It should be done through a connection authorization - Should be consistent for all LDCs, to avoid interpretation, public safety risk and liability

Size: px
Start display at page:

Download "It should be done through a connection authorization - Should be consistent for all LDCs, to avoid interpretation, public safety risk and liability"

Transcription

1 Company/ Organization/ Individual Local Distribution Company (LDC) Electro Federation Canada (EFC) Rule # Stakeholder Comment/ Feedback Submitted to ESA & Suggestions for Improvement/ Alternatives It should be consistently applied for all utilities in the province - Code side work should not be at the direction of LDC - Having no proof of whether licensed electrician is done is difficult and would add administrative burden on management of the process - in the installation example TH tried in the field along with Steve Smith, ESA GM, there was work required to install this device to the meter-base neutral bar, which would require a connection authorization in order to ensure public safety and manage liability It should be done through a connection authorization - Should be consistent for all LDCs, to avoid interpretation, public safety risk and liability We still have issues with deletion of the majority of , contrary to text in red below. The red text is withdrawn but the rest related to rule 02-xxx does stand as acceptable to EFC. Our concerns may now actually been increased with the much more narrowly limited The concern related to flammability, which was the too vague aspect of , (1)(a), but was somewhat salvaged by (2). As noted in the earlier , a member told me during the breakfast meeting last week that a contractor strung together in series about 100 of LED decorative lighting strips, installing a larger driver to boast the current, not even thinking that the tiny wiring in those strips would NOT be able to handle to higher current. It started a fire and they complained back to the member looking for redress. The contractor realized the error once explained. So, while the change to rule 02-xxx provides greater clarity, the deletions to rule may imply even greater latitude for load side Class 2 circuits not requiring approval. ESA Response Rule (f) that exempts a meter mounted transfer device from an application for inspection was introduced into the Ontario Electrical Safety Code in The installation of a meter-base plug-in transfer device without application for inspection is only permitted if the work is done by Licensed Electrical Contractor (LEC). If a supply authority cannot determine that LEC has done the installation, Subrule (2) gives the option to ask for application for inspection. Also, if a supply authority does not permit the installation of a meter-base plug-in transfer device, Subrule (2) gives the option to reject that installation. The suggestion has been considered and certain changes in part have been made based on the comments. Specifically, the changes are made in the Appendix B note based on the comments. The purpose of the proposed amendment is based on the requirements in the updated CSA standard C22.2 No. 37 Christmas tree and other decorative lighting outfits. In accordance with the updated standard, decorative lighting strings are required to be marked with the warning label to prevent overloading the circuit.

2 Licensed Electrical Contractor (LEC) Instead I recommend being specific on (1)(a) as follows, plus a modified Appendix B. Sentence (2) can still be deleted as rule is now clear enough Equipment located on the load side of overcurrent protection, transformers, or current-limiting devices for Class 2 circuits (1) Equipment located on the load side of overcurrent protection, transformers, or current-limiting devices for Class 2 circuits shall (a) for Class 2 circuits operating at not more than 42.4 V peak or dc, but may carry power greater than 100 VA requires approved for that purpose be acceptable for the particular application; and (b) for Class 2 circuits operating at more than 42.4 V peak or dc be arranged so that no live parts are accessible to unauthorized persons. (2) Notwithstanding Subrule (1), lighting products, electromedical equipment, equipment for hazardous locations, and thermostats incorporating heat anticipators shall be approved. Delete Replace the CE Code Appendix B Note to Rule (1)(a). Rule (1)(a) With respect to the acceptance of equipment for connection to Class 2 circuits operating at not more than 42.4 V peak or dc, consideration should be given to the fact that while Class 2 circuits limit the power that can be dissipated in the circuit continuously, this power is more than sufficient to be a fire hazard if dissipated in a fault within improperly designed equipment, e.g., shorted turns in a coil, or too many decorative light strings are serially connected to exceed their rating Most quality gas ranges that include convection and or self-cleaning options require the 50-A receptacle or similar to power those features. The information regarding these options is rarely available at the time of roughing-in and is often not determined until the delivery

