1 MSP1000 Motor Protection Relay I N S T R U C T I O N & M A I N T E N A N C E M A N U A L

2 TABLE OF CONTENTS 1. Introduction Description of Components MSP1000 Specifications MSP1000 List of Connections MSP1000 Protection Unit 115V / 230V MSP1000 Monitor Unit Handling and Storage Installation Planning Installation Operation Front Panel Controls Indicator Lights Trip / Start Indicator LED Alarm Indicator LED Readings Settings Faults Internal Fault Codes Protection Unit Controls Reset Pushbutton Trip Indicator LED Alarm Indicator LED System OK Indicator LED Addressed Indicator LED Maintenance Typical Installation Drawings DOL Reversing Starter Fig CE Marking and the EMC Directive The EMC Requirements Installation EMC requirements Low Voltage Directive Machinery Safety Directive 20 Appendix 1: General Information on Temperature Monitoring 21 Technical specification 22 2

3 1. INTRODUCTION The MSP Systems bv MSP1000 Motor protection relays are designed to protect electrical motors and connected loads from possible damage whilst minimizing the possibility of erroneous tripping and providing full information to the operator. The MSP1000 Motor protection relay is designed to protect the motor from the following occurrences. Thermal overload and cooling problems by RMS current measurement, thermistor monitoring, true thermal models and programmable starting conditions. Mechanical overload by stall protection as well as the thermal overload model. Electrical fault conditions of short circuit, phase imbalance, earth fault and phase reversal. The MSP1000 Motor protection relay may be configured to control Direct on Line (DOL), Direct on Line Reversing (DOLR), 2 Speed, Star-Delta, Auto-Transformer, Soft Start and Variable speed drives. Total protection means system protection not just the motor Up to 99A Full Load current can be monitored directly with the 16mm internal diameter Current transformers which are an integral part of the Protection Unit whilst above this various configurations of CTs can be provided. Earth Leakage current can be monitored either directly with the integral phase Current transformers or for more accurate requirements a Core Balance Current Transformer (CBCT) can be connected. The Monitor Unit provides a local Interface to the operator and can display percentage load current, phase current, unbalance, earth fault current, reserve thermal capacity & remaining time to trip. User configurable settings can be monitored. Alarms and trips can be reset locally or remotely. The MSP1000 Motor protection relay can be configured by PC over a RS232 Serial Link or alternatively via a MSP Gateway Device. 1.1 Description of components The MSP1000 Motor protection relay consists of a Protection unit and an optional Monitor unit. The units are intended for mounting in Motor Control Centers. 3

4 Dimensional Sizes are as follows. Relay dimensions MSP1000 L x W x H = 154 x 74 x 96 mm (6.1 x 2.0 x 3.7") Cable hole diam.: 16mm (.63") Mounting: DIN rail / 2 screws Size L x W x D = 130 x 90 x 42 mm (5.1 x 3.5 x 1.6") Panel cutout 121 x 81 mm (4.8 x 3.2") 4

5 1.2 MSP1000 Specifications Specifications at 25 C unless otherwise noted. Phase current input circuits Max input current: Not limited by the unit; cables pass through the 16mm (0.63") inner diameter openings In the unit, without physical connections; CTs are built in. Full scale input current: >1100% of Inom setting Minimum detection level: <1.5% of Inom setting Setting range: A using integral CTs; 5A-99.9kA/5A using external CTs. Fundamental frequency: Hz Method of measurement: True RMS up to 15kHz within 3dB Accuracy above 20Hz: Greatest of 1% of reading and 0.5% of Inom Drift: <1% per 10 C change Low frequency accuracy: -1% at 10Hz; -2% at 8Hz; -3.5% at 6Hz; -7% at 4Hz Burden (each phase): <0.04mOhm; <0.004VA at 10A; <0.4VA at 100A Isolation voltage: Motor status detection: 1000VRMS continuous; 2000VRMS 1 min. Stopped when current <4% of Inom Starting after current went from <4% to >5% of Inom. Running when current stays 4-100% of Inom Note: Interposing CTs may be low cost Instrument Class to BS7626 / IEC158 because of the very low burden. Earth fault input circuit (core balance) CBCT ratio: 500:1 Max CBCT primary current: 200A continuous; 350A 1 minute Full scale CBCT primary current: >17A Minimum primy detection level: <15mA Fundamental frequency: Hz Method of measurement: True RMS up to 15kHz within 3dB Accuracy above 20Hz: Greatest of 1% of reading and 10mA, excluding accuracy of the core balance CT Drift: <1% per 10 C change Low frequency accuracy: -1% at 10Hz; -2% at 8Hz; -3.5% at 6Hz; -7% at 4Hz Burden to CBCT: <2Ω resistive Wires: mm2, AWG Terminal numbers: 21 and 22; 23 and 24 must be shorted if core balance CT is used There are standard 500:1 core balance transformers with various diameters and split core designs with 2% accuracy over full temperature range. 5

6 Overload protection Type: Fully programmable overload protection curve with true RMS current measurement & thermal model Trip time formula: D(t) = 35.5 T6In ln i2(t) - [1-RC(t)] i2(t) - 1 This is a first order model in which: D(t) = trip time at time t i(t) = motor current normalized with respect to Inom at time t; 1=100% RC(t) = reserve capacity at time t; 1=100% T6In = thermal capacity or locked rotor setting in seconds (at 6xInom) Trip time accuracy: Thermal memory i>1.5 greatest of 5% and 300msec i>2 greatest of 2.5% and 300msec i>4 greatest of 1% and 300msec The state of the thermal model will be retained in non-volatile memory during Power down. When power is restored the thermal model will revert to the pre-power down condition. All trips and alarms are also memorized. Protection functions other than overload Short delay range: Short delay accuracy: Medium delay range: Long delay range: Delay increase function: Delay increase (msec): msec (short circuit, earth fault And stall only) +20/-0msec, excluding delay due to waveshape of current 1-30sec +0/-125msec 1-30min +0/-7sec IACTUAL / ILEVEL > ILEVEL is the current level set for the associated function. Phase reversal detection time 2 cycles 6

