1 IEEE Transformer Committee PC Distribution Transformer Monitoring - User Mark Scarborough Electrical Engineering Consultant DuPont January 9, 2019
2 Transformer Types in DuPont Control power Dry-type in MCCs and control panels Small dry-type Lighting, receptacle, instrument power panel type 5kVA 330kVA (1 phase and 3 phase) Specialty Dry-type and fluid filled for rectifier and ASD applications Pole top Small power Some 20 45MVA main substation transformers Distribution (substation) dry-type VPI conventional wound and cast coil 750kVA 3000kVA Distribution (substation) fluid filled Mineral oil, natural ester, silicone insulation fluids 750kVA 5000kVA (some 10MVA and 30MVA) Pad-mounted Mineral oil and natural ester fluids 100kVA 3000kVA
3 Typical Distribution System Incoming power Purchased power substations Mostly all owned by Utilities 230kV down to 12.47kV Internal plant distribution Typically medium voltage (1 35kV) but mostly 2.4kV to 13.8KV. Few 34.5kV system. Utilization 480V and 575V for most applications 2.4kV and 4.16kV for motor applications about 250HP and above 120V / 230V for small loads Grounding B-Phase HGR LRG Soild
4 Transformer Monitoring Techniques Control power, small dry-type, pole top Usually don t do anything. Investigate when something doesn t work or power goes out. Some pole tops and small dry-types may get an infrared inspection. Visual Probably the most common but questionable as to what people know what to look for. Some plants require an operator or maintenance technician to walk the main electrical system from substation to substation daily, weekly, or monthly. Looking for abnormal sounds and or smells, leaks, broken gages, deterioration in paint system. Infrared Inspection Typically on an annual basis for most facilities. Good way to see if cooling system is working or if low fluid level.
5 Transformer Monitoring Techniques If transformers are fluid filled, then very good at taking samples for oil screen and DGA on an annual basis. Typical issues with sample methods and labs and reporting and interpretation. Need to realize that you have to put some oil back in occasionally. If critical application, will shut down on a 2 or 4 year interval to do inspection, testing, and cleaning. Planned shutdowns sometimes are impossible until the system shuts down automatically.
6 Transformer Monitoring Techniques Internal Specification Three (3) internal standards / guidelines Fluid Filled 300kVA to 10MVA, 3 Ph, primary voltage 2,400 to 46,000V Dry-Type 300 to 7.5MVA, 3 Ph, primary voltage 2,400 to 34,500V Pad Mount 2500kVA and below, primary voltage of 34,500V and below and a secondary voltage of 600V and below Each standard describes the feature sets required on each transformer type. User can add or take away as necessary for their application.
7 Transformer Monitoring Techniques Fluid Filled Standard Field Dial thermometer with alarm and control contacts. Pressure / vacuum gage. Pressure relief valve. Large pressure relief device with alarm contacts (sometimes directional shield). Magnetic liquid level gauge with alarm contacts. Optional / Custom Push to test circuit and/or current monitoring (4-20mA signal) of space heater circuit in ATCs or control box. Space heater control? Thermostat or no thermostat? Fan controls and aux contacts off of fan starter and/or control switch. N2 bottle monitoring system with alarms. Sudden or fault pressure relay with trip and alarm contacts. Winding hot-spot temperature indicator relay with alarm contacts. Add alarm contacts to pressure / vacuum gage. Infrared view ports on ATC.
8 Transformer Monitoring Techniques Dry- Type Standard Winding temperature with 3- phase hot spot temperature indication with peak indicator, contacts for alarm, trip and fan control and fan exerciser. (Typically this is a self contained package from the vendor.) Infrared view ports. Cooling fans w/ running status Optional / Custom Push to test circuit and/or current monitoring (4-20mA signal) of space heater circuit in ATCs or control box. Space heater control? Thermostat or no thermostat? Infrared view ports on ATC.
