WFD Vane-type Waterflow Detectors

Size: px
Start display at page:

Download "WFD Vane-type Waterflow Detectors"

Transcription

1 INSTLLTION ND MINTENNCE INSTRUCTIONS WFD Vane-type Waterflow Detectors Division of Pittway 3825 Ohio venue, St. Charles, Illinois SENSOR2, FX: Specifications Contact Ratings: 125/250 VC 24 VDC Triggering Threshold andwidth (Flow Rate): 4 to 10 gpm Static Pressure Rating: 250 PSI (Max) 2" 8" Dimensions, Installed: 3.5"H x 3.0"W x 6.7"D Operating Temperature Range: 32 F to 120 F (0 C to 49 C) Compatible Pipe: Steel water pipe, schedule 10 or 40. Shipping Weight: 4 to 7 lb., according to size. Enclosure Rating: NEM 4, as tested by Underwriters Laboratories, Inc. (requires optional Outdoor Cover Gasket Model WFDN4 and cover part #C ) Important Please Read Carefully nd Save This instruction manual contains important information about the installation and operation of waterflow detectors. Purchasers who install waterflow detectors for use by others must leave this manual or a copy of it with the user. Read all instructions carefully before beginning. Follow only those instructions that apply to the model you are installing. CUTION Use vane-type waterflow detectors in wet-pipe systems only. Do NOT use them in dry pipe, deluge, or preaction systems. The sudden inrush of water in such systems may break the vane or damage the mechanism. Do not use in potentially explosive atmospheres. Do not allow unused wires to remain exposed. Principles Of Operation Vane-type waterflow detectors mount to water-filled pipes in sprinkler systems. Waterflow in the pipe deflects a vane, which produces a switched output usually after a specified delay. ll waterflow detectors have a pneumatically controlled mechanical delay mechanism. Delays do NOT accumulate; they reset if the flow of water stops before the entire delay has elapsed. ll switches actuate when the water flow rate is 10 gallons per minute or greater, but will not actuate if the flow rate is less than 4 gallons per minute. This System Sensor installation manual covers the following waterflow detectors for sprinkler/fire alarm applications. Models WFD20 Waterflow detector, Schedule 10/40, 2" WFD25 Waterflow detector, Schedule 10/40, 2-1/2" WFD30 Waterflow detector, Schedule 10/40, 3" WFD35 Waterflow detector, Schedule 10/40, 3-1/2" WFD40 Waterflow detector. Schedule 10/40, 4" WFD50 Waterflow detector, Schedule 10/40, 5" WFD60 Waterflow detector, Schedule 10/40, 6" WFD80 Waterflow detector, Schedule 10/40, 8" D I

2 CUTION Do NOT use any of the WFD models on copper pipe. The clamping forces of the mounting bolts may collapse the pipe sufficiently to prevent the detector from functioning properly. Do NOT install steel or iron pipe sections in copper piping for mounting a waterflow detector. Incompatibility between the dissimilar metals causes bimetallic corrosion. Figure 1. Mounting dimensions: 3" 3-3/4" Pipe diameter plus 5-1/4" Installation Guidelines efore installing any waterflow alarm device, be thoroughly familiar with: NFP 72: National Fire larm Code NFP 13: Installation of Sprinkler Systems, Section 3.17 NFP 25: Inspection, Testing and Maintenance of Sprinkler Systems Other applicable NFP standards, local codes, and the requirements of the authority having jurisdiction Failure to follow these directions may prevent the device from reporting the flow of water in the event the associated sprinkler system is activated by a fire. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained. U-bolt nut Pipe saddle U-bolt Overall width = pipe diameter + 3" Pipe Plastic vane Mount the detector where there is adequate clearance for installation and removal and a clear view of it for inspections. See Figure 1 for mounting dimensions. 2. Locate to protect from damage 6 to 7 feet above the floor. 3. On horizontal runs, position the detector on the top or side of the pipe. Do not mount it upside down because condensation may collect in the housing and impair the operation of the detector. For vertical flow applications, mount the detector on pipe through which water flows upward. Otherwise, the unit may not operate properly. 4. Mount the detector at least 6 inches from a fitting that changes the direction of water flow and no less than 24 inches from a valve or drain. 5. e sure the direction-of-flow arrow matches the direction of flow in the pipe. Mounting Instructions 1. Drain the pipe. 2. Cut a hole at the desired location. Center the hole in the pipe, as shown in Figure 2, and be sure the hole is perpendicular to the center of the pipe. efore drilling, use a punch or scribe to mark the drill site to prevent the bit from slipping. If the hole is off center, the vane will bind against the inside wall of the pipe. Use a drill or hole saw to cut a hole of the proper diameter. See Table 1 for hole size. Figure 2. Mounting hole location: Wrong Right Remove burrs from edge of hole. Clean out scale and foreign matter for one pipe diameter on each side of hole D I

3 Table 1: Table 2: WFD SIZE Hole Size WFD SIZE Torque 2" - 3-1/2" 1-1/4" 4" - 8" 2" 2" - 3-1/2" ft-lb 4" - 8" ft-lb CUTION When drilling the hole with a hole saw, make certain that the center of the cut does not remain in the pipe. 3. Remove burrs and sharp edges from the hole. Clean and remove all scale and foreign matter from the inside of the pipe for one diameter on each side of the hole to ensure free movement of the vane. Clean the outside of the pipe to remove dirt, metal chips, and cutting lubricant. 4. Seat the O-ring or gasket against the saddle and mount the detector directly to the pipe. Carefully roll the vane opposite the direction of flow and insert it through the hole. Seat the saddle firmly against the pipe so that the locating boss goes into the hole. 5. Install the U-bolt, tightening the nuts alternately to ensure a uniform seal. See Table 2 for torque values. 6. Remove the metal cover with the tamper-proof wrench provided. Move the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the cause before proceeding. CUTION e sure the direction-of-flow arrow points in the right direction or else water flow will go unreported. See Figure 3. Preoperation Testing 1. Fill the sprinkler system and check for leaks around the waterflow detector. If it leaks, first check for the proper torque on the U-bolt nuts. If the leak persists, drain the system and remove the detector (refer to Maintenance. page 6). Check for dirt or foreign objects under the gasket, and make sure that the pipe surface is not dented. Reinstall the detector and check again for leaks. Do not proceed until all leaks have been stopped. 2. Connect an ohmmeter or continuity tester across the and switch terminals. The ohmmeter should indicate an open circuit. 3. Deflect the actuator lever and hold it until the pneumatic delay shaft releases the switch buttons. The ohmmeter or continuity tester should show a short circuit after the delay has elapsed. If there is no delay, check the setting of the delay adjustment dial. Wiring WRNING High Voltage. Electrocution Hazard. Do not handle live C wiring or work on a device to which C power is applied. Doing so may result in injury or death. 1. ll models have two SPDT switches. Switch contacts and are closed when water is flowing and open when it is not. Connect the switches, as shown in Figure 4 on page 5, depending on the application. 2. When connected to a listed sprinkler/fire alarm control panel, the initiating circuit must be nonsilenceable. 3. ground screw is provided with all waterflow detectors. When grounding is required, clamp wire with screw in hole located between conduit entrance holes. See Figure 5, page If a second conduit entry is required, remove the knockout plug using a flat blade screwdriver as shown on Figure 5, page 5. Strike sharply with a hammer to pierce the wall of the knockout plug. Move to an adjacent wall section and repeat until the plug falls out. Make sure that the waterflow detector is supported adequately during this operation to avoid injury. D I

4 Figure 3. ssembly diagram: Tamper proof wrench (P/N WFDW) Cover Switch enclosure (Replacement P/N ) Delay mechanism (Replacement P/N ) Mounting plate Pipe saddle Conduit entrance Direction-of-flow arrow U-bolt nut Plastic vane Roll paddle opposite of flow arrow while inserting Saddle gasket Pipe Waterflow WFD Size 2" 3-1/2" 4" 8" Hole Size 1-1/4" 2" U-bolt D I

5 Figure 4. WFD wiring: WFD Switch ssembly Top View Switch 1 NOTE: Common and connections will close when vane is deflected, i.e., when water is flowing. Dual switches permit applications to be combined on a single detector. Switch 2 CONTCT RTINGS 125/250 VC 24 VDC 10 MPS 2.5 MPS to nonsilenceable initiating zone of listed FCP WFD WFD end-of-line resistor Typical FCP Connection (Multiple Detectors) to power source compatible with bell Typical Local ell Connection local bell reak wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. Do NOT loop wires Figure 5. Ground screw location: Figure 5. Knockout plug removal: GROUND SCREW (GREEN) MOUNTING PLTE D I