3 Contractor Advisory Council (COAC) of the appliance. Rough-in box, cover, and empty conduit (FNMC or other) to close proximity of service panel for installation of wiring if required at a later date The COAC does not agree with the proposal of the requirement to remove the stove outlets. Consumer As the second consultation seeks feedback on "all other" Ontario amendments to the Ontario Electrical Safety Code, and a recommendation for: "Removal of the mandatory requirement to install an electric range receptacle for all dwelling units. This amendment harmonizes with CEC and aligns with the Building Code requiring one source of energy; electrical, propane or natural gas, for cooking appliances." Consumer Advisory Council Consumer Advisory Council Again, I sense the cooperation of another organization to support an E.S.A. and business interest. What about the Ontario consumer's preference to have an electrical source as mandatory while requesting an other option? It is better to make the investment to add receptacles first than try to retrofit later. The Council agreed that the OESC should not be changed and that an electrical outlet should still be required This amendment will have to be communicated to consumers. ESA is working with CSA to update the requirements in the certification standard in order to require proper luminaire marking for luminaires suitable for installation in clothes closets. Advances in LED technology broadened the application of this

4 Licensed Electrical Contractor (LEC) (e) The code rule consideration for installing smoke detectors on a arc fault bedroom circuit, should not happen. My reason for this is under the event of a power outage, ppl use a generator, which is fine but some of the inrush voltage is too much for the breaker and inadvertently trips, there for leaving the smoke detectors running on simply the battery. This will cause nuisance calls, and we are going the wrong way with our life safety devices. This isn't a theory, we have run across this a good many times just finding arc fault breakers tripped after an outage The other matter is trying to work with the building departments more in regards to smoke detectors. Now they are asking for a flashing device to be added to all smoke detectors. the is a building code rule not a CEC issue. Bottom line is that the end user is going feel taken or mislead with the 2 departments can't seem to commutate. I feel that these devices do not needed to be added throughout every home for the hearing impaired. I understand the purpose. I feel that yes the hearing impaired should have an additional life safety device, but not for every home across the province. They could be installed on a special request basis under a grant program perhaps. I just think we are over complicating things. RV Park While we welcome the guidance on this very important issue and agree with the proposal to have standardized rules for campground owners to follow, detailed discussions need to cover off acceptable expectations where availability of equipment and timelines for upgrades are concerned. Compliance will be dependent on reliable supply sources and availability of technicians to perform what will be a costly upgrade for the industry. Please consider these very important aspects of bringing the industry into compliance. type of illumination so the heat emission may not be the issue in the future. Although the ESA proposal was based on the updated Building Code and product standard requirements, considering the progress with the proposal at Canadian Code, we feel that it is prudent to wait with this permission until the next Canadian Electrical Code (CEC) when products with battery backup are widely available. Please be advised that the OESC is not retroactive. The proposed amendment will not be enforced retroactively, that is to say existing RV parks will not be required to update their infrastructure to comply. The proposed amendments would only apply to new installations where a power pedestal has been provided for on an RV lot.

5 Camping in Ontario/ Ontario Private Campground Association RMOH/ Wastewater Infrastructure Change wording of recreational vehicle parks to campgrounds. Campground is the word used by the industry and Ontario government to describe "trailer parks, or travel trailer parks or RV parks". The Actual length of the Electrical Supply cord and the position of the exit point from the recreational vehicle (Park model, Travel trailer, Motor home, Tent Trailer or Hybrid) The longer the unit is the more imperative that the exit point be on the left side and more removed from the rear of the unit. Appendix B Notes on Rules, Rule Sewage lift and treatment plants Make Wording more inclusive by adding the word Campground to preamble so that it is consistent with the other documentation. You could also increase the length of the electrical cables required on any unit over a certain length, say 8.53m. Every meter in length over 8.53 would require a corresponding 1.5 meter increase in the length of the electrical cord The applicability and application of NFPA 820 Standard for Fire Protection in Wastewater Treatment and Collection Facilities has been causing confusion during the design of wastewater infrastructure. This confusion is realised in discordant infrastructure designs, deviation from the Ontario Electrical Safety Code (OESC), and designs incongruent with Occupational Health and Safety Act protections for worker safety (e.g. Confined Spaces Regulation) and Environmental Protection Act for regulated process emissions (s.9). NFPA 820 does not address corrosion protection, advocates for non-essential equipment within Class 1, Zone 1, Category 2 areas, relies on continuous ventilation of process emissions in conflict with Provincial regulations, and does not address worker safety protections. NFPA 820 advocates for CGD as a fire protection The word campground is used by the industry and Ontario government to describe trailer parks, or travel trailer parks or RV parks. To change from park to campground would be in conflict with the various standards used throughout North America with respect to recreational vehicles ((RV) and recreational vehicle parks. With respect to the length and location of the electrical cord on the RV, this has already been addressed within the certification standard for RVs (Z240 RV). Provided the RV is approved for use, the electrical cord will always be able to reach the power pedestal, regardless of RV length, provided the power pedestal is installed as per the proposed Ontario amendment, which harmonizes the manufacturing standard (length and location) with the power pedestal location on the RV lot. Unfortunately we are unable to consider new code proposals at this point in the process. Should you wish to submit a code change proposal to the CEC, it will be reviewed through the normal process for the next code cycle, and will be considered for adoption in Ontario.