7 Thermistor input Hot trip resistance: /-5% Cold reset resistance: /-5% Short circuit resistance: <45Ω +/-20% 1) Open circuit resistance: 1.5MΩ +/-20% 1) Thermistor type: PTC according to IEC specifications Wires: mm2; AWG Terminal numbers: 27 and 28 Purpose: Thermistor The thermistor input will accept an input from up to six 250 ohm PTC type thermistors embedded in the motor windings 1) If wire fault recognition is switched off, then a short circuit condition is interpreted as a cold thermistor and an open circuit condition is interpreted as a hot thermistor. Contact inputs Contact type: Voltage between input terminals: Max loop resistance: Wires: Terminal numbers: Purpose Remote Reset: Relay contacts Contact type: Rating (resistive): UL/CSA rating: Isolation voltage: Expected life: Wires: Terminal numbers: Purpose Alarm & Trip Relays: Dry contact 5Vdc through 26kΩ 1kΩ (sum of leads resistances plus contact resistance) mm2; AWG (signal) and 26 (return); Remote reset The remote reset input will accept a normally open voltage free contact. It will effect a reset of any trip or alarm condition which is configured for manual reset. 1 NO (form A) + 1 NC (form B) contact Max switching power 1250VA, 150W max switching voltage 380Vac, 125Vdc max switching current 5A 5A 1/6HP 125, 250Vac; 5A 30Vdc 30W max: 1A 30Vdc, 0.24A 125Vdc 1000VRMS continuous; 1500VRMS 1 minute >3x 104 operations mm2; AWG and 12 NO trip relay 13 and 14 NC trip relay 15 and 16 NO alarm relay 17 and 18 NC alarm relay Provides control and alarm functions as configured by the software 7

8 PC (programmer) interface E1A standard: Output voltage: Max cable length: RS232D -5/+5Vdc max 15m Local Datalink interface to MSP Gateway Device Output voltage: 10Vdc max Datalink cable type: Low cost two wire cable (e.g. one twisted pair with optional shield, or coax) Max length of datalink cable: 750m Max DC resistance of cable (sum of signal and return wires): 100Ω Max capacitance of cable: 50nF Max number of systems connected to one MSP Gateway Device 12 Isolation voltage 1500VRMS continuous Inter-unit interfaces Output voltage: Max total cable length: 7Vdc max 10m Control voltage input Ranges: Vac or Vac -20/+10% Under voltage tolerance: -30% 1 second; -70% 50msec Frequency: 50-60Hz Power requirement: 10VA max Isolation voltage: 1000VRMS continuous; 1500VRMS 1 minute Wires: mm2; AWG Terminal numbers: 1 (earth), 2 (neutral) and 3 (line) Environment Operating temperature: Storage temperature: Humidity: Sealing: Noise immunity (EMC): -10/+60 C ambient -30/+70 C ambient 30-95%, non condensing IP54B (Monitor Unit) IP20 (Protection Unit) In conformity with BS EN & BS EN Vibration: In conformity with IEC In conformity with IEC

9 1.3 MSP1000 List of connections MSP1000 Protection Unit 115V/230V For all interconnections employ instrumentation wiring practices 'DISPLAY' 'OPTIONS' 'PC LINK' Connects to a MSP-1000 Monitor Unit. For future connections Optionally connects either temporarily to a programmer PC (RS232), or permanently to the MSP Gateway Device. In the latter case configuration can be achieved by connecting the programmer PC to the Gateway Device. 1, 2, 3 Connect 1 to earth. This should be earthed to the rear mountingplate or DIN rail immediately adjacent to the side of the unit. Connect 2 to Neutral supply. Connect 3 to Line supply. See part numbers for supply voltage. Use isolated stranded copper wire mm2, AWG , 12 NO contact of trip relay (power-off state = open) 13, 14 NC contact of trip relay (power-off state = closed) The relay can be set for failsafe and non-failsafe operation. It must be wired into the motor's start/stop logic such that the motor stops when The relay is operated, and cannot be restarted until the relay is reset. Use isolated stranded copper wire mm2, AWG , 16 NO contact of alarm relay (power-off state = open) 17, 18 NC contact of alarm relay (power-off state = closed) The relay can be set for failsafe and non-failsafe operation. It can optionally be used to generate any sort of action the user finds useful In case of events designated by the programmer PC to be an'alarm'. Use isolated stranded copper wire mm2, AWG

10 21,22 If a Core Balance Current Transformer (CBCT) is used to measure 23,24 Current flowing to earth, it must be connected to terminals 21 and 22, Using twisted pair cable, preferably shielded, mm2, AWG The shield must be connected to instrument earth at either end of the cable. Terminals 23 and 24 must be connected together in this case. The length of the cable is limited by its resistance; the resistance must be low enough not to cause saturation of the CBCT at the maximum current level one wants to be able to measure (this figures limited to 17A, since that is the full scale value of the system). 25, 26 Input for an optional remote reset push button (NO). Use wires mm2, AWG ; for runs longer than 2m twisted pair. Length is not explicitly limited, except by cable resistance (max 1kΩ). 27, 28 Input for an optional thermistor or string of max 6 thermistors. Use twisted pair wire, mm2, AWG Length is not explicitly limited, except by cable resistance (max 20Ω if short circuit detection is required, else max 100ê) MSP1000 Monitor Unit For all interconnections employ instrumentation wiring practices. This unit has only one outlet on the back side. Use cable assembly according to drawing 1 to connect to a MSP-1000 Protection Unit. 10

11 2. HANDLING AND STORAGE Units should be stored in an temperature between -30 C and 70 C. Unless mounted the units should not be removed from their original packaging. 3. INSTALLATION 3.1 Planning In order to avoid the greatest degree of protection from spurious electrical signals and comply with EMC requirements units should be mounted in a metallic enclosure suitably earthed and with the door also bonded to earth according to good electrical practice. The maximum cable size that can be accommodated directly in the current transformer (CTs) apertures is 16mm per phase. Full load current (I-nominal) setting range: One model covering the range of 1.6 to 10,000Amp (Inom). Using../5 CT s Inom range Step CTs A 0.01 A Integral A 0.1 A Integral or External A 1 A External KA 0.01 KA External KA 0.1 KA external NOTE: Interposing CTs may be low cost Instrument Class (IEC158/BS7626) because 11