6 Mechanical Delay djustment The pneumatic delay is preset at the factory to dial setting 2. To adjust the setting, turn the adjustment dial clockwise to increase the delay, counterclockwise to decrease it. The delay is adjustable from 0 to 70 seconds. See Figure 6. NOTE: Set the delay to the minimum required to prevent false alarms from flow surges. fter extended service, parts of the detector may become worn, reducing the delay time and causing false alarms. If this happens, increase the delay. If the delay is already at the maximum, replace the mechanical delay assembly. Refer to Maintenance for ordering replacement parts. Operational Testing lways notify a central station monitoring waterflow alarms before repairing, maintaining, or testing waterflow alarm devices. 1. Replace the cover and tighten the tamper proof screws with the tamper proof wrench. Store the wrench in a secure place. 2. Open the inspector s test valve and time how long it takes for the detector to indicate a flow condition. The detector should remain activated until the inspector s test valve is closed. ir pockets in the sprinkler system may increase the apparent delay. Maintenance To prevent accidental water damage, control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. Inspect detectors monthly for leaks and replace if a leak occurs. Test detectors at least monthly, as described under Operational Testing, to ensure proper operation. Test more often if required by the authority having jurisdiction. Under normal conditions, System Sensor waterflow detectors should provide years of trouble-free service. However, if the delay mechanism or switch enclosure becomes faulty, replace it. To replace the delay mechanism or switch enclosure, use a phillips head screwdriver to remove the three screws that hold it in place. Either mechanism can be easily replaced without removing the detector from the pipe or draining the pipe. Do not repair or replace any other waterflow detector components. If any other part of the detector does not perform properly, replace the entire detector. Failure to to follow this instruction may result in failure of the detector to report the flow of water. To replace the delay mechanism, request Part No For switch enclosure, request Part No Figure 6. Delay adjustment dial: Delay adjustment dial NUMER PPROXIMTE TIME 0 ON DIL DELY Table of dial settings embossed here. See below (SECONDS) Dial setting Seconds (±50%) D I

7 To remove a detector: 1. Drain the pipe. 2. Turn off electrical power to the detector and disconnect the wiring. 3. Loosen the nuts and remove the U-bolts. 4. Gently lift the saddle far enough to get your fingers under it. Then, roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. 5. Lift the detector clear of the pipe. CUTION If a vane breaks in a pipe, find and remove it. If it is not removed, the vane may restrict the flow of water to all or part of the sprinkler system. D I

8 1. Waterflow detectors may not work or operate properly if sprinkler piping being monitored is plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems should be checked regularly for such blocking material, following the instructions in Chapter 5 of NFP Standard larms generated by the activation of waterflow detectors may not be received by a central station if telephone or other communication lines to the detector are out of service, disabled, or open. 3. Vane-type waterflow detectors have a normal service life WRNING The Limitations of Waterflow larm Devices of years. Hard water systems, however, may reduce waterflow detector service life to 4 or 5 years. 4. Waterflow detectors are not a substitute for insurance. uilding owners should always insure property and lives being protected by sprinkler systems. 5. If valves controlling the water supply to a sprinkler system are closed, vane-type waterflow detectors will not work. ll valves controlling a sprinkler water supply should be sealed or locked in the normally open position. The normally open position should be monitored by a sprinkler supervisory switch. System Sensor warrants its enclosed waterflow detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this waterflow detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company s obligation of this Warranty shall be limited to the repair or replacement of any part of the waterflow detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. fter phoning System Sensor s toll free number 800-SENSOR2 ( ) for a Return uthorization number, send defective units postage prepaid to: System Sensor, Three-Year Limited Warranty Repair Department, R #, 3825 Ohio venue, St. Charles, IL Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state. D I System Sensor 1996

9 INSTLLTION ND MINTENNCE INSTRUCTIONS WFDT/WFDTH Vane-type Waterflow Detectors Division of Pittway 3825 Ohio venue, St. Charles, Illinois SENSOR2, FX: Specifications Contact Ratings: Two sets of SPDT (Form C) 125/250 VC; 24 VDC Triggering Threshold andwidth (Flow Rate): 4-10 GPM Service Pressure Rating: 250 PSI (Max.) Overall Dimensions, Installed: WFDT 4 5 /16 H 3 3 /4 W 6 3 /4 D WFDTH 4 5 /16 H 3 9 /16 W 6 3 /4 D Operating Temperature Ranges: 32 F F (0 C - 49 C) Shipping Weight: 2.6 lbs. The WFDT is U.L. listed for indoor and outdoor installations The WFDTH is U.L. listed for indoor use only. The WFDTH can be installed between 2 4 stud wall construction. Important Please Read Carefully nd Save This instruction manual contains important information about the installation and operation of waterflow detectors. Purchasers who install waterflow detectors for use by others must leave this manual or a copy of it with the user. Read all instructions carefully before beginning. CUTION Use vane-type waterflow detectors in wet-pipe systems only. DO NOT USE IN DRY-PIPE, DELUGE, OR PRE-C- TION SYSTEMS. The sudden inrush of water in such systems may break the vane off or damage the mechanism. Do not use in potentially explosive atmospheres. Do not leave unused wires exposed. pproximate Tee Depth Requirements (See Figure 1) Tee Depth Threaded Sweat Poly CPVC /4 1 1 / /2 1 1 / " Figure 1. Mounting dimensions: /8 1 3 /4 N/ 2 1 /4 2 1 /2 2 1 /6 N/ N/ 2 3 /4 2 1 /4 2 1 /2 N/ N/ 2 3 /4 N/ N/ 3 3 /4 (WFDT) 3 9 /16 (WFDTH) Principles Of Operation Vane-type waterflow detectors mount to water filled pipes in sprinkler systems. Water flow in the pipe deflects a vane. Deflection of the vane produces a switched output, usually after a specified delay. Tee dapter Tee Depth Refer to Tee Depth Table 4 5 /16 Gage (End of Paddle Tree) Must Fit etween Top of Tee and ottom of Flange Tee Fitting ll WFDTs have a pneumatically controlled mechanical delay mechanism. Delays are noncumulative; they reset if the flow of water stops before the entire delay has elapsed. ll detectors will activate on a sustained flow of water greater than 10 gallons per minute (gpm) but will not activate if the flow rate is less than 4 gpm. Compatible Pipe Tees The WFDT and WFDTH fit 1 to 1 1 /2 NPT threaded ferrous and brass, 1 to 2 sweat brass, 1 1 /2 polybutylene plastic and 1 pvc plastic tees having a 1 threaded NPT branch (see Figure 1 and chart for recommended tee depths). Plastic Vane Installation Guidelines efore installing any waterflow alarm device, be thoroughly familiar with: NFP 72: National Fire larm Code NFP 13: Installation of Sprinkler Systems NFP 25: Inspection, Testing, and Maintenance of Water-based Fire Protection Systems NFP 13D: Standard for 1 and 2 Family Dwellings and Manufactured Homes NFP 13R: Standard for Multi-family Dwellings N I