6 measure, the Electrical Safety Code only requires their use under Rule and suggests proper area classification should eliminate the need in most situations,[1] and identifies limitation with their use as a failure to perform may give a false indication that an area is safe.[2] Halton s operational practices require the use of handheld (calibrated/tested) multi-gas detectors to properly determine the atmospheric hazards of a confined space. Combustible Gas Detection in the wet well does not further electrical safety or fire prevention as the location has been designated Class 1, Zone 1, Category 2 and fails to address the human health and life-safety risk of entering a confined space, most notably hydrogen sulphide and oxygen deficiency; however by its very presence may be inadvertently judged as an indication of safe conditions within the confined space. Rule should further clarify that conformance with NFPA 820 is not implied and does not satisfy the OESC Rule 18 or 22 (including Bulletin & ), and should not be considered a substitute for proper hazard assessment further adding NFPA 820 is not adopted by the Authority Having Jurisdiction in Ontario and does not conform to the OESC, technical bulletins, and relevant Provincial legislation for worker safety and air emissions. The ESA should clarify that it does not encourage continuous ventilation of wet wells, for de-rating of electrical classification, fire protection, or corrosion prevention, as this process exhaust would be a prohibited discharge of contaminants(environmental Protection Act, R.S.O c. E.19, s. 6 (1)). Remove references to NFPA 820 (Appendix B and Bulletins). Example: A dry well should be suitably cut-off from the wet well, providing a location classification for the below grade

7 portion of dry wells as Category 1 in accordance with the Electrical Safety Code.[3] The classification recommendations include Class I, Div 2 under NFPA 820 for a dry well without continuous ventilation. Master Electrician General I find that there are too many legal and unintelligible phrases in the electrical code and request that the electrical code be re-written in a more understandable grammatical format. I understand that the building code uses a more understandable phraseology, so why shouldn't the electrical code? The code is undergoing continuous changes to clarify wording. If you have changes to suggest, please refer to Appendix C of the OESC.

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

ELECTRICAL BULLETIN

ELECTRICAL BULLETIN PO Box 697 Halifax, Nova Scotia B3J 2T8 Labour and Workforce Development ELECTRICAL BULLETIN 2011-01 From: David MacLeod,C.E.I.,P.Eng. Pg 1 of 6 Provincial Chief Electrical Inspector Date: January 5,2011

More information

Electrical Tech Note 107

Electrical Tech Note 107 Electrical Tech Note 107 Biosystems & Agricultural Engineering Department Michigan State University Understanding the Construction Code Rules, Part 8 1 Based on the 2014 NEC and the 2015 MRC The State

More information

CONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA

CONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA American Electrical Institute 2014 PART 2 83 CONTINUING EDUCATION FOR OREGON ELECTRICIANS AMERICAN ELECTRICAL INSTITUTE PO Box 31131 Spokane, WA 99223 www.aeitraining.com 84 PART 3 American Electrical

More information

JOINT CODE INTERPRETATION

JOINT CODE INTERPRETATION JOINT CODE INTERPRETATION May 2018 Mobile/Temporary Cooking Equipment 14-FCI-003 Page 1 of 8 PURPOSE The purpose of this interpretation is to assist owners/operators of mobile cooking operations and safety

More information

Bulletin An application for inspection not required Rule 2-005

Bulletin An application for inspection not required Rule 2-005 Bulletin 2-3-16 An application for inspection not required Rule 2-005 Scope Issued May 2016 Supersedes Bulletin 2-3-15 (1) Rule 2-005 - An application for inspection not required (Basic exemption) (a)

More information

Building Standards Advisory Promoting construction of safe, healthy, habitable buildings

Building Standards Advisory Promoting construction of safe, healthy, habitable buildings Building Standards Advisory Promoting construction of safe, healthy, habitable buildings Saskatchewan Amendments to the National Building Code 2015 In Canada, provincial and territorial governments have

More information

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS 2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin June 2018 CEC-18 [rev-13] Page 1 of 6 CANADIAN ELECTRICAL CODE SUBJECT: Section 18 Hazardous locations Rule 18-006 Locations containing an explosive gas atmosphere

More information

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are

More information

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...