9 Transformer Monitoring Techniques Pad- Mounted Standard Liquid level gauge on 500kVA and above. Dial type thermometer with peak indicator on 500kVA and above. Vacuum / pressure gage on 500kVA and above. Pressure relief device. Large pressure relief device with alarm contacts on 1000kVA and above. Optional / Custom Require that sample valve be accessible outside of the HV and LV compartments. Require that all gages be accessible outside of the HV and LV compartments. Infrared view ports on HV and LV compartments. Alarm contacts on liquid level gage, liquid thermometer, and vacuum / pressure gages.
10 Alarm and Trip Contacts? In most cases, these transformers are located in an industrial facility and feed a substation or electrical room that has local DCS / PLC (control system) I/O. Historically, some or all of the alarm contacts would be hard wired to local DCS / PLC I/O cabinets. If it didn t exist, then it basically didn t get wired any where. More recently
11 Alarm and Trip Contacts?. we have been using the I/O capabilities on microprocessor based protective relaying and even expansion I/O modules for such devices.
12 Example #1 13.8kV Metal Clad Switchgear Radial feed to 2500kVA transformer but looped to additional substations. Switched breaker local to each substation. Microprocessor relay local to substation not capable of handling I/O from transformer so wired to DCS local I/O.
13 Construction Interconnection Dwg
14 Example # kV Metal Clad Switchgear Radial feed to 1000kVA substation transformer near by. SEL-787 protective relay for transformer with differential.
15 Construction Interconnection Dwg
16 MV Switchgear Vendor Schematic
17 Transformer Vendor Drawing
18 Example #3
19 Signals and What Action? So now we have gotten the signals to the plant DCS or PLC system. A DCS screen or HMI screen is developed with the alarm points. DCS / PLC system is monitored by Operation / Operations. Sometimes they don t know how to respond. Started developing action / resolution matrix. Call the on call maintenance electrician? Go to field and look at the equipment? System automatically send Text message to on call maintenance electrician response? Shutdown the process so the transformer can be shutdown? Alarms can go into a PI Data Historian system but not aware of active trending.
20 Misc. Topics / Considerations Confusion as to what to do with an alarm comes in. What action is required? Firewalls and cyber security. Not all sites have a centralized DCS or PLC to connect to. Typically do not monitor of pad mounted transformer but we have some that are in critical applications. Been some interest in: On line monitoring for moisture. (On line moisture removal systems in service.) On line monitoring for DGA monitoring. Better monitoring of dry-type transformers. Have had some sudden failures. Starting to experiment with wireless communications technology for instruments. Thinking may be able to use for transformers because not part of process control. Trending / data collection.
21 Thank You. Questions / Discussion
A CASE STUDY ON FAILURE OF DRY TYPE TRANSFORMERS IN DISTRIBUTION SYSTEM
A CASE STUDY ON FAILURE OF DRY TYPE TRANSFORMERS IN DISTRIBUTION SYSTEM by B.S.RAJPUROHIT, GAURAV SAVLA, NAUSHAD ALI, P.K.PANDA, S.K.KAUL, H.MISHRA* ENGINEERING SERVICES GROUP, BHABHA ATOMIC RESEARCH CENTRE
More informationBrown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA
PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities
More informationWhat Utility Analytics means to Exelon
What Utility Analytics means to Exelon Presented by Bart Enright IT Director Smart Grid Initiatives at ComEd Exelon s Analytic Journey Exelon Utilities Overview T&D Grids Data Visualization Data Analytics/Notifications
More informationNLR ELECTRIC MURRAY HYDRO PLANT NORTH LITTLE ROCK, ARKANSAS
NLR ELECTRIC MURRAY HYDRO PLANT NORTH LITTLE ROCK, ARKANSAS January, 2013 Infrared Inspection Report NLR Electric Murray Hydro Plant Company Contact James Bray Project: 09170113 2605 CHARTER OAK DRIVE,
More information1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection
Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication
More informationSIDEWINDER DRILLING RIG 107 HOUSTON, TEXAS
SIDEWINDER DRILLING RIG 107 HOUSTON, TEXAS January, 2017 Infrared Inspection Report Sidewinder Drilling Rig 107 Lufkin, Texas Company Contact: Jesse Russell Project: 06050117 2605 CHARTER OAK DRIVE, LITTLE
More informationMaintenance Best Practices & Intervals for Substation Equipment. Presented by: Paul Schlies, President/CEO Energis High Voltage Services, Inc.