12 Earth leakage monitoring can be set to an accuracy of between 3% and 30% of actual running current using the integral CTs, for greater sensitivity than this an external Core Balance Current Transformer (CBCT) can be used. The MSP1000 will then be capable of being set in the range of 0.1 to 10A of actual Ground Fault current. The ratio of the CBCT is 500:1. A range of CBCTs matched to the MSP1000 can be supplied which also include split core types. The MSP1000 Motor protection relays are factory set for 115 or 230 nominal control voltages. Should the wrong control voltage have been ordered then special instructions can be given to alter the control voltage. 3.2 Installation a. The Protection Unit should be mounted on a standard DIN mounting rail or Alternatively directly on a backplate by means of the 2 corner fixings. Orientation of the Protection Unit is not critical. Note: all cables should be run adjacent to the metal surfaces and not suspended freely in mid-air. b. The Control Voltage at 115V or 230V should be attached to terminals 2 & 3. The 115 or 230V supply live and neutral conductors to the Protection Unit should be run side-by-side directly to the units. The return circuit must always follow the path of the supply circuit and not be looped around to the other components before returning. c. The incoming supply earth should be directly bonded to the metal enclosure by a short lead (no longer than 160mm) and a minimum cross section of 1.5mm2 (AWG16). d. The earth connection to terminal 1 should be taken directly to the DIN rail or the metal backplate adjacent to the Right hand side of the Protection Unit. e. The typical system configuration diagrams for MSP1000 connections are included in Chapter 6. f. If the full load motor current is between A the MSP1000 can be used as a stand-alone unit with the motor cable passing through the 16mm (0.63") diameter holes in the unit. If the motor current is between 5-10,000Amp, or cables are of a diameter greater than 16mm interposing CTs can be used. See figure 5 for connections. g. If required connect thermistor units (max. 6 in one line) using screened twisted Pair cable, connected to terminals 27 and 28. h. If required connect the Core Balance Current Transformer to terminals 21 and 22, with twisted pair cable. Connect a short wire link between terminals 23 and 24 if the CBCT is fitted. 12

13 i. The trip relay volt free contacts (NO) should be connected into contactor control circuit from terminals 11 and 12 and if required the (NC) volt free contacts are available at terminals 13 and 14. This is on the basis that the relay is to be set up as failsafe. j. If required the Remote reset can be connected between terminals 25 and 26 using twisted pair cable. k. The volt free contacts of the Alarm Relay can be connected between terminals 15 & 16 (NO) and 17 & 18 (NC). l. Install the MSP1000 monitor in the front panel if required. Use the cable provided (1.5m, 60") to connect the monitor unit to the MSP1000 Protection unit, if the supplied cable is not long enough a similar cable can be made up with a maximum cable length of 10 meters. Ensure that the cable is run in close proximity to metalwork and is spaced 30mm apart from control cables. m. Either connect the MSP1000 Unit permanently to a MSP Gateway device using the cable assembly as drawing 3 or alternatively make a temporary connection to a PC RS232 Serial port as shown in drawing 2. If a permanent connection is made to the MSP Gateway device then the unit can still be configured via the MSP Gateway device, by connecting the PC Programmer to this device. n. Power up the MSP1000 and Personal computer. Check that the "must flash" LED is flashing on the MSP1000 and that the front panels LCD is indicating. o. Install the Software on the PC. (see separate manual) 13

14 4. OPERATION 4.1 Front Panel Controls Indicator Lights Trip /Start Indicator LED The Trip/Start indicator will flash red during the Starting period of the motor. The Trip/Start indicator will be continuously lit red when a trip occurs and remain lit until (a) the reason for the trip is removed and (b) the trip is reset if manual reset was selected Alarm Indicator LED The Alarm indicator light will be continuously lit amber when an alarm occurs and will remain lit until (a) the reason for the trip is removed (b) the trip is reset if manual reset was selected Readings The following readings are available from the Display Panel. Successive presses of the "Readings" button will cycle round the reading from 0 to 11. If the button is depressed longer than 2 seconds the display reverts back to 0. 1: 86 Display showing percentage Full Load Current Flashing values are pre trip values Reading No. Display Notes 0: LOAD Load % Inom 0 to 2500% 1: PH 1 Current Phase 1 A to 9999A 0.01 to 99.99KA* 2: PH 2 Current phase 2 A to 9999A 0.01 to 99.99KA* 3: PH 3 Current Phase 3 A to 9999A 0.01 to 99.99KA* 4: U/B Unbalance % of load 0 to 200% 5: E/F CURRENT Earth fault current %Ph current 0 to 200% 6: E/F CURRENT Earth fault current Amps to (CBCT only) 0.1 to 99.9 (Spill only) 7: RESERVE CAPACITY Reserve thermal capacity% 0 to 100% (-999% Emergence reserve ) 8: TIME TO TRIP/RESET Time to trip at steadystate 1 to 9999 seconds 9: RUNNING HOURS Actual motor running hours 1 to 999,999 10: NO OF STARTS Number of starts 1 to 999,999 11:LAST START LOAD Last start load % Inom 10 to 2500% * Depends on CT ratio 14

15 4.1.3 Settings The following settings are available from the display panel. Successive presses of the "Settings" Button will cycle round the reading from 20 to 32. If the button is depressed longer than 2 seconds the display reverts back to 20. Settings can only be displayed, they cannot be altered except from the RS232 datalink. 20: 76 Typical display showing Inom current Amps Reading No. Display Notes 20: In Load Inom current Amps 1.6A to 99.9KA 21: U/B LIMIT Unbalance limit 3-40% 22: E/F LIMIT (SPILL) Eart fault limit (Spill connection) 3-30% 23: E/F LIMIT (CBCT) Earth fault limit (CBCT in use) to 10.0A 24: S/C LIMIT Short circuit limit % 25: STALL LIMIT Stall limit % 26: U/C LEVEL Under current level % 27: Tx6xIn Trip time at 6 times Inom 1-60 sec 28: RES CAP FOR START Reserve capacity for start 10-90% 29: RES CAP AT 100%LOAD Reserve capacity at 100% load 0-90% 30: COOLING REDUCTION MOTOR OFF Increase in cooling when motor Switched off 1-60 times 31: RES CAP ALARM LEVEL Reserve capacity alarm level 1-99% 32: TIME TO TRIP ALARM LEVEL Time to trip alarm level secs Faults (a) The Faults page is accessed by pressing the FAULT button. (b) If no Alarms or Trips are present then the two dashes are displayed. -- No Alarms or Trips present. (c) When an alarm or trip occurs an "A" is displayed at the extreme left of the display if the alarm or trip is automatically resettable on removal of fault. (d) The Fault code is a one or two character display as tabulated below. (e) Once current has been detected a colon and a "0" or a "1" will be displayed after the fault code as follows. code : 0 trip or alarm during starting code : 1 trip or alarm during running A 12:0 Thermistor Alarm during start-auto reset 15