More information

Red Deer. AMA Regional Meeting. Electrical, Plumbing, Gas, Private Sewage, Building and Fire

Red Deer. AMA Regional Meeting. Electrical, Plumbing, Gas, Private Sewage, Building and Fire Red Deer AMA Regional Meeting Electrical, Plumbing, Gas, Private Sewage, Building and Fire AGENDA 8:30 am Call to Order and Introductions Mike Hill, AMA 8:35 am 8:45 am AMA General Updates Joe Healy, AMA

More information

Fire Inspection Frequently Asked Questions

Fire Inspection Frequently Asked Questions Fire Inspection Frequently Asked Questions What authority does the City have to conduct Fire Inspections? Kirby Fire Marshal conducts fire/safety inspections based on a Fire Code requirement that all commercial,

More information

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017 Interim Amendments to Ontario s 2012 Building Code Retirement Homes August 17, 2017 Notice This presentation is intended for general information purposes only. It is not intended as legal or technical

More information

CHANGES TO THE TEXT OF THE 2010 CODE BOOKS

CHANGES TO THE TEXT OF THE 2010 CODE BOOKS The State Uniform Fire Prevention and Building Code (the Uniform Code) includes the publications that are incorporated by reference in Parts 1220 to 1227 of Title 19 of the New York Codes, Rules and Regulations

More information

Fire Sprinklers Working Group Final Report

Fire Sprinklers Working Group Final Report Introduction The Building Act received Royal Assent on March 25, 2015. The Act aims to establish more consistent building requirements across British Columbia and create a more robust and modern building

More information

OFFICE of the FIRE COMMISSIONER. Recreational Vehicles Life Safety Requirements

OFFICE of the FIRE COMMISSIONER. Recreational Vehicles Life Safety Requirements OFFICE of the FIRE COMMISSIONER Recreational Vehicles Life Safety Requirements The Province of Manitoba Office of the Fire Commissioner has a responsibility to ensure that any recreational vehicle for

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY

More information

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: Manitoba Regulation 221/2015 and Manitoba Regulation 222/2015 DATE: MARCH 17, 2016 1. INTRODUCTION On April 1, 2016, new building and

More information

Installation Requirements for Models:

Installation Requirements for Models: 900 & 9100 Series Refrigerators Installation Requirements for Models: 9162 9163 9182 9183 962 963 982 983 WARNING Improper installation, adjustment, alteration, service, or maintenance can cause injury

More information

ONTARIO Electrical Safety Report. 10th Edition

ONTARIO Electrical Safety Report. 10th Edition ONTARIO Electrical Safety Report 10th Edition 2010 OESR vmesf1.0 Electrical Safety Authority 2012 Electrical Engineers and Consultants perhaps not understanding all of the applicable regulations for Mines

More information

Carbon Monoxide Detectors in New and Existing Buildings

Carbon Monoxide Detectors in New and Existing Buildings Technical Bulletin #18-001 February 2018 / 2017 OFC Carbon Monoxide Detectors in New and Existing Buildings Referenced Codes and Standards: OAC 1301:7-7-9(O); OFC 915 OAC 1301:7-7-11(A)(1); OFC 1101.1

More information

Auditing Association of Canada (AAC) Annual Conference North York, AMEC Environment & Infrastructure

Auditing Association of Canada (AAC) Annual Conference North York, AMEC Environment & Infrastructure Auditing Association of Canada (AAC) Annual Conference North York, 2013 AMEC Environment & Infrastructure The Role of the Fire Code in Compliance Auditing Peter Beukema, P. Eng., EP(CEA), EP(EMSLA) Senior

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

Fire Prevention Plan Program

Fire Prevention Plan Program Fire Prevention Plan Program Effective Date: Revision #: Reference Standard Purpose Occupational Safety and Health Administration (OSHA) standard, 29 CFR 1910.39 Subpart E, Fire Prevention Plan This procedure

More information

UNDERSTANDING ELECTRICAL SAFETY RISKS

UNDERSTANDING ELECTRICAL SAFETY RISKS UNDERSTANDING ELECTRICAL SAFETY RISKS The Electrical Safety Program at BC Safety Authority (BCSA) is responsible for overseeing the safety of electrical systems across British Columbia in accordance with

More information

Understanding Your Options: AFCI Protection and the 2015 CE Code

Understanding Your Options: AFCI Protection and the 2015 CE Code Understanding Your Options: AFCI Protection and the 2015 CE Code November 25, 2014 Eaton 2008 Eaton Corporation. All rights reserved. Classifying An Arc Fault Operational Arcs - occur in a properly functioning

More information

Request For Quotations. For The. Fire Sprinkler Retrofit Program For Licensed Small Or Rural Retirement Homes. October 11, 2017

Request For Quotations. For The. Fire Sprinkler Retrofit Program For Licensed Small Or Rural Retirement Homes. October 11, 2017 Request For Quotations For The Fire Sprinkler Retrofit Program For Licensed Small Or Rural Retirement Homes October 11, 2017 1 Table of Contents Introduction... 3 Retirement Home Information... 3 RFQ Overview...