Maintenance Best Practices & Intervals for Substation Equipment Presented by: Paul Schlies, President/CEO Energis High Voltage Services, Inc. Background - 40 Years in the Industry Education NWTC (Northeast
More informationVAMP 120 & 121. Arc flash detection units. Product picture
Arc flash detection units VAMP 120 and 121(D) are extremely fast arc flash detection units for LV and MV switchgear and controlgear. The units are especially designed to increase the safety and to minimize
More informationGas ventilation monitoring and control system
Gas ventilation monitoring and control system A case study Regulations and customer requirements surrounding the operation and maintenance of gas and ventilation monitoring and control systems in underground
More informationITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual
ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,
More informationCIRCUIT BREAKER - GAS
CIRCUIT BREAKER - GAS Capabilities: In a large substation, circuit breakers are used to interrupt any short-circuits or overload currents that may occur on the network. A 345 kv, high voltage, three position/phase
More informationUser s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas
User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5
More informationIndex Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:
Systems Index Systems - Systems Systems...1 -.16 General information Description...1 System description...2 Overview...3 Ordering details Arc monitor with detectors...4 Current sensing unit...5 Technical
More informationA. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing
A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and 2. Number: PRC-005-1.1b 3. Purpose: To ensure all transmission and generation Protection Systems affecting the reliability
More informationControl Panel For Water Wash Hoods AM2
Control Panel For Water Wash Hoods AM2 For further information Call: (919) 554-1025 Or Fax: (919)554-1525 Aqua-Matic 117 Franklin Park Ave. Youngsville, NC 27506 TABLE OF CONTENTS AQUA-MATIC LIMITED WARRANTY
More informationCONTINUOUS MONITORING IS ON THE RISE:
CONTINUOUS MONITORING IS ON THE RISE: CAN YOU ADAPT? BY WILLIAM HIGINBOTHAM, EA Technology LLC Electrical testing companies have traditionally built their businesses by periodically running tests on electrical
More informationNFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In?
NFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In? Adrian Messer, Manager of US Operations UE Systems, Inc. Ph: 864-224-4517 Cell: 914-282-3504 Web: www.uesystems.com
More informationVAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits
Arc Protection 01 VAmP 120 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during
More informationR E C T I F I E R I N V E R T E R C O N V E R T E R SB7
SCR Battery Charger Product Specifications Description The is RIC Electronics premiere SCR battery charger/rectifier. The provides power to critical DC loads through a wide range of outputs and is engineered
More informationVACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES
Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete
More informationEE034: Electrical Maintenance for Engineers & Technicians
EE034: Electrical Maintenance for Engineers & Technicians EE034 Rev.001 CMCT COURSE OUTLINE Page 1 of 6 Training Description: We have taken all the latest techniques and know-how relating to electrical
More informationC. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.
SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers
More informationMODULAR TRACTION SUBSTATIONS CITY ELECTRIC TRANSPORT
CITY ELECTRIC TRANSPORT 2 MODULAR TRACTION SUBSTATION Modular traction substation produced by PrJSC Pluton is an integrated solution for reliable power supply of electric transport catenary. Modular traction
More informationGuide To Troubleshooting INEFFICIENT COOLING FANS
Guide To Troubleshooting INEFFICIENT COOLING FANS TABLE OF CONTENTS Introduction Enclosure Cooling Basics Key Attributes of Enclosure Cooling Symptoms of Poor Enclosure Cooling Typical Cooling Fan Problems
More informationNEC Requirement Guidelines 2002 Code Options for the Installation of Listed Less-Flammable Liquid-Filled Transformers
NEC Requirement Guidelines 2002 Code Options for the Installation of Listed Less-Flammable Liquid-Filled Transformers BULLETIN 92046 APPLICATION INFORMATION NOVEMBER 2002 SUPERSEDES August 2002 CONTENTS
More informationA. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing
A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and 2. Number: PRC-005-1b 3. Purpose: To ensure all transmission and generation Protection Systems affecting the reliability
More informationSECTION ROTARY-SCREW WATER CHILLERS
PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.
More informationLaboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls
Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Scroll Enclosed Air Compressor System is designed to provide clean, dry air for
More informationArc Fault Detection Devices (AFDDs) Protecting People and Property
Arc Fault Detection Devices (AFDDs) Protecting People and Property Singapore Standard : CP5 Code of practice for electrical installations - Foreword 2 BS 7671 : the 18 th Edition report Short Brief 3 BS
More informationTelecity. Table of Contents. Page. Section 3.2
1 3.2 System Descriptions Table of Contents 3.2 SYSTEM DESCRIPTIONS... 3 3.2.1 General Notes... 3 3.3 Power Distribution MV... 4 3.3.1 Incoming Supply... 4 3.3.2 MV Switch room... 4 3.4 Power Distribution
More informationREA 105 Arc Protection Module. Operator s Manual
REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5
More informationFactory Equipment Testing of Single Lift Substation
Factory Equipment Testing of Single Lift Substation Presented by: Kurt Vosburg & Ronak Goswami IEEE CED Houston Chapter November 17-18, 2015 Objective This technical presentation will discuss various aspects
More informationMonitoring of Electrical Equipment Failure Indicators and Alarming
Past, Present and Future Maintenance Practices: Monitoring of Electrical Equipment Failure Indicators and Alarming Author: Gabe Paoletti, P.E. Eaton Corporation Senior Member, IEEE gabrieljpaoletti@eaton.com
More informationProduct Guide Low Voltage Switchboard & Switchgear
Product Guide 2018 Low Voltage Switchboard & Switchgear General INESING low voltage switchgear is completely designed and engineered by INESING using circuit breakers from a leader manufacturers like ABB,
More informationContents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7
Practical Power System Protection for Engineers and Technicians Contents Preface ix Chapter 1 Need for protection 1 1.1 Need for protective apparatus 1 1.2 Basic requirements of protection 2 1.3 Basic
More information650-EL-C-E-1995 Senior Electrical Engineer. PERSONAL DATA Nationality : Egyptian Birth Date : 06/01/1969 Marital Status : Married
650-EL-C-E-1995 Senior Electrical Engineer Holds a B. Sc. in Electrical Engineering and has about 16 years experience in the field of electrical construction, pre-commissioning and follow up activities
More informationC&I SYSTEM DIAGNOSTICS WITH SELF MONITORING AND REPORTING TECHNOLOGY (SMART)
C&I SYSTEM DIAGNOSTICS WITH SELF MONITORING AND REPORTING TECHNOLOGY (SMART) Suneel kumar P I Shravan Kumar Seema Deo Bhanu Kumar Raine Dy.General Manager, Dy.Manager Sr.Manager Manager NTPC RSTPS NTPC
More information7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management
Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current
More informationNFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC
NFPA 70E Arc Flash Considerations for MV Equipment By: Dominik Pieniazek, P.E. dominik@hv-eng.com HV Engineering, LLC http://sites.ieee.org/houston/ Full link for PDF copies of presentations: http://sites.ieee.org/houston/communities/ie
More informationi-con Switchgear Condition Monitoring HV Switchgear Integrated Substation Condition Monitoring ISCM Answers for Infrastructure & Cities.
i-con Switchgear Condition HV Switchgear Integrated Substation Condition ISCM Answers for Infrastructure & Cities. The challenge: Reliable energy supply is the key to success for every enterprise in a
More information800 MHz US 2 NMR system
800 MHz US 2 NMR system To achieve ultra-high-fields (>700 MHz), the magnet must be cooled to below (ambient pressure) liquid He temperature. The He cryostat is divided into two sections. The upper section
More informationThis guide will discuss the scope of work, and technical requirements of connecting to the Energy Transfer Station(s) (herein referred to as ETS).