16 (f) 8: 55 Once the fault has been reset and has cleared any remaining time to reset (as in the case of an overload of thermistor trip is automatically displayed as follows (the display reverts to the readings page) 55 seconds to auto reset Trip code Trip Event Applies trip And/or Alarm 1 Phase reversal T + A 2 Phase loss T + A 3 Unbalance T + A 4 Earth fault T + A 5 Short Circuit T + A 6 Stall T + A 7 Undercurrent T + A 8 Overload T + A 9-2 Low time to trip due to phase loss A 9-3 Low time to trip due to unbalance A 9-4 Low time to trip due to earth fault A 9-5 Low time to trip due to short circuit A 9-6 Low time to stall A 9-7 Low time to trip due to undercurrent A 9-8 Low time to trip due to overload A 10 Low reserve capacity A 11 Start inhibited T 12 Thermistor hot T + A 20 Thermistor o/c or s/c T + A 21 Current sensed while tripped A 22 Not addressed by Master (>5sec) T + A 30 Eeprom checkword error T + A 3.(x) Option (x) offline (Where (X) is the Option number 3 to 16) (x).0 Notes Internal Fault Codes (after power up only) Should the following messages be displayed at Power up then the unit should be returned to MSP Systems bv for attention. Condition Eeprom not accessible at power up Watchdog fail at power up Display Error.2 Error.3 16

17 4.1.6 Protection Unit Controls Reset Pushbutton The reset pushbutton when pressed will reset all the alarms and trips with the exception of those that have been set for Telemetry only reset Trip Indicator LED The trip indicator will be continuously lit red when a trip occurs and remain lit until the trip is reset if manual reset and also when the reason for the trip is removed Alarm Indicator LED The alarm indicator will be continuously lit amber when an alarm occurs and will remain lit until the alarm is reset if a manual reset is required and also when the reason for the alarm is removed System OK Indicator LED This indicator should continuously flash approximately twice a second whilst the MSP1000 is healthy and operating correctly. Should this fail then the unit should be returned to manufacturer for attention Addressed Indicator LED This indicator should flash intermittently when the MSP1000 is connected either to a MSP Gateway device or a PC the Datalink socket. 5. MAINTENANCE (a) (b) (c) There are no user maintainable parts in either the Display Unit or the Protection Unit. If the unit is not found to be operating correctly then it should be returned to the manufacturer for repair. Calibration checks can be conducted as per sections Commissioning. It is recommended that on an annual basis the exterior of the units and the associated cabling is checked for signs of damage such as chafing of cables and any possible signs of overheating, and any large deposits of dust which may affect the cooling of the units should be removed. 17

18 6. TYPICAL INSTALLATION DRAWINGS 6.1 DOL Reversing Starter Fig. 1 18

19 7. CE MARKING AND THE EMC DIRECTIVE 7.1 The EMC requirements Compliance with the EMC Directive is mandatory from January 1996 for almost all electrical equipment placed on the market or taken into service anywhere in the European Community. The directive applies to apparatus and systems but does not apply to components or installations. In order to CE mark the product the Manufacturer or European Agent has to make a 'Declaration of conformity'. Before a declaration of conformity can be made the product must have either (a) been formally tested to the Generic or Product Specific EMC standards as detailed in the Official Journal (OJ) of the European Community. or (b) a Technical Construction File must have been created which in turn must be approved by an DTI appointed 'Competent Body'. A technical construction file is a document where logic reasoning is used as a complement to laboratory testing. A technical construction file is used where the equipment is too large to be tested in a laboratory or where products exist in many similar versions. MSP1000 On the basis of the tests to the Generic Standards and the approval of the technical construction file a formal declaration of conformity to the EMC Directive is made. Consequently we will now be CE marking these products. 7.2 Installation Data pertinent to EMC requirements The following installation information is given throughout this manual in the appropriate sections: (a) The equipment should be mounted in a metallic enclosure suitably earthed and with the door also bonded to earth according to good electrical practice. (b) The incoming supply earth should be directly bonded to the metal enclosure by a short lead (no longer than 160mm) and a minimum cross section of 1.5mm2 (AWG16). (c) All cables should be run adjacent to the metal surfaces and not suspended freely in mid-air. (d) The 115 or 230V supply live and neutral conductors to the Protection Unit should be run side-by-side directly to the unit. The return circuit must always allow the path of the supply circuit and 19 not be looped around to other components before returning.