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS CHAPTER 23.45 LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS 23.45.100 Local Amendments To The International Fire Code, 2000 Edition 23.45.102.1 Construction and Design Provisions

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?

More information

NFPA 70E Elevates Safety. with Heightened Risk Awareness

NFPA 70E Elevates Safety. with Heightened Risk Awareness NFPA 70E 2015 Elevates Safety with Heightened Risk Awareness Next Page NFPA 70E 2015 Elevates Safety with Heightened Risk Awareness: Significant Changes Since 2012 Compel Updated Electrical Safety Training

More information

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE Summary Guadalupe County requirements for the Permit Issuance and safe operation of a Temporary Special Amusement Occupancy. PURPOSE To

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

TOM BURNS, PLANNING DIRECTOR

TOM BURNS, PLANNING DIRECTOR ~~ 0 173 COUNTY OF SANTA CRUZ August 4,2005 PLANNING DEPARTMENT 701 OCEAN STREET, qth FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 TOM BURNS, PLANNING DIRECTOR Agenda:

More information

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1 IFC Significant Changes from the 2009 to the 2015 Edition Tier 1 Several medical care definitions were created and revised in Chapter 2 of the 2012 IBC, as well as through the occupancy descriptions, and

More information

Please make yourselves familiar with the changes and start implementing them immediately so you can be better prepared for June 30 th, 2018.

Please make yourselves familiar with the changes and start implementing them immediately so you can be better prepared for June 30 th, 2018. Included below are the top fifteen changes within the 2018 Canadian Electrical Code (CEC). Here in Newfoundland and Labrador, the 2018 Code was adopted as of January 1 st, 2018 and will be enforced as

More information

IRC - BUILDING - ELECTRICAL - ELECTRICAL TAC

IRC - BUILDING - ELECTRICAL - ELECTRICAL TAC IRC - BUILDING - ELECTRICAL - ELECTRICAL TAC W A R N I N G Copyright Notice: This document has been reproduced solely for considering proposed changes to the Florida Building Code with the permission of

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

BUILDING CODE INTERPRETATION

BUILDING CODE INTERPRETATION BUILDING CODE INTERPRETATION November 2017 14-BCI-009 Page 1 of 6 FIRE ALARM AND FIRE SUPPRESSION SYSTEM VERIFICATION AND TESTING CERTIFICATES PURPOSE This STANDATA has been developed to give municipalities

More information

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document

More information

FIRE DEPARTMENT PERMIT GUIDELINES

FIRE DEPARTMENT PERMIT GUIDELINES FIRE DEPARTMENT PERMIT GUIDELINES SPECIAL EVENT PUBLIC ASSEMBLY (EACH EVENT) The Special Event Assembly Permit is applicable to any public event, exhibit space, booth, festival or any other similar event

More information

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing

More information

IMPORTANT SAFETY INFORMATION:

IMPORTANT SAFETY INFORMATION: Owner s Manual Model DS7420 DS7425DLX IMPORTANT SAFETY INFORMATION: Always read this manual first before attempting to install or use this stove. For your safety, always comply with all warnings and safety

More information

PORTABLE FIRE EXTINGUISHERS

PORTABLE FIRE EXTINGUISHERS FIRE CODE BULLETIN February 2018 14-FCB-002 Page 1 of 6 PORTABLE FIRE EXTINGUISHERS PURPOSE This bulletin is to clarify the intent of the Alberta Fire Code 2014 (AFC 2014) and NFPA 10, Standard for Portable

More information

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE

More information

Occupational Health and Safety. Radiation Protection Regulation Amended in 2013 Highlights

Occupational Health and Safety. Radiation Protection Regulation Amended in 2013 Highlights Occupational Health and Safety Bulletin Radiation Protection Regulation Amended in 2013 Highlights The Radiation Protection Amendment Regulation came into effect on July 25, 2013. This Regulation was made

More information

Building and Grounds Self-Inspection Program

Building and Grounds Self-Inspection Program www.alterisus.com Building and Grounds Self-Inspection Program Each building and its accompanying grounds should be inspected at regular intervals, ideally on a monthly or quarterly basis. In this way,

