2 1.2. signals types...2
More informationSTRIKE GUARD DELIVERS:
TM Strike Guard employs state-of-the-art technology to address the most demanding lightning safety and equipment protection applications. Designed for critical industrial applications, Strike Guard monitors
More informationPump-Down Controller MODEL 4052
Pump-Down Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4052 Pump-Down
More informationAnalog Annunciator Unit SACO 16 A3. Product Guide
Issued: Aprill 1999 Status: Updated Version: C/20.03.2006 Data subject to change without notice Features Powerful, flexible and field-customizable 16-channel analog input signal annunciator unit A full
More informationOperating Manual. Series Touchscreen Programmable Demand Control Thermostat. UtilityPRO TM
Operating Manual UtilityPRO TM Series Touchscreen Programmable Demand Control Thermostat 85-3126 BE CAREFUL! Never use sharp instruments, such as a pencil or pen, to press touchscreen keys. To prevent
More informationSoft Start Series MP700 Solid State, Reduced Voltage
Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s
More informationSECTION Fluorescent Dissolved Oxygen Measuring System
SECTION 40 75 43 Fluorescent Dissolved Oxygen Measuring System PART 1 General 1.01 SUMMARY A. Requirements for a high-performance, digital fluorescence sensor for measurement of dissolved oxygen in liquid.
More informationVaultGard Communications Network Underground Communication Solutions. VaultGardTM
VaultGard Communications Network Underground Communication Solutions VaultGardTM Can You Imagine... In the future, a network communications solution that combines intelligence, user-friendliness, and security
More informationAir Check EX LEL Gas Monitor Instruction Manual
Air Check EX LEL Gas Monitor Instruction Manual PureAire Monitoring Systems, Inc. 1140 Ensell Road Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 www.pureairemonitoring.com
More informationINSPECT & MONITOR 24/7 SOLUTIONS FOR ELECTRICAL CABINETS. IR Windows & AX8 Thermal Imaging Temperature Sensor
INSPECT & MONITOR 24/7 SOLUTIONS FOR ELECTRICAL CABINETS IR Windows & AX8 Thermal Imaging Temperature Sensor FLIR Solutions FLIR HAS A CABINET MONITORING SOLUTION FOR YOU If your cabinet-monitoring routine
More informationSpecification Data. General:
Specification Data General: Zone Units (ACU s) will be draw through vertical type having double skin construction. All Zone Units will have all necessary components such as control valves and motors to
More information4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head
4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head NET DRAFT version 2.1-2008 Pag. 1 4-20mA Cyber - DRAFT version 2.1-2008 Pag.
More information725B Configuration Software Manual
725B Configuration Software Manual REV DATED DESCRIPTION AUTHOR APPROVED 0 09-03-10 First Issue P.Cartmell Page 1 of 80 SECTION 1 - SOFTWARE INSTALLATION... 5 725B ConfigurationSoftware Installation...
More informationR E C T I F I E R I N V E R T E R C O N V E R T E R SB7
SCR Battery Charger Product Specifications Description The is RIC Electronics premiere SCR battery charger/rectifier. The provides power to critical DC loads through a wide range of outputs and is engineered
More informationDigiTrace NGC-family
DigiTrace NGC-family The world beyond the MoniTrace 200N Robert Kuipers Electronics Marketing Manager Ken Wilson Industrial Sales Manager Peter Sirs UK/Nordics Regional Sales Manager Bruno Guinand Business
More informationINTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description
INTELLIGENT FIRE ALARM CONTROL UNITS MMX-2003-12NDS Intelligent Network Fire Alarm Control Unit Description Secutron's MMX-2003-12NDS is a powerful intelligent networkable fire alarm solution designed
More informationMODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT
TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel
More informationThe system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.
FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001
More information