20 (e) The Protection Unit Earth terminal should be connected to the DIN rail or backplate earth at the immediate side of the unit. (f) The Data cable between the display unit and the protection unit should be run a minimum of 25mm apart from control cables to stop/start pushbuttons, etc. (g) Twisted pair cables should be used for the reset line. (h) Screened cables should be used for the thermistor input. (i) RS485 Datalink cables should be run externally in screened twisted pair cables. The cable should be earthed at the point of entry to the enclosure by means of a cable gland which clamps the cable earth screen through a full 360 degrees. 'Pigtail' earth connections must be avoided. Equipment is required to be installed in line with the above statements in order to comply with the EMC Directive. 8. LOW VOLTAGE DIRECTIVE In order to comply with the Low Voltage Directive the equipment must be (a) Safe. (b) Constructed in accordance with good engineering practice. (c) Safe when connected to the electricity supply system by the provision of protective earthing and other means. (d) Designed and constructed to conform with the principal elements of the Safety Objectives. Note that these safety objectives can be met by compliance with a Harmonised Standard. The Manufacturer or his agent must (e) Draw up and hold a Declaration of Conformity. (f) Compile and hold the Technical Documentation. (g) Have the 'CE' Mark affixed to the Product, its packaging, the instruction sheet or its guarantee certificate. 9. MACHINERY SAFETY DIRECTIVE The MSP1000 is not a machine in the sense of the machinery directive as it has no moving parts and the risks are mainly of electrical origin and covered by the Low Voltage Directive. 20

21 APPENDIX 1 : General Information on Temperature Monitoring Two types of temperature measuring sensors are catered for. Thermistor type (PTC) for use with the MSP overload relay and the PT100 for use with the RTD3 devices. PTC, direct to MSP1000 thermistor input. PT100 via RTD units, relay contact to thermistor input. Thermistor (PTC100) The Thermistor is a semi-conductor element with a temperature-dependent, nonlinear resistance characteristic, also known as a thermistor with Positive Temperature Coefficient (PTC). The resistance of the thermistor is relatively low at normal temperatures and remains nearly constant up to a critical value - referred to as Nominal Actuating Temperature (NAT) - which is selected for the class of winding insulation that is to be protected. At this point (NAT), even a slight increase in temperature will cause the resistance of the thermistor to rise to a value up to several hundred times its normal value when cold. The positive characteristic, i.e. resistance increase with temperature, achieves inherent safety; an open circuit of a thermistor or broken connection will have the same effect as an unsafe temperature. Platinum resistance thermometer (PT100) For precise temperature measurement the PLATINUM RESISTANCE THERMOME- TER, and in particular the ceramic bodied wire-wound platinum resistance temperature detector has the highest performance, when compared against "film" and "glassed" types of detectors. These devices are ideally suited for differential bearing temperature monitoring when suitably located in the bearing outer housing. The suppliers of the devices should be consulted for optimum results. 21

22 In current ranges AMP One model covering the range of 1.6 to 10,000A Using../5 Amp CT s Inom range Step CT s A 0.01 A Integral A 0.1 A Intergral or External A External ka 0.01 ka External ka 0.1 ka External NOTE: Interposing CT s may be low cost instrument class (IEC158/BS7626) because of the low burden. Thermal model T6x In Sec Locked rotor time in 1-60 sec in 0.1 sec steps at 6xIn Reserve cap at 100% load (hot curve) % Level settable % Res.cap for start % Settable reserve capacity level needed for motor start. Start is inhibited below this level. Switchable trip if reserve capacity falls below this level to always guarantee one start capability Res.cap alarm level % Warring level settable in % reserve capacity; switchable on/off Technical specifications Time to trip alarm level Sec Warn if remaining time before trip drops below level settable in sec Switchable on/off. Thermistor input Integrated with thermal model, S/C and O/C detection, switchable on/off. (RTD via separate add-on option). Stall limit % In Level programmable from %, steps 10%. Delay programmable from 50 msec-10 sec, steps 25 msec-1 sec. Switchable on/off, always trip if on. S/C Limit % In Level programmable from % of the set In in 10% steps. Delay 50 msec-10sec., steps 25 msec-1 sec. Excludes contactor trip inhibit. Contactor trip inhibit (class C coordination) Level programmable from % of the set In in 10% steps. If switched on it allows S/C to be cleared without opening contactor. Then trips contactor safely with indication of short circuit. Delay until current falls back below level. E/F Limit (Spill) %PH Level programmable from 3-30% of actual running load, in 1% steps. Delay settable 1-10sec steps 1 sec. Switchable alarm/trip. E/F Limit (CBCT) Amp Level settable 100 ma-10 A, in 100mA steps. Delay settable 50 msec-10 sec in 25 msec-1 sec. steps. Switchable alarm/trip. U/B Limit % Level settable 3-40%,in 1% steps. Delay settable, 1-30 sec in 1 sec steps, or 1-30 min., in 1 min. Steps. Switchable alarm/trip Phase loss (U/B>50%): Delay settable:1-30 sec, 1 sec steps; always trips. 22

23 Phase reversal Switchable trip/off. Phase rotation switchable ABC/BAC. Detection time:2 cycles. U/C Level % In Level settable % of In, in 1% steps. Delay programmable 1-30 sec, in 1 sec steps or 1-30 min, in 1 min Steps. Switchable on/off. Switchable trip or alarm. Memory Reserve capacity is memorized during power down. Running status, trip causes, pre-trip values, number of starts and running hours are all memorized. Trip relay 2 isolated circuits (NO/NC). 5A/380Vac, 1250VA, 150W. Selectable failsafe/non-failsafe. In non-failsafe selectable pulse tripping(shunt). Alarm relay 2 isolated circuits (NO/NC). 5A/380Vac,1250VA,150W Selectable failsafe/non-failsafe. Control Voltage 115 of 230 Vac (specify at order) Plug-in LCD display Shows 12 readings of actual values and 13 settings. Indication of trip and alarm causes. Reset button. Relay test capability. Cooling reduction motor off Specifies reduction in cooling due to stopped fan as compared to running fan. Nomally set at 3. Technical specifications External core balance CT input Use special low power zener protected core balance CT s. *round cores CB500-12/Z CB500-33/Z CB500-30/Z CB500-31/Z CB500-32/Z *Square cores CB5-1015SP/Z CB5-1020SP/Z CB5-1025SP/Z CB5-1030SP/Z CB5-1035SP/Z CB5-1040SP/Z Internal diameter 46 mm 65 mm 85 mm 145 mm 245 mm Inside dimension 100 x 150 mm 100 x 200 mm 100 x 250 mm 100 x 300 mm 100 x 350 mm 100 x 400 mm All these cores are also available at spit cores. Consult factory for other dimensions. Dimensions MSP1000 base unit (WxHxD) 154x74x96mm 3 cables holes round 16mm MPS1000 monitor (WxHxD) door cut-out Ambient temperature range -10 C-+60 C (operating) -50 C-+80 C (storage) 130x90x42mm 81x121mm 23