More information

Secondary Suites. Guidelines for the construction of Accessory Secondary Suites in the City of Abbotsford August

Secondary Suites. Guidelines for the construction of Accessory Secondary Suites in the City of Abbotsford August Secondary Suites Guidelines for the construction of Accessory Secondary Suites in the City of Abbotsford August 2015 PLANNING & DEVELOPMENT SERVICES Building Permits & Licences 1st Floor, 32315 South Fraser

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L )

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L ) NCEHSA Conference Carbon Monoxide Detector Regulations for Lodging Establishments (S.L. 2013-413) 1 Purpose of this session The purpose of this session is to review the provisions of Session Law 2013-413

More information

Fire Inspection FAQ s

Fire Inspection FAQ s Humble Fire Marshal s Office 110 W. Main St., Humble, Texas, 77338 Phone- (281) 446-4928 Fax- (281) 446-3960 Fire Inspection FAQ s 1. What version of the International Fire Code has the City of Humble

More information

2014 Alberta Building Code. Part 9 changes relating to Smoke and CO Alarms

2014 Alberta Building Code. Part 9 changes relating to Smoke and CO Alarms 2014 Alberta Building Code Part 9 changes relating to Smoke and CO Alarms 9.32.3.9 Carbon Monoxide Alarms What has not changed: 4) & 6) In a residential occupancy containing a fuel burning appliance or

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

Advisory Brief to Prince George City Council On the Matter of Bylaw 8727, 2013, Fire Protection and Emergency Response Bylaw

Advisory Brief to Prince George City Council On the Matter of Bylaw 8727, 2013, Fire Protection and Emergency Response Bylaw Advisory Brief to Prince George City Council On the Matter of Bylaw 8727, 2013, Fire Protection and Emergency Response Bylaw November 11, 2013 John Leech, AScT, CAE Executive Director Applied Science Technologists

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin February 2014 CEC-18 [rev-11] Page 1 of 9 CANADIAN ELECTRICAL CODE SUBJECT: Section 18 Hazardous Locations Rule 18-006 Division of Class I Locations General For classification

More information

Fire Prevention Plan Program Prepared by: Allied Insurance Brokers, Inc.

Fire Prevention Plan Program Prepared by: Allied Insurance Brokers, Inc. Fire Prevention Plan Program Prepared by: Allied Insurance Brokers, Inc. Commonwealth Scaffold, LLC Effective Date: 12/14/2012 Revision Number: 1 TABLE OF CONTENTS 1. Fire Prevention Plan Program 1 2.

More information

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION

More information

IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator

IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator 215 E Seventh Street; Des Moines, IA 50319 Email: sfmlicense@dps.state.ia.us APPLICATION CHECKLISTS (EFFECTIVE IMMEDIATELY) 1. DO NOT mail

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

Family Foster Home Fire Safety Evaluation Checklist Instructions

Family Foster Home Fire Safety Evaluation Checklist Instructions Family Foster Home Fire Safety Evaluation Checklist Instructions Please read these instructions prior to commencing your inspection. This checklist is provided to specific Foster Family Homes for the purpose

More information

Commercial Renovation Investigation Program

Commercial Renovation Investigation Program TM News, Views and Updates from the Electrical Safety Authority Summer 2018 Commercial Renovation Investigation Program 445 investigations completed from Oct 2017 Mar 2018 2 regions Durham + Ottawa 260

More information

Get it Right the First Time Avoid These Commonly Cited Errors

Get it Right the First Time Avoid These Commonly Cited Errors May 2014 Get it Right the First Time Avoid These Commonly Cited Errors By Mark Earley and Mark Hilbert Copyright 2014 National Fire Protection Association. All rights reserved. Good electrical contractors

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1. EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-003 EFFECTIVE 06-03-2009 PURPOSE To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified

More information

Carbon Monoxide Alarms Smoke and Carbon Alarms Upgrade Requirements for Single and Two Family Dwellings

Carbon Monoxide Alarms Smoke and Carbon Alarms Upgrade Requirements for Single and Two Family Dwellings Planning and Building Department INFORMATIONAL GUIDE Updated: 2017 July 31 Smoke Alarms This brochure explains the requirements for smoke alarms in new or renovated buildings. It provides information to

More information

CFAA Alberta Technical Seminar 2010

CFAA Alberta Technical Seminar 2010 CFAA Alberta Technical Seminar 2010 Kevan D. Jess Chief Fire Administrator Government of Alberta Fire Alarm Requirements AFC 2006 & ABC 2006 AFC 2006 deals with existing buildings, particularly maintenance