10 Figure 2. ssembly diagram: DELY MECHNISM (REPLCEMENT P/N ) WTERFLOW FLOW FILLISTER HED SCREW 1 NPT THRED CTUTOR LEVER (Cover tamper option is available.) COVER SWITCH ENCLOSURE (REPLCEMENT P/N ) GROUND SCREW (GREEN) MOUNTING PLTE TMPER PROOF WRENCH (P/N WFDW) PDDLE (PDDLE REPLCEMENT KIT (P/N PRK9) lso, follow other applicable NFP standards, local codes and the requirements of the authority having jurisdiction. Failure to follow these directions may result in failure of the device to report a waterflow condition. System Sensor is not responsible for devices that have been improperly installed, tested or maintained. 1. Mount the detector where there is adequate clearance for installation and removal and a clear view of it for inspection. See Figure 1 for mounting dimensions. 2. Locate to protect from damage, 6-7 feet above the floor. 3. On horizontal runs, position the detector on top of the pipe or on the side of it. Do not mount it upside down because condensation may collect in the housing and impair the operation of the detector. For vertical flow applications, mount detector on pipe where upflow conditions exist. Failure to do so may prevent unit from operating properly. 4. Mount detector at least 6 inches from a fitting which changes the direction of the water flow, or no closer than 24 inches from a valve or drain. 5. E SURE DIRECTION-OF-FLOW RROW MTCHES C- TUL DIRECTION OF FLOW IN THE PIPE. Mounting Instructions 1. The WFDT and WFDTH waterflow detectors are designed to fit only the appropriate tee fitting. 2. WFDT and WFDTH units are shipped without paddles mounted to the actuator. Select the correct size paddle for the type of tee being used. lign hole on stem of paddle with hole on actuator lever. Fasten together using a #4-40 x 1/4" fillister head screw supplied in bag assembly. See Figure 2. Use only the screw provided with the unit. Drive screw head through hole in paddle until it seats to actuator lever surface. No washer is required. For paddle replacement refer to Maintenance section. 3. Carefully roll the vane opposite the direction of flow and insert through tee. Thread detector onto tee fitting and tighten with wrench. Use of thread sealant or tape is recommended. Use height gage (located at end of paddle tee) to ensure proper depth of detector on tee fitting. See Figure 1. Height gage must fit between top of tee fitting and under side of hex tee adapter. gap between gage and tee adapter is acceptable. When correctly installed, the detector must face in the proper direction of waterflow and be aligned with the pipe. 4. Remove the metal cover. Move the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the problem before proceeding. CUTION e sure the direction-of-flow arrow points in the right direction, otherwise a waterflow condition will go unreported. See Figure 2. Preoperation Testing 1. Fill the sprinkler system with water and check for leaks around the WFDT or WFDTH. If there is a leak, check to see that the fittings are tight. If leak persists, drain the system and remove the detector (see removal instructions under Maintenance). Check for damaged threads or cracked fitting. Reinstall the detector and check again for leaks. Do not proceed until all leaks have been stopped. 2. Connect an ohmmeter or continuity tester across ( and ) terminal switch contacts. The ohmmeter should show an open circuit, no continuity. 3. Deflect the actuator lever and hold it until the pneumatic delay shaft releases the switch buttons. The ohmmeter or continuity tester should show a short circuit after the delay has elapsed. If there is no delay, check the setting of the delay adjustment dial. NOTE: Leg of tee perpendicular to flow of water must have a 1" NPT thread. Do not use a reducer to achieve the correct thread size. Failure to follow this instruction will result in failure of the detector to report a waterflow condition. N I

11 Figure 3. Field wiring: Top View Switch 1 NOTE: Common and connections will close when vane is deflected, i.e., when water is flowing. Dual switches permit applications to be combined on a single detector. WFDTH WFDT Switch 2 WFDTH WFDT CONTCT RTINGS 125/250 VC 24 VDC 10 MPS 2.5 MPS to nonsilenceable initiating zone of listed FCP end-of-line resistor Typical FCP Connection Field Wiring to power source compatible with bell Typical Local ell Connection local bell WFDT and WFDTH switch assembly reak wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires WRNING High Voltage. Electrocution Hazard. Do not handle live C wiring or work on a device to which C power is applied. Doing so may result in severe injury or death. 1. The WFDT and WFDTH have two SPDT switches. Switch contacts ( and ) are closed when water is flowing and open when water is not flowing. Connect the switches as shown in Figure 3 depending on the application. 2. When connected to a listed sprinkler/fire alarm control panel, the initiating circuit must be non-silenceable. 3. ground screw is provided with all units. When grounding is required, clamp wire with screw in hole located between conduit entrance holes. See Figure 2. fter extended service, parts of the detector may become worn reducing the delay time and causing false alarms. If this happens, increase the delay. If the delay is already at maximum, replace the mechanical delay assembly. Refer to Maintenance section for ordering replacement parts. Figure 4. Delay adjustment dial: Table of dial settings embossed here. See below Mechanical Delay djustment The pneumatic delay is preset at dial setting 2 at the factory. To adjust the delay, turn the adjustment dial on the delay mechanism. Turn clockwise to increase the delay, counterclockwise to decrease the delay. Delay can be adjusted over a range from 0-70 seconds. See Figure 4. Delay adjustment dial 2 3 NOTE: Set the delay to the minimum required to prevent false alarms due to flow surges. Dial setting Seconds (±50%) N I

12 Operational Testing lways notify a central station monitoring waterflow alarms before repairing, maintaining or testing waterflow alarm devices. 1. Replace the cover and tighten the security screws with the tamper proof wrench. Store the wrench in a secure place. 2. Open the inspector s test valve and time how long it takes for the detector to indicate a flow condition. The detector should remain activated until the inspector s test valve is closed. ir pockets in the sprinkler system may increase the apparent time delay. Maintenance To prevent accidental water damage, control valves should be shut tightly and the system completely drained before waterflow detectors are removed or replaced. Inspect detectors monthly for leaks. Test detectors at least monthly as described under Operational Testing above to insure proper operation. This device is not designed for use on dry pipe systems. Test more often if required by the authority having jurisdiction. Under normal conditions System Sensor waterflow detectors should provide years of trouble-free service. If, however, the delay mechanism becomes faulty, replacement kits are available. To replace the delay mechanism, request Part No ; for switch enclosure, request Part No Complete instructions are enclosed with each. Either mechanism can be easily replaced without removing the detector from the pipe or draining the pipe. If damage occurs to paddle, order replacement kit PRK9. Refer to procedure below for removal of detector on pipe. Do not repair or replace any other waterflow detector components in the field. If any other part of the detector does not perform properly, replace the entire detector. Failure to follow this instruction may result in failure of the detector to report a waterflow condition. Proceed as follows to remove a detector. 1. Drain the pipe. 2. Turn off electrical power to the detector, and then disconnect wiring. 3. Unscrew WFDT or WFDTH from tee fitting. 4. Lift detector clear of pipe. CUTION If a vane breaks off in a pipe, find and remove it. Failure to do so may restrict the proper flow of water to part of the sprinkler system. 1. Waterflow detectors may not work or operate properly if sprinkler piping being monitored is plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems should be checked regularly for such blocking material, following the instructions in NFP Standard larms generated by the activation of waterflow detectors may not be received by a central station if telephone or other communication lines to the detector are out of service, disabled, or open. System Sensor warrants its enclosed waterflow detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this waterflow detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company s obligation of this Warranty shall be limited to the repair or replacement of any part of the waterflow detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. fter phoning System Sensor s toll free number 800-SENSOR2 ( ) for a Return uthorization number, send defective units postage prepaid to: System Sensor, WRNING The Limitations of Waterflow larm Devices Three-Year Limited Warranty 3. Vane-type waterflow detectors have a normal service life of years. Hard water systems, however, may reduce waterflow detector service life to 4 or 5 years. 4. If valves controlling the water supply to a sprinkler system are closed, vane-type waterflow detectors will not work. ll valves controlling a sprinkler water supply should be sealed or locked in the normally open position. The normally open position should be monitored by a sprinkler supervisory switch. Repair Department, R #, 3825 Ohio venue, St. Charles, IL Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state. N I System Sensor 1996

13 INSTLLTION ND MINTENNCE INSTRUCTIONS WFDTNR Vane-type Waterflow Detector Division of Pittway 3825 Ohio venue, St. Charles, Illinois SENSOR2, FX: Specifications Contact Ratings: 125/250 VC 24 VDC Triggering Threshold andwidth (Flow Rate): 4-10 GPM Static Pressure Rating: 250 PSI (Max.) Overall Dimensions, Installed: 3.25" x 4.25" cover dia. 3.25" above pipe tee Operating Temperature Range: 32 F F (0 C - 49 C) Shipping Weight: 1.5 lbs. Important Please Read Carefully nd Save This instruction manual contains important information about the installation and operation of waterflow detectors. Purchasers who install waterflow detectors for use by others must leave this manual or a copy of it with the user. Read all instructions carefully before beginning. pproximate Tee Depth Requirements (See Figure 1) Tee Depth Threaded Sweat Poly CPVC /4 1 1 / /2 1 1 / " 2 1 /8 1 3 /4 N/ 2 1 /4 2 1 /2 2 1 /6 N/ N/ 2 3 /4 2 1 /4 2 1 /2 N/ N/ 2 3 /4 N/ N/ CUTION Use vane-type waterflow detectors in wet-pipe systems only. DO NOT USE IN DRY-PIPE, DELUGE, OR PRE-C- TION SYSTEMS. The sudden inrush of water in such systems may break the vane off or damage the mechanism. Do not use in potentially explosive atmospheres. Do not leave unused wires exposed. Figure 1. Mounting dimensions: 3 1/4" 1 3/4" 3 1/4" HEX TEE DPTOR Principles Of Operation Vane-type waterflow detectors mount to wet-pipe systems only. Water flow in the pipe deflects a vane. Deflection of the vane produces a switched output. ll detectors will activate on a sustained flow of water greater than 10 gallons per minute (gpm) but will not activate if the flow rate is less than 4 gpm. "TEE DEPTH" REFER TO TEE DEPTH TLE PIPE TEE FITTING PLSTIC VNE INSTLLTION GGE (END OF PDDLE TREE) MUST FIT ETWEEN TOP OF TEE ND OTTOM OF HEX TEE DPTOR FLNGE Compatible Pipe Tees Model WFDTNR fits 1" 1 1 /2" NPT threaded ferrous and brass, 1" - 2" sweat brass, 1 1 /2" polybutylene plastic and 1" pvc plastic tees having a 1" threaded NPT branch (see Figure 1 and chart for recommended tee depths). Installation Guidelines efore installing any waterflow alarm device, be thoroughly familiar with: NFP 72: Installation, Maintenance and Use of Local Protective Signalling Systems NFP 13: Installation of Sprinkler Systems, specifically Section 3.17 NFP 25: Inspection, Testing and Maintenance of Sprinkler Systems, specifically Chapters 4 and 5 NFP 13D: Standard for Residential Dwellings NFP 13R: Standard for Multifamily Dwellings Other applicable NFP standards, local codes and the requirements of the authority having jurisdiction. Failure to follow these directions may result in failure of the device to report a waterflow condition. System Sensor is N I