24 MSP1000 Motor Protection Relay HOLLAND Alectryon P.O. BOX AK Hengelo Holland Tel +31(0) Fax +31(0) Revised Febi 2009 RRINTED IN HOLLAND 24

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

EARTH LEAKAGE RELAY. User Manual - Issue 1.0 Earth Leakage Relay www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters EARTH

More information

HTC-915-CONT. Heat-Trace Control system

HTC-915-CONT. Heat-Trace Control system Heat-Trace Control system Product overview The Raychem HTC-915 system is a compact, full-featured microprocessor-based single-point heat-trace controller. The HTC-915-CONT provides control and monitoring

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1- DPR-45 User Manual V-2.0 (2..206) DPR-45 TEMPERATURE PROTECTION RELAY PT00 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT 9-50VDC SUPPLY DESCRIPTION DPR-45 is a precision unit designed for the temperature

More information

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) IRDH375_D00124_01_D_XXEN/07.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1 VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1. INTRODUCTION This manual contains information for the installation and operation and tuning of our Vertex VT10 series self-tuning

More information

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must

More information

Lodam Compressor Protection Module. Technical manual. Version 3.0 SE-G1

Lodam Compressor Protection Module. Technical manual. Version 3.0 SE-G1 Lodam Compressor Protection Module Technical manual Version 3.0 SE-G1 Contents 1. Read this first... 4 1.1. Reading instructions... 4 1.2. User manual... 4 1.3. Safety... 4 2. General... 5 3. Definitions...

More information

Programmable Output Dual Relay Quad Relay. (Trip Points, High Alarm, Low Alarm, Failsafe, Non-Failsafe, Normally Open, Normally Closed)

Programmable Output Dual Relay Quad Relay. (Trip Points, High Alarm, Low Alarm, Failsafe, Non-Failsafe, Normally Open, Normally Closed) June 2004 Description The universal SPA 2 Programmable Limit Alarm Trips provide on/off control, warn of unwanted process conditions, alarm on rate-of-change and provide emergency shutdown. Very versatile,

More information

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) T M 1 isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) Technical Bulletin NAE1012670 / 08.2013 isopv425

More information

Motogard. Over Temperature Protection System. Installation Instructions

Motogard. Over Temperature Protection System. Installation Instructions Motogard Over Temperature Protection System Installation Instructions Motogard General Information Motogard Over-Temperature Protection Systems provide immediate overheating protection for: motors, equipment

More information

Temperature Controllers

Temperature Controllers Model TEC-4100 1/4 DIN Model TEC-4100 1/4 DIN Temperature Controller Ordering Code: Power Input BOX 1 4 = 90-250 VAC 5 = 11-26 VAC / VDC TEC-4100- Configurable for 4 Programmable Outputs and NEMA 4X/IP65

More information

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15 with coupling device AGH675-7 and AGH675-7MV15 Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems) IRDH275BM-7_D00123_03_D_XXEN/01.2017 with coupling device

More information

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements Specifications COMMANDER 150 Universal Process Indicator High visibility 6-digit LED display the clearest view of your process status 0.1% measurement accuracy precise indication of process measurement

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

DTA. Motor thermistor relay. Benefits. Description

DTA. Motor thermistor relay. Benefits. Description DTA Motor thermistor relay Description DTA71 and are precise Motor thermistor monitoring relays. They can monitor up to 6 motor temperatures through the motor internal temperature. PTCs are connected in

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) T M 1 isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) Technical Bulletin NAE1012372 / 03.2015 isopv

More information

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required. TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.

More information

DGC-500 DIGITAL GENSET CONTROLLER

DGC-500 DIGITAL GENSET CONTROLLER DGC-500 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-500) offers a low cost microprocessor based integrated alternative for the control and monitoring of small to medium sized

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic

More information

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM APPLICATION OVERVIEW Control and monitoring systems play an essential role in heat tracing applications which range from freeze protecting water lines to

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors

More information

INSTRUCTION MANUAL & 8200 Monitor. Manual Issue 06

INSTRUCTION MANUAL & 8200 Monitor. Manual Issue 06 INSTRUCTION MANUAL 8100 & 8200 Monitor Manual Issue 06 ** This page is intentionally left blank ** Table of Contents 1 Introduction... 4 1.1 Manual Conventions... 4 1.2 Version 4 PCBA's... 4 1.3 Product

More information

C-Bus Four Channel General Input Unit Installation Instructions

C-Bus Four Channel General Input Unit Installation Instructions C-Bus Four Channel General Input Unit Installation Instructions 5504GI Series REGISTERED DESIGN REGISTERED PATENT Table of Contents Section...Page 1.0 Product Range... 3 2.0 Description... 3 3.0 Capabilities...

More information

DGC-1000 DIGITAL GENSET CONTROLLER

DGC-1000 DIGITAL GENSET CONTROLLER DGC-1000 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-1000) offers a low cost microprocessor based integrated alternative for small to medium sized genset control and monitoring.

More information

VACIE REFERENCE GUIDE REVISION 1.2.6

VACIE REFERENCE GUIDE REVISION 1.2.6 VACIE REFERENCE GUIDE REVISION 1.2.6 November 2016 INTRODUCTION... 3 SECTION 1... 4 VACIE CONFIGURATION... 4 Communications... 4 Vocia VACIE Devices... 4 Vocia Support devices:... 5 Power Supply and Network

More information

CTT8 TEMPERATURE MONITOR DEVICE

CTT8 TEMPERATURE MONITOR DEVICE INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The nvent RAYCHEM NGC-40 is a multipoint

More information

LC2200 Level Controller Installation and Maintenance Instructions

LC2200 Level Controller Installation and Maintenance Instructions 4025250/9 IM-P402-77 AB Issue 9 LC2200 Level Controller Installation and Maintenance Instructions LC2200 ALARM TEST >50% >100%

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 505 Grünberg Tel.: 060 807-0 Fax: 060 807-59 A-ISOMETER IRDH575 Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with

More information

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE Insulation monitoring device with integrated load and temperature monitoring and locating current injector for insulation fault location systems for medical IT systems _D00043_02_D_XXEN/09.2016 Insulation