Introduction This guide will discuss the scope of work, and technical requirements of connecting to the Energy Transfer Station(s) (herein referred to as ETS). The Purpose of the ETS is to deliver chilled
More informationRisk Mitigation of Aging Electrical Infrastructure
Risk Mitigation of Aging Electrical Infrastructure 2014 WWOA Annual Conference 10:55am Thursday October 9 th, 2014 Presented by and Authored by Jeff M. Miller, PE, ENV SP About the Presenter Jeff M. Miller,
More informationAQ 100 Series. Arc Flash Protection System
AQ 100 Series Arc Flash Protection System THE CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR THE CONSEQUENCES OF AN ARC FAULT IN OIL-FILLED SWITCHGEAR Arc Phenomena Arc Phenomena Arc fault - facts
More informationOperation Manual. Programmable Logic Controller
Operation Manual Programmable Logic Controller Part No. 9983-0000-E01 / January 2018 OPERATION MANUAL TABLE OF CONTENTS CUSTOMER SERVICE 3 CONTACT INFORMATION 3 ORDER INFORMATION 3 INTRODUCTION 4 THE PROCESS
More informationFB10000 Error Messages Troubleshooting
Error ID: 66300 - UV UV System Active Alarm (UV will shut down). 66300 UV System Active Alarm (UV will shut down). Tap Get Ready. For more details open the Troubleshooting guide This UV error
More informationPredictive Maintenance Training
Predictive Maintenance Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq This predictive maintenance
More informationAlways keep this manual in a safe readily accessible location. MODEL SERIAL SERVICE COMPANY TELEPHONE NUMBER
Always keep this manual in a safe readily accessible location. MODEL SERIAL SERVICE COMPANY TELEPHONE NUMBER For Operating Instructions or Technical Support Call 1-507-886-6666 Last Revision: 1/31/12 Starting
More informationStandard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance
A. Introduction 1. Title: Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance 2. Number: PRC-005-6 3. Purpose: To document and implement programs for the maintenance of all
More informationGuide Specification Model CTG Automatic Transfer Switch
Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards
Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product
More informationElement D Services Electrical
PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.
More informationA. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing
A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and 2. Number: PRC-005-1.1b 3. Purpose: To ensure all transmission and generation Protection Systems affecting the reliability
More informationVAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits
01 VAMP 120 & 121 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during work
More information17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee
17 TH APRIL Switch Board Monitoring Protecting Switchboard Courtesy of ABB. www.fengshengelectric.com.sg Paul Lee Agenda 1. Introduction 2. IEC 61439 3. Why Switchboard Monitoring 4. Switchboard Monitoring
More informationContinuous, real-time detection, alarming and analysis of partial discharge events
DMS PDMG-R Partial discharge monitor for EHV GIS Continuous, real-time detection, alarming and analysis of partial discharge events Automatic PD fault classification Robust design allows for reliable operation
More informationEVLA Memorandum 107 Failure Pathology of EVLA WIDAR Correlator Support Systems October 18 th, 2006 Bob Broilo, Brent Carlson
EVLA Memorandum 107 Failure Pathology of EVLA WIDAR Correlator Support Systems October 18 th, 2006 Bob Broilo, Brent Carlson INTRODUCTION The WIDAR correlator being developed for the EVLA project will
More informationMulti-Zone Wireless Control Training Systems ( )
Multi-Zone Wireless Control Training Systems 593306 (3467-00) LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 11/2018 Table of Contents General Description 2 Courseware 2 Topic Coverage 3 List
More informationSECTION LIGHTING CONTROLS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to
More informationOpen Source Home Security System
Open Source Home Security System Final Report ECE 410: Senior Project By: Allen Chu March 28, 2012 Project Advisor: Dr. John Ventura, PE Table of Contents Title 1 Table of Contents 2 1. Abstract 3 2. Customer
More informationRelay Performance Index for a Sustainable Relay Replacement Program
Relay Performance Index for a Sustainable Relay Replacement Program Aaron Feathers, Abesh Mubaraki, Nai Paz, Anna Nungo Pacific Gas & Electric Company San Francisco, CA Western Protective Relay Conference
More informationHGM1750 Automatic Generator Module OPERATING MANUAL Smartgen Electronics