14 Figure 2. ssembly diagram: CTUTOR LEVER FLOW CTUTOR SSEMLY WTER FLOW FILLISTER HED SCREW COVER GROUND SCREW (GREEN) 1" NPT THRED MOUNTING PLTE PDDLE TMPER PROOF WRENCH (P/N WFDW) not responsible for devices that have been improperly installed, tested or maintained. 1. Mount the detector where there is adequate clearance for installation and removal and a clear view of it for inspection. See Figure 1 for mounting dimensions. 2. Locate to protect from damage, 6-7 feet above the floor. 3. On horizontal runs, position the detector on top of the pipe or on the side. Do not mount it upside down. 4. Mount detector at least 6 inches from a fitting which changes the direction of the water flow. 5. E SURE DIRECTION-OF-FLOW RROW MTCHES C- TUL DIRECTION OF FLOW IN THE PIPE. Mounting Instructions 1. This WFDTNR waterflow detector is designed to fit only the appropriate tee fitting. NOTE: Leg of tee perpendicular to flow of water must have a 1" NPT thread. Do not use a reducer to achieve the correct thread size. Failure to follow this instruction will result in failure of the detector to report a waterflow condition. 2. WFDT units are shipped without the paddles mounted to the actuator. Select the correct size paddle for the tee being used the appropriate nominal pipe diameter size is molded on the surface of the paddles). lign hole on stem of paddle with hole on actuator lever. Fasten together using a #4-40 x 1 / 4 " fillister head screw supplied in bag assembly. See Figure 2. Use only the screw provided with the WFDTNR. Drive screw head through hole in paddle until it seats firmly to actuator lever surface. No washer is required. For paddle replacement refer to Maintenance section. 3. Thread detector onto tee fitting and tighten with wrench. Use of thread sealant or tape is recommended. Use height gage (located at end of paddle tee) to ensure proper depth of detector on tee fitting. See Figure 1. Height gage must fit between top of tee fitting and under side of hex tee adapter. gap between gage and tee adapter is acceptable. When correctly installed, the detector must face in the proper direction of waterflow and be aligned with the pipe. 4. Remove the plastic cover with the tamper proof wrench provided. Move the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the problem before proceeding. CUTION e sure the direction-of-flow arrow points in the correct direction, otherwise a waterflow condition will go unreported. See Figure 2. Operational Testing lways notify a central station monitoring waterflow alarms before repairing, maintaining, or testing waterflow alarm devices. 1. Fill the sprinkler and check for leaks around the WFDTNR. If it leaks, check to see that the fittings are tight. If leak persists, drain the system and remove the detector (see removal instructions under Maintenance). Check for damaged threads or cracked fitting. Reinstall detector and check again for leaks. Do not proceed until all leaks have been stopped. 2. With cover removed, connect an ohmmeter or continuity tester across ( and ) terminal switch contacts. The ohmmeter should show an open circuit, no continuity (when the red switch buttons are depressed). 3. Deflect the actuator lever to release the switch buttons. The ohmmeter or continuity tester should show a short circuit when the switch buttons are released. 4. Open the inspector's test valve to allow the detector to indicate a flow condition. The detector should remain activated until the inspector's test valve is closed. ir pockets in the sprinkler system may prevent the detector from firing immediately. 5. Replace the cover and tighten the security screws with the tamper proof wrench. Store wrench is a secure place. Field Wiring 1. The WFDT has two SPDT switches. Switch contacts ( and ) are closed when water is flowing and open when water is not flowing. Connect the switches as shown in Figure 3 depending on the application. 2. When connected to a listed sprinkler/fire alarm control panel, the initiating circuit must be non-silenceable. N I

15 Figure 3. Field wiring: Switch 1 NOTE: Common and connections will close when vane is deflected, i.e., when water is flowing. Dual switches permit applications to be combined on a single detector. Strip Gauge Switch 2 CONTCT RTINGS 125/250 VC 24 VDC 10 MPS 2.5 MPS WFDTNR WFDTNR to nonsilenceable initiating zone of listed FCP end-of-line resistor Typical FCP Connection to power source compatible with bell Typical Local ell Connection local bell reak wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires. 3. ground screw is provided with all WFDT units. When grounding is required, clamp wire with screw in hole located between conduit entrance holes. See Figure 2. WRNING High Voltage. Electrocution Hazard. Do not handle live C wiring or work on a device to which C power is applied. Doing so may result in severe injury or death. Maintenance To prevent accidental water damage, control valves should be shut tightly and the system completely drained before waterflow detectors are removed or replaced. Inspect detectors monthly for leaks. Test detectors at least monthly as described under Operational Testing to insure proper operation. This device is not designed for use on dry pipe systems. Test more often if required by the authority having jurisdiction. Under normal conditions System Sensor waterflow detectors should provide years of trouble-free service. If, however, the switch enclosure becomes faulty, request Part No If damage occurs to paddle, order replacement kit PRK9. Refer to procedure below for removal of detector on pipe. Do not repair or replace any other waterflow detector components in the field. If any other part of the detector does not perform properly, replace the entire detector. Failure to follow this instruction may result in failure of the detector to report a waterflow condition. Proceed as follows to remove a detector: 1. Drain the pipe 2. Turn off electrical power to the detector, and then disconnect wiring 3. Unscrew WFDTNR from tee fitting N I

16 1. Waterflow detectors may not work or operate properly if sprinkler piping being monitored is plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems should be checked regularly for such blocking material, following the instructions in Chapter 5 of NFP Standard larms generated by the activation of waterflow detectors may not be received by a central station if telephone or other communication lines to the detector are out of service, disabled, or open. 3. Vane-type waterflow detectors have a normal service life WRNING The Limitations of Waterflow larm Devices of years. Hard water systems, however, may reduce waterflow detector service life to 4 or 5 years. 4. Waterflow detectors are not a substitute for insurance. uilding owners should always insure property and lives being protected by sprinkler systems. 5. If valves controlling the water supply to a sprinkler system are closed, vane-type waterflow detectors will not work. ll valves controlling a sprinkler water supply should be sealed or locked in the normally open position. The normally open position should be monitored by a sprinkler supervisory switch. System Sensor warrants its enclosed waterflow detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this waterflow detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company s obligation of this Warranty shall be limited to the repair or replacement of any part of the waterflow detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. fter phoning System Sensor s toll free number 800-SENSOR2 ( ) for a Return uthorization number, send defective units postage prepaid to: System Sensor, Three-Year Limited Warranty Repair Department, R #, 3825 Ohio venue, St. Charles, IL Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state. N I System Sensor 1996