More information

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU with Automatic Power Transfer Switch Contents: NOTE: The drawings included in this package are for controllers covered under our standard

More information

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

DEB71. Earth Leakage Monitoring Relay. Benefits. Description Earth Leakage Monitoring Relay Benefits Adjustable trip level. Adjustable leakage threshold from 30mA to 5A or from 300mA to 30A. 2 outputs. Two relay outputs provide, besides the alarm signal an additional

More information

Oxygen (O2) Single-Point Gas Detection System

Oxygen (O2) Single-Point Gas Detection System Oxygen (O) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in oxygen (O) sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity

More information

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents) Residual current monitor RCM470LY/RCM475LY for TN and TT systems (AC and pulsating DC currents) TDB401003en/03.2010 Residual current monitor RCM470LY Residual current monitor for TN and TT systems (AC

More information

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM APPLICATION OVERVIEW Control and monitoring systems play an essential role in heat tracing applications which range from freeze protecting water lines to

More information

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content 8 Appendix 8.1 Wiring examples...4 8.2 Start configuration...4 8.3 Sensor configuration...4 8.4 Actuator configuration...5 Operating instructions.............pages 1 to 6 Original 9 EU Declaration of conformity

More information

Series Temperature Controller Instruction Sheet

Series Temperature Controller Instruction Sheet Series Temperature Controller Instruction Sheet Thank you very much for purchasing DELTA A Series. Please read this instruction sheet before using your A series to ensure proper operation and please keep

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

02/11/2015

02/11/2015 MIC48 With RS 485 link Part number 89422418 Heating and / or cooling function 2 independent alarms Load break detection 2 setpoint which can be selected remotely Manual / automatic power adjustment RS

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

Table of Contents. T538 Instruction Manual Rev # 6 June R6T538 June rtf E L Switchgear and Control Inc

Table of Contents. T538 Instruction Manual Rev # 6 June R6T538 June rtf E L Switchgear and Control Inc Table of Contents Introduction...2 Mounting...2 Dimensions...2 Controls...3 Screen Displays...3 Screen Messages...4 Light Test...5 Control Power...5 Wiring...5 Inputs...7 Outputs...7 Programming...8 Technical

More information

02/11/2015

02/11/2015 CTH 46 - CTD 43 / 46 CTD 46 Part number 89422108 CTH 46 Heating / cooling function Measurement and setpoint display CTD 43 Heating or cooling function Measurement display Measurement deviation display-setpoint

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

Table of Contents. Protective Relays

Table of Contents. Protective Relays Table of Contents KILOVAC WD Series, DIN Rail or Screw Mounted Introduction..........................................................11-2 KILOVAC WD25 Paralleling Relays........................................11-3

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

Operating Manual MS220KA and MSR220KA

Operating Manual MS220KA and MSR220KA Temperature Relays and MINIKA, Mains Monitoring, Digital Panel meters MINIPAN, Switching Relays and Controls Operating Manual MS220KA and MSR220KA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße

More information

Models 4623, 4628 & 5999/980 USP<645> Conductivity Analyzers

Models 4623, 4628 & 5999/980 USP<645> Conductivity Analyzers Data sheet USP Conductivity Analyzers A conductivity system designed to meet USP for the Pharmaceutical Industry incorporating automatic Stage 1 test Meets USP requirements ensures compliance

More information

DTA04. Motor thermistor relay. Benefits. Description

DTA04. Motor thermistor relay. Benefits. Description Motor thermistor relay Benefits High operating safety. The thresholds are determined by the Motor PTC. Beyond the specified temperature the output stops the motor/s. Save time and costs.there is no need

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information

Vocia VACIE. Reference Guide

Vocia VACIE. Reference Guide Vocia VACIE Reference Guide Document Revision 1.2.3, August 2015 Biamp Systems 9300 SW Gemini Drive Beaverton, Oregon 97008, U.S.A. (503) 641-7287 www.biamp.com INTRODUCTION... 3 SECTION 1... 4 VACIE CONFIGURATION...

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary

More information

7SG17-Rho 3 Multifunction Protection Relays Answers for energy

7SG17-Rho 3 Multifunction Protection Relays Answers for energy Reyrolle Protection Devices 7SG17-Rho 3 Multifunction Protection Relays Answers for energy 7SG17 Rho3 Contents Contents Technical Manual Chapters 1. Description of Operation 2. Performance Specification

More information

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new

More information

Instruction Manual August sitrans CU 02

Instruction Manual August sitrans CU 02 Instruction Manual August 2005 sitrans CU 02 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment.

More information

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document 1 About this document Operating instructions... pages 1 to 6 Translation of the original operating instructions 1.1 Function This operating instructions manual provides all the information you need for

More information

NGC-40 Advanced Heat-Tracing Control System

NGC-40 Advanced Heat-Tracing Control System NGC-40 Advanced Heat-Tracing Control System Local configuration and monitoring with Raychem Touch 1500 touch screen display Heat-tracing system NGC-40 system Remote configuration and monitoring with Raychem

More information

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504 Remote Monitor PTE0700 SECURITY ELECTRONICS User Manual PTE0700 V2 Series Remote Monitor Pakton Technologies Pty Ltd ABN 66 405 694 842 16 Ferrier Road, Narangba Qld 4504 PO Box 408, Narangba QLD 4504

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

C-Bus Four Channel Analogue Output Unit Installation Instructions

C-Bus Four Channel Analogue Output Unit Installation Instructions C-Bus Four Channel Analogue Output Unit Installation Instructions 5504AMP Series REGISTERED PATENT Table of Contents Section... Page 1.0 Product Range...3 2.0 Description...3 3.0 Capabilities...3 4.0 Wiring

More information

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE Cat. N STOP & GO automatic resetting 87045 LIMOGES Cedex - FRANCE Telephone : + 33 5 55 06 87 87 Fax: + 33 5 55 06 88 88 Cat. N (s) : 4 062 88 / 4 062 89 CONTENTS PAGE 1. Description - Use... 1 2. Product

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) IR425-D4_D00039_04_D_XXEN/05.2017 ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits

More information

Monitoring Devices 11/1

Monitoring Devices 11/1 11/4 Introduction 11/6 5TE5 8 light indicators 11/7 4AC3 0, 4AC3 1 bells, buzzers 11/7 5TT3 46 fault signaling units 11/8 7LQ2 1, 5TT3 3 dusk switches 11/9 7LQ2 0 temperature controllers 11/9 5TT3 170

More information

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel

More information

vibration switch

vibration switch user manual 440-450 vibration switch INSTALLATION - OPERATION - MAINTENANCE Z0592822_A ISSUED 06/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. contents Section 1 -

More information

DIGITAL METERS Large Display Temperature Meters Instruction Manual

DIGITAL METERS Large Display Temperature Meters Instruction Manual DIGITAL METERS Large Display Temperature Meters PD755 PD756 PD757 Handles Thermocouple & RTD Inputs with Simplicity J, K, T, E, R, & S Thermocouples 100 Ω Platinum RTD (0.00385 or 0.00392 curve) Large

More information

Inverter control panels........................ 152 Inverter control panels with safety............... 153 Level control panel........................... 155 Temperature control panel.....................

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

Model 1062 Environment Monitor

Model 1062 Environment Monitor Model 1062 Environment Monitor Continuously Monitors Environment Temperature Humidity Barometric Pressure Line Voltage Line Frequency Applications Manufacturing The 1062A Environment Monitor will ensure

More information

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V IR1575_D00116_00_D_XXEN/05.2015 Insulation monitoring device for unearthed AC/3(N)AC systems up to 480

More information

ADDITIONAL INFORMATION

ADDITIONAL INFORMATION MODEL APS-3C AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL MODEL APS-4C AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL MODEL SC-40C MODULAR SNOW/ICE HEATER CONTROL SYSTEM SAFETY This device provides

More information

MTRA-FSP Level Control Relay. Installation & Operation Manual

MTRA-FSP Level Control Relay. Installation & Operation Manual MTRA-FSP Level Control Relay Installation & Operation Manual This Manual is the support documentation for the installation, commissioning and operation of the MTRA-FSP Level Control Relay. Document Revision

More information

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model

More information

Variable Frequency Drive SERIES MP800 VFD

Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controls and Accessories Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for

More information

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current

More information

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev. TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL Microener- Copyright 2010 FW 2.1 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection

More information

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

TraceNet ECM Series Control System

TraceNet ECM Series Control System TraceNet ECM Series Control System ECM Operating Guide Thermon Manufacturing Company TraceNet is a registered trademark of Thermon Manufacturing Company. ECM Operating Guide 2014, 2015 Thermon Manufacturing

More information

Product Manual SZ1145

Product Manual SZ1145 Product Manual SZ114 General Purpose Monitor Communicating Controls Description The SZ114 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum temperature

More information

SPA 2 IS. IECEx. Programmable Limit Alarm Trips with Intrinsically-Safe Field Connections

SPA 2 IS. IECEx. Programmable Limit Alarm Trips with Intrinsically-Safe Field Connections April 2016 Description The universal SPA 2 IS Programmable Limit Alarm Trips provide on/off control, warn of unwanted process conditions, alarm on rate-of-change and provide emergency shutdown. Very versatile,

More information

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals Technical Information RTA421 Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals Application Plant and machine construction Panel builders Process monitoring Process

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 505 Grünberg Tel.: 00 807-0 Fax: 00 807-259 Insulation monitoring device for unearthed AC/DC systems (IT systems for the supply of operating theatre

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-59 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control

More information

Operating Manual MS220DA

Operating Manual MS220DA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panel Meters MINIPAN

More information

PAC1500Xi PORTABLE APPLIANCE CHECKER

PAC1500Xi PORTABLE APPLIANCE CHECKER PAC1500Xi PORTABLE APPLIANCE CHECKER OPERATING INSTRUCTIONS 211A912 CONTENTS 1) Safety... 1 2) Introduction & Description... 2 3) Applications... 2 4) Test Sequence... 3 5) Visual Inspection... 3 6) Earth

More information

Unipower HPL420. User s Manual. True Motor Power Monitor with... Typical Applications. High Trip Alarm. Low Trip Alarm.

Unipower HPL420. User s Manual. True Motor Power Monitor with... Typical Applications. High Trip Alarm. Low Trip Alarm. Unipower HPL420 D i g i t a l P o w e r M o n i t o r User s Manual True Motor Power Monitor with... High Trip Alarm Low Trip Alarm Dual Relays Hysteresis Function Analog Output Typical Applications Pumps

More information

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems) ISOSCAN EDS460/490 EDS461/491 Insulation fault locators with control and display function for EDS systems (insulation fault location systems) EDS460-490_D00085_01_D_XXEN/01.2017 ISOSCAN EDS460/490 EDS461/491

More information

Speed and Frequency Seite 1 von 7

Speed and Frequency Seite 1 von 7 Speed and Frequency Seite 1 von 7 E16 Systems for High Safety Speed ing, all with Triple Modular Redundancy. A choice of versions to meet various demands. Compliant with SIL3 / IEC 61508 and/or API 670.

More information

IT system floor-standing distribution

IT system floor-standing distribution IT system floor-standing distribution cabinet series -IPS-F/EDS for supplying power to medical locations in accordance with IEC 60364-7-710 and featuring a built-in insulation fault location system IT

More information

OPERATION / INSTALLATION

OPERATION / INSTALLATION OPERATION / INSTALLATION & PROGRAMMING MANUAL AFP-2800 LCD-80 Fire Alarm Panel Revision 1.01 November 16, 2004 NSW (Head Office) 7 Columbia Court Norwest Business Park Baulkham Hills NSW 2153 Ph: (02)

More information

Danfoss gas detection unit Type GD Heavy Duty

Danfoss gas detection unit Type GD Heavy Duty Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx

More information

Wallace & Tiernan Controllers & Analysers ChemTrim Disinfection Controller

Wallace & Tiernan Controllers & Analysers ChemTrim Disinfection Controller Wallace & Tiernan s & Analysers ChemTrim Disinfection Introduction The ChemTrim Disinfection is a modern, dedicated controller incorporating the latest advanced electronics and process control application

More information