More information

FIRE PREVENTION AND PROTECTION*

FIRE PREVENTION AND PROTECTION* Chapter 30 (Replaced old ordinance September10, 2012) FIRE PREVENTION AND PROTECTION* * Cross References: Buildings and building regulations, ch. 14; environment, ch. 26; manufactured homes and trailers,

More information

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal M.S. Montgomery Fire Marshal September 1, 2010 This document describes rules changes affecting the operation and fire safety in foster homes licensed and regulated by the Texas Department of Family and

More information

From Your Building Inspector

From Your Building Inspector The Sound of Safety What is the most important thing to remember when installing a smoke alarm or carbon monoxide alarm? Location, location, location! Smoke Alarm Safety: Install at least one smoke alarm

More information

OPERATIONAL GUIDELINE. Office of the Fire Commissioner O.G.# Revision #1 TITLE: ISSUING ORDERS Page 1 of 8

OPERATIONAL GUIDELINE. Office of the Fire Commissioner O.G.# Revision #1 TITLE: ISSUING ORDERS Page 1 of 8 TITLE: ISSUING ORDERS Page 1 of 8 PURPOSE: SCOPE: POLICY: To ensure a consistent approach to the issuance of Province fire orders. All Local Assistants to the Fire Commissioner. All orders shall be dealt

More information

NFPA Talking Points on NFPA 1 Fire Code update to the 2015 Edition:

NFPA Talking Points on NFPA 1 Fire Code update to the 2015 Edition: NFPA Talking Points on NFPA 1 Fire Code update to the 2015 Edition: The legislative study committee established by HB 427 report dated November 1, 2016 reads Members support uniformity for the most fundamental

More information

BY-LAW NO AND WHEREAS Council has, by By-law Number adopted a Forest Fire Management Plan for the Town of Bracebridge;

BY-LAW NO AND WHEREAS Council has, by By-law Number adopted a Forest Fire Management Plan for the Town of Bracebridge; A BY-LAW OF THE CORPORATION OF THE TOWN OF BRACEBRIDGE TO REGULATE THE SETTING OF FIRES AND TO SET OUT PRECAUTIONS TO BE TAKEN WITH OPEN AIR FIRES, BARBECUES AND GAS FIRED OUTDOOR APPLIANCES WHEREAS, Section

More information

Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014

Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014 Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014 Philip Rizcallah, P. Eng. NRC-IRC Canadian Codes Centre Presented by Stan Dueck CRBO Overview Where are the major

More information

BYLAW # A BYLAW RESPECTING OUTDOOR FIRES IN THE TOWN OF DIGBY

BYLAW # A BYLAW RESPECTING OUTDOOR FIRES IN THE TOWN OF DIGBY BYLAW # 2018-04 A BYLAW RESPECTING OUTDOOR FIRES IN THE TOWN OF DIGBY A By-law for the Town of Digby, in the Province of Nova Scotia, to provide for the regulation of outdoor fires and nuisance caused

More information

FHCA 2014 Annual Conference & Trade Show

FHCA 2014 Annual Conference & Trade Show FHCA 2014 Annual Conference & Trade Show CE Session #5 Preparing for the Upcoming Code Changes Don t Look Back Tuesday, July 8 8:15 to 9:15 a.m. Canary 3 Operations/Quality Improvement Upon completion

More information

Ontario is taking another step to keep families and homes in Ontario safe by making carbon monoxide alarms mandatory in all residential homes.

Ontario is taking another step to keep families and homes in Ontario safe by making carbon monoxide alarms mandatory in all residential homes. Carbon Monoxide Please be advised that the Chief Fire Official has the authority to enforce the Fire Code within his or her jurisdiction and should be contacted prior to implementing any opinion expressed

More information

How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers

How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers AFCI and GFCI Homeowner s Guide How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers Congratulations on the purchase of your new home. This guide will help you understand

More information

Safety Code. Update on the 25th edition of the Ontario Electrical Safety Code p.4. What s Inside. Ontario Electrical.