17 INSTLLTION ND MINTENNCE INSTRUCTIONS OSY2 Gate Valve Supervisory Switch Division of Pittway 3825 Ohio venue, St. Charles, Illinois SENSOR2, FX: Specifications Contact Ratings: Dimensions: Maximum Stem Extension: 2 5 /8" Minimum Stem Extension: 5 /8" racket Span: 6 3 /4" 125/250 VC 24 VDC 5 3 /4"H X 3 1 /2"W X 3 1 /4"L Operating Temperature Range: F (0-49 C) Shipping Weight: 2 3 /4 lb. Important Please Read Carefully nd Save This manual contains important information about the installation and operation of supervisory switches. These instructions apply to System Sensor switches for outside screw and yoke valves only. Read all instructions carefully before beginning installation. Figure 1: WRNING Do NOT use this switch in explosive or potentially explosive atmospheres. Do NOT leave unused wires exposed. ll supervisory switch installations must comply with local codes and ordinances and the requirements of the authority having jurisdiction. dditional information is available in National Fire Protection ssociation standards NFP 13, 13D, 13R, 71, and 72. General Installation Considerations The OSY2 Supervisory Switch can be mounted on open yoke valves between 1 /2" and 12" in diameter in the positions shown in Figure 1 only. If the switch is installed with the actuator pointing upward, water may leak into the interior of the switch. Therefore, do NOT install the OSY2 with its actuating lever pointing upward. ll OSY2 models are equipped with a ground screw inside the switch housing near the conduit exit hole for those applications where grounding is required. Narrow Yoke Valves s Figure 2 suggests, installing the valve with mounting bolts inside the yoke is recommended. However, some valves may have yokes that are too narrow for this arrange- CTUTOR VERTICL (DOWN) CTUTOR HORIZONTL ment. If this is the case, the bolts can be positioned on the outside of the yoke. Limited Clearance Valves The OSY2 mounting bracket fits most of the open yoke valves used in fire protection systems. However, some of these valves, especially those less than 1 1 /2" in diameter, have irregularly shaped yokes or such limited clearances that the clamping bar cannot be installed properly and/or it causes the valve to bind. If this is the case, the use of the supplied J-bolts is required to attach the OSY2 to the valve (see J-olt Detail, Figure 2). Installation Procedure See Figures 2 and 3, as required, while performing the procedure that follows. Perform step 1 on valves 1 1 /2" in diameter and smaller only. Proceed directly to step 2 if the switch is being installed on a valve larger than 1 1 /2" in diameter. 1. Remove and discard the two C-clips and roller from the actuating lever. 2. Set the valve to its fully open position. Remove the OSY2 Supervisory Switch from the carton and adjust the position of the retaining washers to provide sufficient bolt length for the yoke thickness of the valve. N I

18 Figure 2: Wrench for tamper-resistant screws (P/N WFDW) Cover Tamper-resistant screws ctuating Cam Spring ctuating lever set screw Mounting screws Terminal block Seal ase housing Mounting racket "C" clip ctuating lever roller (2 thru 12"only) Valve Stem Carriage olt Yoke Clamping ar J-olt Detail Hex wrench (P/N HEXW) SLIDE CLMPING R TO REMOVE OR INSTLL. Retaining Washer Nut NOTE: LRGER GTE SHOWN (2" THRU 12"). WHEN INSTLLING SUPERVISORY SWITCH TO SMLLER GTE S (1/2" THRU 1 1/2") CRRIGE OLTS RE TO E LOCTED ON OUTORD SIDE OF YOKE. ON SMLL S WITH LIMITED CLERNCE THE USE OF J-OLTS MY E REQUIRED. N I

19 Figure 3: STEM GLND THREDED STEM HEX YOKE CLMPING R NOT SHOWN GROOVE GLND HEX NUT OR OLT Position the switch on the valve with the bolts on the inside (preferably) or outside of the yoke, depending on clearances. djust the position of the OSY2 as far as possible from the valve gland and in a location where the actuating lever contacts the unthreaded section of the valve stem (if the valve stem is already grooved, proceed directly to step 6). 3. When the switch is in position on the valve, slide the open end of the clamping bar onto the bolts and under the retaining washers. If necessary, adjust the length of the actuating lever by loosening the set screw on the cam, sliding the lever in or out, as appropriate, and retightening the set screw. The lever is properly adjusted when it clears the clamping bar. Tighten the nuts by hand and slide the OSY2 until the second switch trip points are found as the lever rests on the valve stem. This approximates the final position of the OSY2 after the valve stem is grooved. Carefully check all clearances of the bolts, actuator, mounting bracket, clamping bar, and OSY2 cover. djust the position as necessary. If clearance is a problem, refer to the Limited Clearance Valves (page 1) section of this manual. 4. Mark the point on the valve stem where the actuating lever contacts the valve stem. 5. Remove the OSY2 by loosening the nuts and sliding the clamping bar from beneath the retaining washers. Remove the OSY2 from the valve and set it aside. (a) Valves 1 1 /2" in diameter and smaller only. Use a 1 /4" untapered round file to file a groove 3 /32" deep in the valve stem at the mark that was made in step 4. e sure to remove any burrs resulting from the filing to avoid damaging the valve stem packing gland. (b) Valves larger than 1 1 /2" inches in diameter only. Use a 3 /8" untapered round file to file a groove 1 /8" deep in the valve stem at the mark that was made in step 4. e sure to remove any burrs resulting from the filing to avoid damaging the valve stem packing gland. 6. Mount the switch loosely with the actuating lever centered in the groove. When the switch is in position on the valve, slide the open end of the clamping bar onto the bolts and under the retaining washers, as indicated in Figure Ensure that the actuating lever does not hit the inside of the cover or the clamping bar at any point in its travel. If it does, adjust the length of the lever by loosening the set screw, sliding the lever in or out, as needed, and retightening the set screw. 8. djust the supervisory switch position on the valve so that both switches are depressed ( to circuit open) when the actuating lever is in the groove with the valve in the full open position. The to circuit should close when the valve is closed 1 /5 of its travel or 2 full turns of the handle, whichever is less. The switch produces an audible click when it closes. The switch closure can also be tested electrically by using an ohmmeter to test for continuity between its terminals. 9. Tighten the nuts securely with a wrench and check the operation of the OSY2 as in step 8. If necessary, reposition the OSY2 and test it again. 10. Wire the supervisory switch as shown in Figure Replace the OSY2 cover and tighten the tamper-resistant cover screws with the special wrench provided. Store this wrench in a secure location. 12. Test the operation of the OSY2 by closing the valve the 1 /5 of its travel distance or two full turns, whichever is less. The circuit between and should indicate a closure during this procedure. If it does not, readjust the supervisory switch and actuator positions until the switch closes when the valve is operated. Testing Test the operation of all supervisory switches before they are placed into service and at least semiannually, or as required by the authority having jurisdiction. NOTE: Notify the proper authorities that the supervisory switch(es) is (are) undergoing maintenance and, therefore, will be temporarily out of service. Disable the system or zone undergoing testing to prevent unwanted alarms. Test the operation of the OSY2 by closing the valve the 1 /5 of its total travel distance or two full turns, whichever is less. contact closure must occur during this procedure. If it does not, readjust the supervisory switch and actuator positions until the switch closes when the valve operated. N I

20 Figure 4. Supervisory switch wiring diagram: Switch 1 Top View Strip Gage Switch 2 CONTCT RTINGS 125/250 VC 24 VDC 10 MPS 2.5 MPS Sup. Switch Sup. Switch to nonsilenceable initiating zone of listed FCP end-of-line resistor Typical FCP Connection to power source compatible with bell local bell reak wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires. Typical Local ell Connection larms generated by the actuation of the activating lever may not be received by a central station if telephone or other communication lines to the detector are out of service, disabled, or open. 2. Supervisory switch alarm devices have a normal service life of years. WRNING The Limitations of Supervisory Switch larm Devices 3. Supervisory switches are not a substitute for insurance. uilding owners should always insure property and lives being protected. System Sensor warrants its enclosed supervisory switch to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this supervisory switch. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company s obligation of this Warranty shall be limited to the repair or replacement of any part of the supervisory switch which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. fter phoning System Sensor s toll free number 800-SENSOR2 ( ) for a Return uthorization number, send defective units postage prepaid to: System Sensor, Three-Year Limited Warranty Repair Department, R #, 3825 Ohio venue, St. Charles, IL Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state. N I System Sensor 1996

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold Features NEMA 4 solid metal enclosure Factory installed neoprene gasket 0-90 second field replaceable pneumatic retard 350 PSI system pressure rated Synchronized switch action Waterflow switches that are

More information

WFDE Series Waterflow Detector

WFDE Series Waterflow Detector WFDE Series Waterflow Detector The System Sensor WFDE series is compatible with pipe diameters ranging from 50mm through 200mm and can be mounted in a vertical or horizontal position. Features Compliant

More information

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature AutoTest VSR (VSR-AT) (EU) Features Assembled in USA 0-30 second field replaceable electronic retard Two SPDT (Form C) switch contacts Weatherproof Easy to read wire terminal designations Easy to read

More information

DH500 Intelligent Air Duct Smoke Detector Housing

DH500 Intelligent Air Duct Smoke Detector Housing INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500 Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com Specifications

More information

0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS

0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS INSTALLATION AND MAINTENANCE INSTRUCTIONS 2251EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2,