HGM1750 Automatic Generator Module OPERATING MANUAL Smartgen Electronics CONTENT 1. SUMMARY...4 2. PERFORMANCE AND CHARACTERISTICS...4 3. SPECIFICATION...5 4. OPERATION...5 5. PROTECTION...6 6. PARAMETER
More informationFLUID BED EQUIPMENT. Drying
Drying FLUID BED EQUIPMENT Tapasya s Fluid Bed Equipment (FBE) is specially designed unit for agglomeration and simultaneous drying for top spray granulation conforming to the international quality norms
More informationPROFILE. industrial services rental trading
PROFILE industrial services rental trading Introduction Power Corp General Trading & Contracting Company W.L.L. is incorporated by technocrats having vast experience in Engineering and Construction field
More informationExecutive Summary. CNBC Global Headquarters Christine Cajilig
Executive Summary This report contains an analysis and description of the existing electrical distribution of the including the distribution type, emergency power, uninterruptible power system, over current
More information! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C)
Models 51, 51-S and 53 Boiler Water Feeders Models 51-2, 51-S-2 and 53-2 Feeder Cut-Off Combinations McDonnell & Miller Installation & Maintenance Instructions MM-315(C) OPERATION Maximum Water Supply
More informationLMR Electric Fire Pump Controllers Features
1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status
More informationHeating Cable. Description
ITLS Base Panel 10 VGA Touch Screen HMI 40 Amps/Loop @ 100 480 VAC 6 Loops to 72 Loops NEMA 4 or NEMA 4X Enclosure SCR Control Integral Circuit Panel with Circuit Breakers Optional Main Disconnect Soft
More informationConstruction Electrical
INDEECO offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the previous section, makes it easy to specify
More information4. Applicability: 4.1. Functional Entities: 4.2. Facilities:
Standard PRC-005-2(i) Protection System A. Introduction 1. Title: Protection System 2. Number: PRC-005-2(i) 3. Purpose: To document and implement programs for the maintenance of all Protection Systems
More informationLife Cycle Considerations for Microprocessor Relays
2017 Texas A&M Conference for Protective Relay Engineers Life Cycle Considerations for Microprocessor Relays Michael Kleman, Regional Technical Manager ABB Coral Springs, FL - USA Todd Moyer P.E., Distribution
More informationSIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL
SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3
More informationDESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES
2.07 ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.07 It is expected that the electrical design professional will conform to accepted good engineering design practices.
More informationProservo NMS5- / NMS7-
Functional Safety Manual Proservo NMS5- / NMS7- Tank gauge for Liquid level measurement with 4 to 20mA Output or with Alarm Relay Contact Output Application Operating minimum (e.g. dry run protection),
More informationDistribution Control Center Operator Training
Distribution Control Center Operator Training OnlineTraining 15-Hour Course COURSE I BASIC DISTRIBUTION 1. Introduction to Distribution Systems a. Terminology b. Basic electricity and Ohm s Law c. BES
More informationMission Critical. Fuel Supply Systems
Fuel Supply Systems Insight Onsite Fuel Supply Systems Page 2 Simplex Mission Critical Fuel Supply Systems are comprehensive, integrated, project-matched fuel management systems for diesel and turbine
More informationMYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL
MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TPC VISIT OUR WEBSITE SIGMACONTROLS.COM MYRIADI&O062705 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 7,8
More informationFlexible Air-sampling Smoke Detection
Flexible Air-sampling Smoke Detection BY Technology Pioneers in Highsensitivity Air-sampling Smoke Detection Systems Providing Solutions Beyond Traditional Smoke and Fire Detection Hochiki, a world-leader
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationWhite Paper. Maintenance Inspection Windows on Transformers. Maintenance Inspection Windows on Transformers. Abstract: iriss.com
Maintenance Inspection Windows on Transformers By Rudy Wodrich, P.Eng., MBA, CRL, VP Engineering Services, IRISS Inc. Abstract: Everyone knows that Thomas Alva Edison invented the lightbulb but who invented
More informationTRANSMISSION ENGINEERING STANDARDS SUBSTATIONS
This standard was reviewed and approved by key managers with final approval by an officer of Oncor Electric Delivery on. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Customer with the Company