Safety Code. Update on the 25th edition of the Ontario Electrical Safety Code p.4. What s Inside. Ontario Electrical. News, Views and Updates from the Electrical Safety Authority Winter 011 Safety Code Update on the 5th edition of the Ontario Electrical Safety Code p.4 1-877-ESA-SAFE WWW.ESASAFE.COM What s Inside Ontario

More information

South Elgin & Countryside Fire Protection District

South Elgin & Countryside Fire Protection District MARY VAN WINKLE President RONALD R. BOHLMAN Secretary JEFFREY A. SPEYERS Treasurer South Elgin & Countryside Fire Protection District 150 WEST STATE STREET SOUTH ELGIN, ILLINOIS 60177 Business Phone (847)

More information

Habitability Guidelines

Habitability Guidelines Habitability Guidelines for Relocated Manufactured Homes dced.pa.gov/mh @PADCEDnews Purpose The purpose of these habitability guidelines is to provide a reasonable level of assurance that the relocated

More information

A2L Refrigerants. Objectives 14/09/2017

A2L Refrigerants. Objectives 14/09/2017 A2L Refrigerants RMC HRAI Quebec City August 17, 2017 Greg Scrivener greg.scrivener@colddynamics.com Objectives 1) Learn the current state of codes and standards in relation to A2L refrigerants 2) Examine

More information

Mt. Crested Butte Code

Mt. Crested Butte Code Mt. Crested Butte Code Chapter 8 FIRE PREVENTION AND PROTECTION ARTICLE I. IN GENERAL Note * Editor s note Ord. No. 12-05, 1, adopted October 2, 2012, repealed former Ch. 8, Art I in its entirety, and

More information

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE. CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE. CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE. INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE. CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE. INSTALLATION AND OPERATING INSTRUCTIONS CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA

More information

Division of Fire Safety

Division of Fire Safety STATE OF NEW HAMPSHIRE DEPARTMENT OF SAFETY John J. Barthelmes, Commissioner Division of Fire Safety Office of the State Fire Marshal J. William Degnan, State Fire Marshal Office: 110 Smokey Bear Boulevard,

More information

Recent Revisions and Proposed Key Changes to Fire Code

Recent Revisions and Proposed Key Changes to Fire Code Recent Revisions and Proposed Key Changes to Fire Code 2014 CFAA Presentation Kim Bailey - Office of the Fire Marshal and Emergency Management New Section 9.7 Buildings with a Care Occupancy or Retirement

More information

FEO Initiation Devices Dean McLellan

FEO Initiation Devices Dean McLellan FEO Initiation Devices Dean McLellan Enforcement Protocol 1. TSSAct 2. Ontario Regulation 209/01 3. Code Adoption Document (CAD) 4. Director s Orders 5. Applicable Code 1. Sub Codes (NBCC, CEC) A17/B44

More information

SCHULTE & ASSOCIATES Building Code Consultants 3500 Creighton Road, K5 Pensacola, FL

SCHULTE & ASSOCIATES Building Code Consultants 3500 Creighton Road, K5 Pensacola, FL SCHULTE & ASSOCIATES Building Code Consultants 3500 Creighton Road, K5 Pensacola, FL 32504 fpeschulte@aol.com 847.312.7617 FIRE PROTECTION HISTORY-PART 122: 1958 (SPRINKLER SYSTEM HYDRAULICS/WILBUR STUMP)

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

Building Self-Inspection Program

Building Self-Inspection Program Building Self-Inspection Program www.tridentinsurance.net Lines of Business: Property, General Liability, Worker s Compensation, Public Official Liability Risk Control Strategy/Key Issues: Reduce physical

More information

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification Electrical Engineering Guide for Determining Electrical Area Classification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice

More information

Ontario Homes for Special Needs Association

Ontario Homes for Special Needs Association Ontario Homes for Special Needs Association Response to the Ministry of Community Safety and Correctional Services Consultation on Fire Safety for Vulnerable Residents in Ontario March 28, 20011 For more

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-16-871 Application No. 2002-07 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.2.4.20.(2)

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program Developed by: The Office of Environmental Health and Safety June, 2010 Table of Contents Introduction 3 Scope..3 Definitions.3-5 CSU Electrical Shop...5 Responsibilities.5-6 Employees.....5

More information

Building Standards Division. Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems

Building Standards Division. Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems Building Standards Division Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems Crown Copyright 2015 Produced by the Buildings Standards Division February 2015 Version

More information

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES Established 1949 FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES The following are guidelines for new development. Any submitted plans must comply with these guidelines,

More information

Questions for the HFD regarding Bill 69, Evaluation Worksheet for High-Rise Residential Buildings User s Guide ( New User s Guide or NUG )

Questions for the HFD regarding Bill 69, Evaluation Worksheet for High-Rise Residential Buildings User s Guide ( New User s Guide or NUG ) Questions for the HFD regarding Bill 69, Evaluation Worksheet for High-Rise Residential Buildings User s Guide ( New User s Guide or NUG ) 1. Condo and co-op associations believed that the Life Safety

More information