More information

DH400 Air Duct Smoke Detector

DH400 Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS DH400 Air Duct Smoke Detector Before Installing Please thoroughly read System Sensor s Guide for Proper Use of Smoke Detectors in Duct Applications (I56-473-XX),

More information

D2E Duct Smoke Detector

D2E Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS D2E Duct Smoke Detector Specifications Operating Temperature: 20 to 60 C Storage Temperature: 20 to 60 C Humidity: 0% to 93% Relative Humidity Non-condensing Air

More information

DH100ACDCI Ionization Air Duct Smoke Detector

DH100ACDCI Ionization Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),

More information

DH500ACDC Intelligent Air Duct Smoke Detector Housing

DH500ACDC Intelligent Air Duct Smoke Detector Housing INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500ACDC Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Specifications Length: 14.5

More information

DH100ACDCI Ionization Air Duct Smoke Detector

DH100ACDCI Ionization Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),

More information

Fire Sprinkler Monitoring Products. Solutions and Service for Sprinkler System Integrity

Fire Sprinkler Monitoring Products. Solutions and Service for Sprinkler System Integrity Fire Sprinkler Monitoring Products Solutions and Service for Sprinkler System Integrity waterflow monitoring Monitoring Fire Sprinkler System Flow During a fire condition, sprinkler system reliability

More information

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800-736/7672, FAX: 630-377-6495 Before

More information

1400 Direct Wire Ionization Smoke Detector

1400 Direct Wire Ionization Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS 1400 Direct Wire Ionization Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1800SENSOR2, FAX: 6303776495 Specifications Diameter:

More information

Installation Instructions

Installation Instructions GE Consumer & Industrial Appliances Installation Instructions Junction Box Cover Within this user bag, you will find a junction box cover and a #10 hex head screw used to attach the junction box cover

More information

7251DH Intelligent Air Duct Smoke Detector

7251DH Intelligent Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS 7251DH Intelligent Air Duct Smoke Detector Specifications Length: Width: Depth: Weight: Operating Temperature Range: Operating Humidity Range: Duct Air Velocity:

More information

DH100LP Air Duct Smoke Detector with Extended Air Speed Range

DH100LP Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH100LP Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 The Innovair DH100LP

More information

Installation Instructions

Installation Instructions GE Consumer & Industrial Appliances Installation Instructions Junction Box Cover Within this user bag, you will find a junction box cover and a #10 hex head screw used to attach the junction box cover

More information

DNRECL Eclipse Duct Smoke Detector

DNRECL Eclipse Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS DNRECL Eclipse Duct Smoke Detector 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com SPECIFICATIONS Operating

More information

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800/736-7672, FAX: 630-377-6495 www.systemsensor.com

More information

SC-6 Six Supervised Control Module

SC-6 Six Supervised Control Module INSTALLATION AND MAINTENANCE INSTRUCTIONS SC-6 Six Supervised Control Module SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories:

More information

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS Air Duct Smoke Detector with Extended Air Speed Range A Division of Pittway 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495 The Innovair

More information

DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800/736-7672, FAX: 630-377-6495 Before

More information

CZ-6A Six Zone Interface Module

CZ-6A Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS CZ-6A Six Zone Interface Module 658 Kitimat Rd. Unit #6 Mississauga, Ontario L5N T5-800-SENSOR, FAX: 905-8-077 www.systemsensor.ca SPECIFICATIONS Normal Operating

More information

Installation Instructions

Installation Instructions Installation Instructions Built-In Dishwasher If you have questions, call 800-GECARES or visit our website at: www.geappliances.com BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT

More information

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495

More information

Built-In Dishwasher. Installation Instructions. BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT The dishwasher MUST be

Built-In Dishwasher. Installation Instructions. BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT The dishwasher MUST be Installation Instructions Built-In Dishwasher If you have questions, call 800.GE.CARES (800.432.2737) or visit our website at: www.ge.com BEFORE YOU BEGIN Read these instructions completely and carefully.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Harwil Model Q-16 fluid flow switch is intended for use in flow lines with fluids not harmful to brass, stainless steel, and EPDM. The switch is used to signal, start, or stop electrically operated equipment

More information

ZC450-IB-09/13-01 US. Instruction Booklet. Zonecheck 450

ZC450-IB-09/13-01 US. Instruction Booklet. Zonecheck 450 ZC450-IB-09/13-01 US Instruction Booklet Zonecheck 450 Zonecheck 450 Copyright This instruction booklet is property of Project Fire Products Ltd and must not be used or copied without its written permission.

More information

DNR-AUS Duct Smoke Detector

DNR-AUS Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3642-000R DNR-AUS Duct Smoke Detector Specifications Operating Temperature: 20 to 70 C ( 4 to 158 F) 0 C to 49 C (32 F to 120 F) with module installed in the

More information

TECHNICAL DATA. Wet 26a. February 22, 2009

TECHNICAL DATA. Wet 26a. February 22, 2009 February 22, 2009 Wet 26a 1. DESCRIPTION The Viking Alarm Check Valve serves as a check valve by trapping pressurized water above the clapper and preventing reverse flow from sprinkler piping. The valve

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-284. Series PSE-800 Probe Type Low Water Cut-Off for Steam Boilers

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-284. Series PSE-800 Probe Type Low Water Cut-Off for Steam Boilers Series PSE-800 Probe Type Low Water Cut-Off for Steam Boilers McDonnell & Miller Installation & Maintenance Instructions MM-284 U.S. Patents 7,161,492 & 7,436,187 pplications: Residential and Commercial!

More information

Fire Sprinkler Systems Monitoring

Fire Sprinkler Systems Monitoring A P P L I C A T I O N S G U I D E Fire Sprinkler Systems Monitoring A P P L I C A T I O N S G U I D E Fire Sprinkler Systems Monitoring Contents Preface.............................................................

More information

DNR Duct Smoke Detector

DNR Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3051-004R DNR Duct Smoke Detector Specifications Operating Temperature: 4 to 158 F ( 20 to 70 C); 32 F to 120 F (0 C to 49 C) with module installed in the

More information

Installation Instructions

Installation Instructions Installation Instructions Built-In Dishwasher If you have questions, call 800-944-9400(US),800-245-8352(Canada)or visit our website at: www.frigidaire.com BEFORE YOU BEGIN Read these instructions completely

More information

Audi-Larm Audible Alarm

Audi-Larm Audible Alarm Audi-Larm Audible Alarm MAINTENANCE AND REPAIR TAL 1706 (L) Rev. 7 MSA 2017 Prnt. Spec. 10000005389(I) Mat. 10093084 Doc. 10093084 REPLACEMENT KITS AND PARTS LIST TAL 1706 (L) Rev. 7-10093084 2 Exploded

More information

Dishwasher Installation Instructions DW 24XT/DW 24XV

Dishwasher Installation Instructions DW 24XT/DW 24XV Dishwasher Installation Instructions DW 24XT/DW 24XV Installation Instructions Dishwasher BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT Observe all governing codes and ordinances.

More information

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels Installation Instructions For the 18 Built-In Dishwasher and Front Color Panels Printed in USA 154232102 Before You Begin DO NOT INSTALL DISHWASHER UNTIL YOU HAVE READ ALL INSTRUCTIONS. FOR YOUR SAFETY,

More information

2-Stage Under Counter Filtration System Model: WP-2 LCV

2-Stage Under Counter Filtration System Model: WP-2 LCV INSTALLATION, OPERATION AND MAINTENANCE MANUAL Save manual for future reference 2-Stage Under Counter Filtration System Model: WP-2 LCV IMPORTANT If you are unsure about installing your WATTS water filter,

More information

52 SAN LUCAS CEILING FAN

52 SAN LUCAS CEILING FAN 52 SAN LUCAS CEILING FAN Owner s Manual Models #20551 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9 a.m.-

More information

OSCILLATING WALL FAN. LISTED For Damp Location E ITEM # MODEL #JP18EB3. Español p. 15 ATTACH YOUR RECEIPT HERE.