More informationPart: I TECHNICAL SPECIFICATION
Part: I TECHNICAL SPECIFICATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR THE WORK OF DESIGN, SUPPLY, ERECTION AND COMMISSIONING INCLUDING CIVIL WORK OF NITROGEN INJECTION
More informationApplications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards
Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards LIN ZHOU M Eng, MIEAust RIZNER Australia YANG YIJUN B. Eng, Senior Engineer State Grid, Zhejiang
More informationDelta T Alert: Wireless Temperature Monitoring of Electrical Enclosures
Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Fred Baier, Level III Certified Infrared Thermographer Delta T Engineering, LLC 136 Main Street Metuchen, NJ 08840 Ph: 877-321-0576
More informationUNFIRED STEAM GENERATORS STANDARD EQUIPMENT
CEMLINE Unfired Steam Generators are designed to produce clean steam with steam or high temperature hot water as an energy source for use where there is a need to produce clean steam from boiler steam
More informationADVANCED MONITORING AND DIAGNOSTIC SYSTEMS FOR INDUSTRIAL GAS TURBINES
ADVANCED MONITORING AND DIAGNOSTIC SYSTEMS FOR INDUSTRIAL GAS TURBINES Jon Aylett BSc Senior Diagnostic Systems Engineer jaylett@chromalloy.com CHROMALLOY TURBINE SERVICES Venture Building Kelvin Campus
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationOperating instructions SENTRI4 Control panel based Fire detection and alarm system
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32 Zones Healthy 15:45 Fault Power Fault System Fault SenTRI 4 Fire System Designed to EN54 Pt 2 & 4 Operating instructions
More informationElectrical Energy department
Al-Balqa Applied University Power systems Protection course Dr Audih al-faoury Electrical Energy department 2018-2019 Department of Electrical Energy Engineering 1 Part 1 Power System protection Introduction
More informationTECHNICAL DATA SHEET ADDRESSABLE FIRE ALARM SYSTEMS FIRE ALARM CONTROL PANEL LF-6100 A 1/2
FEATURES: Closed Loop Design (Class A Wiring) Microprocessor Based System Intelligent Distributed System Structure Quick Response Time Fire Alarm in
More informationMAXIMUM SERIES. Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 70 F chilled water.
Temperature Control Units Water & Oil 30-500 F Portable Chillers Air & Water-Cooled 20-70 F Central Chillers Air & Water-Cooled Packages & Modules 20-70 F Pump Tank Stations Chilled or Tower Water 200-3600
More informationElectrical Design Guidelines Table of Contents
C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6
More informationIntroduction Consultant shall incorporate the material in the DSS into the project specifications.
DIVISION 16 - ELECTRICAL Section 16000 - General Discussion Introduction Consultant shall incorporate the material in the DSS into the project specifications. Refer any questions, clarifications regarding
More informationAS950 ALL-WEATHER REFRIGERATED SAMPLERS
AS950 ALL-WEATHER REFRIGERATED SAMPLERS Applications Wastewater Collections Industrial Pretreatment Environmental Monitoring Stormwater Sampling has never been this easy. The AS950 All-Weather Refrigerated
More informationHOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4
HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 INTRODUCTION Thank you for purchasing the Hokkim Integrated Automatic Mains Failure Control Board model HAMF- 8 or HAMF-4. We shall
More informationSYSTEM 3400 ANALOGUE ADDRESSABLE FIRE DETECTION. (with Devices) Operating Manual Version 3.3X Issue 2 September 1996
User responsibility SYSTEM 3400 (with 34000 Devices) Control and indicating equipment Quick reference Emergency conditions ANALOGUE ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM Other controls Site labels
More informationElectrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts
Standard Construction Control Options HEATREX offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the
More informationStandard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance
Standard PRC-005-5 Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance Standard Development Timeline This section is maintained by the drafting team during the development
More informationArc Flash Protection Training - NFPA 70e Electrical Safety
Arc Flash Protection Training - NFPA 70e Electrical Safety Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq
More informationSTCP 02-1 Issue 005 Alarm & Event Management
STCP 02-1 Issue 005 Alarm & Event Management STC Procedure Document Authorisation Party Name of Party Representative Signature Date National Grid Electricity Transmission plc SP Transmission plc Scottish
More information