OSCILLATING WALL FAN. LISTED For Damp Location E ITEM # MODEL #JP18EB3. Español p. 15 ATTACH YOUR RECEIPT HERE. Off On ITEM #0275422 OSCILLTING WLL FN MODEL #JP18EB3 Harbor Breeze is a registered trademark of LF, LLC. ll Rights Reserved. Español p. 15 TTCH YOUR RECEIPT HERE Serial Number Purchase Date LISTED For

More information

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description The Tyco ILLUSION,

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE Page 1 of 12 1. (Refer to Figures 1-7.) Viking supervised Single-Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system piping

More information

SAN RAPHAEL PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET

SAN RAPHAEL PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET SAN RAPHAEL PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET BEFORE YOU BEGIN HOW TO USE THESE INSTRUCTIONS Please read these instructions carefully to familiarize yourself with the required tools, materials,

More information

Operating Instructions & Parts Manual Models 99533, 99532

Operating Instructions & Parts Manual Models 99533, 99532 Operating Instructions & Parts Manual Models 99533, 99532 2 Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Installation Instructions Built-In Dishwasher

Installation Instructions Built-In Dishwasher RINSE CHINA CRYSTAL SPEED CYCLE NORMAL WASH COOK WARE SELECTIONS ANTI BACTERIA START RESET ENHANCEMENTS DELAY HOURS ADDED HEAT PRE WASH HEATED DRY TO LOCK CONTROLS PRESS HEATED DRY FOR 3 SECONDS GE Consumer

More information

BARRINGTON PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET K-4327

BARRINGTON PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET K-4327 BARRINGTON PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET K-4327 BEFORE YOU BEGIN INSTALLER HAZARD NOTIFICATION WARNING: Risk of injury or water damage. Contents of vessel under pressure can cause severe

More information

18 INCHES, OSCILLATING STAND FAN

18 INCHES, OSCILLATING STAND FAN To Buy: Contact Sylvane at 800-934-9194 or visit www.sylvane.com For Product Support: Contact Soleus Air at (888) 876-5387 18 INCHES, OSCILLATING STAND FAN OWNER S MANUAL Model # FSM-45 PLEASE READ AND

More information

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2 I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

Technical Data. Installation

Technical Data. Installation Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems Customer Service/Sales: Tel: (15) 6-0700 / (800) 5-651

More information

TILGHMAN CEILING FAN. LISTED For Damp Location E ITEM # MODEL #WCK52LMW5N WCK52NWZ5N. Español p. 20 ATTACH YOUR RECEIPT HERE

TILGHMAN CEILING FAN. LISTED For Damp Location E ITEM # MODEL #WCK52LMW5N WCK52NWZ5N. Español p. 20 ATTACH YOUR RECEIPT HERE ITEM #0294980 0294981 TILGHMAN CEILING FAN Harbor Breeze is a registered trademark of LF, LLC. All Rights Reserved. MODEL #WCK52LMW5N WCK52NWZ5N Español p. 20 ATTACH YOUR RECEIPT HERE Serial Number Purchase

More information

Gemini. Gemini Instruction Booklet. Addressable & Conventional versions GE-IB-06/18-01

Gemini. Gemini Instruction Booklet. Addressable & Conventional versions GE-IB-06/18-01 Gemini Gemini Instruction Booklet Addressable & Conventional versions GE-IB-06/18-01 Copyright This instruction booklet is property of Project Fire Products Ltd and must not be used or copied without its

More information

TECHNICAL DATA. model c-2

TECHNICAL DATA. model c-2 Page 1 of 6 1. PRODUCT DESCRIPTION The Viking Model C-2 is a rate-of-rise releasing device for use on hydraulic and pneumatic release systems controlling operation of Viking deluge valves on deluge or

More information

DNRHS Intelligent Air Duct Smoke Detector

DNRHS Intelligent Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS DNRHS Intelligent Air Duct Smoke Detector Specifications Length: Width: Depth: Weight: Operating Temperature Range: Operating Humidity Range: Duct Air Velocity:

More information

A PROUD HERITAGE OF EXPERIENCE & QUALITY DISHWASHER BR- DWSH01- S

A PROUD HERITAGE OF EXPERIENCE & QUALITY DISHWASHER BR- DWSH01- S A PROUD HERITAGE OF EXPERIENCE & QUALITY DISHWASHER BR- DWSH01- S W W W. V I N O T E M P. C O M Installation Instructions Dishwasher BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT

More information

Instant Hot Water Dispenser Owner s Manual

Instant Hot Water Dispenser Owner s Manual Model Hot1 Instant Hot Water Dispenser Owner s Manual Installation, Care & Use Instalacion, cuidado & uso Installation, soin et utilisation WHAT YOU SHOULD KNOW BEFORE YOU BEGIN For your satisfaction and

More information

Installation Instructions Built-In Dishwasher

Installation Instructions Built-In Dishwasher GE Consumer & Industrial Appliances Installation Instructions Built-In Dishwasher If you have questions, call 800.GE.CARES (800.432.2737) or visit our website at: www.ge.com BEFORE YOU BEGIN Read these

More information

24 & 30 Quiet Design Oscillating Wall Mount Fan

24 & 30 Quiet Design Oscillating Wall Mount Fan Operating Instructions & Parts Manual Models: 99538, 99539 Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

DNR Duct Smoke Detector

DNR Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3051-007R DNR Duct Smoke Detector Specifications Operating Temperature: 4 to 158 F ( 20 to 70 C); 32 F to 120 F (0 C to 49 C) with module installed in the

More information

ST. KITTS CEILING FAN

ST. KITTS CEILING FAN ITEM #0845047 ST. KITTS CEILING FAN MODEL #40829 Questions, problems or missing parts? Before returning this item to your retailer, call our customer service department at 1-800-643-0067, Monday - Thursday,

More information

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage General Description

More information

WFD Series Waterflow Detector

WFD Series Waterflow Detector S P R I N K L E R S Y S T E M S M O N I T O R I N G WFD Series Waterflow Detector UL Models WFD20 WFD25 WFD30-2 WFD35 WFD40 WFD50 WFD60 WFD80 ULC/Canadian Models WFD20A WFD25A WFD30-2A WFD35A WFD40A WFD50A

More information

Installation Instructions

Installation Instructions Installation Instructions Free-Standing Electric Ranges Questions? Call 800.GE.CRES (800.432.2737) or Visit our Website at: ge.com EFORE YOU EGIN Read these instructions completely and carefully. IMPORTNT

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

MKTF CRO-Series 5-Stage Reverse Osmosis System Installation and Maintenance Manual

MKTF CRO-Series 5-Stage Reverse Osmosis System Installation and Maintenance Manual MKTF - 215 CRO-Series 5-Stage Reverse Osmosis System Installation and Maintenance Manual Please fill out the following information at the time of installation. Save for future reference. Model: Date Code:

More information

CEILING FAN LIGHT KIT

CEILING FAN LIGHT KIT ITEM #0384193 #0384195 CEILING FN LIGHT KIT MODEL #EC-WNWZ #EC-WLMW Español p. 10 Federal regulations require ceiling fans with light kits manufactured or imported after January 1, 2009, to limit total

More information

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System 1 Revised 11/18/10 2320 Lakecrest Drive, Pekin IL 61554 PH. (888) 747-4389 Fax (309) 495-0625 Website: www.getzequipment.com LIMITED

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS TM READ AND SAVE THESE INSTRUCTIONS CF2000AB02 CF2000AW02 CF2000BC02 CF2000ORB02 Model No. CF2000PW02 CF2000WB02 CF2000WW02 DATE CODE: The date code of this fan may be found on the box, stamped in ink

More information

SUTTON 52 CEILING FAN

SUTTON 52 CEILING FAN SUTTON 52 CEILING FAN MODELS #50188, 50189, 50190 Español p. 19 Questions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-877-361-3883, Monday - Thursday,

More information

IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS 1800 Power Curve Snowthrower Model No. 38381 Serial No. 313000001 and Up Form No. 3373-449 Rev A Operator's Manual Register your product at www.toro.com IMPORTANT SAFETY INSTRUCTIONS When using an electrical

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Proper Disposal of Your Old Refrigerator WRNING Suffocation Hazard Remove doors from your old refrigerator. Failure to do so can result in death or brain damage. IMPORTNT: hild entrapment and suffocation

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE January 27, 2012 311a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system.

More information

MAYFIELD CEILING FAN LISTED E ITEM # MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE.

MAYFIELD CEILING FAN LISTED E ITEM # MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE. Harbor Breeze is a registered trademark of LF, LLC. All Rights Reserved. ITEM #0331094 0331096 MAYFIELD CEILING FAN MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE Serial Number Purchase

More information

TOUCHDOWN 48 CEILING FAN

TOUCHDOWN 48 CEILING FAN TOUCHDOWN 48 CEILING FAN MODEL #50205 Español p. 20 Questions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-877-361-3883, Monday - Thursday, 8 am

More information

52 STRATHMERE CEILING FAN

52 STRATHMERE CEILING FAN 52 STRATHMERE CEILING FAN Owner s Manual Models #20341 If a problem cannot be remedied or you are experiencing difficulty with installation, please contact the Service Department: 1-877-459-3267, 9 a.m.-

More information

HI Industrial Utility Heater HI Soleus Air International

HI Industrial Utility Heater HI Soleus Air International HI1-50-03 Industrial Utility Heater HI1-50-03 2010 Soleus Air International Thank you for choosing a Soleus Air Utility Heater. This owner s manual will provide you with valuable information necessary

More information

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description. Technical Services: Tel: (00) 31-9312 / Fax: (00) 91-5500 Customer Service/Sales: Tel: (1) 50-5000 / (00) 55-523 Fax: (1) 50-5010 / (00) -1295 Model A Pipe Line Strainer 3,,, & 10 Inch (DN0, DN100,, DN200

More information

Nitin Ventures FZE. (A Division of Nitin Fire Protection Industries Ltd.)

Nitin Ventures FZE. (A Division of Nitin Fire Protection Industries Ltd.) Model : A TECHNICAL DATA : Model Nominal Size Maximum Service Pressure Threaded Opening Mounting Flange Connection Trim Factory Hydrostatic Test Pressure Frictional Loss in Terms of Equivalent Length of

More information

Installation Guide. For Models: E-MLV36BNK4LK1 E-MLV36ESP4LK1 E-MLV36WW4LK1 READ THESE INSTRUCTIONS AND AND SAVE THEM FOR FUTURE USE

Installation Guide. For Models: E-MLV36BNK4LK1 E-MLV36ESP4LK1 E-MLV36WW4LK1 READ THESE INSTRUCTIONS AND AND SAVE THEM FOR FUTURE USE READ THESE INSTRUCTIONS AND AND SAVE THEM FOR FUTURE USE Federal regulations require ceiling fans with light kits manufactured or imported after January 1, 2009, to limit total wattage consumed by the

More information

ELSTON 52 CEILING FAN

ELSTON 52 CEILING FAN ELSTON 52 CEILING FAN MODEL #10290 Español p. 21 Questions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-877-361-3883, Monday - Thursday, 8 am -

More information

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. Page 1 of 9 1. (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally held closed by supervisory

More information

IMPORTANT INFORMATION. Revised Dishwasher Installation Instructions

IMPORTANT INFORMATION. Revised Dishwasher Installation Instructions IMPORTANT INFORMATION Revised Dishwasher Installation Instructions To obtain a revised copy of the entire Dishwasher User s Manual, go to www.eurotechappliances.com. SPECIAL EDITION 11-20-02 SAVE THESE

More information

52 BARSTOW CEILING FAN

52 BARSTOW CEILING FAN 52 BARSTOW CEILING FAN Owner s Manual Models #20519 If a problem cannot be remedied or you are experiencing difficulty with installation, please contact the Service Department: 1-877-459-3267, 9 a.m.-

More information

PRO Series Energy Star Ceiling Fan Owner's Manual

PRO Series Energy Star Ceiling Fan Owner's Manual READ AND SAVE THESE INSTRUCTIONS Model Numbers: CF713BS00 CF713ORB00 CF713WW00 Net Weight: 19.0 Lbs. PRO Series Energy Star Ceiling Fan Owner's Manual Part No. F40BP74200002 Form No. BP7420-2 ETL Model

More information

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats. Three Phase Simplex Installation Instructions and Operation/Troubleshooting Manual This control panel must be installed and serviced by a licensed electrician in accordance with the National Electric Code

More information

! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions. McDonnell & Miller Installation & Maintenance Instructions MM-607(B) Series FS7-4 Industrial Liquid Flow Switch (specified models only) Series FS7-4 OPERATION This control is an independently mounted water

More information

MODELS 304GC, 304GCX, 314GC, and 314GCX

MODELS 304GC, 304GCX, 314GC, and 314GCX 2562109A REV. A1 0317 Printed in U.S.A. MODELS 304GC, 304GCX, 314GC, and 314GCX INSTALLATION AND SERVICE INSTRUCTIONS FOR SELECTONE Limited Warranty This product is subject to and covered by a limited

More information

SOLO OWNERS MANUAL, OPERATING INSTRUCTIONS & INSTALLATION INSTRUCTIONS

SOLO OWNERS MANUAL, OPERATING INSTRUCTIONS & INSTALLATION INSTRUCTIONS SOLO OWNERS MANUAL, OPERATING INSTRUCTIONS & INSTALLATION INSTRUCTIONS READ MANUAL BEFORE OPERATING SYSTEM Read the owner s manual thoroughly before operating to ensure the most efficient use of the system.

More information

48 TAYLOR CEILING FAN

48 TAYLOR CEILING FAN 48 TAYLOR CEILING FAN Owner s Manual Models #20554 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9 a.m.- 5 p.m.

More information

D1C HP Centrifugal Grinder Pump Installation & Service Manual with Parts List. Grinder Pump for Residential and Pressure Sewer Applications

D1C HP Centrifugal Grinder Pump Installation & Service Manual with Parts List. Grinder Pump for Residential and Pressure Sewer Applications 2HP Centrifugal Grinder Pump Installation & Service Manual with Parts List D1C20-21 Grinder Pump for Residential and Pressure Sewer Applications NOTE! To the installer: Please make sure you provide this

More information

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description The Tyco

More information

FLUSH WATER SAVER DUAL FLUSH KIT

FLUSH WATER SAVER DUAL FLUSH KIT FLUSH CH ICE Version 12.26.08 FC002 WATER SAVER DUAL FLUSH KIT Dear Consumer; You have purchased a high quality water saver dual flush toilet valve kit. Every care has been taken during manufacturing to

More information

52 BAYTOWNE CEILING FAN

52 BAYTOWNE CEILING FAN 52 BAYTOWNE CEILING FAN Owner s Manual Models #20501 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9 a.m.- 5

More information

The Series LFII (TY3596) Residential

The Series LFII (TY3596) Residential Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series LFII Residential Concealed Pendent Sprinklers, Flat Plate 4.9 K-factor General Description The Tyco Rapid Response Series LFII (TY3596)

More information

Worldwide Contacts. Technical Data

Worldwide Contacts.  Technical Data Worldwide Contacts www.tyco-fire.com Model BFV- Butterfly Valve Wafer Style General Description The TYCO Model BFV- Wafer Style Butterfly Valves are indicating type valves designed for use in fire protection

More information

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA. 319a. January 27, 2012 January 27, 2012 319a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally

More information

harborbreezeoutlet.com

harborbreezeoutlet.com Harbor Breeze is a registered trademark of LF, LLC. All Rights Reserved. ATTACH YOUR RECEIPT HERE Serial Number Purchase Date ITEM #0373684 BUILDER S SERIES CEILING FAN MODEL #40016 Español p. 18 Questions,

More information

Camarillo 52 Ceiling Fan

Camarillo 52 Ceiling Fan Owner s Manual Camarillo 52 Ceiling Fan Part # 269263, 269259, 269287 Model # 32091, 32092, 32087 Exclusively Distributed by: HD Supply Facilities Maintenance, Ltd. Atlanta, GA 30339 2017 Made in China

More information

Battery Powered Actuator with Watering Timer RBC MVA

Battery Powered Actuator with Watering Timer RBC MVA Battery Powered Actuator with Watering Timer RBC MVA I N S T R U C T I O N M A N U A L TABLE OF CONTENTS 1. Introduction 1 2. About the RBC MVA battery operated timer 1 3. Component identification 1 4.

More information

Bliss Box Former Troubleshooting. 6.1 Troubleshooting Chart. Troubleshooting INTRODUCTION SAFETY PROCEDURES

Bliss Box Former Troubleshooting. 6.1 Troubleshooting Chart. Troubleshooting INTRODUCTION SAFETY PROCEDURES 6.0 Bliss Box Former 1.0 INTRODUCTION Table 6-1 provides a logical sequence of tests that are designed to isolate problems with the Bliss Box Former machines. This table includes a list of probable causes

More information

COMPRESSED AIR DRYER. SAFETY... Page 2 MAINTENANCE... Page 5. INSTALLATION... Page 3 PARTS AND KITS... Page 6

COMPRESSED AIR DRYER. SAFETY... Page 2 MAINTENANCE... Page 5. INSTALLATION... Page 3 PARTS AND KITS... Page 6 OWNERS MANUAL BOSS COMPRESSED AIR DRYER Distributed by Air & Vacuum Process, Inc. Phone: 281-866-9700 Fax: 281-866-9717 Email: sales@airvacuumprocess.com SAFETY... Page 2 MAINTENANCE... Page 5 INSTALLATION...

More information